Installation instructions

for contractors

Vitovent 300-W

Mechanical ventilation system with heat recovery

3

3

for a maximum air flow rate of 300 m

/h and 400 m

/h

VITOVENT 300-W

Dispose after installation.

5793 589 GB

5/2013

loading

Related Manuals for Viessmann Vitovent 300-W

Summary of Contents for Viessmann Vitovent 300-W

  • Page 1
    VIESMANN Installation instructions for contractors Vitovent 300-W Mechanical ventilation system with heat recovery for a maximum air flow rate of 300 m /h and 400 m VITOVENT 300-W Dispose after installation. 5793 589 GB 5/2013…
  • Page 2
    Safety instructions Please follow these safety instructions closely to prevent accidents and mate- rial losses. Safety instructions explained ■ The Code of Practice of relevant trade associations Danger ■ All current safety regulations as This symbol warns against the defined by DIN, EN, DVGW, VDE and risk of injury.
  • Page 3: Table Of Contents

    Index Preparing for installation Intended use………………….Passive house use………………..Air distribution/ductwork………………■ Supply air and extract air ducts…………….. ■ Supply air/extract air valvesSupply air/extract air valves……■ Air routing between rooms…………….■ Preventing flow noise and pressure drop…………10 ■ Thermal insulation of the ductwork…………..12 Siting……………………

  • Page 4
    Index (cont.) Electrical connections………………. 48 ■ Terminal overview………………… 49 ■ Fitting and connecting the remote control…………50 ■ Connecting air pressure switch and sensors………… 52 ■ Connecting an external electric preheater coil……….52 ■ Power supply………………..52 Commissioning and adjustment…………….53 Keyword index………………..
  • Page 5: Intended Use

    Passive house use Vitovent 300-W meets the requirements for passive house use.

  • Page 6: Air Distribution/Ductwork

    Air distribution/ductwork Supply air and extract air ducts The air is distributed from the ventilation Installation information unit to the living spaces (supply air) or ■ In order to avoid complicated duct from the wet areas to the ventilation unit runs, install the ventilation ductwork (extract air) via air distribution boxes with prior to installing the central heating,…

  • Page 7
    K Exhaust air C Kitchen L Air distribution box D WC M Flat duct E Bathroom N Vitovent 300-W F Extract air P EPP pipe G Supply air R Diverter ■ Secure components with butt straps, perforated straps (on site) or mounting brackets (accessory).
  • Page 8
    L Air distribution box E Bathroom M Flat duct F Extract air N Vitovent 300-W ■ Secure components with plastic- ■ Secure EPP pipes on the connectors coated perforated straps (on site) and of the ventilation unit to the wall using seal with shrink tape.
  • Page 9: Supply Air/Extract Air Valvessupply Air/Extract Air Valves

    Air distribution/ductwork (cont.) ■ If flexible System 150 flat ducts are routed within the insulation layer below the screed, e.g. as the supply pipe for the air distribution box, protect these with cover panels (on-site provision) against deformation by concentrated loads (impact protection).

  • Page 10: Preventing Flow Noise And Pressure Drop

    Air distribution/ductwork (cont.) Preventing flow noise and pressure drop ■ Install air distribution boxes close to Measures against structure-borne the ventilation unit. noise Maximum length of supply air and extract air ducts between the ventila- No additional measures are required if tion unit and the air distribution box: the ventilation unit is mounted on con- crete or screed floors and on solid walls,…

  • Page 11
    Air distribution/ductwork (cont.) Silencers Silencer, round, flexible Connection Dimensions in mm DN 125 DN 160 DN 180 Silencer, flat, flexible, system 100/150 System Dimensions in mm…
  • Page 12: Thermal Insulation Of The Ductwork

    Air distribution/ductwork (cont.) Silencer, flat, crush-resistant version, system 100 Thermal insulation of the ductwork ■ Thermally insulate the outdoor air ■ Avoid gaps. and exhaust air lines to prevent the ■ Isolate ceiling and wall outlets with formation of condensate; these must insulation strips.

  • Page 13: Siting

    Open flue combustion equipment and Ensure ambient temperatures Vitovent between 2 and 35 °C. Danger ■ The Vitovent 300-W can be floorstand- The simultaneous operation of ing or wall mounted. open flue combustion equipment ■ Keep ductwork to the extract air and, (e.g.

  • Page 14
    Siting (cont.) Information regarding the operation Set up kitchen extractor hoods as recir- of the Vitovent in conjunction with culating extractors, which is more open flue combustion equipment energy efficient. ■ The installation of an air pressure switch (accessory) that stops the ven- Never connect existing extractor tilation unit in the case of negative hoods to the extract air duct of the…
  • Page 15: Dimensions

    Siting (cont.) Dimensions…

  • Page 16
    DN 180 Exhaust air DN 160 DN 180 Condensate drain connector 1¼ male thread 1¼ male thread Note Fit the connection piece supplied (see page 21) to connect the condensate pipe DN 32 (on site). Minimum clearances A Vitovent 300-W…
  • Page 17: Protecting The Mechanical Ventilation System

    Protecting the mechanical ventilation system Please note Dust entering the ventilation unit and the ductwork can result in faulty operation of the mechani- cal ventilation system. Prevent the ingress of dust whilst building work is in progress by the following measures: ■…

  • Page 18: Installing The Vitovent

    Installing the Vitovent Wall mounting 2 . 5 2 . 5 A Rubber washers as anti-vibration measure…

  • Page 19: Floorstanding Installation

    Installing the Vitovent (cont.) Floorstanding installation 1. In order to safeguard that the con- 2. Level the Vitovent horizontally densate can drain off freely, site the Vitovent on a mounting plinth (acces- sory). Vibrations are isolated by means of adjustable anti-vibration feet.

  • Page 20
    Connecting the condensate drain (cont.) Maintenance-free dry siphon (accessory) A Vitovent 300-W C Dry siphon B Condensate drain connector D Waste water pipe DN 40, e.g. HT 1¼ male thread pipe (on site) with fall…
  • Page 21
    Connecting the condensate drain (cont.) Siphon with stench trap (on site) A Vitovent 300-W C Connection piece outside diameter 32 mm (supplied) B Condensate drain connector 1¼ male thread D Siphon with stench trap (on site)
  • Page 22: Outdoor Air/Exhaust Air Ductwork

    Connecting the condensate drain (cont.) Note Secure pipe connections with PVC adhesive. Outdoor air/exhaust air ductwork Push EPP pipes onto the respective Vitovent connectors (possibly fit check valves on site).

  • Page 23: System Diagram

    Outdoor air/exhaust air ductwork (cont.) System diagram…

  • Page 24
    Outdoor air/exhaust air ductwork (cont.) Outdoor air/exhaust air ductwork Pos. Component System/DN Vitovent 300-W 300 m /h: DN 160 400 m /h: DN 180 Exterior wall duct DN 160 ■ With weather grille and insulating sleeve DN 180 ■ With bird guard ■…
  • Page 25: Exterior Wall Connection

    Outdoor air/exhaust air ductwork (cont.) Exterior wall connection Exterior wall duct with weather grille A EPP pipe sleeve…

  • Page 26
    Outdoor air/exhaust air ductwork (cont.) A EPP pipe sleeve B Mounting ring, sealing level Note on step 5: Note Seal mounting ring sealing level B with Thermally insulate the outdoor air duct suitable adhesive tape towards the seal- from the exterior wall connection to the Vitovent in vapour diffusion-proof mate- ing level.
  • Page 27
    Outdoor air/exhaust air ductwork (cont.) Exterior wall duct with bird guard A EPP pipe EPP pipe Dimension a in DN 125 DN 190 DN 180…
  • Page 28
    Outdoor air/exhaust air ductwork (cont.) A EPP pipe…
  • Page 29: Roof Outlet

    Outdoor air/exhaust air ductwork (cont.) Roof outlet Made from stainless steel with a removable cowl A EPP pipe sleeve D Air discharge vents B Mounting ring, sealing level C Mounting clip to secure the EPP pipe sleeve Installation information ■ Installation sequence similar to the installation of the exterior wall duct with weather grille.

  • Page 30: Outdoor Air And Exhaust Air Extension

    Outdoor air/exhaust air ductwork (cont.) C Universal roof tile, adjustable for Made from painted sheet steel roof pitch 20 to 50° (accessory) D Roof outlet E Air discharge vents A EPP pipe B Female connection Outdoor air and exhaust air extension Light well installation.

  • Page 31: Supply Air/Extract Air Ductwork: Plastic

    Outdoor air/exhaust air ductwork (cont.) A EPP pipe B Wall rose C Bend with condensate drain con- nector (outside Ø 18 mm), for con- necting an on-site waste water pipe D Wall mounting bracket E Pipe F Bend with insect grille Supply air/extract air ductwork: Plastic Make all connections airtight with lip seals.

  • Page 32: System Diagram

    Supply air/extract air ductwork: Plastic (cont.) System diagram qE qR qE qW qE qW qTqZ qTwQ qTwQ…

  • Page 33
    Supply air/extract air ductwork: Plastic (cont.) Plastic ductwork (flat) Pos. Component System/DN Vitovent 300-W 300 m /h: DN 160 400 m /h: DN 180 Pipe with female connection (EPP) DN 160 DN 180 Flexible pipe Female connection (EPP) DN 160…
  • Page 34: Restrictors For Adjusting The Air Flow Rate

    Restrictors for adjusting the air flow rate Calculate the flow rate and pressure drop with the aid of the calculation pro- gram (download from www.viessmann.de) prior to installa- tion. Individual rings are knocked out of the restrictors to adjust the flow rate. How…

  • Page 35
    Supply air/extract air ductwork: Plastic (cont.) Note For easier installation and cleaning, we recommend you mark the relevant con- nector on the air distribution box (e.g. kitchen or living/dining room). 1 2 3 4…
  • Page 36: Connecting The Diverter

    Supply air/extract air ductwork: Plastic (cont.) Connecting the diverter…

  • Page 37
    Supply air/extract air ductwork: Plastic (cont.)
  • Page 38: Fitting The Floor Vent

    Supply air/extract air ductwork: Plastic (cont.) Fitting the floor vent After completing the floor: ■ Remove the plastic cover from the floor vent (step 4). ■ Remove cardboard insert. ■ Insert the grille (step 6).

  • Page 39: Supply Air/Extract Air Ductwork: Metal

    Supply air/extract air ductwork: Metal Make all connections airtight. System diagram qIqE…

  • Page 40
    2 distribution levels, it may me necessary to provide a butterfly valve (on site) in the supply air line. Metal ductwork (flat) Pos. Component System/DN Vitovent 300-W 300 m /h: DN 160 400 m /h: DN 180 Pipe with female connection (EPP) DN 160…
  • Page 41
    Supply air/extract air ductwork: Metal (cont.) Pos. Component System/DN Supply air valve with mounting ring for setting DN 100 into ceilings Supply air vent for wall mounting DN 100 Slotted vent with connecting chamber DN 100 Silencer, flat, impact-resistant version System 100 Silencer, flat, flexible System 100…
  • Page 42: Fitting The Slotted Vent

    Supply air/extract air ductwork: Metal (cont.) Fitting the slotted vent Separate installation instructions Note on step 4: ■ Unfinished wall: After rendering/plastering, insert and secure the slotted vent. ■ Light wall construction: Make a slot 305 x 40 mm, then insert and secure the slotted vent.

  • Page 43: Fitting The Floor Vent

    Supply air/extract air ductwork: Metal (cont.) Fitting the floor vent…

  • Page 44: Supply Air/Extract Air Valves

    Supply air/extract air ductwork: Metal (cont.) Separate installation instructions Note on steps 5 to 8: ■ Only carry out steps 5 to 8 after the floor has been completed. Supply air/extract air valves Installation versions, supply air/extract air valves Wall mounting Ceiling mounting A Screed B Impact sound insulation…

  • Page 45: Fitting Metal Supply Air/Extract Air Valves

    Supply air/extract air valves (cont.) C Flat duct with compensating insula- Floor mounting tion: 60 mm D Floor vent A Screed B Impact sound insulation Fitting metal supply air/extract air valves Example with wall mounted extract air valve Nominal diameter Dimension a in mm DN 100 DN 125…

  • Page 46: Fitting Plastic Supply Air/Extract Air Valves

    Supply air/extract air valves (cont.) Note on step 2: Insulate the ductwork connection with permanently flexible material against structure-borne noise transmission. Fitting plastic supply air/extract air valves Note on step 2: ■ Insulate the ductwork connection with permanently flexible material against structure-borne noise transmission.

  • Page 47: Fitting The Kitchen Extract Air Valve

    Supply air/extract air valves (cont.) Fitting the kitchen extract air valve A Grease filter made from aluminium B Gasket mesh Nominal diameter Dimension a in mm DN 100 DN 125 Note on step 2: Insulate the ductwork connection with permanently flexible material against structure-borne noise transmission.

  • Page 48: Electrical Connections

    Electrical connections Danger Note Damaged cable insulation can If 2 components are connected to the cause injury and damage to the same terminal, press both cores appliance. together in a single wire ferrule. Route cables so that they cannot touch very hot, vibrating or sharp- edged components.

  • Page 49: Terminal Overview

    Electrical connections (cont.) Terminal overview A Power cable with standard plug C Input, changeover (X15.1/X15.2) (1/N/PE 230 V/50 Hz, factory-fitted) ■ Input 0 to 10 V– for CO sensor B Remote control (2-pole plug, inter- (set «V1 mode» to «1», for «V1 changeable cores, X1.1/X1.2) Vmin»…

  • Page 50: Fitting And Connecting The Remote Control

    Electrical connections (cont.) D Input, changeover (X15.3/X15.4) G Output 0 to 10 V– (X15.9) ■ Input 0 to 10 V– for humidity sen- H External electric preheater coil, fit- sor (delivered condition), (for «V2 ted into the outdoor air duct Vmin»…

  • Page 51
    Electrical connections (cont.)
  • Page 52: Connecting Air Pressure Switch And Sensors

    ■ IEC 60364-4-41 ■ VDE regulations ■ Connection conditions speci- fied by your local power supply utility The Vitovent 300-W is delivered fully wired. Insert the mains plug into a standard socket with separate fuse/MCB protec- tion 230 V/50 Hz.

  • Page 53: Commissioning And Adjustment

    Commissioning and adjustment «Vitovent 300-W» service instruc- tions…

  • Page 54: Keyword Index

    Keyword index Connection piece……8, 33 Adaptor……….40 Countercurrent heat exchanger…14, 19 Adjustable feet……..10 Cover panel……….9 Adjusting the air flow rate….34 Air discharge vent……29, 30 Air distribution……..6 Dimensions……..15 Air distribution box…..7, 8, 33 Discharge vent……..29 Air distribution box, connecting..34 Diverter……7, 33, 40, 44 Air pressure switch…….14, 52 Door gap……….9 Air routing between rooms….9…

  • Page 55
    Keyword index (cont.) Flat duct…….7, 8, 33, 40 Minimum clearances……16 Floorstanding installation….19 Mounting bracket………8 Floor vent….33, 38, 40, 43, 45 Mounting clip……..29 Mounting plinth……..19 Geothermal heat exchanger….14 Grease filer……..47 Noise transmission……46 Grille, floor vent……..33 Open flue combustion equipment 13, 14 Heat losses, ductwork……12 Operation Heat recovery…….12, 19…
  • Page 56
    Supply air vents for fitting in floors..45 System diagram Wall mounting……..18 ■ Metal ductwork (flat)….39, 40 ■ Plastic ductwork (flat)….32, 33 ■ Supply air/exhaust air ducts…23 Viessmann Werke GmbH&Co KG Viessmann Limited D-35107 Allendorf Hortonwood 30, Telford Telephone: +49 6452 70-0 Shropshire, TF1 7YP, GB…

Viessmann VITOVENT 300-W Installation And Service Instructions Manual

  1. Manuals
  2. Brands
  3. Viessmann Manuals
  4. Fan
  5. Vitovent 300-W
  6. Installation and service instructions manual

  • Contents

  • Table of Contents

  • Bookmarks

Quick Links

VIESMANN

Installation and service instructions

for contractors

Vitovent 300-W

Type H32S C325

Type H32S C400

Mechanical ventilation system with heat recovery

for a maximum air flow rate of 325 m

3

/h and 400 m

3

/h

VITOVENT 300-W

Please keep safe.

6152162 GB

4/2020

loading

Related Manuals for Viessmann VITOVENT 300-W

Summary of Contents for Viessmann VITOVENT 300-W

  • Page 1
    VIESMANN Installation and service instructions for contractors Vitovent 300-W Type H32S C325 Type H32S C400 Mechanical ventilation system with heat recovery for a maximum air flow rate of 325 m /h and 400 m VITOVENT 300-W Please keep safe. 6152162 GB…
  • Page 2: Target Group

    Safety instructions Safety instructions Please follow these safety instruc- tions closely to prevent accidents and material losses. Safety instructions explained Danger Note This symbol warns against the risk Details identified by the word «Note» of injury. contain additional information. Please note This symbol warns against the risk of material losses and environmen- tal pollution.

  • Page 3: Repair Work

    Please note Repairing components that fulfil a safety function can compromise the safe operation of the system. Replace faulty components only with genuine Viessmann spare parts. Auxiliary components, spare and wearing parts Please note Spare and wearing parts that have…

  • Page 4
    Index Index 1. Information Disposal of packaging …………….Symbols ………………..Intended use ………………Passive house use …………….. Product information …………….Spare parts lists ……………… ■ Information about parameter settings, diagnosis and troubleshooting ■ 2. Preparing for installation Siting …………………. Installation requirements …………..■…
  • Page 5: Disposal Of Packaging

    Information Disposal of packaging Please dispose of packaging waste in line with statu- tory regulations. Symbols The steps in connection with commissioning, inspec- Symbol Meaning tion and maintenance are found in the «Commission- Reference to other document containing ing, inspection and maintenance» section and identified further information as follows: Step in a diagram:…

  • Page 6: Passive House Use

    440 m trol unit, type WO1C», of a Viessmann heat pump. living space. The Vitovent 300-W is available in left or right-hand versions. In the left-hand version, the supply air and extract air connections are on the left side of the unit.

  • Page 7
    Product information (cont.) Spare parts lists Information about spare parts can be found at www.viessmann.com/etapp or in the Viessmann spare part app. Information about parameter settings, diagnosis and troubleshooting Installation and service instructions for «Ventila- tion programming unit, type LB1» or heat pump…
  • Page 8: Preparing For Installation

    Preparing for installation Siting Installation requirements Preferably site the ventilation unit inside the airtight Information regarding the operation of the Vitovent ■ and thermally insulated building envelope. in conjunction with open flue combustion equip- Please note ment The installation room must be dry and free ■…

  • Page 9
    Preparing for installation Siting (cont.) Dimensions Type H32S C325/C400 (R), right-hand version Fig. 1 Extract air Electrical terminal area Exhaust air Waterless trap (standard delivery) with continuing Outdoor air connection DN 32 Supply air Type Connections H32S C325 (R) DN 160 H32S C400 (R) DN 180…
  • Page 10
    Preparing for installation Siting (cont.) Type H32S C325/C400 (L), left-hand version Fig. 2 Extract air Electrical terminal area Exhaust air Waterless trap (standard delivery) with continuing Outdoor air connection DN 32 Supply air Type Connections H32S C325 (L) DN 160 H32S C400 (L) DN 180…
  • Page 11: Minimum Clearances

    Preparing for installation Siting (cont.) Minimum clearances Fig. 3 Vitovent 300-W Protecting the mechanical ventilation system Please note Following the installation, close all supply air and ■ Dust entering the ventilation unit and the duct- extract air vents, for example with self-adhesive film.

  • Page 12: Wall Mounting

    Floorstanding installation 1. In order to safeguard that the condensate can 2. Level the Vitovent 300-W horizontally. drain off freely, site the Vitovent 300-W on a mounting base (accessories). Vibrations are isola- ted by means of adjustable anti-vibration feet.

  • Page 13: Installation Sequence

    Installation sequence Connecting the outdoor air and exhaust air pipes Push ducts onto the respective ventilation unit connec- tors (install check valve on site if necessary). The con- nectors must be completely covered by the duct, other- wise condensate may appear on the colder connec- tors.

  • Page 14: Electrical Connections

    Installation sequence Connecting the condensate drain (cont.) Maintenance-free waterless trap (standard delivery) Fig. 6 Ventilation unit (right-hand version) Connection for waterless trap for ventilation unit, Waterless trap (standard delivery) left-hand version Example for stench trap (on site) Waste water pipe DN 32 (on site) Please note Note The waterless trap can be damaged or leaks…

  • Page 15: Overview Of Electrical Connections

    Installation sequence Electrical connections (cont.) Overview of electrical connections Fig. 7 Power cable with standard plug (1/N/PE 230 V/ Modbus connection (X15), for connecting cable to 50 Hz, factory-fitted) ventilation programming unit, type LB1 or Vitocal/ Signal output (X19) Vitovent connecting cable Wireless receiver for wireless operating switch 24 V connection (X18) eBus connection (X17), additional preheating coil,…

  • Page 16
    Installation sequence Electrical connections (cont.) Installing the wireless operating switch (accessories) The ventilation unit can be operated via max. 6 wire- Where to install wireless components less operating switches. Choose the installation location such that the radio ■ When selecting an installation site for the wireless signals impinge on walls and other equipment as receiver and wireless operating switches, note that the horizontally as possible.
  • Page 17
    Installation sequence Electrical connections (cont.) Fig. 9 Installing the wireless operating switch on the wall Fig. 10…
  • Page 18
    Installation sequence Electrical connections (cont.) 1. On smooth surfaces, the wireless operating switch can be affixed with the supplied adhesive tape. Enabling the wireless operating switch 1. Press the «LRN/SET» button on the wireless receiver. The «LRN/SET» button flashes red. 2.
  • Page 19: Power Supply

    Electrical connections (cont.) Power supply Danger The Vitovent 300-W is delivered fully wired. Incorrectly executed electrical installations can Insert the mains plug into a standard socket result in injuries from electrical current and dam- (230 V/50 Hz) with separate fuse/MCB protection.

  • Page 20
    Commissioning, inspection, maintenance Steps — commissioning, inspection and maintenance Commissioning steps Inspection steps Maintenance steps Page • 1. Checking the mechanical ventilation system…………..21 • • • 2. Starting the ventilation unit………………..21 • 3. Setting the language, time and date…………….. 22 •…
  • Page 21
    Commissioning, inspection, maintenance Checking the mechanical ventilation system Danger Please note The simultaneous operation of open flue com- The simultaneous operation of extractor hoods bustion equipment (e.g. an open fireplace) and or extracting tumble dryers and the Vitovent in the Vitovent in a space with combustion air inter- interconnected rooms results in negative pres- connection results in dangerous negative pres- sure inside the room.
  • Page 22
    Commissioning, inspection, maintenance Setting the language, time and date Operating instructions Setting air flow rates Installation and service instructions for «Ventila- tion programming unit, type LB1» or heat pump control unit «Vitotronic 200, type WO1C» Adjusting the air flow rates Set ventilation level 2.
  • Page 23: Cleaning And Replacing Filters

    Commissioning, inspection, maintenance Adjusting the air flow rates (cont.) Note Adjusting the air flow rates with the use of an impeller air speed meter will not provide high accuracy. Devia- tions by 10 % are possible. What is important is the ±…

  • Page 24
    Commissioning, inspection, maintenance Cleaning and replacing filters (cont.) Fig. 14 For fine filters F7 (= ISO ePM1 50 %), dispose of ■ the entire filter in the household waste. ■ For coarse filters G4 (= ISO Coarse 60 %), only replace the filter fleece in the filter frame;…
  • Page 25: Removing The Front Panel

    Commissioning, inspection, maintenance Cleaning and replacing filters (cont.) Ventilation unit Pos. Right-hand version Left-hand version Outdoor air filter G4 = ISO Coarse 60 % Extract air filter G4 = ISO Coarse 60 % or fine filter F7 = ISO ePM1 50 % Extract air filter G4 = ISO Coarse 60 % Outdoor air filter G4 = ISO Coarse 60 % or fine filter F7 = ISO ePM1 50 %…

  • Page 26: Cleaning Information

    Commissioning, inspection, maintenance Cleaning the countercurrent heat exchanger Please note Mechanical stress can damage the fins of the countercurrent heat exchanger. ■ Never grip the heat exchanger by its fins. ■ Only pull out by the loop. When inserting, push evenly with both hands ■…

  • Page 27: Cleaning The Interior

    Commissioning, inspection, maintenance Cleaning the interior Fig. 19 1. Remove the front panel; see page 25. Pull out the 2. Wipe the interior with a damp cloth. Clean with a outdoor air filter, extract air filter and countercurrent vacuum cleaner if required. heat exchanger;…

  • Page 28: Instructing The System User

    Commissioning, inspection, maintenance Checking the condensate drain Fig. 20 Condensate drain Waterless trap Note 1. Check that the condensate can drain freely. If nec- The position of the trap connection depends on the essary, clean the condensate drain and trap. unit version.

  • Page 29: Maintenance

    Maintenance Removing the PCB cover Danger Contact with live components can lead to seri- ous injury from electric current. Disconnect the power plug before removing the cover. Safeguard against reconnection. Fig. 21 Assembly in reverse order Temperature sensor resistance curve Temperature sensors NTC 10 k Ω…

  • Page 30
    Connection and wiring diagram Controller PCB X18 X17 1 2 3 4 5 6 1 2 3 4 1 2 3 4 5 6 7 8 9 101112 Fig. 23 X01 Earthing X08 Do not connect anything here! X02 Power supply 1/N/PE, 230 V/50 Hz X10 Do not connect anything here! X03 Power supplies X12 Jumper, terminator, Modbus 120…
  • Page 31
    Commissioning/service reports Commissioning report Fig. 24…
  • Page 32
    Commissioning/service reports Example of commissioning report Fig. 25…
  • Page 33: Specification

    Specification Specification Vitovent 300-W Type H32S C325 H32S C400 Max. air flow rate Max. external pressure drop at max. air flow rate Factory setting of air flow rates Background ventilation Reduced ventilation Nominal ventilation Intensive ventilation Setting ranges for air flow rates…

  • Page 34
    Specification Specification (cont.) Type H32S C325 H32S C400 Max. power consumption Operation without preheating coil 144.5 Operation with integral electric preheating coil 1144.5 1178 Energy efficiency class to Commission Delegated Regulation (EU) No 1254/2014 Manual control ■ — — Time control ■…
  • Page 35: Final Decommissioning And Disposal

    Decommissioning and disposal Final decommissioning and disposal Viessmann products can be recycled. Components For decommissioning the system, isolate the system and substances from the system are not part of ordi- from the power supply and allow components to cool nary household waste.

  • Page 36
    Certificates Declaration of conformity We, Viessmann Werke GmbH & Co. KG, D-35107 Allendorf, declare as sole responsible body that the named product complies with the European directives and supplementary national requirements in terms of its design and operational characteristics. Using the serial number, the full Declaration of Con- formity can be found on the following website: www.viessmann.co.uk/eu-conformity…
  • Page 37
    Keyword index Keyword index Air flow rate Electrical connections………. 14, 15 – Adjusting…………..22 Electrical plug-in connectors, checking…… 28 – Factory setting…………33 Electrical terminal area………..9, 10 – Setting ranges…………33 Electric preheater coil……….8, 21 Air intake temperature……….33 Electric preheating coil……….18 Air pressure switch……….8, 21 Energy efficiency class……….34 Air pressure switch, connecting………
  • Page 38
    – Closing…………..28 – Installing…………..12 Radial fan…………..33 – Opening…………..25 Rated voltage…………. 33 Vitovent, installing…………12 Rate of humidity change……….33 Vitovent 300-W Recirculating extractors……….8 – Left-hand version………… 10 Reports……………31 – Right-hand version………… 9 Resistance curve, temperature sensors…..29 Ribbon heater………….13 Wall duct……………6…
  • Page 40
    Viessmann Werke GmbH & Co. KG Viessmann Limited D-35107 Allendorf Hortonwood 30, Telford Telephone: +49 6452 70-0 Shropshire, TF1 7YP, GB Fax: +49 6452 70-2780 Telephone: +44 1952 675000 www.viessmann.com Fax: +44 1952 675040 E-mail: info-uk@viessmann.com…

Alubox

Alubox X-treme

Alucon

Antifrogen

Aquacarbon

Aquahome

Atola

CeraCell

Condensola

Dekamatik

Divicon

EOMIX

EON

Eurola

Fauch

HoriCell

IS1500

Kospel EKCO

Kospel VSWK

Litola

Litola-CL

MatriX

Paromat

Pendola

Rondomat

RudoCell

SpiroTech

ST250

SW250

SW250LD

Trimatik

Turbomat

Ultrabox

Unit-P

Unomatik

VertiCell

VICare

Vitoair

Vitobloc 200

Vitocal

Vitocal 100-S/111-S

Vitocal 200-G

Vitocal 222-G

Vitocal 242-G

Vitocal 300

Vitocal 300-G

Vitocal 300-G Pro

Vitocal 300-G/350-G

Vitocal 300-G/W Pro

Vitocal 300-W Pro

Vitocal 333-G

Vitocal 343-G

Vitocal 350-G

Vitocal 350-G Pro

Vitocell

Vitocell 050-E

Vitocell 100

Vitocell 100-B

Vitocell 100-B/100-W

Vitocell 100-E

Vitocell 100-H

Vitocell 100-L

Vitocell 100-U

Vitocell 100-V

Vitocell 100-V/-W

Vitocell 100-W

Vitocell 100-W 100 л

Vitocell 100-W 80 л

Vitocell 120-E

Vitocell 140-E

Vitocell 160-E

Vitocell 300-B

Vitocell 300-H

Vitocell 300-V

Vitocell 300-V/-W

Vitocell 300-V/300-W

Vitocell 300-W

Vitocell 333

Vitocell 333/353

Vitocell 340-M

Vitocell 340?M/360?M

Vitocell 353

Vitocell 360-M

Vitocell-W 100

Vitocell-W 300

Vitoclima 230-S

Vitocom 100

Vitocom 200

Vitocom 300

Vitoconnect

Vitocrossal

Vitocrossal 100

Vitocrossal 200

Vitocrossal 300

Vitodens

Vitodens 050-W

Vitodens 100-W

Vitodens 111-F

Vitodens 111-W

Vitodens 141-F

Vitodens 200-W

Vitodens 200-W/300-W/333-W

Vitodens 200?W

Vitodens 222-F

Vitodens 222-W

Vitodens 222/333

Vitodens 242-F

Vitodens 300-W

Vitodens 333

Vitodens 333-F

Vitoflame 100

Vitoflame 200

Vitoflame 300

Vitogas

Vitogas 050

Vitogas 100

Vitogas 100-F

Vitogate 200

Vitogate 300

Vitola

Vitola 100

Vitola 200

Vitola-biferral

Vitola-comferral

Vitoladens

Vitoladens 300-C

Vitoladens 300-T

Vitoladens 300-W

Vitolig 150

Vitoligno 100-S

Vitomax

Vitomax 100

Vitomax 100-HS

Vitomax 100-LW

Vitomax 200

Vitomax 200-HS

Vitomax 200-HW

Vitomax 200-LW

Vitomax 300

Vitomax 300-HS

Vitomax 300-HW

Vitomax 300-LT

Vitomax 300-LW

Vitomax HS

Vitomax HW

Vitomax LCB

Vitomax LW

Vitomax-HS

Vitopend

Vitopend 050-W

Vitopend 100

Vitopend 100-W

Vitopend 100-W/200-W

Vitopend 111-W

Vitopend 200-W

Vitopend 222-W

Vitoplex

Vitoplex 100

Vitoplex 100-LS

Vitoplex 200

Vitoplex 300

Vitoplex 300 895-1750 кВт

Vitoplex/Vitorond/Vitomax

Vitoplus

Vitoradial

Vitoradial 300-T

Vitorond

Vitorond 100

Vitorond 111

Vitorond 200

Vitorondens 200-T

Vitorondens 222-F

Vitoset

Vitosoft 300

Vitosol

Vitosol 100

Vitosol 100-F

Vitosol 100-F/-FM

Vitosol 100-FM

Vitosol 141-FM

Vitosol 200

Vitosol 200-F

Vitosol 200-FM

Vitosol 200-T

Vitosol 200-TM

Vitosol 300

Vitosol 300-T

Vitosol 300-TM

Vitosolar 300-F

Vitosolic 100

Vitosolic 200

Vitotherm

Vitotrans

Vitotrans 100

Vitotrans 100-LW

Vitotrans 200

Vitotrans 200-LW

Vitotrans 222

Vitotrans 300/333

Vitotrans 300/333 1860-6600 кВт

Vitotrans 300/333 575-2000 кВт

Vitotrans 353

Vitotrol 100

Vitotrol 200-A

Vitotrol 200-E

Vitotrol 300

Vitotrol 300-A

Vitotrol 300-B

Vitotrol 300-E

Vitotron 100

Vitotronic

Vitotronic 050

Vitotronic 100

Vitotronic 100 HC1B

Vitotronic 100/200/300

Vitotronic 100/333

Vitotronic 200

Vitotronic 200 HO1B

Vitotronic 200 WPR3. Контроллер теплового насоса Vitocal

Vitotronic 200-H

Vitotronic 200. Контроллер теплового насоса Vitocal

Vitotronic 300

Vitotronic 300-K

Vitotronic 333

Vitotronic SPS

Vitovent 050-D

Vitovent 100-D

Vitovent 200-C

Vitovent 300-F

Vitovent 300-W

Vitplex

Vitоdens 200-W

Wallcon X-treme

WBS Ligna 050

ZONT H-2000/2000+

Адаптер электрических подключений

Блок управления приводом смесителя OpenTherm

Горелки

Горелки Bluetwin

Горелки Bluetwin/Unit

Датчик СО2 Vitovent 300-W

Дополнительный комплект/манометр

Комнатный термостат ST-BSOP/ST-PSOP

Контроллер KR

Контроллер SR

Контроллер Vitotrans 353

Модуль управления гелиоустановкой SDIO/SM1A

Насосные группы PAW

Нормативные показатели качества воды

Панель управления системой вентиляции

Платформа для техобслуживания котла

Примеры схем отопительных установок. Часть I

Примеры схем отопительных установок. Часть II

Примеры схем отопительных установок. Часть III

Примеры схем установок Vitosolic 100

Принадлежности

Принадлежности Vitotronic

Регулятор температуры помещения OpenTherm

Системы воздухораспределения Vitovent 300-W

Сифон Aquahome

Смесители отопительных контуров

Термическая станция водоподготовки Деаэратор

Универсальные радиаторы

Шкаф управления Vitocontrol

Шлюз WAGO MB/TCP-MB/RTU

Штиль ИнСтаб IS550

Штиль ИнСтаб SW250SL

Экономические показатели котельных установок

Понравилась статья? Поделить с друзьями:
  • Смена руководства сокращение
  • Предложения по эффективному руководству
  • Зарплата руководства почта россии
  • Lavita зарядное устройство 6 12 вольт инструкция по применению
  • 5 нок цена инструкция по применению от почек