VAMP 120

Arc protection unit

User manual

loading

Summary of Contents for VAMP 120

  • Page 1
    VAMP 120 Arc protection unit User manual…
  • Page 2
    VAMP 120 Arc protection unit VAMP Ltd User manual VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001…
  • Page 3: Table Of Contents

    Environmental conditions ……….13 8. Dimensions…………….14 8.1. VAMP 120 …………….14 8.2. VA 1 DA arc sensor …………15 8.3. Mounting plates for VA 1 DA………..15 9. Order information…………..16 10. Reference information …………17 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264…

  • Page 4: General

    (VAMP 221 / VAM 4C). It is possible to connect 4 arc sensors, of the type VA 1 DA or VA 1 EH, to the VAMP 120 unit. VAMP 24h support phone : +358 (0)20 753 3264…

  • Page 5: Unit Configuration

    VAMP 120 User manual Unit configuration Figure 2-1. VAMP 120 dipswitch operations and sensor connection The unit is configured using the dipswitches: Dipswitches 1-5 (see Figure 2-1): If only one arc sensor in use, SENSOR 1 input should be used.

  • Page 6: Sensors

    The active part of the sensor is mounted in a 10 mm hole, to the area in the switchgear that should be protected, and fastened with a 4 mm self-tapping screw (see Figure 3.1-3). VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001…

  • Page 7
    VYX 01 (Z- shaped) or VYX 02 (L-shaped). (See Figure 8.3-1) Active part of the sensor 10mm Anchoring Fastening screw 4 x 15 Sensor cable Figure 3.1-3. Arc sensor mounting picture. VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264…
  • Page 8: Functions

    Arc protection unit VAMP Ltd User manual Functions VAMP 120 includes an extensive self-supervision. The self- supervision includes internal functions as well as all arc sensors. Figure 4-1. Self-supervision block diagram If an internal fault occurs the self-supervision relay is activated and the ERROR-led is lit.

  • Page 9: Applications

    User manual Applications Every compartment is equipped with an arc sensor. Up to four sensors can be connected to the VAMP 120 unit. The trip relays are electromechanical and can be connected directly to control the circuit-breakers (see chapter Technical data).

  • Page 10: Connections

    *Connection for shield if shield sensor cable used (VA1DA-20s) Figure 6-1. VAMP 120 connection The VAMP 120 unit comprises two independent arc protection zones. Both zones have their own trip relay, trip 1 and trip 2. Trip 1 is controlled by sensor inputs 1 and 2. Trip is controlled by sensors 3 and 4.

  • Page 11
    X2- 15/16. This I> signal can e.g. be taken from a VAM 4C or VAMP 221 unit. The external reset is possible by correcting an auxiliary voltage to X2-17/18. The auxiliary boltage is connected to X2-1 and X2-2. VAMP has a wide range power supply from 19 to 265 Vdc or 40 to 265 Vac in the same hardware.
  • Page 12: Technical Data

    — RF electromagnetic field test (According. to f = 80….1000 MHz 10V /m EN 61000-4-3, class III) — Conducted RF field (According. to EN 61000- f = 150 kHz….80 MHz 10V 4-6, class III) VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001…

  • Page 13: Voltage Tests

    2 … 13.2 Hz ±3.5mm 13.2 … 100Hz, ±1.0g Shock/Bump test acc. to IEC 60255-21-2 20g, 1000 bumps/dir. Environmental conditions Specified ambient service temp. range -35…+70°C Transport and storage temp. range -40…+70°C VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264…

  • Page 14: Dimensions

    VAMP 120 Arc protection unit VAMP Ltd User manual Dimensions 8.1. VAMP 120 Figure 8.1-1. Arc protection unit VAMP 120 dimensions VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001…

  • Page 15: Va 1 Da Arc Sensor

    VA 1 DA arc sensor Figure 8.2-1. VA 1 DA arc sensor dimensions 8.3. Mounting plates for VA 1 DA VYX 001 VYX002 10 mm 10 mm 3 mm Figure 8.3-1. Mounting plate dimensions. VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264…

  • Page 16: Order Information

    Installation kit for flush mounting VB 263 Arc sensor, 6 m cable VA 1 DA-6 Arc sensor, 6 m cable VA 1 EH-6 (1P65) Arc sensor, 20 m cable VA 1 DA-20 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001…

  • Page 17: Reference Information

    P.O.Box 810 FIN-65101 Vaasa, Finland Visiting address: Yrittäjänkatu 15 Phone: +358 (0)20 753 3200 Fax: +358 (0)20 753 3205 24h support phone: Tel . +358 (0)20 753 3264 Email: vampsupport@vamp.fi VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264…

  • Page 18
    We reserve the rights to changes without prior notice VAMP Ltd Street address: Yrittäjänkatu 15 Phone: +358 20 753 3200 Post address: Fax: +358 20 753 3205 Box 810, FIN 65101 Vaasa, Internet: www.vamp.fi Finland Email: vamp@vamp.fi VM120.EN001…

File Specifications:

1360/1360538-120.pdf file (16 Sep 2023)

Accompanying Data:

VAMP 120 Power distribution unit PDF Operation & User’s Manual (Updated: Saturday 16th of September 2023 05:56:29 PM)

Rating: 4.4 (rated by 90 users)

Compatible devices: BASE, Sun Fire V1280, VP9559, PSA-16A3S, AP-S15HR, FlexPDU, RigSwitch, PSA-321.

Recommended Documentation:

Operation & User’s Manual (Text Version):

(Ocr-Read Summary of Contents of some pages of the VAMP 120 Document (Main Content), UPD: 16 September 2023)

  • 12, VAMP 120 Arc protection unit User manual VAMP Ltd 12 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 7. Technical data Auxiliary voltage Us 19 … 265 V dc / 40 … 265 V ac In (stby) 30mA IsensAct 20mA Iarc 120mA + (IsensAct x n); n = number of active sensors Tripping contacts Number 1 Rated voltage ≤250V ac/dc Continuous carry 5A Make and carry for 0.5s 30A Make and ca…

  • 17, VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 17 10. Reference information Manufacturer data: VAMP Ltd P.O.Box 810 FIN-65101 Vaasa, Finland Visiting address: Yrittäjänkatu 15 Phone: +358 (0)20 753 3200 Fax: +358 (0)20 753 3205 Service: VAMP Ltd P.O.Box 810 FIN-65101 Vaasa, Finland Visiting address: Yrittäjänkatu 15 Phone: +358 (0)20…

  • 2, VAMP 120 Arc protection unit User manual VAMP Ltd 2 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001

  • 5, VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 5 2. Unit configuration Figure 2-1. VAMP 120 dipswitch operations and sensor connection The unit is configured using the dipswitches: Dipswitches 1-5 (see Figure 2-1): If only one arc sensor in use, SENSOR 1 input should be used. • SW nr. 1 : if sensor input 2 is also required, SEN 1 sho…

  • 7, VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 7 The arc sensor can alternatively be mounted completely in the protected area with the help of a mounting plate VYX 01 (Z- shaped) or VYX 02 (L-shaped). (See Figure 8.3-1) 10mm Fastening screw4 x 15 Active part of the sensor Anchoring Sensor cable Figure 3.1-3. Arc sensor mounting pi…

  • 14, VAMP 120 VAMP 120 Arc protection unit User manual VAMP Ltd 14 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 8. Dimensions 8.1. VAMP 120 Figure 8.1-1. Arc protection unit VAMP 120 dimensions

  • 6, VAMP 120 Arc protection unit User manual VAMP Ltd 6 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 3. Sensors 3.1. Arc sensor VA 1 DA The arc sensor is a light sensitive element, which is activated by strong light. Arc sensors should be mounted in the switch- gear cubicles, in such a way that the light sensitive part (see Figure 3.1-2) covers the protected area as completely as possible. F…

  • 4, VAMP 120 Arc protection unit User manual VAMP Ltd 4 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 1. General This manual describes the general functions of the arc protection unit, it also includes mounting and configuration instructions. 1.1. Arc protection unit VAMP 120 Figure 1.1-1. Arc protection unit VAMP 120 1.2. Unit features VAMP 120 is a state of the art arc protec…

  • 3, VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 3 Table of content 1. General ………………………………………………………………………..4 1.1. Arc protection unit VAMP 120…………………………………….4 1.2. Unit features ……………………………………………………………….4 2. Unit configuration……………..…

  • 15, VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 15 8.2. VA 1 DA arc sensor 25 14 22 4 10 Figure 8.2-1. VA 1 DA arc sensor dimensions 8.3. Mounting plates for VA 1 DA 50 10 mm 3m m 44 59 25 15 15 26 50 50 30 10 mm 3 mm 44 59 15 15 26 30 VYX 001 VYX002 Figure 8.3-1. Mounting plate dimensions.

  • 11, VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 11 If overcurrent criteria is required simultaneously with light activation, a binary current signal has to be connected to X2- 15/16. This I> signal can e.g. be taken from a VAM 4C or VAMP 221 unit. The external reset is possible by correcting an auxiliary voltage to X2-17/18. The auxiliary boltage is connected…

  • 10, VAMP 120 Arc protection unit User manual VAMP Ltd 10 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 6. Connections *Connection for shield if shield sensor cable used (VA1DA-20s) Figure 6-1. VAMP 120 connection The VAMP 120 unit comprises two independent arc protection zones. Both zones have their own trip relay, trip 1 and trip 2. Trip 1 is controlled by sensor inputs 1 and 2. Trip is controlled…

  • 18, VM120.EN001 VAMP Ltd Street address: Yrittäjänkatu 15 Phone: +358 20 753 3200 Post address: Fax: +358 20 753 3205 Box 810, FIN 65101 Vaasa, Internet: www.vamp.fi Finland Email: [email protected] We reserve the rights to changes without prior notice

  • 9, VAMP 120 VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 9 5. Applications Every compartment is equipped with an arc sensor. Up to four sensors can be connected to the VAMP 120 unit. The trip relays are electromechanical and can be connected directly to control the circuit-breakers (see chapter Technical data). The VAMP 120 is suitable for small power generation pl…

Recommended: IM613-B, Enercell 61-184, Centrino Cleancontrol, NS-55E480A13A

Links & Tools

Operating Impressions, Questions and Answers:

Specifications:

1360/1360538-120.pdf file (15 Jan 2023)

Accompanying Data:

VAMP 120 Power distribution unit PDF Operation & User’s Manual (Updated: Sunday 15th of January 2023 11:28:50 AM)

Rating: 4.3 (rated by 38 users)

Compatible devices: OP1, SP-EVCP-T, DN-95620, PD-6359A, SIVACON S 8PQ Series, PSA-32A12S, 138-118, PowerPak 8I.

Recommended Documentation:

VAMP 120: Text of Operation & User’s Manual

(Ocr-Read Version Summary of Contents, UPD: 15 January 2023)

  • 12, VAMP 120 Arc protection unit User manual VAMP Ltd 12 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 7. Technical data Auxiliary voltage Us 19 … 265 V dc / 40 … 265 V ac In (stby) 30mA IsensAct 20mA Iarc 120mA + (IsensAct x n); n = number of active sensors Tripping contacts Number 1 Rated voltage ≤250V ac/dc Contin…

  • 9, VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 9 5. Applications Every compartment is equipped with an arc sensor. Up to four sensors can be connected to the VAMP 120 unit. The trip relays are electromechanical and can be connected directly to control the circuit-breakers (see chapter Technical …

  • 17, VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 17 10. Reference information Manufacturer data: VAMP Ltd P.O.Box 810 FIN-65101 Vaasa, Finland Visiting address: Yrittäjänkatu 15 Phone: +358 (0)20 753 3200 Fax: +358 (0)20 753 3205 Service: VAMP Ltd P.O.Box 810 FIN-65101 Vaasa, Finland Visiting address: Yritt…

  • 4, VAMP 120 Arc protection unit User manual VAMP Ltd 4 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 1. General This manual describes the general functions of the arc protection unit, it also includes mounting and configuration instructions. 1.1. Arc protection unit VAMP 120 Figure 1.1-1. Arc protection unit VAMP 120 1.2. Unit f…

  • 5, VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 5 2. Unit configuration Figure 2-1. VAMP 120 dipswitch operations and sensor connection The unit is configured using the dipswitches: Dipswitches 1-5 (see Figure 2-1): If only one arc sensor in use, SENSOR 1 input should be used. • SW n…

  • 15, VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 15 8.2. VA 1 DA arc sensor 25 14 22 4 10 Figure 8.2-1. VA 1 DA arc sensor dimensions 8.3. Mounting plates for VA 1 DA 50 10 mm 3m m 44 59 25 15 15 26 50 50 30 10 mm 3 mm 44 59 15 15 26 30 VYX 001 VYX002 Figure 8.3-1. Mounting plat…

  • 10, VAMP 120 Arc protection unit User manual VAMP Ltd 10 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 6. Connections *Connection for shield if shield sensor cable used (VA1DA-20s) Figure 6-1. VAMP 120 connection The VAMP 120 unit comprises two independent arc protection zones. Both zones have their own trip relay, trip 1 and trip 2. Trip 1 is controlled by sensor…

  • 2, VAMP 120 Arc protection unit User manual VAMP Ltd 2 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001

  • 13, VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 13 Voltage tests Insulation test voltage acc- to IEC 60255-5 2 kV, 50Hz, 1min Impulse test voltage acc- to IEC 60255-5 5 kV, 1.2/50us, 0.5J Mechanical tests Vibration test 2 … 13.2 Hz ±3.5mm 13.2 … 100Hz, ±1.0g Shock/Bump test acc. to IEC 60255-21-2 20g, 10…

  • 6, VAMP 120 Arc protection unit User manual VAMP Ltd 6 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 3. Sensors 3.1. Arc sensor VA 1 DA The arc sensor is a light sensitive element, which is activated by strong light. Arc sensors should be mounted in the switch- gear cubicles, in such a way that the light sensitive part (see Figure 3.1-2) covers the protected area …

  • 3, VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 3 Table of content 1. General ………………………………………………………………………..4 1.1. Arc protection unit VAMP 120…………………………………….4 1.2. Unit features …………………………

  • 16, VAMP 120 Arc protection unit User manual VAMP Ltd 16 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 9. Order information Unit UnitUnit Unit Ordering code Ordering codeOrdering code Ordering code VAMP 120 unit VAMP 120 Installation kit for flush mounting VB 263 Arc sensor, 6 m cable VA 1 DA-6 Arc sensor, 6 m cable VA 1 EH-6 (1P65)…

  • 7, VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 7 The arc sensor can alternatively be mounted completely in the protected area with the help of a mounting plate VYX 01 (Z- shaped) or VYX 02 (L-shaped). (See Figure 8.3-1) 10mm Fastening screw4 x 15 Active part of the sensor Anchoring Sensor cable Figure 3.1-3.…

VAMP 120: Recommended Instructions

ALPHA, Latitude KR954, ABR-2401b, UN40B7000WF, HWPG1

  • JG 8 Series POWER DISTRIBUTION UNIT JUICE GOOSE 7320 Ashcroft, Suite 104 Houston, Texas 77081 p: 713-772-1404 f: 713-772-7360 e: [email protected] www.juicegoose.com OWNERS MANUAL 06-04 JG 8 Series Owners Manua… page 1Monday, June 21, 2004 11:22 …

    JG 8 Series 4

  • Campetto 7 Underfloor distributor system Seite 1 / 10 Created 01.12.2013 ROEN Modified 01.12.2013 ROEN Object-ID 359749 Campetto 7 Underfloor distributor system Manual VERSION MODIFICATIONS 1.0 First edition 1.1 Editional changes …

    Campetto 7 10

  • 40 CD13DIN 26DIN 39DIN 52DINGW 40 501250x225x93,513M GW 40 502250x350x93,526MGW 40 503250x475x93,539MGW 40 504250x600x93,552MGW 40 516250x225x50GW 40 517250x350x50GW 40 518250x475x50GW 40 519250x600x50GW 40 531250x225x34GW 40 532250x350x34GW 40 533250x475x34GW 40 534250x600x34GW 40 536250x225x34GW 40 537250x350x34GW 40 538250x475x34GW 40 539250x600x34GW 40 526156x216x2GW 40 52 …

    40 CD Series 4

  • LIEBERT® TDU TRANSFORMER DISTRIBUTION UNITQuick Installation User Guide590-1811-501B/SL-23206_REV1 1SAVE THESE INSTRUCTIONS: This manual contains important instructions that are to be followed during installation and maintenance of the TDU.I M P O RTANT: Before installing, connecting to supply or operating your Liebert TDU, please review the Safety and Regulatory sheet. INSTALL ATION …

    Liebert TDU-3500RTL620 2

  • CRITO®185 Power Anschlussleiste 800 A / 1400 AConnection rail 800 A / 1400 ARegleta de conexión 800 A / 1400 Abornier de raccordement 800 A / 1400 AModulo verticale di connessione 800 A / 1400 A条形转接器 800 A / 1400 AAchtung: Vor Installations- oder Servicearbeiten Stromver -sorgung unterbrechen, um Unfälle zu vermeiden.Die Geräte müssen in einem passende …

    CRITO 185 Power 6

  • SAG582140600 System Application Guide Spec. No. 582140600 (Model 8100DB) Revision E, November 15, 2018 Page 1 of 67 SYSTEM OVERVIEW Description: -48 VDC Power Distribution System The NetSure™ 8100DB DC Power Distribution System is a -48 VDC Battery Distribution Fuse / Circuit Breaker Bay (BDF/CBB). • The NetSure™ 8100DB can be ordered as an 8-distribution panel or 6-distribution pane …

    NetSure 8100DB 67

  • hager1orion plus6L488400.56L488400.56L488400.5x 1 x 4 x 4 x 4 x 4M81310MontageanleitungNotice d’instructionsMounting instructionsMontage instructieMonteringsvejledningAsennusohjeMontasjeanvisningMonterings instruktionerIstruzioni di montaggioInstrucciones de montajeInstrućões de montagemMontážní návodUputstvo za montažuITESPTCZBAHRHULTGRDESEFRFINONLDKUpute za montažu …

    orion plus 16

  • System pro E powerInstruction handbookManuale istruzioniMontageanleitungInstructions de montageManuale de instruccionesInstrukcja montażowaWarning! Installation by person with electrotechnical expertise only.Lebensgefahr durch elektrischen Strom!Nur Elektrofachkräfte und elektrotechnischunterwiesene Personen dürfen die im folgendenbeschriebenen Arbeiten ausführen.Avvertenza! Fare installare …

    System pro E power 4

  • 4 WWW.CRISTEC.FR switchisopened.Normallyinthiscasethestatusledislidgreenandtheoutputisswitchedon.Dependingonthebatteryvoltagetheledstatuscanbedifferent.Withoutusingtheswitchinput,thevoltageguardwilljustfunctionasalowvoltageprotectionforyourbatter …

    Voltage Guard-70 2

Additional Information:

Popular Right Now:

Operating Impressions, Questions and Answers:

Arc flash protection unit

Publication version: V120/EN M/A 003

User manual

1 Arc p ro te c tio n unit VAMP 120 1 G e ne ra l VAMP 120

1. General

####### This manual describes the general functions of the arc protection

####### unit, it also includes mounting and configuration instructions.

1. Arc protection unit VAMP 120

Figure 1-1. Arc protection unit VAMP 120

1. Unit features

####### VAMP 120 is a state of the art arc protection unit for electrical

####### power distribution systems.

####### By using VAMP 120 in switchgears considerable safety

####### improvements are obtained in the form of minimized injury and

####### damage in case of an arc fault.

####### VAMP 120 is a “stand alone” system, which gives a compact

####### solution when the application doesn’t require overcurrent

####### measurement or when the overcurrent information is available

####### from the incomer protection relay or any other arc protection unit

####### (VAMP 221 / VAM 4C). It is possible to connect 4 arc sensors, of

####### the type VA 1 DA or VA 1 EH, to the VAMP 120 unit.

VAMP 120 2 Unit c o nfig ura tio n

2. Unit configuration

Figure 2-1. VAMP 120 dipswitch operations and sensor connection

####### The unit is configured using the dipswitches:

####### Dipswitches 1-5 (see Figure 2-1):

####### If only one arc sensor in use, SENSOR 1 input should be used.

  • SW nr. 1 : if sensor input 2 is also required, SEN 1

####### should be set to the left position.

  • SW nr. 2 and 3 : if sensor input 3 and 4 are used, SW nr. 2

####### and 3 should respectively be set to left

####### position.

  • SW nr. 4 : is setting the system selectivity. If set to the

####### left position, sensor nr. 1 and 2 will trip relay

####### T1. Accordingly sensor nr. 3 and 4 will trip

####### relay T2. The NC trip signal out put will

####### always work in parallel with T1. If SW nr. 4

####### is to the right, all four sensor channels will

####### activate both trip groups.

  • SW nr. 5 : is the selection of tripping criteria. If set to

####### the right, the unit will trip for light only. If set

####### to the left, the unit needs both light and

####### current information for tripping.

  • SW nr. 6 and 7 : the Latch switches enables latching of the

####### trip relays. When it is in ON position the

####### latching function is activated.

  • SW nr. 8 : is the configuration switch for sensor inputs

####### 2 and 3. If it is in “ON” position, sensor 2 or

####### 3 activation will make a common trip of both

####### T1 and T2. If it is in “OFF” position, sensor

####### 2 is linked to T1 and sensor 3 to T2.

VAMP 120 3 Se nso rs 3 A rc se nso r VA 1 DA

Figure 3-3. Arc sensor mounting picture.

4 Func tio ns VAMP 120

4. Functions

####### VAMP 120 includes an extensive self-supervision. The self-

####### supervision includes internal functions as well as all arc sensors.

Figure 4-1 Self-supervision block diagram

####### If an internal fault occurs the self-supervision relay is activated and

####### the ERROR-led is lit.

5 A p p lic a tio ns VAMP 120

Figure 5-2 Diesel power plant application

VAMP 120 6 C o nne c tio ns

6. Connections

*C o nne c tio n fo r shie ld if shie ld se nso r c a b le use d (VA 1DA — 20 s)
Figure 6-1. VAMP 120 connection

####### The VAMP 120 unit comprises two independent arc protection

####### zones. Both zones have their own trip relay, trip 1 and trip 2. Trip 1

####### is controlled by sensor inputs 1 and 2. Trip is controlled by sensors

####### 3 and 4.

####### Trip alarm is activated if either or both are tripping. If “T1=T2” dip

####### switch is at “on” position, both trip outputs will work in parallel for

####### any sensor activation.

####### If “S2=S3” dip switch is at “on” position, sensors 2 and 3 activation

####### will cause both T1 and T2 to trip. This is e. used for CB

####### compartment supervision where two zones are overlapping each

####### other.

VAMP 120 7 Te c hnic a l d a ta

7. Technical data

Auxiliary voltage

Us 19 – 265 V dc / 40 – 265 V ac
In (stby) 30mA
IsensAct 20mA
Iarc 120mA + (IsensAct x n);
n = number of active sensors

Trip contacts

Number of contacts 2
Rated voltage 250V ac/dc
Continuous carry 5A
Minimum making current 100 mA @ 24 Vdc
Typical operation time 7 ms ± 15%
Make and carry for 0 30A
Make and carry for 3s 15A
Breaking capacity DC (L/R=40ms)
at 48 Vdc:
at 110 Vdc:
at 220 Vdc:

1 A
0 A
0 A
Contact material AgNi 90/
Terminal block:
-Phoenix MVSTBW or equivalent

Maximum wire dimension:
2 mm 2 (13-14 AWG)

Signal contacts

Number of contacts 1
Rated voltage 250V ac/dc
Continuous carry 3A
Minimum making current 100 mA @ 24 Vdc
Breaking capacity DC (L/R=40ms)
at 48 Vdc:
at 110 Vdc:
at 220 Vdc:

1 A
0 A
0 A
Contact material AgNi 0 gold plated
Terminal block:
-Phoenix MVSTBW or equivalent

Maximum wire dimension:
2 mm 2 (13-14 AWG)

I>> Input & Reset input

Rated voltage 18 – 265 Vac/dc
Rated current / input 5 mA
Number of inputs 2

7 Te c hnic a l d a ta VAMP 120

Disturbance tests

Test S tandard & Test class / level Test value
Emission
EN 61000-6-4 / IEC 60255-

  • Conducted EN 55011, Class A / IEC 60255-25 0 – 30 MHz

  • Emitted EN 55011, Class A / IEC 60255-25 30 – 1 000 MHz

Immunity EN 61000-6-2 / IEC 60255-

  • 1Mhz damped oscillatory wave IEC 60255-22-1 ±2 CM, ±2 DM

  • Static discharge (ESD)

  • Emitted HF field

EN 61000-4-2 Level 4 / IEC 60255-22-2 Class 4

EN 61000-4-3 Level 3 / IEC 60255-22-

±8 kV contact, ±16 kV air

80 — 2700 MHz, 10 V/m

  • Fast transients (EFT) EN 61000-4-4 Level 4 / IEC 60255-22-4 Class A ±4 kV 5/50 ns, 5 kHz

  • Surge EN 61000-4-5 Level 4 / IEC 60255-22-5 ±4 kV, 1/50 μs, CM
    ±2 kV, 1/50 μs, DM

  • Conducted HF field EN 61000-4-6 Level 3 / IEC 60255-22-6 0 — 80 MHz, 10 Vemf

  • Power-frequency magnetic field
    EN 61000-4-8 300A/m (continuous), 1000A/m 1- 3s

  • Pulse magnetic field EN 61000-4-9 Level 5 1000A/m, 1/50 μs

  • Voltage interruptions EN 61000-4-29 / IEC 60255-11 30%/1s, 60%/0, 100%/0

  • Voltage alternative component EN 61000-4-17 / IEC 60255-11 15% of operating voltage (DC) / 10min

  • Voltage dips and short interruptions EN 61000-4- 11 30%/10ms, 100%/10ms, 60%/100ms
    >95%/5000ms

Electrical safety tests

Test S tandard & Test class / level Test value

  • Impulse voltage withstand EN 60255-5, Class III 5 kV, 1/50 μs

  • Dielectric test EN 60255-5, Class III 2 kV, 50 Hz

  • Insulation resistance EN 60255-

  • Protective bonding resistance EN 60255-

  • Power supply burden IEC 60255-

8 VA MP 120 p a ne l
m o unting

8 Dim e nsio ns VAMP 120

8. Dimensions

8. VAMP 120 panel mounting

VAMP 120 8 Dim e nsio ns 8 VA MP d in ra il m o unting

8. VAMP din rail mounting

VAMP 120 9 O rd e r info rm a tio n

9. Order information

####### Unit Ordering code

####### VAMP 120 unit V

####### Installation kit for flush mounting V120-F-KIT

####### Arc sensor, 6 m cable VA 1 DA-

####### Arc sensor, 6 m cable VA 1 EH-6 (IP65)

####### Arc sensor, 20 m cable VA 1 DA-

Table of Contents for VAMP 120:

  • VAMP 120 Arc protection unit User manual

  • VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 15 8.2. VA 1 DA arc sensor 25 14 22 4 10 Figure 8.2-1. VA 1 DA arc sensor dimensions 8.3. Mounting plates for VA 1 DA 50 10 mm 3m m 44 59 25 15 15 26 50 50 30 10 mm 3 mm 44 59 15 15 26 30 VYX 001 VYX002 Figure 8.3-1. Mounting plate dimensions.

  • VM120.EN001 VAMP Ltd Street address: Yrittäjänkatu 15 Phone: +358 20 753 3200 Post address: Fax: +358 20 753 3205 Box 810, FIN 65101 Vaasa, Internet: www.vamp.fi Finland Email: [email protected] We reserve the rights to changes without prior notice

  • VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 3 Table of content 1. General ………………………………………………………………………..4 1.1. Arc protection unit VAMP 120…………………………………….4 1.2. Unit features ……………………………………………………………….4 2. Unit configuration………………………………………………………….5 3. Sensors ………………………………………..

  • VAMP 120 Arc protection unit User manual VAMP Ltd 8 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 4. Functions VAMP 120 includes an extensive self-supervision. The self- supervision includes internal functions as well as all arc sensors. Figure 4-1. Self-supervision block diagram If an internal fault occurs the self-supervision

  • VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 17 10. Reference information Manufacturer data: VAMP Ltd P.O.Box 810 FIN-65101 Vaasa, Finland Visiting address: Yrittäjänkatu 15 Phone: +358 (0)20 753 3200 Fax: +358 (0)20 753 3205 Service: VAMP Ltd P.O.Box 810 FIN-65101 Vaasa, Finland Visiting address: Yrittäjänkatu 15 Phone: +358 (0)20 753

  • VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 7 The arc sensor can alternatively be mounted completely in the protected area with the help of a mounting plate VYX 01 (Z- shaped) or VYX 02 (L-shaped). (See Figure 8.3-1) 10mm Fastening screw4 x 15 Active part of the sensor Anchoring Sensor cable Figure 3.1-3. Arc sensor mounting picture.

  • VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 13 Voltage tests Insulation test voltage acc- to IEC 60255-5 2 kV, 50Hz, 1min Impulse test voltage acc- to IEC 60255-5 5 kV, 1.2/50us, 0.5J Mechanical tests Vibration test 2 … 13.2 Hz ±3.5mm 13.2 … 100Hz, ±1.0g Shock/Bump test acc. to IEC 60255-21-2 20g, 1000 bumps/dir. Environmental conditions

  • VAMP 120 Arc protection unit User manual VAMP Ltd 14 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 8. Dimensions 8.1. VAMP 120 Figure 8.1-1. Arc protection unit VAMP 120 dimensions

  • VAMP 120 Arc protection unit User manual VAMP Ltd 10 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 6. Connections *Connection for shield if shield sensor cable used (VA1DA-20s) Figure 6-1. VAMP 120 connection The VAMP 120 unit comprises two independent arc protection zones. Both zones have their own trip relay, trip 1 and trip 2. Trip 1 is controlled by sensor inputs 1 and 2. Trip is controlled

  • VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 11 If overcurrent criteria is required simultaneously with light activation, a binary current signal has to be connected to X2- 15/16. This I> signal can e.g. be taken from a VAM 4C or VAMP 221 unit. The external reset is possible by correcting an auxiliary voltage to X2-17/18. The auxiliary boltage is co

  • VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 5 2. Unit configuration Figure 2-1. VAMP 120 dipswitch operations and sensor connection The unit is configured using the dipswitches: Dipswitches 1-5 (see Figure 2-1): If only one arc sensor in use, SENSOR 1 input should be used. • SW nr. 1 : if sensor input 2 is also required, SEN 1

  • VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 9 5. Applications Every compartment is equipped with an arc sensor. Up to four sensors can be connected to the VAMP 120 unit. The trip relays are electromechanical and can be connected directly to control the circuit-breakers (see chapter Technical data). The VAMP 120 is suitable for small power generation plants where light is the only crite

Questions, Opinions and Exploitation Impressions:

You can ask a question, express your opinion or share our experience of VAMP 120 device using right now.

[Page 1] VAMP 120

VAMP 120 Arc protection unit User manual

[Page 2] VAMP 120

VAMP 120 Arc protection unit User manual VAMP Ltd 2 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001

[Page 3] VAMP 120

VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 3 Table of content 1. General ………………………………………………………………………..4 1.1. Arc pr…

[Page 4] VAMP 120

VAMP 120 Arc protection unit User manual VAMP Ltd 4 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 1. General This manual describes the general functions of the arc protection unit, it also includes mounting and configura…

[Page 5] VAMP 120

VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 5 2. Unit configuration Figure 2-1. VAMP 120 dipswitch operations and sensor connection The unit is configured using the…

[Page 6] VAMP 120

VAMP 120 Arc protection unit User manual VAMP Ltd 6 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 3. Sensors 3.1. Arc sensor VA 1 DA The arc sensor is a light sensitive element, which is activated by strong light. Arc…

[Page 7] VAMP 120

VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 7 The arc sensor can alternatively be mounted completely in the protected area with the help of a mounting plate VYX 01 (Z- shape…

[Page 8] VAMP 120

VAMP 120 Arc protection unit User manual VAMP Ltd 8 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 4. Functions VAMP 120 includes an extensive self-supervision. The self- supervision includes internal functions as well as …

[Page 9] VAMP 120

VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 9 5. Applications Every compartment is equipped with an arc sensor. Up to four sensors can be connected to the VAMP 120 unit. T…

[Page 10] VAMP 120

VAMP 120 Arc protection unit User manual VAMP Ltd 10 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 6. Connections *Connection for shield if shield sensor cable used (VA1DA-20s) Figure 6-1. VAMP 120 connection The VA…

[Page 11] VAMP 120

VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 11 If overcurrent criteria is required simultaneously with light activation, a binary current signal has to be connected to X2- 1…

[Page 12] VAMP 120

VAMP 120 Arc protection unit User manual VAMP Ltd 12 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 7. Technical data Auxiliary voltage Us 19 … 265 V dc / 40 … 265 V ac In (stby) 30mA IsensAct 20mA Iarc 120mA +…

[Page 13] VAMP 120

VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 13 Voltage tests Insulation test voltage acc- to IEC 60255-5 2 kV, 50Hz, 1min Impulse test voltage acc- to IEC 60255-5 5 kV…

[Page 14] VAMP 120

VAMP 120 Arc protection unit User manual VAMP Ltd 14 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 8. Dimensions 8.1. VAMP 120 Figure 8.1-1. Arc protection unit VAMP 120 dimensions

[Page 15] VAMP 120

VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 15 8.2. VA 1 DA arc sensor 25 14 22 4 10 Figure 8.2-1. VA 1 DA arc sensor dimensions 8.3. Mounting plates for VA 1 DA 50 1…

[Page 16] VAMP 120

VAMP 120 Arc protection unit User manual VAMP Ltd 16 VAMP 24h support phone : +358 (0)20 753 3264 VM120.EN001 9. Order information Unit UnitUnit Unit Ordering code Ordering codeOrdering code Ordering code VAMP 120 unit …

[Page 17] VAMP 120

VAMP Ltd Arc protection unit User manual VAMP 12 0 VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264 17 10. Reference information Manufacturer data: VAMP Ltd P.O.Box 810 FIN-65101 Vaasa, Finland Visiting address: Yrittäjänk…

[Page 18] VAMP 120

VM120.EN001 VAMP Ltd Street address: Yrittäjänkatu 15 Phone: +358 20 753 3200 Post address: Fax: +358 20 753 3205 Box 810, FIN 65101 Vaasa, Internet: www.vamp.fi Finland Email: [email protected] We reserve the rights t…

Понравилась статья? Поделить с друзьями:
  • Каждое из руководств в мире
  • Нитросорбид инструкция по применению цена отзывы аналоги таблетки цена инструкция
  • Холодильник liebherr сервис мануал
  • Как выписать ребенка из квартиры через госуслуги пошаговая инструкция
  • Вакцина адсм инструкция по применению взрослым