KEOR LP 1, 2, 3 kVA
26
26
28
30
31
34
39
40
43
25
Related Manuals for LEGRAND Keor LP
Summary of Contents for LEGRAND Keor LP
-
Page 1: Table Of Contents
KEOR LP 1, 2, 3 kVA Index 1 Introduction 2 Condition of use 3 LED Panel 4 Rear Panel 5 Installation 6 Functions and Signal 7 UPS software 8 Possible malfunctioning 9 Technical features…
-
Page 2: Introduction
• The front control panel is provided for manual operations; Do not press on the panel with sharp or pointed objects. • The UPS Keor LP has been designed to work in closed, clean rooms where there are no inflammable liquids or corrosive substances and where it is not too damp.
-
Page 3
KEOR LP 1, 2, 3 kVA Do not place the UPS in a dusty or corrosive environment or near any flammable objects. This UPS is not designed for outdoor use. 0%~90% • Keep the ventilation slits clean to dissipate the heat of the UPS. -
Page 4: Led Panel
® 3 LED Panel Control Symbol Description a. UPS Power-On Switch (Press and hold until the buzzer beeps.) b. Alarm silence c. Error Code Display Mode After an alarm, press to mute the alarm buzzer and show an Error Code. (Do not hold for > 1 second.) UPS Power-Off Switch (Press and hold until the buzzer beeps.) a.
-
Page 5
KEOR LP 1, 2, 3 kVA Symbol Description Indicator 1. Steadily on indicates normal utility voltage. Blinking indicates insufficient utility voltage for the full load. Off indicates abnormal Normal utility voltage. Mode LED 2. In Battery/Load Test Mode indicates battery capacity is 50%. -
Page 6: Rear Panel
® 4 Rear panel 3 101 54 3 101 56 3 101 58 3 101 55 3 101 57 3 101 59 1. Slot for optional communication cards 2. Emergency Power Off (EPO) dry contact signal inputs 3. NA 4. RS-232 port 5.
-
Page 7: Installation
KEOR LP 1, 2, 3 kVA 5 Installation Unpacking Inspect the UPS upon receipt After removing the packing foam please be careful handling the UPS while it is still in the plastic bag and check for the following standard package contents : http://ups.legrand.com/biblioteca/…
-
Page 8
® 5 Installation The following main connections are available on the rear of the uninterruptible power supply : • Output sockets (6) and input connector (8). • Socket for connecting computer serial interface RS232 (9 female pins) [4]: required when using the diagnostic and shutdown management software. -
Page 9
KEOR LP 1, 2, 3 kVA five seconds. At the same time, the fan at the front of the UPS will start operating. 5. Press and hold the ON button for approximately one second to start the UPS. The buzzer will beep and the LED indicators will shine after 1-5 seconds. -
Page 10: Functions And Signal
® 6 Functions and Signals Beep Codes The following table contains common UPS statuses with their beep codes. UPS Status Beep Code UPS faulty, Inverter shut down. All functions inhibited. Long Continuous Beep Control keypad error Long Continuous Beep UPS faulty, loads continue to be supplied via Inverter or Bypass. Single beep every two seconds In battery mode Single beep once per second…
-
Page 11
KEOR LP 1, 2, 3 kVA The table below provides a summary of the UPS operating modes under various utility AC power source and battery conditions. Utility Condition UPS Operating Mode LEDs Working power starts after approximately LED ON 5 seconds, LEDs on the panel will blink and… -
Page 12
® 6 Functions and Signals When Utility is Abnormal or Absent The operating mode of the UPS under abnormal utility conditions is illustrated as follows. Figure 5.3 1. When the utility is abnormal the UPS will direct the battery energy automatically to the Inverter without delay and turn off the charger and AC/DC converter. -
Page 13
KEOR LP 1, 2, 3 kVA 1. Generally, modern electronics and IT equipment generate an inrush current when switching on. The amount of inrush current varies from equipment to equipment, sometimes as high as six times rated capacity, other times negligible. To prevent severe damage to its inverter caused by the inrush produced by the loads, the UPS is equipped with an electronic overload-protection feature as standard. -
Page 14
® 6 Functions and Signals Overheating If the UPS overheats when the utility is normal it will switch into bypass mode. The UPS will switch back to inverter mode when the overheating is eliminated. If overheating occurs when the utility is abnormal the buzzer will beep continuously and the Fault will shine. -
Page 15: Ups Software
KEOR LP 1, 2, 3 kVA 7 UPS software From the website www.ups.legrand.com it is possible to download UPS software. This software can be used for the following functions: — Automatic shutdown of the local computer — UPS parameters reading…
-
Page 16: Possible Malfunctioning
® 8 Possible malfunctioning Troubleshooting Problem Check Items Solution 1. Check for proper battery connection. Measure battery voltage to ensure that batteries are charged and healthy. Recharge batteries for 8 1. Er05,Er24 hours if necessary. Simulate utility outage to verify that UPS is able to provide DC backup.
-
Page 17
KEOR LP 1, 2, 3 kVA Problem Check Items Solution The UPS switches into 1. A power strip is battery mode and then back connected to the 1. Do not use the power strip. into utility mode when a UPS. See if there 2. -
Page 18
® 8 Possible malfunctioning Error Codes When the Fault LED is lit press the ON button briefly to check the error code. The error codes 1, 2, 4, 8, and 16 are represented by the four bar LEDs 25%, 50%, 75%, and 100%, and the Overload LED Each LED represents a number as shown in the figure below. -
Page 19: Technical Features
KEOR LP 1, 2, 3 kVA 9 Technical features 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 1000 VA 2000 VA 3000 VA Capacity when input voltage is 210~240Vac PF=0.9 (900/1800/2700W) Power Factor when input voltage is 185~260Vac PF=0.8 (800/1600/2400W)
-
Page 20
® 9 Technical features 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 <105% continuous 106-120% for 30 seconds Line 121-150% for 10 seconds mode >150% Immediately transfer to bypass. Buzzer continuously alarms. -
Page 21
KEOR LP 1, 2, 3 kVA 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 Battery Recharge time (to 90%) DC start Self By panel button or software control… -
Page 22
® 9 Technical features 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 Unit Dimensions 236 × 144 × 367 322 x 151 x444 322 × 189 × 444 (HxWxD in mm) Physical Weight…
(Ocr-Read Summary of Contents of some pages of the LEGRAND KEOR LP Document (Main Content), UPD: 02 April 2023)
-
128, 128 ® 8 Problemen oplossen Controleer of alle kabels correct zijn aangesloten als de UPS niet goed werkt. Zoek vervolgens in onderstaande tabel het probleem en de voorgestelde oplossing. Neem contact op met de technische dienst als het probleem aanhoudt. Situatie Te controleren Oplossing Controlelampje Alarm 1 2 . Lees de foutcode (zie volgende pagina) weergeven door de combina- tie van de leds en …
-
115, LEGRAND KEOR LP 115 KEOR LP 1, 2, 3 kVA NL • Plaats de UPS niet in een stoffige of agressieve omgeving of in de nabijheid van brandbare objecten. Deze UPS is niet ontworpen voor buiten gebruik. • Houd de ventilatieopeningen schoon en bedek ze niet, zodat de interne warmte van de UPS kan wor- den afgevoerd. Plaats niets op de UPS. Bewaar steeds 20 cm afstand tussen het achterpaneel van de UPS en de muur of andere obstakels. • Gebruik een geaarde kabel …
-
95, 95 KEOR LP 1, 2, 3 kVA ES Indicadores luminosos LED Símbolo Descripción LED Modalidad normal 1 2 1. El led encendido jo indica que la tensión eléctrica de red es normal. Si en cambio destella indica que la tensión eléctrica de red es insuciente para la carga completa. El led apagado indica una tensión eléctrica de red anómala. 2. En modalidad Prueba batería/carga, indica la capacidad de las bater…
-
104, LEGRAND KEOR LP 104 ® 6 Funciones y señalizaciones Recalentamiento del SAI Si el SAI se recalienta en condición de alimentación de red normal pasa a la modalidad bypass. Vuelve a la modalidad inverter sólo cuando se haya eliminado el recalentamiento. En caso de recalentamiento, en el momento en que la red presente anomalías, la señal acústica emite un beep continuo, el indicador luminoso 1 2 de avería se enciende y el SAI …
-
4, 4 1 Introduction ® Le Keor LP est une Alimentation Sans Interruption (ASI) conçue pour une utilisation domestique, commercial ou industrielle. Ce manuel contient les informations concernant les modèles ASI Keor LP 1000, ,2000,3000 kVA. Lire attentivement les consignes de sécurité que vouz trouvez dans l’emballage et respecter les instructions contenues dans ce livret avant de procéder à l’installation de l’onduleur. En cas de problème concernant l…
-
90, 90 ® 9 Technische Daten MODELL ARTIKEL 3 101 54 3 101 55 3 101 56 3 101 57 3 101 58 3 101 59 Gewichte und Maße Abmessung (H x L x T) (mm) 236 × 144 × 367 322 x 151 x444 322 × 189 × 444 Gewicht (kg) 10kg 16,5kg 22,5kg Umgebung Betriebstemperatur 0-40°C Geräuschpegel < 50 dBA Feuchtigkeit 0-90% (nicht kondensierend) Schnittstelle Schnittstellentyp RS-232 , EPO Slots Dry contact, SNMP Andere Funktionen Statischer Bypass Periodischer Batterietest Standard und…
-
105, 105 KEOR LP 1, 2, 3 kVA ES 7 Software Comprobar la disponibilidad y descargar el software del SAI desde la página web www.ups. legrand.com. Este software puede utilizarse para las funciones siguientes: — Parada automática del ordenador local conectado al SAI a través del RS232. — Lectura de los parámetros del SAI. Conexión Conectar el cable de interfaz RS232 entre el puerto que se encuentra en la parte trasera del SAI y el puerto de interfaz de…
-
32, 32 ® 5 Installation The following main connections are available on the rear of the uninterruptible power supply : • Output sockets (6) and input connector (8). • Socket for connecting computer serial interface RS232 (9 female pins) [4]: required when using the diagnostic and shutdown management software. • Presetting for the connection of additional batteries [5]. True RS-232 Pin Assignments: …
-
62, 62 ® 8 Risoluzione dei problemi Troubleshooting Problema Cosa verificare Soluzione Spia Guasto. Leggere il codice errore (vedere pagina seguente) visualizzato tramite la sequenza LED e vericare i guasti come segue: 1. Er05,Er24 1 2 1. Vericare che la batteria sia correttamente collegata. Misurare la tensione delle batterie per accertarsi che sia carica e in buono stato. Ricaricatela per 8 ore se nec…
-
89, 89 KEOR LP 1, 2, 3 kVA DE MODELL ARTIKEL 3 101 54 3 101 55 3 101 56 3 101 57 3 101 58 3 101 59 Batterie Auadezeit (zu 90%) 3 Stunden Inbetriebnahme im AC-Modus Ja Selbstdiagnose Durch Drücken der Taste am Display oder durch eine Software-Steuerung Display an der Vorderseite LED Auslastung/Batterieladung/Batterie Modus/ Normaler Modus/Bypass-Modus/Self-Test/Schwach/ Batterie defekt/Verkabelung defekt/Störung/Überlast Taste ON (Alarm quittie…
-
91, 91 KEOR LP 1, 2, 3 kVA ES Tabla de contenidos 1 Introducción 92 2 Condiciones de uso 92 3 Panel LEDs 94 4 Panel trasero 96 5 Instalación 97 6 Funciones y señalizaciones 100 7 Software 105 8 Resolución de los problemas 106 9 Características técnicas 109
… -
150, 150 ® 8 Возможные неисправности Поиск и устранение неисправностей Неисправность Что проверяется Действия по устранению «». (Er)* (. ), …
-
27, LEGRAND KEOR LP 27 KEOR LP 1, 2, 3 kVA EN Do not place the UPS in a dusty or corrosive environment or near any flammable objects. This UPS is not designed for outdoor use. • Keep the ventilation slits clean to dissipate the heat of the UPS. To prevent overheating of the UPS keep all ventilation openings free from obstruction, and do not place anything on top of the UPS. Keep the UPS rear panel 20 cm away from the wall or other obstructions • Use grounded power cable to conn…
-
160, Legrand reserves at any time the right to modify the contents of this booklet and to communicate, in any form and modality, the changes brought to the same. World Headquarters and International Department 87045 LIMOGES CEDEX FRANCE : 33 5 55 06 87 87 Fax : 33 5 55 06 74 55 www.legrandelectric.com ®
… -
63, 63 KEOR LP 1, 2, 3 kVA IT Problema Cosa verificare Soluzione UPS normale ma non c’è uscita al carico. Vericare che tutti i cavi d’alimentazione siano collegati correttamente. Se il problema persiste contattate il vostro rivenditore locale Legrand per ottenere assistenza tecnica. L’UPS passa a batteria e torna a rete quando un carico è collegato e non smette di passare da una modalità all’altra. 1. Una presa multipla è collegata all’UPS. Veric…
-
28, 28 ® 3 LED Panel 1 2 Control Key Symbol Description ON 1 2 a. UPS Power-On Switch (Press and hold until the buzzer beeps.) b. Alarm silence c. Error Code Display Mode After an alarm, press to mute the alarm buzzer and show an Error Code. (Do not hold for > 1 second.) OFF 1 2 UPS Power-O Switch (Press and hold until the buzzer beeps.) Self-Test 1 2 a. Commands the UPS to perform self-testing (Press and hold until the buzzer beeps.) b. …
-
133, 133 KEOR LP 1, 2, 3 kVA NL MODEL ITEM 3 101 54 3 101 55 3 101 56 3 101 57 3 101 58 3 101 59 Batterij Oplaadtijd (tot 90%) 3 uur Opstarten op DC Ja Auto- diagnose Met knop op paneel of met besturingssoftware Voorpaneel Led Belastingsniveau/Batterijniveau/Batterijmodus/Normale modus/Bypassmodus/Autotest/Zwakke of defecte batterij/ Defecte bekabeling/Storing/Overbelasting Knop ON (alarm stil)/OFF (test/knop niveau) Geluidssignaal Batterijmodus…
Table of Contents for LEGRAND KEOR LP:
-
44 ® 9 Technical features MODEL ITEM 3 101 54 3 101 55 3 101 56 3 101 57 3 101 58 3 101 59 Output Overload Capacity (tolerance +/-1%) Line mode <105% continuous 106-120% for 30 seconds 121-150% for 10 seconds >150% Immediately transfer to bypass. Buzzer continuously alarms. Battery mode <105% continuous 106-120% for 30 seconds 121-150% for 10 seconds >150% Immediately shuts down. Buzzer continuously alarms. Bypass mode <105% continuous
-
27 KEOR LP 1, 2, 3 kVA EN Do not place the UPS in a dusty or corrosive environment or near any flammable objects. This UPS is not designed for outdoor use. • Keep the ventilation slits clean to dissipate the heat of the UPS. To prevent overheating of the UPS keep all ventilation openings free from obstruction, and do not place anything on top of the UPS. Keep the UPS rear panel 20 cm away from the wall or other obstructions • Use grounded power cable
-
39 KEOR LP 1, 2, 3 kVA EN 7 UPS software From the website www.ups.legrand.com it is possible to download UPS software. This software can be used for the following functions: — Automatic shutdown of the local computer — UPS parameters reading Connection It is possible to to use RS-232 communication Connect a male RS-232 connector to the UPS communication port. Connect the female RS-232 connector to the computer.
-
25 KEOR LP 1, 2, 3 kVA EN Index 1 Introduction 26 2 Condition of use 26 3 LED Panel 28 4 Rear Panel 30 5 Installation 31 6 Functions and Signal 34 7 UPS software 39 8 Possible malfunctioning 40 9 Technical features 43
-
46 ® 9 Technical features MODEL ITEM 3 101 54 3 101 55 3 101 56 3 101 57 3 101 58 3 101 59 Physical Unit Dimensions (HxWxD in mm) 236 × 144 × 367 322 x 151 x444 322 × 189 × 444 Weight 10kg 16.5kg 22.5kg Environmental Operating Temperature 0-40°C Noise Level < 50 dBA Relative Humidity 0-90% (without condensation) Interface Interface Type RS-232 , EPO Slots Dry contact, SNMP Other function Static Bypass Peroidic Battery tes
-
42 ® 8 Possible malfunctioning Error Codes When the Fault LED 1 2 is lit press the ON button 1 2 briefly to check the error code. The error codes 1, 2, 4, 8, and 16 are represented by the four bar LEDs 25%, 50%, 75%, and 100%, and the Overload LED 1 2 . Each LED represents a number as shown in the figure below. For example, if the 25%, 50%, and 100% bar LEDs are lit, the error code is therefore 8 + 2 + 1 = 11, or Er11, which indicates that th
-
37 KEOR LP 1, 2, 3 kVA EN 1. Generally, modern electronics and IT equipment generate an inrush current when switching on. The amount of inrush current varies from equipment to equipment, sometimes as high as six times rated capacity, other times negligible. To prevent severe damage to its inverter caused by the inrush produced by the loads, the UPS is equipped with an electronic overload-protection feature as standard. If the UPS
-
36 ® 6 Functions and Signals When Utility is Abnormal or Absent The operating mode of the UPS under abnormal utility conditions is illustrated as follows. 1. When the utility is abnormal the UPS will direct the battery energy automatically to the Inverter without delay and turn off the charger and AC/DC converter. The inverter reverts DC to AC to supply energy to the output load connected wit
-
32 ® 5 Installation The following main connections are available on the rear of the uninterruptible power supply : • Output sockets (6) and input connector (8). • Socket for connecting computer serial interface RS232 (9 female pins) [4]: required when using the diagnostic and shutdown management software. • Presetting for the connection of additional batteries [5]. True RS-232 Pin Assignments: Pin 3: RS-232 Rx Pin 2: RS-232 Tx Pin 5: Ground EPO Pin Assignments: 1 2 1 = REPO+ 2 = Ground To enable the EPO function short pins 1 and 2. Proceed to t
-
29 KEOR LP 1, 2, 3 kVA EN LED Indicator Symbol Description Normal Mode LED 1 2 1. Steadily on indicates normal utility voltage. Blinking indicates insucient utility voltage for the full load. O indicates abnormal utility voltage. 2. In Battery/Load Test Mode indicates battery capacity is 50%. Battery Mode LED 1 2 1. Indicates load supplied by battery power. 2. In Battery/Load Test Mode indicates batte
-
38 ® 6 Functions and Signals Overheating If the UPS overheats when the utility is normal it will switch into bypass mode. The UPS will switch back to inverter mode when the overheating is eliminated. If overheating occurs when the utility is abnormal the buzzer will beep continuously and the Fault 1 2 will shine. The UPS will cut off supply to the loads. Inverter Current or Voltage Out of Tolerance If the UPS inverter delivers over-curr
-
43 KEOR LP 1, 2, 3 kVA EN 9 Technical features MODEL ITEM 3 101 54 3 101 55 3 101 56 3 101 57 3 101 58 3 101 59 Capacity VA 1000 VA 2000 VA 3000 VA Power Factor when input voltage is 210~240Vac PF=0.9 (900/1800/2700W) when input voltage is 185~260Vac PF=0.8 (800/1600/2400W) when input voltage is 160~300Vac PF=0.7 (700/1400/2100W) Input Voltage Rating 110/140/160-300 VAC (Based on load percentage 0-25% / 25-50% / 50-100%)
Questions, Opinions and Exploitation Impressions:
You can ask a question, express your opinion or share our experience of LEGRAND KEOR LP device using right now.
-
Contents
-
Table of Contents
-
Bookmarks
Quick Links
Index
KEOR LP 1, 2, 3 kVA
26
26
28
30
31
34
39
40
43
25
Related Manuals for LEGRAND Keor LP
Summary of Contents for LEGRAND Keor LP
-
Page 1: Table Of Contents
KEOR LP 1, 2, 3 kVA Index 1 Introduction 2 Condition of use 3 LED Panel 4 Rear Panel 5 Installation 6 Functions and Signal 7 UPS software 8 Possible malfunctioning 9 Technical features…
-
Page 2: Introduction
• The front control panel is provided for manual operations; Do not press on the panel with sharp or pointed objects. • The UPS Keor LP has been designed to work in closed, clean rooms where there are no inflammable liquids or corrosive substances and where it is not too damp.
-
Page 3
KEOR LP 1, 2, 3 kVA Do not place the UPS in a dusty or corrosive environment or near any flammable objects. This UPS is not designed for outdoor use. 0%~90% • Keep the ventilation slits clean to dissipate the heat of the UPS. -
Page 4: Led Panel
® 3 LED Panel Control Symbol Description a. UPS Power-On Switch (Press and hold until the buzzer beeps.) b. Alarm silence c. Error Code Display Mode After an alarm, press to mute the alarm buzzer and show an Error Code. (Do not hold for > 1 second.) UPS Power-Off Switch (Press and hold until the buzzer beeps.) a.
-
Page 5
KEOR LP 1, 2, 3 kVA Symbol Description Indicator 1. Steadily on indicates normal utility voltage. Blinking indicates insufficient utility voltage for the full load. Off indicates abnormal Normal utility voltage. Mode LED 2. In Battery/Load Test Mode indicates battery capacity is 50%. -
Page 6: Rear Panel
® 4 Rear panel 3 101 54 3 101 56 3 101 58 3 101 55 3 101 57 3 101 59 1. Slot for optional communication cards 2. Emergency Power Off (EPO) dry contact signal inputs 3. NA 4. RS-232 port 5.
-
Page 7: Installation
KEOR LP 1, 2, 3 kVA 5 Installation Unpacking Inspect the UPS upon receipt After removing the packing foam please be careful handling the UPS while it is still in the plastic bag and check for the following standard package contents : http://ups.legrand.com/biblioteca/…
-
Page 8
® 5 Installation The following main connections are available on the rear of the uninterruptible power supply : • Output sockets (6) and input connector (8). • Socket for connecting computer serial interface RS232 (9 female pins) [4]: required when using the diagnostic and shutdown management software. -
Page 9
KEOR LP 1, 2, 3 kVA five seconds. At the same time, the fan at the front of the UPS will start operating. 5. Press and hold the ON button for approximately one second to start the UPS. The buzzer will beep and the LED indicators will shine after 1-5 seconds. -
Page 10: Functions And Signal
® 6 Functions and Signals Beep Codes The following table contains common UPS statuses with their beep codes. UPS Status Beep Code UPS faulty, Inverter shut down. All functions inhibited. Long Continuous Beep Control keypad error Long Continuous Beep UPS faulty, loads continue to be supplied via Inverter or Bypass. Single beep every two seconds In battery mode Single beep once per second…
-
Page 11
KEOR LP 1, 2, 3 kVA The table below provides a summary of the UPS operating modes under various utility AC power source and battery conditions. Utility Condition UPS Operating Mode LEDs Working power starts after approximately LED ON 5 seconds, LEDs on the panel will blink and… -
Page 12
® 6 Functions and Signals When Utility is Abnormal or Absent The operating mode of the UPS under abnormal utility conditions is illustrated as follows. Figure 5.3 1. When the utility is abnormal the UPS will direct the battery energy automatically to the Inverter without delay and turn off the charger and AC/DC converter. -
Page 13
KEOR LP 1, 2, 3 kVA 1. Generally, modern electronics and IT equipment generate an inrush current when switching on. The amount of inrush current varies from equipment to equipment, sometimes as high as six times rated capacity, other times negligible. To prevent severe damage to its inverter caused by the inrush produced by the loads, the UPS is equipped with an electronic overload-protection feature as standard. -
Page 14
® 6 Functions and Signals Overheating If the UPS overheats when the utility is normal it will switch into bypass mode. The UPS will switch back to inverter mode when the overheating is eliminated. If overheating occurs when the utility is abnormal the buzzer will beep continuously and the Fault will shine. -
Page 15: Ups Software
KEOR LP 1, 2, 3 kVA 7 UPS software From the website www.ups.legrand.com it is possible to download UPS software. This software can be used for the following functions: — Automatic shutdown of the local computer — UPS parameters reading…
-
Page 16: Possible Malfunctioning
® 8 Possible malfunctioning Troubleshooting Problem Check Items Solution 1. Check for proper battery connection. Measure battery voltage to ensure that batteries are charged and healthy. Recharge batteries for 8 1. Er05,Er24 hours if necessary. Simulate utility outage to verify that UPS is able to provide DC backup.
-
Page 17
KEOR LP 1, 2, 3 kVA Problem Check Items Solution The UPS switches into 1. A power strip is battery mode and then back connected to the 1. Do not use the power strip. into utility mode when a UPS. See if there 2. -
Page 18
® 8 Possible malfunctioning Error Codes When the Fault LED is lit press the ON button briefly to check the error code. The error codes 1, 2, 4, 8, and 16 are represented by the four bar LEDs 25%, 50%, 75%, and 100%, and the Overload LED Each LED represents a number as shown in the figure below. -
Page 19: Technical Features
KEOR LP 1, 2, 3 kVA 9 Technical features 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 1000 VA 2000 VA 3000 VA Capacity when input voltage is 210~240Vac PF=0.9 (900/1800/2700W) Power Factor when input voltage is 185~260Vac PF=0.8 (800/1600/2400W)
-
Page 20
® 9 Technical features 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 <105% continuous 106-120% for 30 seconds Line 121-150% for 10 seconds mode >150% Immediately transfer to bypass. Buzzer continuously alarms. -
Page 21
KEOR LP 1, 2, 3 kVA 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 Battery Recharge time (to 90%) DC start Self By panel button or software control… -
Page 22
® 9 Technical features 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 Unit Dimensions 236 × 144 × 367 322 x 151 x444 322 × 189 × 444 (HxWxD in mm) Physical Weight…
инструкцияLegrand KEOR LP
Part. LE07381AC-10/17-01 GF
KEOR LP BATTERY BANK
1, 2, 3 kVA
Manuel d’installation • Installation manual
Посмотреть инструкция для Legrand KEOR LP бесплатно. Руководство относится к категории Без категории, 1 человек(а) дали ему среднюю оценку 7.5. Руководство доступно на следующих языках: английский. У вас есть вопрос о Legrand KEOR LP или вам нужна помощь? Задайте свой вопрос здесь
Главная
Вес и размеры
Высота | 322 mm |
Ширина | 151 mm |
Глубина | 444 mm |
Вес | 31000 g |
Высота | 322 mm |
Ширина | 151 mm |
Глубина | 444 mm |
Вес | 31000 g |
Условия эксплуатации
Диапазон температур при эксплуатации | 0 — 40 °C |
Диапазон относительной влажности при эксплуатации | 20 — 80 % |
Диапазон температур при эксплуатации | 0 — 40 °C |
Диапазон относительной влажности при эксплуатации | 20 — 80 % |
Дизайн
Формат | Tower |
Цвет товара | Черный |
Совместимые продукты | KEOR LP 2kVA |
Содержимое упаковки
Сертификаты
Сертификация | EN 62040-1, EN 62040-2 |
Свойства
Цвет товара | Черный |
Сертификация | EN 62040-1, EN 62040-2 |
Совместимость | KEOR LP 2kVA |
Напряжение батареи | 48 V |
Батарея
показать больше
Не можете найти ответ на свой вопрос в руководстве? Вы можете найти ответ на свой вопрос ниже, в разделе часто задаваемых вопросов о Legrand KEOR LP.
Какой вес Legrand KEOR LP?
Какие сертификаты Legrand KEOR LP имеет?
Какая высота Legrand KEOR LP?
Какая ширина Legrand KEOR LP?
Какая толщина Legrand KEOR LP?
Инструкция Legrand KEOR LP доступно в русский?
Не нашли свой вопрос? Задайте свой вопрос здесь
Table of Contents for LEGRAND KEOR LP:
-
113 KEOR LP 1, 2, 3 kVA NL Index 1 Inleiding 114 2 Gebruiksvoorwaarden 114 3 Ledpaneel 116 4 Achterpaneel 118 5 Installatie 119 6 Functies en signalen 122 7 UPS Software 127 8 Problemen oplossen 128 9 Technische kenmerken 131
-
13 KEOR LP 1, 2, 3 kVA FR Le tableau ci-dessous résume le fonctionnement de l’ASI sous différentes puissances et conditions des batteries. Fonctionnement en secteur Normal Le mode de fonctionnement de l’onduleur dans des conditions normales d’utilisation est illustré comme suit : Lorsque l’utilisation est normale, la source de courant alternatif est redressée en courant continu et introduit dans le
-
45 KEOR LP 1, 2, 3 kVA EN MODEL ITEM 3 101 54 3 101 55 3 101 56 3 101 57 3 101 58 3 101 59 Battery Recharge time (to 90%) 3hr DC start Yes Self Diagnostics By panel button or software control Front Panel LED Load Level/Battery Level/ Battery Mode/ Normal Mode/ Bypass Mode/ Self-Test/ Weak/Bad Battery/Site Wiring Fault/ Fault/ Overload Button ON (Alarm Silence)/ OFF (Test/Level Button) Audible Alarm Battery Mode Sounds once every 1.5 seconds Low Battery Sounds once every 0.2 seconds Overload Sounds once every 3 se
-
34 ® 6 Functions and Signals Beep Codes The following table contains common UPS statuses with their beep codes. UPS System Block Diagram Figure 5.1 illustrates the True On-Line Double Conversion architecture of the UPS system. The major modules consist of: 1) AC-to-DC power converter (rectifier) with PFC control circuit 2) DC-to-AC high frequency inverter 3) Smart battery charger 4) Bank of stationary, maintenance-free batteries 5) DC-to-DC push/pull co
-
83 KEOR LP 1, 2, 3 kVA DE 7 Software Sie können die Software der USV von der Website www.ups.legrand.com herunterladen. Diese Software kann für folgende Funktionen verwendet werden: — Automatisches Abschalten des lokalen Computers, der über die RS232-Schnittstelle an die USV angeschlossen ist. — Ablesen der USV-Parameter Anschluss Das Kabel der RS232-Schnittstelle an den Port an der Rückseite der USV und an den Port des Computers anschließen.
-
12 ® 6 Fonctions et signaux Codes sonores Le tableau suivant contient des statuts communs ASI avec leurs codes sonores. Schéma Bloc de l’ASI Figure 5.1 illustre la véritable On-line double conversion du système ASI. Les principaux modules sont constitués de : 1) Un AC-to-DC convertisseur de puissance (redresseur) avec PFC circuit de commande 2) Un DC-to-AC inverter haute fréquence 3) Un chargeur batteries 4) Batteries sans entretien 5) Un contrôleur de la conversion
-
23 KEOR LP 1, 2, 3 kVA FR MODEL ITEM 3 101 54 3 101 55 3 101 56 3 101 57 3 101 58 3 101 59 Batterie Temps de recharge (à 90%) 3hr Démarrage DC Oui Auto diagnostique Par action sur le bouton du panneau ou par contrôle logiciel Panneau avant LED Niveau de charge/Batterie Niveau/ Batterie Mode/ Normal Mode/Bypass Mode/ Auto-Test/ Faible/Batterie défectueuse/Défaut câblage/ Défaut/ Surcharge Bouton ON (Alarme Silence)/ OFF (Test/Bouton Niveau) Alarme sonore Mode Batterie Sonne une
-
146 ® 6 Управление и сигнализация Если напряжение сети не в норме или отсутствует , . 1. ,
-
150 ® 8 Возможные неисправности Поиск и устранение неисправностей Неисправность Что проверяется Действия по устранению «». (Er)* (. ), �
-
138 ® 3 ЖК дисплей Кнопка управления Символ Описание ВКЛ. 1 2 a. ( , ) b. c.
-
40 ® 8 Possible malfunctioning Troubleshooting Problem Check Items Solution Fault LED Read the error code* (see next page) displayed by the combination of LEDs, and verify the fault as follows. 1. Er05,Er24 1 2 1. Check for proper battery connection. Measure battery voltage to ensure that batteries are charged and healthy. Recharge batteries for 8 hours if necessary. Simulate utility outage to verify that UPS is able to provide DC backup. Otherwise consult your local dealer right away. 2. Ove
Questions, Opinions and Exploitation Impressions:
You can ask a question, express your opinion or share our experience of LEGRAND KEOR LP device using right now.
-
68, 68 ® 9 Caratteristiche tecniche MODELLO ITEM 3 101 54 3 101 55 3 101 56 3 101 57 3 101 58 3 101 59 Pesi e misure Dimensioni (H x l x p in mm) 236 × 144 × 367 322 x 151 x444 322 × 189 × 444 Peso (Kg) 10kg 16.5kg 22.5kg Ambiente Temperatura di funzionamento 0-40°C Livello di rumorosità < 50 dBA Tasso di umidità 0-90% (non condensante) Interfaccia Ti…
-
100, 100 ® 6 Funciones y señalizaciones Códigos de señalización acústica La tabla siguiente contiene una lista de los estados comunes del SAI y sus señalizaciones acústicas correspondientes. Esquema de bloques del SAI La figura 5.1 representa una verdadera conversión doble en línea del sistema SAI. Los módulos principales están constituidos por: 1)…
-
138, 138 ® 3 ЖК дисплей Кнопка управления Символ Описание ВКЛ. 1 2 a. ( , ) b. c. �…
-
86, 86 ® Fehlercodes Wenn die Leuchte Störung 1 2 leuchtet, die Tasten ON 1 2 kurz drücken, um den Fehlercode zu kontrollieren. Die Fehlercode 1, 2, 4, 8, und 16 werden durch die 4 Balken 25%, 50%, 75%, und 100%, und die Meldeleuchte für Überlast 1 2 . dargestellt. Jede LED stellt eine Nummer dar, wie in der nachfolgenden Abbildung gezeigt. Es…
-
16, 16 ® 6 Fonctions et signaux Surchauffe de l’onduleur Si l’ASI surchauffe en condition d’alimentation secteur normal, il passe en mode bypass. Il retourne en mode onduleur lorsque celle-ci est éliminée. En cas de surchauffe, lorsque le réseau présente des anomalies, le buzzer émet un bip continu, le voyant 1 2 de défaut s’allume et l’onduleur coupe l’ali…
-
156, 156 ® 9 Технические характеристики 3 101 54 3 101 55 3 101 56 3 101 57 3 101 58 3 101 59 ( x x , ) 236 × 144 × 367 322 x 151 x 444 322 × 189 × 444 10 16,5 22,5 �…
-
155, 155 KEOR LP 1, 2, 3 kVA RU KEOR LP 1, 2, 3 kVA 3 101 54 3 101 55 3 101 56 3 101 57 3 101 58 3 101 59 (90%) 3 …
-
116, 116 ® 3 Ledpaneel 1 2 Toetsen Symbool Beschrijving ON 1 2 a. Knop om de UPS in te schakelen. (Druk en houd de knop ingedrukt totdat u een piep hoort). b. Het alarm geluid uitschakelen c. Weergave foutcodes Druk na een alarm op deze knop om het geluidssignaal uit te schakelen en de foutcode te bekijken. (Druk de knop niet langer dan 1 seconde in) OFF 1 2 Knop ‘uit…
-
140, 140 ® 4 Задняя панель 1. 2. (EPO) 3. �…
-
147, 147 KEOR LP 1, 2, 3 kVA RU 1. IT . …
-
115, 115 KEOR LP 1, 2, 3 kVA NL • Plaats de UPS niet in een stoffige of agressieve omgeving of in de nabijheid van brandbare objecten. Deze UPS is niet ontworpen voor buiten gebruik. • Houd de ventilatieopeningen schoon en bedek ze niet, zodat de interne warmte van de UPS kan wor- den afgevoerd. Plaats niets op de UPS. Bewaar steeds 20 cm afstand tussen het achterpaneel van de …
-
127, 127 KEOR LP 1, 2, 3 kVA NL 7 UPS Software U kunt de software van de UPS downloaden op de website www.ups.legrand.com. Die software heeft de volgende functies: — De plaatselijke pc die is aangesloten op de UPS via RS232 automatisch gecontroleerd uitschakelen. — De parameters van de UPS raadplegen. Aansluiting Het is mogelijk om RS-232 communicatie te gebruiken Sluit d…
-
8, 8 ® 4 Panneau arrière 1 2 3 6 1 2 3 6 5 1 7 8 4 1 2 3 6 8 7 5 9 4 8 7 5 4 1 2 3 6 1 8 7 5 4 1 2 3 6 5 7 8 4 1 2 3 6 8 5 9 7 4 1. Slot pour carte de communication 2. Arrêt d’urgence (EPO) 3. Non disponible 4. Port RS-232 5. Connecteur batteries externes 6. Prises de sorties 7. Porte fusible d’entrée 8. Prise d’entrée alimentation 9. Porte fusible de sortie. Pour 2 s…
-
152, 152 ® 8 Возможные неисправности Коды ошибок «» 1 2 , 1 2 , . …
-
87, 87 KEOR LP 1, 2, 3 kVA DE 9 Technische Daten 9 Technische Daten MODELL ARTIKEL 3 101 54 3 101 55 3 101 56 3 101 57 3 101 58 3 101 59 Kapazität VA 1000 VA 2000 VA 3000 VA Leistungsfaktor Spannungsintervall am Eingang 210~240Vac PF=0,9(900/1800/2700W ) Spannungsintervall am Eingang 185~240Vac PF=0,8(800/1600/2400W ) Spannungsintervall am Eingang 160~240Vac PF=0,7(700/1400/2100…
-
34, 34 ® 6 Functions and Signals Beep Codes The following table contains common UPS statuses with their beep codes. UPS System Block Diagram Figure 5.1 illustrates the True On-Line Double Conversion architecture of the UPS system. The major modules consist of: 1) AC-to-DC power converter (rectifier) with PFC control circuit 2) DC-to-AC high frequency inverter 3) Smart battery charger 4) Bank…
-
Contents
-
Table of Contents
-
Bookmarks
Quick Links
KEOR LP
®
1, 2, 3 kVA
Manuel d’installation
Installation manual
•
Part. LE07360AC-10/17-01 GF
Related Manuals for LEGRAND KEOR LP
Summary of Contents for LEGRAND KEOR LP
-
Page 1
KEOR LP ® 1, 2, 3 kVA Manuel d’installation Installation manual • Part. LE07360AC-10/17-01 GF… -
Page 2
® KEOR LP 1, 2, 3 kVA FRANÇAIS ENGLISH ITALIANO DEUTSCH ESPAÑOL NEDERLANDS PУСCKИЙ… -
Page 3: Table Of Contents
KEOR LP 1, 2, 3 kVA Index 1 Introduction 2 Conditions d’utilisation 3 Panneau LED 4 Panneau arrière 5 Installation 6 Fonctions et signaux 7 Logiciel 8 Dépannages 9 Caractéristiques techniques…
-
Page 4: Introduction
• Le panneau frontal de contrôle est prévu pour des opérations manuelles ; ne pas appuyer sur le panneau avec des objets pointus ou coupants. • Les ASI Keor LP ont été conçus pour fonctionner dans un environnement fermé, propre, en absence de liquide ou objets inflammables, substances corrosives et contaminants conducteurs. Ne pas installer l’onduleur dans un environnement avec des étincelles, de la fumée ou du gaz.
-
Page 5
KEOR LP 1, 2, 3 kVA • Éviter d’exposer l’ASI directement à la lumière du soleil ou à proximité d’une source de chaleur. • Assurez-vous que l’environnement dans lequel est installé l’onduleur corresponde aux critères 0%~90% de température et d’humidité demandés ( lire les spécifications techniques) •… -
Page 6: Panneau Led
® 3 Panneau LED Voyants Symbole Descriptions a. Bouton de mise en Marche Appuyez et maintenez en- foncé jusqu’à ce que le buzzer émette un bip b. Neutralisation de l’alarme c. Fonction affichage des codes erreurs Après une alarme, appuyez pour arrêter l’alarme sonore et vérifiez le code d’erreur.
-
Page 7
KEOR LP 1, 2, 3 kVA Voyants Symbole Descriptions 1. Le voyant fixe indique que la tension secteur est normale. Le clignotement LED Mode indique que la tension secteur est insuffisante pour la pleine charge. Normal Lorsqu’il est éteint, cela indique une tension secteur anormale. -
Page 8: Panneau Arrière
® 4 Panneau arrière 3 101 54 3 101 56 3 101 58 3 101 55 3 101 57 3 101 59 1. Slot pour carte de communication 2. Arrêt d’urgence (EPO) 3. Non disponible 4. Port RS-232 5. Connecteur batteries externes 6.
-
Page 9: Installation
KEOR LP 1, 2, 3 kVA 5 Installation Déballage Après avoir enlevé les protections, vérifier les contenu du paquet standard: http://ups.legrand.com/biblioteca/ IEC — IEC 2000/3000 VA (2) 1000/2000VA: Schucko/ French — IEC 320-C14 1000 VA (1) 3000VA: Schucko/ French – IEC 320-C20…
-
Page 10
® 5 Installation Les connexions suivantes sont disponibles à l’arrière de l’ASI : • Prises de sortie (6) et connecteur d’entrée (8). • Prise RS232 (9 broches femelle) [4] pour la connexion de l’ordinateur lorsque vous utilisez le logiciel de diagnostic et de gestion d’arrêt. •… -
Page 11
KEOR LP 1, 2, 3 kVA après cinq secondes. Dans le même temps, le ventilateur à l’avant de l’onduleur commence à fonctionner. 5. Maintenir appuyé le bouton OK ‘ ’ pendant environ 1 seconde pour démarrer l’onduleur. Le bipeur va retentir et les indicateurs LED vont s’allumer après 1 à… -
Page 12: Fonctions Et Signaux
® 6 Fonctions et signaux Codes sonores Le tableau suivant contient des statuts communs ASI avec leurs codes sonores. ASI Statuts Codes sonores ASI défectueux, variateur arrêté. Toutes les fonctions inhibées Bip long et continu Erreur clavier de commande Bip long et continu ASI défectueux, les charges continuent à…
-
Page 13
KEOR LP 1, 2, 3 kVA Le tableau ci-dessous résume le fonctionnement de l’ASI sous différentes puissances et conditions des batteries. Conditions Secteur Mode de fonctionnement ASI Voyants LEDs Environ 5 secondes aprés la mise en marche de l’ A SI, voyant LED allumé… -
Page 14
® 6 Fonctions et signaux Fonctionnement en cas de problème secteur Le mode de fonctionnement de l’onduleur dans des conditions anormales d’utilisation est illustré comme suit : Figure 5.3 1. Lorsque le réseau présente une anomalie, l’onduleur dirige l’énergie de la batterie automatiquement vers l’inverseur sans délai et éteint le chargeur ainsi que le convertisseur AC / DC. -
Page 15
KEOR LP 1, 2, 3 kVA 1. En règle générale, l’électronique moderne et le matériel informatique génèrent de forts courants d’appel lors de l’allumage. Les courants d’appel varient selon les appareils, parfois jusqu’à six fois la capacité nominale, d’autres fois négligeable. Pour éviter de graves dommages à l’onduleur causés par l’irruption produite par les charges, il est équipé… -
Page 16
® 6 Fonctions et signaux Surchauffe de l’onduleur Si l’ASI surchauffe en condition d’alimentation secteur normal, il passe en mode bypass. Il retourne en mode onduleur lorsque celle-ci est éliminée. En cas de surchauffe, lorsque le réseau présente des anomalies, le buzzer émet un bip continu, le voyant de défaut s’allume et l’onduleur coupe l’alimentation aux charges. -
Page 17: Logiciel
KEOR LP 1, 2, 3 kVA 7 Logiciel Vérifier la disponibilité et télécharger le logiciel de l’onduleur depuis le site web www.ups.legrand.com. Ce logiciel peut être utilisé pour les fonctions suivantes: — Arrêt automatique de l’ordinateur local connecté a l’onduleur par RS232 — Lecture des paramètres de l’onduleur…
-
Page 18: Dépannages
Si le temps de sauvegarde n’ e st toujours pas satisfaisant de secours ou son après 8 heures de charge, contactez votre revendeur temps d’autonomie Legrand local pour le remplacement de la batterie. est plus court que la performance prévue…
-
Page 19
KEOR LP 1, 2, 3 kVA Situations A vérifier Solution Vérifiez que tous les Si le problème persiste, consultez votre ASI normal mais il n’y a pas cordons d’alimentation revendeur Legrand local pour obtenir une de sortie à la charge. -
Page 20
® 8 Dépannages Codes erreurs Lorsque le voyant défaut est allumé, appuyez brièvement sur le bouton ON pour vérifier le code d’erreur. Les codes erreurs 1, 2, 4, 8, et 16 sont représentés par les 4 barres LEDs 25%, 50%, 75%, et 100%, et le voyant surcharge Chaque LED représente un nombre comme montré… -
Page 21: Caractéristiques Techniques
KEOR LP 1, 2, 3 kVA 9 Caractéristiques techniques 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 1000 VA 2000 VA 3000 VA Capacity Plage de tension d’entrée 210~240Vac PF=0.9(900/1800/2700W) Facteur de Plage de tension d’entrée 185~260Vac PF=0.8(800/1600/2400W)
-
Page 22
® 9 Caractéristiques techniques 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 <105% continu 106-120% pendant 30 sec Mode On 121-150% pendant 30 sec line >150% transféré immédiatement sur bypass. Bip alarme continu <105% continu Mode… -
Page 23
KEOR LP 1, 2, 3 kVA 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 Batterie Temps de recharge (à 90%) Démarrage DC Auto Par action sur le bouton du panneau diagnostique ou par contrôle logiciel… -
Page 24
® 9 Caractéristiques techniques 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 Dimensions 236 × 144 × 367 322 x 151 x444 322 × 189 × 444 (Hxlxp en mm) Colisage Poids (Kg) 10kg… -
Page 25
KEOR LP 1, 2, 3 kVA Index 1 Introduction 2 Condition of use 3 LED Panel 4 Rear Panel 5 Installation 6 Functions and Signal 7 UPS software 8 Possible malfunctioning 9 Technical features… -
Page 26
• The front control panel is provided for manual operations; Do not press on the panel with sharp or pointed objects. • The UPS Keor LP has been designed to work in closed, clean rooms where there are no inflammable liquids or corrosive substances and where it is not too damp. -
Page 27
KEOR LP 1, 2, 3 kVA Do not place the UPS in a dusty or corrosive environment or near any flammable objects. This UPS is not designed for outdoor use. 0%~90% • Keep the ventilation slits clean to dissipate the heat of the UPS. -
Page 28
® 3 LED Panel Control Symbol Description a. UPS Power-On Switch (Press and hold until the buzzer beeps.) b. Alarm silence c. Error Code Display Mode After an alarm, press to mute the alarm buzzer and show an Error Code. (Do not hold for > 1 second.) UPS Power-Off Switch (Press and hold until the buzzer beeps.) a. -
Page 29
KEOR LP 1, 2, 3 kVA Symbol Description Indicator 1. Steadily on indicates normal utility voltage. Blinking indicates insufficient utility voltage for the full load. Off indicates abnormal Normal utility voltage. Mode LED 2. In Battery/Load Test Mode indicates battery capacity is 50%. -
Page 30
® 4 Rear panel 3 101 54 3 101 56 3 101 58 3 101 55 3 101 57 3 101 59 1. Slot for optional communication cards 2. Emergency Power Off (EPO) dry contact signal inputs 3. NA 4. RS-232 port 5. -
Page 31
KEOR LP 1, 2, 3 kVA 5 Installation Unpacking Inspect the UPS upon receipt After removing the packing foam please be careful handling the UPS while it is still in the plastic bag and check for the following standard package contents : http://ups.legrand.com/biblioteca/… -
Page 32
® 5 Installation The following main connections are available on the rear of the uninterruptible power supply : • Output sockets (6) and input connector (8). • Socket for connecting computer serial interface RS232 (9 female pins) [4]: required when using the diagnostic and shutdown management software. -
Page 33
KEOR LP 1, 2, 3 kVA five seconds. At the same time, the fan at the front of the UPS will start operating. 5. Press and hold the ON button for approximately one second to start the UPS. The buzzer will beep and the LED indicators will shine after 1-5 seconds. -
Page 34
® 6 Functions and Signals Beep Codes The following table contains common UPS statuses with their beep codes. UPS Status Beep Code UPS faulty, Inverter shut down. All functions inhibited. Long Continuous Beep Control keypad error Long Continuous Beep UPS faulty, loads continue to be supplied via Inverter or Bypass. Single beep every two seconds In battery mode Single beep once per second… -
Page 35
KEOR LP 1, 2, 3 kVA The table below provides a summary of the UPS operating modes under various utility AC power source and battery conditions. Utility Condition UPS Operating Mode LEDs Working power starts after approximately LED ON 5 seconds, LEDs on the panel will blink and… -
Page 36
® 6 Functions and Signals When Utility is Abnormal or Absent The operating mode of the UPS under abnormal utility conditions is illustrated as follows. Figure 5.3 1. When the utility is abnormal the UPS will direct the battery energy automatically to the Inverter without delay and turn off the charger and AC/DC converter. -
Page 37
KEOR LP 1, 2, 3 kVA 1. Generally, modern electronics and IT equipment generate an inrush current when switching on. The amount of inrush current varies from equipment to equipment, sometimes as high as six times rated capacity, other times negligible. To prevent severe damage to its inverter caused by the inrush produced by the loads, the UPS is equipped with an electronic overload-protection feature as standard. -
Page 38
® 6 Functions and Signals Overheating If the UPS overheats when the utility is normal it will switch into bypass mode. The UPS will switch back to inverter mode when the overheating is eliminated. If overheating occurs when the utility is abnormal the buzzer will beep continuously and the Fault will shine. -
Page 39
KEOR LP 1, 2, 3 kVA 7 UPS software From the website www.ups.legrand.com it is possible to download UPS software. This software can be used for the following functions: — Automatic shutdown of the local computer — UPS parameters reading… -
Page 40
® 8 Possible malfunctioning Troubleshooting Problem Check Items Solution 1. Check for proper battery connection. Measure battery voltage to ensure that batteries are charged and healthy. Recharge batteries for 8 1. Er05,Er24 hours if necessary. Simulate utility outage to verify that UPS is able to provide DC backup. -
Page 41
KEOR LP 1, 2, 3 kVA Problem Check Items Solution The UPS switches into 1. A power strip is battery mode and then back connected to the 1. Do not use the power strip. into utility mode when a UPS. See if there 2. -
Page 42
® 8 Possible malfunctioning Error Codes When the Fault LED is lit press the ON button briefly to check the error code. The error codes 1, 2, 4, 8, and 16 are represented by the four bar LEDs 25%, 50%, 75%, and 100%, and the Overload LED Each LED represents a number as shown in the figure below. -
Page 43
KEOR LP 1, 2, 3 kVA 9 Technical features 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 1000 VA 2000 VA 3000 VA Capacity when input voltage is 210~240Vac PF=0.9 (900/1800/2700W) Power Factor when input voltage is 185~260Vac PF=0.8 (800/1600/2400W) -
Page 44
® 9 Technical features 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 <105% continuous 106-120% for 30 seconds Line 121-150% for 10 seconds mode >150% Immediately transfer to bypass. Buzzer continuously alarms. -
Page 45
KEOR LP 1, 2, 3 kVA 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 Battery Recharge time (to 90%) DC start Self By panel button or software control… -
Page 46
® 9 Technical features 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 Unit Dimensions 236 × 144 × 367 322 x 151 x444 322 × 189 × 444 (HxWxD in mm) Physical Weight… -
Page 47
KEOR LP 1, 2, 3 kVA Indice 1 Introduzione 2 Condizioni di utilizzo 3 Pannello LED 4 Pannello posteriore 5 Installazione 6 Funzioni e segnalazioni 7 Software 8 Risoluzione dei problemi 9 Caratteristiche tecniche… -
Page 48: Introduzione
• Il pannello di comando frontale è previsto per effettuare operazioni manuali : non esercitare pressione sul pannello con oggetti appuntiti o taglienti. • Gli UPS Keor LP sono stati progettati per funzionare in un ambiente chiuso, pulito e in assenza di liquidi o oggetti infiammabili, sostanze corrosive e conduttori contaminanti. Non installare il gruppo di continuità…
-
Page 49
KEOR LP 1, 2, 3 kVA • Assicuratevi che l’ambiente nel quale è installato il gruppo di continuità corrisponda alle caratteristiche di temperatura e di umidità richieste (leggere le specifiche tecniche) 0%~90% • Mantenere le feritoie d’areazione sempre pulite e non ostruite per permettere la dissipazione del calore interno dell’UPS. -
Page 50: Pannello Led
® 3 Pannello a LED Spie Simbolo Descrizione a. Pulsante di Messa in funzione. Premere e mantenere premuto fino all’emissione del bip sonoro b. Neutralizzazione allarme c. Funzione di visualizzazione dei codici errore Dopo un allarme, premere per tacitare l’allarme acustico e verifica- re il codice di errore (Non premere per un tempo >…
-
Page 51
KEOR LP 1, 2, 3 kVA Spie Simbolo Descrizione 1. Il led acceso fisso indica che la tensione di rete è normale. Se invece lampeggia indica che la tensione di rete è insufficiente per il carico Modalità completo. Il led spento indica una tensione di rete anomala. -
Page 52: Pannello Posteriore
® 4 Pannello posteriore 3 101 54 3 101 56 3 101 58 3 101 55 3 101 57 3 101 59 1. Slot per scheda di comunicazione 2. Arresto d’emergenza (EPO) 3. Non disponibile 4. Porta RS-232 5. Connettore batterie esterne 6.
-
Page 53: Installazione
KEOR LP 1, 2, 3 kVA 5 Installazione Disimballaggio Verificare l’UPS alla ricezione Dopo avere rimosso le protezioni, verificare il contenuto della confezione standard: http://ups.legrand.com/biblioteca/ IEC — IEC 2000/3000 VA (2) 1000/2000VA: Schucko/ French — IEC 320-C14 1000 VA (1)
-
Page 54
® 5 Installazione I collegamenti seguenti sono disponibili nella parte posteriore dell’UPS : • Uscite (6) e connettore d’ingresso (8). • Presa RS232 (9 pin femmina) [4] per il collegamento di computer nel caso si utilizzi il software di diagnostica e di gestione dell’arresto •… -
Page 55
KEOR LP 1, 2, 3 kVA 5. Mantenere premuto il pulsante OK per circa 1 secondo per avviare il gruppo di continuità. L’avvisatore acustico emette un bip e gli indicatori LED si accendono dopo un periodo che può variare da 1 a 5 secondi. La procedura di accensione è finita e le uscite del gruppo di continuità… -
Page 56: Funzioni E Segnalazioni
® 6 Funzioni e segnalazioni Codici di segnalazione acustica La tabella seguente contiene un elenco degli status comuni dell’UPS e le loro relative segnalazioni acustiche. Stato UPS Segnali acustici UPS difettoso, inverter non funzionante. Bip lungo e continuo Tutte le funzioni disabilitate Errore tastiera di comando Bip lungo e continuo UPS difettoso, i carichi continuano…
-
Page 57
KEOR LP 1, 2, 3 kVA La tabella seguente riassume il funzionamento dell’UPS in varie condizioni di potenza e delle batterie. Condizioni rete Modalità di funzionamento UPS Spie LED di alimentazione La potenza di lavoro è disponibile dopo LED accesa… -
Page 58
® 6 Funzioni e segnalazioni Funzionamento in caso di problema sulla rete La modalità di funzionamento del gruppo di continuità in condizioni anomale di utilizzo è illustrato di seguito : Figura 5.3 1. Quando la rete presenta un’anomalia, l’UPS dirige l’energia della batteria automaticamente verso l’inverter, senza ritardo, e spegne il carica batterie e il convertitore CA /CC. -
Page 59
KEOR LP 1, 2, 3 kVA 1. Generalmente l’elettronica moderna e il materiale informatico generano forti correnti di spunto in fase di accensione. Le correnti di spunto variano a seconda delle apparecchiature, in certi casi arrivando anche a sei volte la capacità nominale, in altri casi sono quasi trascurabili. Per evitare gravi danni all’UPS causati dalla corrente di spunto prodotta dai carichi, lo stesso è… -
Page 60
® 6 Funzioni e segnalazioni Surriscaldamento dell’UPS Se l’UPS si surriscalda in condizione di alimentazione da rete normale passa in modalità bypass. Torna in modalità inverter solo quando il surriscaldamento è stato eliminato. In caso di surriscaldamento, nel momento in cui la rete presenta anomalie, l’avvisatore acustico emette un bip continuo, la spia di guasto si accende e l’UPS interrompe l’alimentazione ai carichi. -
Page 61: Software
KEOR LP 1, 2, 3 kVA 7 Software Verificare la disponibilità e scaricare il software dell’UPS dal sito web www.ups.legrand.com. Questo software può essere utilizzato per le seguenti funzioni : — Arresto automatico del computer locale collegato all’UPS tramite RS232 — Lettura dei parametri dell’UPS…
-
Page 62: Risoluzione Dei Problemi
5. Verificare che le ventole funzionino correttamente. (ventole Non cercate di sostuirle da soli. fuori servizio) 6. Altri codici 6. Consultare il vostro rivenditore locale Legrand. errore L’UPS non interviene fornendo un’alimentazione di Se questo tempo rimane insufficiente dopo 8 ore…
-
Page 63
KEOR LP 1, 2, 3 kVA Problema Cosa verificare Soluzione Verificare che tutti i Se il problema persiste contattate il UPS normale ma non c’è cavi d’alimentazione vostro rivenditore locale Legrand per uscita al carico. siano collegati ottenere assistenza tecnica. -
Page 64
® 8 Risoluzione dei problemi Codici errori Quando la spia di guasto è accesa, premere brevemente sul pulsante ON per verificare il codice dell’errore. I codici errore 1, 2, 4, 8, e 16 sono rappresentati tramite le 4 barre LED 25%, 50%, 75%, e 100%, e la spia di sovraccarico Ogni LED rappresenta un numero, come si può… -
Page 65: Caratteristiche Tecniche
KEOR LP 1, 2, 3 kVA 9 Caratteristiche tecniche 3 101 54 3 101 56 3 101 58 MODELLO ITEM 3 101 55 3 101 57 3 101 59 1000 VA 2000 VA 3000 VA Intervallo tensione d’ingresso 210~240Vac PF=0.9(900/1800/2700W) Capacità…
-
Page 66
® 9 Caratteristiche tecniche 3 101 54 3 101 56 3 101 58 MODELLO ITEM 3 101 55 3 101 57 3 101 59 < 105% continuativo Modalità 106-120% per 30 secondi 121-150% per 30 secondi line > 150% trasferimento immediato a bypass Bip di allarme continuo <105% continuativo 106-120% per 30 secondi… -
Page 67
KEOR LP 1, 2, 3 kVA 3 101 54 3 101 56 3 101 58 MODELLO ITEM 3 101 55 3 101 57 3 101 59 Tempo di ricarica Batteria 3 ore (al 90%) Avviamento in CC Agendo sul pulsante del pannello o… -
Page 68
® 9 Caratteristiche tecniche 3 101 54 3 101 56 3 101 58 MODELLO ITEM 3 101 55 3 101 57 3 101 59 Dimensioni 236 × 144 × 367 322 x 151 x444 322 × 189 × 444 (H x l x p in mm) Pesi e misure Peso (Kg) 10kg… -
Page 69
KEOR LP 1, 2, 3 kVA Inhaltsverzeichnis 1 Einleitung 2 Gebrauchsbedingungen 3 LED-Display 4 Anschlüsse auf der Rückseite 5 Installation 6 Funktionen und Meldungen 7 Software 8 Fehlerbehebung 9 Technische Daten… -
Page 70: Einleitung
Gewerbe oder in der Industrie entwickelt worden ist. Die in diesem Handbuch enthaltenen Informa- tionen beziehen sich auf die USV-Modelle Keor LP 1000, 2000, 3000 VA. Vor der Installation der unterbre- chungsfreien Stromversorgung lesen Sie bitte die Sicherheitsanweisungen aufmerksam durch, die in der Packung enthalten sind und beachten Sie die Anweisungen des Handbuchs genau.
-
Page 71
KEOR LP 1, 2, 3 kVA • Vergewissern Sie sich, dass die Umgebung, in der die unterbrechungsfreie Stromversorgung installiert wird, die erforderliche Temperatur und Feuchtigkeit aufweist (siehe technische Spe- zifikationen). • Halten Sie die Belüftungsschlitze immer sauber und vergewissern Sie sich, dass sie nicht ver- 0%~90% stopft sind, um die sich in der USV bildende Wärme ableiten zu können. -
Page 72: Led-Display
® 3 LED-Tafel Meldeleuch- Symbol Beschreibung ten (LED) a. Taste zur Inbetriebsetzung Die Taste drücken und gedrückt halten, bis ein Piepton ausgelöst wird. b. Alarm quittieren c. Anzeigemodus der Fehlercodes Nach einem Alarm drücken, um den akustischen Alarm zu quittieren und den Fehlercode zu kontrollieren (nicht länger als 1 Sekunde lang drücken) Aus-Taste Die Taste drücken und gedrückt halten, bis ein Piepton…
-
Page 73
KEOR LP 1, 2, 3 kVA Meldeleuchten Symbol Beschreibung (LED) 1. Die LED leuchtet dauernd, um zu melden, dass die Netzspannung normal ist. Wenn sie blinkt, meldet sie, dass die Netzspannung nicht für die ganze Stromlast ausreicht. Die LED leuchtet nicht, wenn die normaler Netzspannung gestört ist. -
Page 74: Anschlüsse Auf Der Rückseite
® 4 Anschlüsse auf der Rückseite 3 101 54 3 101 56 3 101 58 3 101 55 3 101 57 3 101 59 1. Slot für eine Kommunikationskarte 2. Notaus (EPO) 3. Nicht belegt 4. Port RS-232 5. Anschluss für externe Batterien 6.
-
Page 75: Installation
KEOR LP 1, 2, 3 kVA 5 Installation Auspacken Die USV nach Erhalt prüfen Die Schutzelemente entfernen und den Inhalt der Standardpackung kontrollieren: http://ups.legrand.com/biblioteca/ IEC — IEC 2000/3000 VA (2) 1000/2000VA: Schucko/ French — IEC 320-C14 1000 VA (1) 3000VA: Schucko/ French – IEC 320-C20…
-
Page 76
® 5 Installation An der Rückseite der USV sind folgende Anschlüsse vorhanden: • Ausgänge [6] und Spannungseingang [8]. • RS232 Buchse (9 Pin) Aufnahmeteil streichen [4] zum Anschluss eines Computers, für den Fall, dass die Software zur Diagnostik und zur Abschaltsteuerung verwendet wird. •… -
Page 77
KEOR LP 1, 2, 3 kVA leuchten nach etwa 1 bis 5 Sekunden auf. Nun ist das Gerät eingeschaltet und die Ausgänge der unterbrechungsfreien Stromversorgung sind bereit die Stromlast zu versorgen. 6. Wir empfehlen einen Test im Modus Batterie durchzuführen, bevor Geräte an die USV ang- eschlossen werden, um sicherzustellen, dass die Batterien richtig funktionieren. -
Page 78: Funktionen Und Meldungen
® 6 Funktionen und Meldungen Akustische Meldecodes In der nachfolgenden Tabelle ist eine Liste der allgemeinen Zustände der USV mit den entsprech- enden akustischen Meldungen enthalten. USV-Zustand Akustische Signale USV defekt, Frequenzumrichter nicht funktionstüchtig. Langer und kontinuierlicher Alle Funktionen sind ausgeschaltet Piepton Fehler an der Steuertastatur Langer und kontinuierlicher Piepton…
-
Page 79
KEOR LP 1, 2, 3 kVA In der nachstehenden Tabelle wird der Betrieb der USV unter verschiedenen Leistungsbedingun- gen und der Batterie zusammengefasst. Zustand des Meldeleuchten Betriebsmodus USV Stromnetzes (LED) Die Betriebsleistung wird nach ca. 5 Sekunden bereit- LED leuchtet gestellt, die LEDs an der Tafel blinken und die Lüfter… -
Page 80
® 6 Funktionen und Meldungen Betrieb bei einer Störung im Netz Nachstehend wird der Betriebsmodus der unterbrechungsfreien Stromversorgung unter gestörten Bedingungen beschrieben: Abbildung 5.3 1. Wenn eine Störung im Netz auftritt, versorgt die USV den Frequenzumrichter automatisch und ohne Verzögerung über die Batterie und schaltet das Batterieladegerät und den Umrichter AC/ DC aus. -
Page 81
KEOR LP 1, 2, 3 kVA 1. In der Regel benötigen moderne elektronische Geräte und Datenverarbeitungssysteme einen starken Spitzenstrom, wenn sie eingeschaltet werden. Die Spitzenströme sind je nach Gerät unterschiedlich. In einigen Fällen erreichen sie das Sechsfache der normalen Kapazität; in anderen Fällen sind sie geradezu geringfügig. -
Page 82
® 6 Funktionen und Meldungen Überhitzung der USV Bei einer Überhitzung der USV im Normalbetrieb, schaltet diese auf den Bypass-Modus. Sie schaltet auf den Modus Frequenzumrichter erst wieder um, wenn die Ursache der Überhitzung behoben worden ist. Falls es zu einer Überhitzung kommt, wenn das Netz gestört ist, erzeugt das akustische Meldegerät einen kontinuierlichen Piepton, die Meldeleuchte Störung leuchtet auf und die USV unterbricht die Stromversorgung der Stromlasten. -
Page 83: Software
KEOR LP 1, 2, 3 kVA 7 Software Sie können die Software der USV von der Website www.ups.legrand.com herunterladen. Diese Software kann für folgende Funktionen verwendet werden: — Automatisches Abschalten des lokalen Computers, der über die RS232-Schnittstelle an die USV angeschlossen ist.
-
Page 84
Kontrollieren, ob der Lüfter des durch die Reihen- überhitzt) Kühlungssystems richtig funktioniert. Anderenfalls folge der LED ange- wenden Sie sich an Ihren nächsten Legrand-Händler. zeigt wird und den Fehler folgenderma- ßen kontrollieren: 4. Verkabe- 4. Kontrollieren, ob die Phasen “L” und “N” der Stromquelle… -
Page 85
KEOR LP 1, 2, 3 kVA Problem Zu kontrollieren Abhilfe USV im Normalbetrieb aber Kontrollieren, ob alle Sollte das Problem weiter bestehen, kein Ausgang an der Strom- Versorgungskabel rich- wenden Sie sich an Ihren nächsten Le- last. tig angeschlossen sind. -
Page 86: Fehlerbehebung
® 8 Fehlerbehebung Fehlercodes Wenn die Leuchte Störung leuchtet, die Tasten ON kurz drücken, um den Fehlercode zu kontrollieren. Die Fehlercode 1, 2, 4, 8, und 16 werden durch die 4 Balken 25%, 50%, 75%, und 100%, und die Meldeleuchte für Überlast .
-
Page 87: Technische Daten
KEOR LP 1, 2, 3 kVA 9 Technische Daten 9 Technische Daten 3 101 56 3 101 58 3 101 54 MODELL ARTIKEL 3 101 55 3 101 57 3 101 59 1000 VA 2000 VA 3000 VA Spannungsintervall am Eingang 210~240Vac PF=0,9(900/1800/2700W ) Kapazität…
-
Page 88
® 9 Technische Daten 3 101 54 3 101 56 3 101 58 MODELL ARTIKEL 3 101 55 3 101 57 3 101 59 < 105% kontinuierlich 106-120% 30 Sekunden lang Online- 121-150% 30 Sekunden lang Modus > 150% sofortiger Übergang auf Bypass Kontinuierlicher Piepton <… -
Page 89
KEOR LP 1, 2, 3 kVA 3 101 54 3 101 56 3 101 58 MODELL ARTIKEL 3 101 55 3 101 57 3 101 59 Aufladezeit Batterie 3 Stunden (zu 90%) Inbetriebnahme im AC-Modus Durch Drücken der Taste am Display oder durch eine… -
Page 90
® 9 Technische Daten 3 101 54 3 101 56 3 101 58 MODELL ARTIKEL 3 101 55 3 101 57 3 101 59 Abmessung 236 × 144 × 367 322 x 151 x444 322 × 189 × 444 Gewichte und (H x L x T) (mm) Maße Gewicht (kg) -
Page 91
KEOR LP 1, 2, 3 kVA Tabla de contenidos 1 Introducción 2 Condiciones de uso 3 Panel LEDs 4 Panel trasero 5 Instalación 6 Funciones y señalizaciones 7 Software 8 Resolución de los problemas 9 Características técnicas… -
Page 92: Introducción
• El panel de control frontal se ha previsto para realizar operaciones manuales: no ejercer una presión en el panel con objetos puntiagudos o cortantes. • Los SAI Keor LP se han diseñado para funcionar en un ambiente cerrado, limpio y en ausencia de líquidos u objetos inflamables, sustancias corrosivas y conductores contaminantes. No instalar el grupo de continuidad en un ambiente donde estén presentes chispas, humos o gases.
-
Page 93
KEOR LP 1, 2, 3 kVA • Comprobar que el ambiente en que se instala el grupo de continuidad corresponda a las características de temperatura y de humedad que se requieren (leer las especificaciones técnicas). 0%~90% • Mantener la rejilla de ventilación siempre limpia y no obstruidas, para permitir la disipación del calor… -
Page 94: Panel Leds
® 3 Panel de LEDs Indicadores luminosos Símbolo Descripción a. Pulsador de Puesta en función. Apretar y mantener apretado hasta la emisión del beep acústico. b. Neutralización de la alarma. c. Función de visualización de los códigos de error. Después de una alarma, apretar para desactivar la alarma acústica y controlar el código de error (no apretar durante un tiempo >…
-
Page 95
KEOR LP 1, 2, 3 kVA Indicadores luminosos Símbolo Descripción 1. El led encendido fijo indica que la tensión eléctrica de red es normal. Si en cambio destella indica que la tensión eléctrica de red es insuficiente Modalidad para la carga completa. El led apagado indica una tensión eléctrica de normal red anómala. -
Page 96: Panel Trasero
® 4 Panel trasero 3 101 54 3 101 56 3 101 58 3 101 55 3 101 57 3 101 59 1. Ranura para tarjeta de comunicación 2. Parada de emergencia (EPO) 3. No disponible 4. Puerto RS-232 5. Conector baterías externas 6.
-
Page 97: Instalación
KEOR LP 1, 2, 3 kVA 5 Instalación Desembalaje Comprobar el SAI a la receptión Después de haber quitado las protecciones, controlar el contenido del paquete estándar: http://ups.legrand.com/biblioteca/ IEC — IEC 2000/3000 VA (2) 1000/2000VA: Schucko/ French — IEC 320-C14 1000 VA (1) 3000VA: Schucko/ French –…
-
Page 98
® 5 Instalación Las conexiones siguientes están disponibles en la parte trasera del SAI: • Salidas (6) y conector de entrada (8). • Toma RS232 (9 polos hembra) [4] para la conexión del ordenador en caso de que se utilice el software de diagnóstico y de gestión de la parada. -
Page 99
KEOR LP 1, 2, 3 kVA 5. Mantener apretado el pulsador ON durante 1 segundo para arrancar el grupo de continuidad. La señal acústica emite un beep y los indicadores LED se encienden después de un período que puede variar entre 1 y 5 segundos. El procedimiento de encendido ha terminado y las salidas del grupo de continuidad están listas a alimentar energía a la carga. -
Page 100: Funciones Y Señalizaciones
® 6 Funciones y señalizaciones Códigos de señalización acústica La tabla siguiente contiene una lista de los estados comunes del SAI y sus señalizaciones acústicas correspondientes. Estado del SAI Señales acústicas SAI defectuoso, inverter que no funciona. Beep largo y continuo. Todas las funciones inhabilitadas.
-
Page 101
KEOR LP 1, 2, 3 kVA La tabla siguiente resume el funcionamiento del SAI en varias condiciones de potencia y de las baterías. Condiciones de la red de Indicadores Modalidad de funcionamiento SAI alimentación luminosos LED eléctrica La potencia de trabajo está disponible después LED encendido de unos 5 segundos. -
Page 102
® 6 Funciones y señalizaciones Funcionamiento en caso de problema en la red La modalidad de funcionamiento del grupo de continuidad en condiciones anómalas de uso se indica a continuación: Figura 5.3 1. Cuando la red presenta una anomalía, el SAI dirige la energía de la batería automáticamente hacia el inverter, sin retraso, y apaga el cargador de baterías y el convertidor CA/CC. -
Page 103
KEOR LP 1, 2, 3 kVA 1. Generalmente la electrónica moderna y el material informático generan fuertes corrientes de arranque durante la fase de encendido. Las corrientes de arranque varían en función de los equipos; en algunos casos alcanzan hasta seis veces la capacidad nominal, en otros casos son casi descuidables. -
Page 104
® 6 Funciones y señalizaciones Recalentamiento del SAI Si el SAI se recalienta en condición de alimentación de red normal pasa a la modalidad bypass. Vuelve a la modalidad inverter sólo cuando se haya eliminado el recalentamiento. En caso de recalentamiento, en el momento en que la red presente anomalías, la señal acústica emite un beep continuo, el indicador luminoso de avería se enciende y el SAI interrumpe la alimentación a las cargas. -
Page 105: Software
KEOR LP 1, 2, 3 kVA 7 Software Comprobar la disponibilidad y descargar el software del SAI desde la página web www.ups. legrand.com. Este software puede utilizarse para las funciones siguientes: — Parada automática del ordenador local conectado al SAI a través del RS232.
-
Page 106: Resolución De Los Problemas
Si este tiempo queda insuficiente después de 8 alimentación de backup o su tiempo horas de carga, contactar vuestro vendedor local de autonomía es más Legrand para la sustitución de las baterías. corto con respecto a lo que se prevé.
-
Page 107
KEOR LP 1, 2, 3 kVA Situations A vérifier Solution Comprobar que todos los cables Si el problema persiste contactar SAI normal pero no hay de alimentación se vuestro vendedor local Legrand para salida hacia la carga. hayan conectado obtener asistencia técnica. -
Page 108
® 8 Resolución de los problemas Códigos de error Cuando se enciende el indicador luminoso de avería , apretar brevemente el pulsador ON para controlar el código de error. Los códigos de error 1, 2, 4, 8 y 16 están representados por las 4 barras LED 25%, 50%, 75% y 100% y el indicador de sobrecarga ∏. -
Page 109: Características Técnicas
KEOR LP 1, 2, 3 kVA 9 Características técnicas 3 101 54 3 101 56 3 101 58 MODELO ARTÍCULO 3 101 55 3 101 57 3 101 59 1000 VA 2000 VA 3000 VA Intervalo tensión de entrada 210~240Vca PF=0.9(900/1800/2700W)
-
Page 110
® 9 Características técnicas 3 101 54 3 101 56 3 101 58 MODELO ARTÍCULO 3 101 55 3 101 57 3 101 59 < 105% continuativo Modalidad 106-120% durante 30 segundos 121-150% durante 30 segundos Línea > 150% transferencia inmediata a bypass (On-Line) Beep de alarma continuo <105% continuativo… -
Page 111
KEOR LP 1, 2, 3 kVA 3 101 54 3 101 56 3 101 58 MODELO ARTÍCULO 3 101 55 3 101 57 3 101 59 Tiempo de Batería 3 horas recarga (al 90%) Arranque Sí en CC Autodiag- Accionando el pulsador del panel nóstico… -
Page 112
® 9 Características técnicas 3 101 54 3 101 56 3 101 58 MODELO ARTÍCULO 3 101 55 3 101 57 3 101 59 Dimensiones 236 × 144 × 367 322 x 151 x444 322 × 189 × 444 Pesos y (Hxlxp en mm) medidas Peso (Kg) -
Page 113
KEOR LP 1, 2, 3 kVA Index 1 Inleiding 2 Gebruiksvoorwaarden 3 Ledpaneel 4 Achterpaneel 5 Installatie 6 Functies en signalen 7 UPS Software 8 Problemen oplossen 9 Technische kenmerken… -
Page 114
De Keor LP is een UPS (Uninterruptable Power Supply of ononderbroken stroomtoevoer), ontworpen voor huishoudelijk, commercieel en industrieel gebruik. Deze handleiding bevat informatie over de modellen Keor LP van 1000, 2000 en 3000 kVA. U wordt geadviseerd om de veiligheidsvoorschriften op de verpakking en de instructies in deze handleiding aandachtig door te lezen en methodisch te volgen alvorens de UPS en de batterijkast te installeren. -
Page 115
KEOR LP 1, 2, 3 kVA • Plaats de UPS niet in een stoffige of agressieve omgeving of in de nabijheid van brandbare objecten. 0%~90% Deze UPS is niet ontworpen voor buiten gebruik. 0%~90% 0%~90% • Houd de ventilatieopeningen schoon en bedek ze niet, zodat de interne warmte van de UPS kan wor- den afgevoerd. -
Page 116
® 3 Ledpaneel Toetsen Symbool Beschrijving a. Knop om de UPS in te schakelen. (Druk en houd de knop ingedrukt totdat u een piep hoort). b. Het alarm geluid uitschakelen c. Weergave foutcodes Druk na een alarm op deze knop om het geluidssignaal uit te schakelen en de foutcode te bekijken. -
Page 117
KEOR LP 1, 2, 3 kVA Led indicatie Symbool Beschrijving lampjes 1. Als het lampje constant brandt, is de netspanning normaal. Als het lampje knippert, is de netspanning onvoldoende voor de volledige normale belasting. Als het lampje uit is, is de netspanning abnormaal. -
Page 118
® 4 Achterpaneel 3 101 54 3 101 56 3 101 58 3 101 55 3 101 57 3 101 59 1. Slot voor optionele communicatiekaart 2. Noodstop (EPO) (Emergency Power Off ) droge contacten signaal ingangen 3. Niet beschikbaar 4. -
Page 119
KEOR LP 1, 2, 3 kVA 5 Installatie Uitpakken Controleer de UPS bij ontvangst Verwijder de verpakking en ga voorizhtig om met de UPS, terwijl deze nog in de plastic verpakking zit en controleer of onderstaande inhoud van het standaardpakket aanwezig is: http://ups.legrand.com/biblioteca/… -
Page 120
® 5 Installatie De volgende aansluitingen zijn beschikbaar aan de achterkant van de UPS: • Uitgangsconnectoren (6) en ingangsconnectoren (8). • Vrouwelijke RS232-aansluiting met 9 pinnen [4] om de computer aan te sluiten als u de software voor diagnose en uitschakelingsbeheer gebruikt. •… -
Page 121
KEOR LP 1, 2, 3 kVA 5. Houd de knop ON ongeveer een seconde ingedrukt om de UPS op te starten. De zoemer gaat af en de leds y en gaan na 1 tot 5 seconden branden. De opstart procedure is nu voltooid ,en de UPS uitgangen zijn klaar om spanning te leveren aan de belasting. -
Page 122
® 6 Functies en signalen Geluidssignalen Onderstaande tabel geeft de meest voorkomende toestanden van de UPS weer met de bijhoren- de geluidssignalen. Toestand UPS Geluidssignalen UPS defect, omvormer uitgeschakeld. Alle functies Lange aanhoudende piep zijn uitgeschakeld. Bedieningspaneel fout Lange aanhoudende piep UPS defect, de belastingen worden gevoed door de Enkele piep om de twee seconden UPS of bypass… -
Page 123
KEOR LP 1, 2, 3 kVA Onderstaande tabel vat samen hoe de UPS werkt bij verschillende vermogens en batterijtoestanden. Toestand Werkingsmodus UPS Leds elektriciteitsnet Ongeveer 5 seconden nadat de UPS is opgestart, ledlampje aan gaan de LEDs op het paneel knipperen en ledlampje aan beginnen de ventilatoren te werken. -
Page 124
® 6 Functies en signalen Werking bij een probleem op het elektriciteitsnet In abnormale omstandigheden werkt de UPS als volgt: GELIJKRICHTER STATISCHE AC/DC-OMVORMER WISSELRICHTER UITGANG SCHAKELAAR DC/DC-OMVORMER ELEKTRICITEITSNET LADER BATTERIJ Afbeelding 5.3 1. Bij abnormale omstandigheden in het elektriciteitsnet richt de UPS de energie van de batterij automatisch en onmiddellijk naar de wisselrichter. -
Page 125
KEOR LP 1, 2, 3 kVA 1. Doorgaans genereren moderne elektronica en IT-apparatuur een hoge aanspreekstroom wanneer ze worden ingeschakeld. Die aanspreekstroom varieert naargelang het apparaat en kan tot zes keer de nominale capaciteit bedragen of juist verwaarloosbaar zijn. Om ernstige schade aan de UPS ten gevolge van deze aanspreekstroom te vermijden, is hij uitgerust met een elektronische overbelas- tingbeveiliging. -
Page 126
® 6 Functies en signalen Oververhitting van de UPS Als de UPS oververhit geraakt terwijl de netvoeding normaal is, schakelt hij over op bypassmodus. Hij keert terug naar de UPS-modus wanneer hij is afgekoeld. Bij oververhitting door abnormale omstandigheden geeft de zoemer een constante pieptoon. De alarmled gaat branden en de UPS schakelt de voeding van de belastingen uit. -
Page 127
KEOR LP 1, 2, 3 kVA 7 UPS Software U kunt de software van de UPS downloaden op de website www.ups.legrand.com. Die software heeft de volgende functies: — De plaatselijke pc die is aangesloten op de UPS via RS232 automatisch gecontroleerd uitschakelen. -
Page 128
Neem contact verhitting UPS) verifieer de storing op met uw verdeler van Legrand om eventueel de als volgt: ventilatoren te vervangen. 4. Ga na of de fasen “L” en” N” van de AC- 4. -
Page 129
KEOR LP 1, 2, 3 kVA Situatie Te controleren Oplossing Ga na of de UPS normaal maar geen Vraag technische bijstand aan uw voedingskabels uitgangsspanning naar de lokale verdeler als het probleem correct aangesloten belasting. aanhoudt. zijn. De UPS schakelt over op 1. -
Page 130
® 8 Problemen oplossen Foutcodes Als het controlelampje brandt, moet u kort op de knop ON drukken om de foutcode te lezen. Foutcodes 1, 2, 4, 8 en 16 worden weergegeven met de 4 ledbalken 25%, 50%, 75% en 100% en het controlelampje ‘overbelasting’… -
Page 131
KEOR LP 1, 2, 3 kVA 9 Technische kenmerken 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 1000 VA 2000 VA 3000 VA Bereik ingangsspanning 210~240Vac PF=0.9(900/1800/2700W) Capaciteit Power factor Bereik ingangsspanning 185~260Vac PF=0.8(800/1600/2400W) -
Page 132
® 9 Technische kenmerken 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 <105% continu 106-120% gedurende 30 sec Modus 121-150% gedurende 10 sec ‘online’ >150% onmiddellijk overschakeling op bypass. Aanhoudende pieptoon <105% continu 106-120% gedurende 30 sec… -
Page 133
KEOR LP 1, 2, 3 kVA 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 Oplaadtijd (tot Batterij 3 uur 90%) Opstarten op Auto- Met knop op paneel of met besturingssoftware… -
Page 134
® 9 Technische kenmerken 3 101 54 3 101 56 3 101 58 MODEL ITEM 3 101 55 3 101 57 3 101 59 Afmetingen (h x b x d) 236 × 144 × 367 322 x 151 x444 322 × 189 × 444 Fysieke (mm) kenmerken… -
Page 135
KEOR LP 1, 2, 3 kVA Содержание 1 Введение 2 Условия эксплуатации и меры безопасности 3 ЖК дисплей 4 Задняя панель 5 Монтаж 6 Управление и сигнализация 7 Программное обеспечение ИБП 8 Возможные неисправности 9 Технические характеристики… -
Page 136: Введение
Keor Line LP – это источник бесперебойного питания (ИБП) бытового, коммерческого и промышленного назначения. В данном руководстве содержится информация для пользователей ИБП модели Keor LP мощностью 1, 2, 3 кВА. Перед тем, как приступать к монтажу ИБП, настоятельно рекомендуется внимательно изучить требования настоящего руководства и тщательно следовать…
-
Page 137: Жк Дисплей
KEOR LP 1, 2, 3 kVA 3 ЖК дисплей • Не устанавливайте ИБП в запыленной или коррозионной атмосфере или возле огнеопасных объектов. Данный ИБП не предназначен для эксплуатации вне помещения. Во избежание перегрева ИБП не перекрывайте его вентиляционные отверстия и не ставьте…
-
Page 138
® 3 ЖК дисплей Кнопка Символ Описание управления a. Кнопка включения ИБП (нажмите и удерживайте, пока не услышите сигнал зуммера) b. Отключение зуммера ВКЛ. c. Визуализация кодов ошибок Получив аварийный сигнал, нажмите кнопку, чтобы выключить зуммер и отобразить код ошибки (не удерживайте более 1 с) Кнопка… -
Page 139
KEOR LP 1, 2, 3 kVA Светодиодный Символ Описание индикатор 1. Ровное свечение – напряжение сети в норме. Мигание – недостаточный уровень напряжения сети для питания полной Нормальный нагрузки. Не горит – недопустимое отклонение напряжения сети. режим 2. В режиме автономной работы/тестирования нагрузки указывает, что… -
Page 140: Задняя Панель
® 4 Задняя панель 3 101 54 3 101 56 3 101 58 3 101 55 3 101 57 3 101 59 1. Слот для опциональных коммуникационных карт 2. Вход с сухим контактом для приёма сигнала аварийного отключения питания (EPO) 3.
-
Page 141: Монтаж
KEOR LP 1, 2, 3 kVA 5 Монтаж Распаковка Проверка ИБП при получении Получив ИБП, освободите его от защиты из пенопласта и проверьте состав комплекта: http://upslegrand.ru/ru/biblioteca/ IEC — IEC 2000/3000 ВA (2) 1000/2000 ВА Schucko/французская – IEC 320-C14 2000/1000 ВA (1)
-
Page 142
® 5 Монтаж На задней панели ИБП расположены следующие разъёмы: • Выходные розетки [6], входной разъём [8]. • 9-контактная розетка RS232 для подключения последовательного кабеля компьютера [4]: требуется для использования программного обеспечения для диагностики и управления корректным завершением работы нагрузок. •… -
Page 143
KEOR LP 1, 2, 3 kVA 5. Чтобы запустить ИБП, нажмите кнопку ВКЛ. и удерживайте ее около 1 с. Сработает и загорятся через 1-5 с. Процедура зуммер и светодиодные индикаторы запуска закончена. Выходные розетки ИБП готовы питать нагрузку. 6. Перед подключением нагрузки рекомендуется проверить исправную работу ИБП в… -
Page 144
® 5 Монтаж Звуковые сигналы В таблице ниже указаны звуковые сигналы, соответствующие различным состояниям ИБП. Состояние ИБП Звуковые сигналы ИБП неисправен, отказ инвертора. Все функции не Непрерывное звучание работают. Неисправна клавиатура управления Непрерывное звучание ИБП неисправен, нагрузка продолжает питаться через 1 сигнал… -
Page 145: Управление И Сигнализация
KEOR LP 1, 2, 3 kVA 6 Управление и сигнализация В таблице ниже показана светодиодная индикация в зависимости от режима работы ИБП и состояния сети переменного тока. Состояние сети Режим работы ИБП Светодиоды Пуск происходит в течение приблизительно Ровное свечение…
-
Page 146
® 6 Управление и сигнализация Если напряжение сети не в норме или отсутствует Ниже показана схема работы ИБП, когда напряжение сети не в норме. Выпрямитель Статический Преобразователь АС/DС Инвертор переключатель Выход Усилитель DС/DС (SSM) Сеть Батарея ЗУ Рис. 5.3. 1. Если сеть не в норме, ИБП автоматически и без задержки переходит в автономный режим. Энергия… -
Page 147
KEOR LP 1, 2, 3 kVA 1. Современная электроника и IT оборудование генерируют высокие пусковые токи. Их величина варьируется от устройства к устройству, иногда превышая в шесть раз их номинальный ток, а иногда оставаясь практически незаметной. Для предотвращения повреждения инвертора пусковыми токами нагрузок, ИБП оборудован электронной… -
Page 148
® 6 Управление и сигнализация Перегрев Если ИБП перегреется при работе в нормальном режиме, то он автоматически переключится в режим байпаса. ИБП автоматически вернется в нормальный режим, когда перегрев исчезнет. Если ИБП перегреется в режиме байпаса, то зуммер будет звучать непрерывно и загорится… -
Page 149: Программное Обеспечение Ибп
KEOR LP 1, 2, 3 kVA 7 Программное обеспечение ИБП С сайта www.upslegrand.ru можно загрузить программное обеспечение ИБП. Оно может использоваться для выполнения следующих функций: — автоматическое завершение работы локального компьютера, — отображение параметров ИБП. Подключение к ПК Можно использовать кабель RS-232: Подключите…
-
Page 150: Возможные Неисправности
® 8 Возможные неисправности Поиск и устранение неисправностей Неисправность Что проверяется Действия по устранению 1. Проверьте правильность подключения батареи. Измерьте напряжение батареи, чтобы проверить ее заряд и исправность. При необходимости зарядите батарею в течение 8 ч. 1. Er05,Er24 Сымитируйте пропадание сетевого напряжения, чтобы…
-
Page 151
KEOR LP 1, 2, 3 kVA Неисправность Что проверяется Действия по устранению Проверьте ИБП в норме, но питание правильность Если проблема не устраняется, на выход не подается. подключения всех обратитесь в сервисный центр. шнуров питания. ИБП переключается 1. ИБП подключен к… -
Page 152
® 8 Возможные неисправности Коды ошибок Если горит светодиод «Неисправность» , кратковременно нажмите кнопку ВКЛ чтобы проверить код ошибки. Коды ошибки 1, 2, 4, 8, и 16 отображаются четырьмя светодиодами «25%», «50%», «75%» и «100%», а также светодиодом «Перегрузка» Каждый светодиод соответствует числу, указанному на рисунке ниже. Например, если… -
Page 153: Технические Характеристики
KEOR LP 1, 2, 3 kVA 9 Технические характеристики 3 101 54 3 101 56 3 101 58 3 101 55 3 101 57 3 101 59 Полная 1000 ВА 2000 ВА 3000 ВА при входном напряжении 210~240 В, КМ=0,9 (900/1800/2700 Вт)
-
Page 154
® 9 Технические характеристики 3 101 54 3 101 56 3 101 58 3 101 55 3 101 57 3 101 59 <105% длительно 106-120% в течение 30 с Нормальный 121-150% в течение 10 с режим >150% немедленное переключение на байпас Зуммер… -
Page 155
KEOR LP 1, 2, 3 kVA KEOR LP 1, 2, 3 kVA 3 101 54 3 101 56 3 101 58 3 101 55 3 101 57 3 101 59 Время заряда Батарея 3 ч (до 90%) Холодный старт Да Самодиагностика… -
Page 156
® 9 Технические характеристики 3 101 54 3 101 56 3 101 58 3 101 55 3 101 57 3 101 59 Размеры 236 × 144 × 367 322 x 151 x 444 322 × 189 × 444 Физические (В x Ш x Г, мм) характеристики… -
Page 158
®… -
Page 160
: 33 5 55 06 87 87 Fax : 33 5 55 06 74 55 www.legrandelectric.com Legrand reserves at any time the right to modify the contents of this booklet and to communicate, in any form and modality, the changes brought to the same.