Sitrans lg250 руководство по эксплуатации

  • Contents

  • Table of Contents

  • Bookmarks

Quick Links

Guided Wave Radar

SITRANS LG250

4 … 20 mA/HART — two-wire

Coax probe

With SIL qualification

Operating Instructions • 04/2016

loading

Related Manuals for Siemens SITRANS LG250

Summary of Contents for Siemens SITRANS LG250

  • Page 1
    Guided Wave Radar SITRANS LG250 4 … 20 mA/HART — two-wire Coax probe With SIL qualification Operating Instructions • 04/2016…
  • Page 2
    SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 3: Table Of Contents

    Parameter adjustment — Extended adjustment…………..32 Saving the parameter adjustment data …………….52 Setup with PACTware Connect the PC ………………….53 Parameter adjustment with PACTware …………….54 Saving the parameter adjustment data …………….55 Set up with other systems PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 4
    12.2 Dimensions ……………………77 12.3 Trademark ……………………80 Safety instructions for Ex areas Take note of the Ex specific safety instructions for Ex applications. These instructions are attached as documents to each instrument with Ex approval and are part of the operating instructions manual. Editing status: 2016-04-18 SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 5: About This Document

    This arrow indicates a single action. Sequence of actions Numbers set in front indicate successive steps in a procedure. Battery disposal This symbol indicates special information about the disposal of bat- teries and accumulators. PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 6: For Your Safety

    During work on and with the device the required personal protective equipment must always be worn. Appropriate use SITRANS LG250 is a sensor for continuous level measurement. You can find detailed information about the area of application in chapter «Product description». Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.

  • Page 7: Sil Qualification According To Iec 61508

    Germany. The published NAMUR recommendations are accepted as the standard in field instrumentation. The device fulfils the requirements of the following NAMUR recom- mendations: • NE 21 – Electromagnetic compatibility of equipment • NE 43 – Signal level for malfunction information from measuring transducers • NE 53 – Compatibility of field devices and display/adjustment components • NE 107 – Self-monitoring and diagnosis of field devices For further information see www.namur.de. PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 8: Product Description

    • Standard electronics: Type FX80H.-SIL Scope of delivery The scope of delivery encompasses: • Sensor • Documentation – This operating instructions manual SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 9: Principle Of Operation

    Due to the qualification up to SIL2 or homogeneous redundant up to SIL3 (IEC 61508) the SITRANS LG250 is suitable for the use in safety-instrumented systems (SIS). The safety function (SIF) can be a monitoring of the max. or min. level or a combination of both.

  • Page 10
    Example: upper medium dielectric constant 2, lower medium at least dielectric constant 12. Gas phase (L3) • Air or gas mixture • Gas phase — dependent on the application, gas phase does not always exist (d2 = 0) SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 11: Packaging, Transport And Storage

    Ex-d double chamber housing. It is suitable for measured value indication and adjustment of sensors and is connected to the sensor with a four-wire standard cable up to 50 m (164 ft) long. PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 12
    DIN 2501, EN 1092-1, ASME B 16.5, JIS B 2210- 1984, GOST 12821-80. You can find additional information in the supplementary instructions manual «Flanges according to DIN-EN-ASME-JIS» (Document-ID 47574). Electronics module The electronics module SITRANS series LG is a replacement part for TDR sensors of SITRANS series LG. There is a different version avail- able for each type of signal output. You can find further information in the operating instructions manual «Electronics module SITRANS series LG». SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 13: Mounting

    These are mainly: • Active measuring component • Process fitting • Process seal Process conditions are particularly: • Process pressure • Process temperature • Chemical properties of the medium • Abrasion and mechanical influences PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 14: Mounting Instructions

    Fig. 4: Vessel with conical bottom Welding work Before beginning the welding work, remove the electronics module from the sensor. By doing this, you avoid damage to the electronics through inductive coupling. Inflowing medium Do not mount the instruments in or above the filling stream. Make sure that you detect the product surface, not the inflowing product. SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 15
    If there is a danger of the coaxial probe touching the vessel wall, then the probe must be fastened at the bottom end. Keep in mind that below the fastening, a measurement is not possible. PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 16
    Fig. 6: Fasten the probe 1 Coax probe Retaining sleeve SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 17: Connecting To Power Supply

    Prior to setup you have to replace these protective caps with ap- proved cable glands or close the openings with suitable blind plugs. With plastic housing, the NPT cable gland or the Conduit steel tube must be screwed without grease into the threaded insert. PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 18: Connecting

    4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx. 1 cm (0.4 in) of insulation from the ends of the individual wires 5. Insert the cable into the sensor through the cable entry SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 19
    When the screwdriver is released, the terminal closes again. You can find further information on the max. wire cross-section under «Technical data — Electromechanical data» 7. Check the hold of the wires in the terminals by lightly pulling on them PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 20: Wiring Plan, Single Chamber Housing

    The following illustrations apply to the non-Ex as well as to the Ex-ia version. Electronics compartment 4…20mA 6 7 8 Fig. 10: Electronics compartment, double chamber housing Internal connection to the terminal compartment For display and adjustment module or interface adapter SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 21: Double Chamber Housing With Disadapt

    Double chamber housing with DISADAPT Electronics compartment Fig. 12: View to the electronics compartment with DISADAPT for connection of the external display and adjustment unit DISADAPT Internal plug connection Plug connector M12 x 1 PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 22: Wiring Plan, Ex-D-Ia Double Chamber Housing

    Electronics compartment 4…20mA 6 7 8 Fig. 14: Electronics compartment, double chamber housing Internal connection to the terminal compartment For display and adjustment module or interface adapter Internal connection to the plug connector for external display and adjust- ment unit (optional) SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 23
    Fig. 17: View to the plug connector M12 x 1 Pin 1 Pin 2 Pin 3 Pin 4 Contact pin Colour connection ca- Terminal, electronics ble in the sensor module Pin 1 Brown PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 24: Supplementary Electronics

    As soon as a plausible measured value is found, the corresponding current is outputted to the signal cable. The value corresponds to the actual level as well as the settings already carried out, e.g. factory setting. SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 25: Functional Safety (Sil)

    Application area The instrument can be used for point level detection or level measure- ment of liquids and bulk solids in safety-instrumented systems (SIS) according to IEC 61508 and IEC 61511. Take note of the specifica- tions in the Safety Manual. PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 26: Safety Concept Of The Parameterization

    The DTM suitable for the signal conditioning instrument in con- junction with an adjustment software according to the FDT/DTM standard, e. g. PACTware Note: To operate SITRANS LG250, the DTM Collection version 1.67.2 or higher is required. The modification of safety-relevant parameters is only possible with active connection to the instrument (online mode). Safe parameterization…

  • Page 27: Setup Process

    Safety Manual. Setup — Function test When locking the adjustment, the instrument checks the data of the measurement loop and decides on the basis of the evaluation results if a function test is required. PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 28
    4 and 20 mA. You then can calculate the respective output current. Measure the output current of SITRANS LG250 with a suitable multi- meter and compare the measured output current with the calculated output current.
  • Page 29
    Then you carry out a comparison of two character strings. You must confirm that the character strings are identical. This is used to check the character presentation. Then you confirm that the serial number of your instrument has been carried over correctly. This is used to check device communication. Then, all modified parameters that have to be confirmed are listed. After this process is terminated, the safety function is again ensured. PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 30: Set Up With The Display And Adjustment Module

    Fig. 19: Insertion of the display and adjustment module with single chamber housing Note: If you intend to retrofit the instrument with a display and adjustment module for continuous measured value indication, a higher lid with an inspection glass is required. SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 31: Adjustment System

    5 s, the display returns to the main menu. The menu language is then switched over to «English». Approx. 60 minutes after the last pressing of a key, an automatic reset to measured value indication is triggered. Any values not confirmed with [OK] will not be saved. PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 32: Parameter Adjustment — Extended Adjustment

    Switch-on phase After switching on, the SITRANS LG250 carries out a short self-test where the device software is checked. The output signal transmits a fault signal during the switch-on phase. The following information is displayed on the display and adjustment module during the startup procedure: •…

  • Page 33
    When choosing «Yes», then the probe length will be determined automatically. When choosing «No», you can enter the probe length manually. Setup — Application — Type Coax probes can be only used in liquids. In this menu item, the fixed of medium adjusted medium type «Liquid» is displayed. PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 34
    «Application». In this menu item you can enter if there is a superimposed gas phase in your application. Only set the function to «Yes», if the gas phase is permanently pre- sent. SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 35
    In this menu item you can enter the min. adjustment for the level. With Level interface measurement this is the minimum total level. Adjust the requested percentage value with [+] and store with [OK]. PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 36
    (accept adjustment of the level measure- ment), the current setting will be displayed. If you have selected «No», you can enter the adjustment for the inter- face measurement separately. SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 37
    For the socket correction you have to enter the height of the socket above the upper edge of the vessel. If the socket is lower than the up- per edge of the vessel, this value can also be negative. PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 38
    The default setting is output characteristics 4 … 20 mA, failure mode < 3.6 mA. Setup — Current output In the menu item «Current output Min./Max.», you determine the reac- Min./Max. tion of the current output during operation. SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 39
    This is useful if the saved false signal suppression no longer matches the metrological conditions in the vessel. Unlock setup — adjust- With this menu item you safeguard the sensor parameters against ment unauthorized or unintentional modifications. PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 40
    4 and 20 mA. You then can calculate the respective output current. Measure the output current of SITRANS LG250 with a suitable multi- meter and compare the measured output current with the calculated output current.
  • Page 41
    If you have to interrupt the function, you can leave the SITRANS LG250 in the respective situation. As long as SITRANS LG250 is powered, the display and adjustment module remains in the currently set adjustment menu. To interrupt the function test, you have to push the button «ESC».
  • Page 42
    The default setting for the displayed value 2 is the electronics tem- perature. Display — Backlight The integrated background lighting can be switched off via the adjustment menu. The function depends on the strength of the supply voltage, see «Technical data». In delivery status, the lighting is switched on. SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 43
    Diagnostics — Peak values Additional sensor. The values are displayed in the menu item «Peak values Ad- ditional». This menu item displays the peak values of the electronics tempera- ture as well as the dielectric constant. PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 44
    Select the requested simulation variable and set the requested value. Caution: During simulation, the simulated value is outputted as 4 … 20 mA cur- rent value and digital HART signal. Push the [ESC] key to deactivate the simulation. SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 45
    During the function test, the safety function must be treated as unsafe. Keep in mind that the function test influences downstream connected devices. You can find detailed information on the proof test in the Safety Manual (SIL). In this menu item, the internal clock of the sensor is adjusted. Additional adjustments — Date/Time PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 46
    Superimposed gas phase Dielectric constant, upper medium (TS) Tube inner diameter 200 mm Max. adjustment — Level 100 % Max. adjustment — Level Distance: 0.000 m(d) — note block- ing distances Min. adjustment — Level SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 47
    Current output 2 — Output characteristics 0 … 100 % correspond to 4 … 20 mA Current output 2 — Reaction in case of failure ≤ 3.6 mA Current output — Min. 3.8 mA Current output — Max. 20.5 mA PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 48
    Actual time Time — Format 24 hours Probe type Device-specific HART mode Analogue current output Additional adjustments — The instrument settings are copied with this function. The following Copy instrument settings functions are available: SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 49
    Since scaling is very extensive, scaling of the level value was divided ing level 2 into two menu items. In menu item «Level 2» you define the scaling format on the display and the scaling of the measured level value for 0 % and 100 %. PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 50
    In menu item «Current output, variable» you specify which measured rent output, size variable the current output refers to. Additional settings — Cur- In menu item «Current output, adjustment» you can assign a respec- rent output, adjustment tive measured value to the current output. SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 51
    PC. Info — Sensor character- In this menu item, the features of the sensor such as approval, pro- istics cess fitting, seal, measuring range, electronics, housing and others are displayed. PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 52: Saving The Parameter Adjustment Data

    If it is necessary to exchange a sensor, the display and adjustment module is inserted into the replacement instrument and the data are likewise written into the sensor via the menu item «Copy sensor data». SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 53: Setup With Pactware

    Setup with PACTware Connect the PC Via the interface adapter directly on the sensor Fig. 22: Connection of the PC directly to the sensor via the interface adapter 1 USB cable to the PC Interface adapter Sensor Connection via HART Fig. 23: Connecting the PC via HART to the signal cable Sensor 2 HART resistance 250 Ω (optional depending on evaluation) Adapter cable for HART modem 4 Processing system/PLC/Voltage supply HART modem PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 54: Parameter Adjustment With Pactware

    Furthermore a tank calculation program as well as a multiviewer for indication and analysis of the saved measured value and echo curves are available. The supplied DVD includes the respective device DTM. How- ever, you can also download the DTM from our homepage www.siemens.com/sitranslg. SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 55: Saving The Parameter Adjustment Data

    Saving the parameter adjustment data We recommend documenting or saving the parameter adjustment data via PACTware. That way the data are available for multiple use or service purposes. PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 56: Dd Adjustment Programs

    This software is updated via the Internet and new EDDs are automatically taken over into the device catalogue of this software after they are released by the manufacturer. They can then be transferred to a Field Communicator. SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 57: Diagnostics And Servicing

    Event memory Up to 500 events are automatically stored with a time stamp in the sensor (non-deletable). Each entry contains date/time, event type, event description and value. Event types are for example: PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 58: Status Messages

    Fig. 25: Pictographs of the status messages Failure — red 2 Out of specification — yellow 3 Function check — orange Maintenance — blue Failure: Due to a malfunction in the instrument, a failure message is outputted. SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 59
    – Check probe and exchange, if Bit 13 of defective necessary Byte 0 … 5 Probe loss F080 – General software error – Disconnect operating voltage Bit 5 of briefly Byte 0 … 5 General software error PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 60
    – Finish simulation «Simulation Active» in «Stand- – Wait for the automatic end after Simulation active ardized Status 0» 60 mins. C701 – Parameter verification was inter- – Finish parameter verification Bit 12 of rupted Byte 14 …24 Parameter verifi- cation SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 61: Rectify Faults

    – False signal suppression faulty 10.4 Rectify faults Reaction when malfunc- The operator of the system is responsible for taking suitable meas- tion occurs ures to rectify faults. Procedure for fault recti- The first measures are: fication PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 62
    Wherever the sensor displays a constant value, the reason could also be the fault setting of the current output to «Hold value» • If the level indication is too low, the reason could be a line resist- ance that is too high SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 63
    – Check installation conditions range. The sensor goes into – If possible, switch off the func- overfill protection mode. The time tion «Overfill protection» max. level (0 m distance) as well as the status message «Overfill protection» are output- ted. PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 64: Exchanging The Electronics Module

    A new setup is no more necessary. After the new setup and the transfer of the parameterization date, you have to verify the parameters. Only then, the instrument will be ready for operation, again. SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 65: Software Update

    Instruments with approvals can be bound to certain software versions. Therefore make sure that the approval is still effective after a software update is carried out. You can find detailed information in the download area on our home- page: www.siemens.com/sitranslg. 10.7 How to proceed if a repair is necessary If it is necessary to repair the instrument, please contact Sie- mens Milltronics Process Instruments. You find the locations on «www.siemens.com/sitranslg». PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 66: Dismount

    Pass the instrument directly on to a spe- cialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive. SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 67: Supplement

    Ʋ Inspection window in housing cover Polycarbonate (with Ex d version: glass) (optional) Ʋ Ground terminal 316L Ʋ Cable gland PA, stainless steel, brass Ʋ Sealing, cable gland Ʋ Blind plug, cable gland Not suitable for hot steam applications PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 68
    Ʋ Plastic housing max. 10 Nm (7.376 lbf ft) Ʋ Aluminium/Stainless steel housing max. 50 Nm (36.88 lbf ft) Input variable Measured variable Level of liquids Min. dielectric constant of the medium ε ≥ 1.4 SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 69
    Ʋ Displayed value 2 Electronics temperature Resolution, digital < 1 mm (0.039 in) The output values can be assigned individually The indication values can be assigned individually The indication values can be assigned individually PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 70
    Probe end does not touch the vessel bottom Sensor parameter adjustment No gating out of false signals carried out Fig. 35: Measuring ranges — SITRANS LG250 Reference plane Probe length L Measuring range (default setting refers to the measuring range in water)
  • Page 71
    0,05 m 0,03 m (1.181 » 0,15 m (5.906 » (1.969 «) Fig. 36: Deviation SITRANS LG250 in coax version in water Dead band — no measurement possible in this area Probe length 10 mm (0.394 «) 5 mm (0.197 «) 2 mm (0.079…
  • Page 72
    -40 … +80 °C (-40 … +176 °F) ture Also for the additional current output (optional) Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2). SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 73: Process Conditions

    -40°C / -40°F Fig. 38: Ambient temperature — process temperature, standard version Ambient temperature Process temperature (depending on the seal material) Aluminium housing Plastic housing Stainless steel housing, precision casting Stainless steel housing, electropolished PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 74
    1 x blind plug NPT, 1 x closing cap (red) ½ NPT Wire cross-section (spring-loaded terminals) Ʋ Massive wire, stranded wire 0.2 … 2.5 mm² (AWG 24 … 14) Ʋ Stranded wire with end sleeve 0.2 … 1.5 mm² (AWG 24 … 16) SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 75
    Integrated Permissible residual ripple — Non-Ex, Ex-ia instrument Ʋ for 9.6 V< U < 14 V ≤ 0.7 V (16 … 400 Hz) Ʋ for 18 V< U < 36 V ≤ 1.0 V (16 … 400 Hz) PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 76
    IP 66/IP 68 (0.2 bar) Type 6P Protection class Approvals Instruments with approvals can have deviating technical data (depending on the version). For such instruments, the corresponding approval documents must be noted. IEC 61010-1 SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 77: Dimensions

    Aluminium housing ~ 91 mm (3.58″) ~ 116 mm (4.57″) ø 84 mm ø 84 mm (3.31″) (3.31″) M16x1,5 M20x1,5 M20x1,5/ ½ NPT M20x1,5/ ½ NPT Fig. 41: Housing versions with protection rating IP 66/IP 68 (0.2 bar) — with integrated display and adjustment module the housing is 9 mm/0.35 in higher Single chamber version Double chamber version PBD-51041387 SITRANS LG250 — Operating Instructions…

  • Page 78
    ø 80 mm ø 77 mm (3.31″) (3.15″) (3.03″) M16x1,5 M20x1,5/ ½ NPT M20x1,5/ M20x1,5/ ½ NPT ½ NPT Fig. 42: Housing versions with protection rating IP 66/IP 68 (0.2 bar) — with integrated display and adjustment module the housing is 9 mm/0.35 in higher Single chamber version, electropolished Single chamber version, precision casting Double chamber version, precision casting SITRANS LG250 — Operating Instructions PBD-51041387…
  • Page 79
    G¾, ¾ NPT, G1, 1 NPT, G1½, 1½ NPT G1½, 1½ NPT ø 21,3 mm ø 42,2 mm (0.84″) (1.66″) Fig. 43: SITRANS LG250, threaded version Sensor length, see chapter «Technical data» Coaxial version ø 21.3 mm (0.839 in) Coaxial version ø 42.2 mm (1.661 in) PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 80: Trademark

    12.3 Trademark All the brands as well as trade and company names used are property of their lawful proprietor/ originator. SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 81
    Read out info 51 Event memory 57 Repair 65 Replacement parts – Electronics module 12 Factory calibration date 51 Reset 46 False signal suppression 39 Fault rectification 61 Functional principle 9 Scaling measured value 49, 50 PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 82: Sitrans Lg250 — Operating Instructions Pbd

    Sensor characteristics 51 Sensor status 43 SIL 25 Simulation 44 Special parameters 51 Type label 8 Type of medium 33 Units 33 Unlock adjustment 39 Verify parameter 29 SITRANS LG250 — Operating Instructions PBD-51041387…

  • Page 83
    Notes PBD-51041387 SITRANS LG250 — Operating Instructions…
  • Page 84
    For more information www.siemens.com/level www.siemens.com/weighing Siemens Canada Limited Subject to change without prior notice PD PA PI LW PBD-51041387 Rev. 3.0 1954 Technology Drive P.O. Box 4225 © Siemens AG 2016 Peterborough, ON K9J 7B1, Canada email: techpubs.smpi@siemens.com Printed in Canada www.siemens.com/processautomation…

  • Contents

  • Table of Contents

  • Bookmarks

Quick Links

Guided Wave Radar

SITRANS LG250

Profibus PA

Rod and cable probe

Operating Instructions • 01/2020

Related Manuals for Siemens SITRANS LG250

Summary of Contents for Siemens SITRANS LG250

  • Page 1
    Guided Wave Radar SITRANS LG250 Profibus PA Rod and cable probe Operating Instructions • 01/2020…
  • Page 2
    SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 3: Table Of Contents

    Saving the parameterisation data ………………. 52 Set up with other systems ………………..53 DD adjustment programs ………………..53 Diagnostics and servicing ………………..54 Maintenance ……………………54 Diagnosis memory ………………….54 Status messages ………………….55 Rectify faults ……………………58 PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 4
    11.3 Dimensions ……………………84 11.4 Trademark ……………………89 Safety instructions for Ex areas Take note of the Ex specific safety instructions for Ex applications. These instructions are attached as documents to each instrument with Ex approval and are part of the operating instructions. Editing status: 2020-01-24 SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 5: About This Document

    The dot set in front indicates a list with no implied sequence. Sequence of actions Numbers set in front indicate successive steps in a procedure. Battery disposal This symbol indicates special information about the disposal of bat- teries and accumulators. PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 6: For Your Safety

    During work on and with the device, the required personal protective equipment must always be worn. Appropriate use SITRANS LG250 is a sensor for continuous level measurement. You can find detailed information about the area of application in chapter «Product description». Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.

  • Page 7: Eu Conformity

    English language. Installations in the US shall comply with the relevant requirements of the National Electrical Code (ANSI/NFPA 70). Installations in Canada shall comply with the relevant requirements of the Canadian Electrical Code. PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 8: Product Description

    • Optional accessory The further scope of delivery encompasses: • Documentation – Operating instructions SITRANS LG250 – Instructions for optional instrument features – Ex-specific «Safety instructions» (with Ex versions) – If necessary, further certificates Information: Optional instrument features are also described in this operating instructions manual.

  • Page 9: Principle Of Operation

    13 ID numbers, instrument documentation 14 Hardware and software version Principle of operation Application area The SITRANS LG250 is a level sensor with cable or rod probe for continuous level or interface measurement, suitable for applications in liquids. Functional principle -…

  • Page 10
    Distance to the interface d2 Distance to the level TS Thickness of the upper medium (d1 — d2) h1 Height — Interface h2 Height — Level L1 Lower medium L2 Upper medium L3 Gas phase SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 11: Packaging, Transport And Storage

    Ascertained transit damage or con- cealed defects must be appropriately dealt with. Storage Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside. PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 12: Accessories

    Rod segments: 20 … 5900 mm (0.79 … 232 in) • Curved segments: 100 x 100 mm (3.94 … 3.94 in) If you mount the SITRANS LG250 in a bypass tube or standpipe, you Centering have to avoid contact to the bypass tube by using a spacer at the probe end.

  • Page 13: Mounting

    Prior to setup you have to replace these protective caps with ap- proved cable glands or close the openings with suitable blind plugs. Note: Process conditions For safety reasons, the instrument must only be operated within the permissible process conditions. You can find detailed information on PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 14: Mounting Instructions

    Mounting instructions Installation position Mount SITRANS LG250 in such a way that the distance to vessel installations or to the vessel wall is at least 300 mm (12 in). In non- metallic vessels, the distance to the vessel wall should be at least 500 mm (19.7 in).

  • Page 15
    In such cases, always carry out a false signal suppression after mounting. You can find further information under «Setup procedure». DN25 … DN150 ≤ 150 mm (5.91″) > DN150 … DN200 ≤ 100 mm (3.94″) Fig. 6: Mounting socket When welding the socket, make sure that the socket is flush with the vessel top. PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 16
    «Technical data». Keep in mind for the adjustment that the default setting for the measuring range refers to water. SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 17
    If durability is no problem, we recommend the use of uncoated metal standpipes. When the SITRANS LG250 is used in bypass tubes, contact with the tube wall must be avoided. We recommend for this purpose a cable probe with centering weight.
  • Page 18
    It does not matter if the standpipe is perforated or slotted for better mixing. Measuring probes can be mounted in standpipes up to DN 200. SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 19
    If durability is no problem, we recommend the use of uncoated metal standpipes. When the SITRANS LG250 is used in standpipes, contact with the tube wall must be avoided. We recommend for this purpose a cable probe with centering weight.
  • Page 20
    If there is a risk of the cable probe touching the vessel wall during operation due to product movements or agitators, etc., the measuring probe can be strained. For this purpose there is an internal thread (M12 or M8) in the gravity weight. SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 21
    Rod extension In case of difficult installation conditions, for example in a socket, the probe can be suitably adapted with a rod extension. To compensate for the resulting changes in signal runtime, let the instrument determine the probe length automatically. You can find further information in the supplementary instructions of the rod and cable components. PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 22: Connecting To Power Supply

    Note: Prior to setup you have to replace these protective caps with ap- proved cable glands or close the openings with suitable blind plugs. SITRANS LG250 — Operating Instructions PBD-51041053…

  • Page 23: Connecting

    5. Insert the cable into the sensor through the cable entry Fig. 13: Connection steps 5 and 6 Single chamber housing Double chamber housing 6. Insert the wire ends into the terminals according to the wiring plan PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 24: Wiring Plan, Single Chamber Housing

    Selection switch for instrument address For external display and adjustment unit Ground terminal for connection of the cable screening Wiring plan, double chamber housing The following illustration applies to the non-Ex, Ex-ia and Ex-d ver- sion. SITRANS LG250 — Operating Instructions PBD-51041053…

  • Page 25: Set Instrument Address

    The address setting is carried out either via: • The address selection switch in the electronics compartment of the instrument (address setting via hardware) • The display and adjustment module (address setting via software) • PACTware/DTM (address setting via software) PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 26: Switch-On Phase

    PC • Status byte goes to fault value Then the actual measured value is output to the signal cable. The value takes into account settings that have already been carried out, e.g. default setting. SITRANS LG250 — Operating Instructions PBD-51041053…

  • Page 27: Set Up With The Display And Adjustment Module

    Fig. 18: Insertion of the display and adjustment module with single chamber housing Note: If you intend to retrofit the instrument with a display and adjustment module for continuous measured value indication, a higher lid with an inspection glass is required. PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 28: Adjustment System

    [OK] will not be saved. Switch-on phase After switching on, the SITRANS LG250 carries out a short self-test where the device software is checked. The output signal transmits a fault signal during the switch-on phase. The following information is displayed on the display and adjustment module during the startup procedure: •…

  • Page 29: Parameter Adjustment — Quick Setup

    False signal suppression You can find the description of the individual menu items in the follow- ing chapter «Parameter adjustment — Extended adjustment». Parameter adjustment — Extended adjustment For technically demanding measuring points, you can carry out extended settings in «Extended adjustment». Main menu The main menu is divided into five sections with the following func- tions: PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 30
    The display and adjustment module (address setting via software) • PACTware/DTM (address setting via software) Hardware addressing Hardware addressing is effective if an address less than 126 is set with the address selection switches on the electronics module of SITRANS LG250. In such case, software addressing has no effect — only the set hardware address applies. SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 31
    In this menu item you can enter the probe length or have the length determined automatically by the sensor system. When choosing «Yes», then the probe length will be determined automatically. When choosing «No», you can enter the probe length manually. PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 32
    «Application». In this menu item you can enter if there is a superimposed gas phase in your application. Only set the function to «Yes», if the gas phase is permanently pre- sent. SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 33
    Min. adjustment level In this menu item you can enter the min. adjustment for the level. With interface measurement this is the minimum total level. Adjust the requested percentage value with [+] and store with [OK]. PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 34
    Enter the respective distance value in m for the interface correspond- ing to the percentage value of the interface. False signal suppression The following circumstances cause interfering reflections and can influence the measurement: • High mounting sockets • Vessel internals such as struts SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 35
    Corresponding linearisation curves are preprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume. PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 36
    If the socket is lower than the up- per edge of the vessel, this value can also be negative. Fig. 20: Vessel height and socket correction value D Vessel height +h Positive socket correction value -h Negative socket correction value SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 37
    AI FB1 — damping To damp process-dependent measured value fluctuations, you can set a time of 0 … 999 s in this menu item. The damping applies to the level and interface measurement. The default setting is a damping of 0 s. PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 38
    This menu item enables the setting of the requested national lan- guage. In delivery status, the sensor is set to English. Displayed value 1 In this menu item, you define the indication of the measured value on the display. You can display two different measured values. In this menu item, you define measured value 1. The default setting for the displayed value 1 is «Filling height Level». SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 39
    The two values are displayed in the menu item «Peak values, distance». If you have selected interface measurement under the menu item «Setup — Application», the peak values of the interface measurement are displayed in addition to the peak values of the level measurement. PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 40
    This menu item displays the peak values of the electronics tempera- ture as well as the dielectric constant. In another window you can carry out a reset of the two peak values separately. SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 41
    With this, you can detect signal changes over the operating time. With the adjustment software PACTware and the PC, the high-resolution echo curve can be displayed and used to compare the echo curve of the setup with the actual echo curve. PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 42
    Basic settings: Resetting of the parameter settings incl. special parameters to the default values (presettings) of the respective instru- SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 43
    Primary Value (lin. percent level) AI FB1 scaling PV Scale (min.) AI FB1 scaling PV Scale (max.) 100 % AI FB1 Lin. Type Linear AI FB1 Out Scale Unit AI FB1 Out Scale Decimal Point #.## PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 44
    Device memory — Measured value memory — Start with meas- Not active ured value Device memory — Measured value memory — Stop with meas- Not active ured value Device memory — Measured value memory — Stop recording Not active when memory is full SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 45
    AI FB3 Out Scale (min.) AI FB3 Out Scale (max.) 100 % AI FB3 PV FTime AI FB3 Hi Hi Limit 3.402823E+38 % AI FB3 Hi Limit 3.402823E+38 % AI FB3 Lo Lo Limit -3.402823E+38 % PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 46
    TAG-no. this sensor had. Tip: We recommend to save the instrument adjustments. In case of an electronics exchange the saved parameter adjustment data relieve this process. SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 47
    PC. Profibus Ident Number In this menu item, the Profibus ident number of your sensor is dis- played. Sensor characteristics In this menu item, the features of the sensor such as approval, pro- cess fitting, seal, measuring range, electronics, housing and others are displayed. Example for displayed sensor features. PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 48: Saving The Parameterisation Data

    In the display and adjust- If the instrument is equipped with a display and adjustment module, ment module the parameter adjustment data can be saved therein. The procedure is described in menu item «Copy device settings». SITRANS LG250 — Operating Instructions PBD-51041053…

  • Page 49: Setup With Pactware

    A description of the update procedure is also available in the Internet. The further setup steps are described in the online help of PACTware and the DTMs. PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 50: Set Up With The Quick Setup

    The quick setup is another option for parameter adjustment of the sensor. It allows fast, convenient adjustment of the most important parameters to adapt the sensor quickly to standard applications. To use it, select the function «Quick setup» in the start screen. SITRANS LG250 — Operating Instructions PBD-51041053…

  • Page 51
    Extended adjustment Maintenance Quick setup With quick setup you can carry out the parameter adjustment of SITRANS LG250 for your application in just a few simple steps. The assistant-driven adjustment includes the basic settings for simple, reliable setup and commissioning. Information: If the function is inactive, then possibly no instrument is connected.
  • Page 52: Saving The Parameterisation Data

    Saving the parameterisation data We recommend documenting or saving the parameterisation data via PACTware. That way the data are available for multiple use or service purposes. SITRANS LG250 — Operating Instructions PBD-51041053…

  • Page 53: Set Up With Other Systems

    Set up with other systems DD adjustment programs Device descriptions as Enhanced Device Description (EDD) are available for DD adjustment programs such as, for example, AMS↑ and PDM. PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 54: Diagnostics And Servicing

    • Modification of a parameter • Switch-on and switch-off times • Status messages (according to NE 107) • Error messages (according to NE 107) The data are read out via a PC with PACTware/DTM or the control system with EDD. SITRANS LG250 — Operating Instructions PBD-51041053…

  • Page 55: Status Messages

    This status message is always active. It cannot be deactivated by the user. Function check: The instrument is being worked on, the measured value is temporarily invalid (for example during simulation). This status message is inactive by default. PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 56
    Disconnect operating voltage briefly munication Communication Send instrument for repair error F125 Temperature of the electronics in the Check ambient temperature Bit 7 non-specified range Impermissible Insulate electronics electronics tem- Use instrument with higher temper- perature ature range SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 57
    S601 Level echo in the close range not Reduce level Bit 24 available Overfilling 100 % adjustment: Increase value Check mounting socket Remove possible interfering signals in the close range Use coaxial probe PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 58: Rectify Faults

    The operator of the system is responsible for taking suitable meas- tion occurs ures to rectify faults. The first measures are: Fault rectification • Evaluation of fault messages • Checking the output signal • Treatment of measurement errors SITRANS LG250 — Operating Instructions PBD-51041053…

  • Page 59
    Amplitude or position of a false signal Determine the reason for the changed has changed (e.g. buildup); false signal false signals, carry out false signal sup- time suppression no longer matches pression, e.g. with buildup PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 60
    Measured value remains re- Stored false signals in this position are Delete false signal suppression producible in one position larger than the level echo Carry out a new false signal suppression during emptying time SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 61
    Amplitude or position of a false signal has Determine the reason for the changed false changed (e.g. condensation, buildup); false signals, carry out false signal suppression, signal suppression no longer matches ac- e.g. condensation time tual conditions PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 62
    Carry out false signal suppression or in- jumps sporadically the antenna crease false signal suppression in the close towards 100 % dur- range by editing ing emptying With bulk solids use radar sensor with purg- ing air connection or flexible antenna cover time SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 63: Exchanging The Electronics Module

    If necessary, the cable or rod (measuring part) of the probe can be exchanged. Loosen the rod or cable with a fork wrench, wrench size 7 (rod ø 8, cable ø 2 and 4) or wrench size 10 (rod ø 12). Note: When exchanging the rod or cable, make sure that the instrument and the new rod or cable are dry and clean. PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 64
    3. Cable: remove the pins 4. Cable: Pull the cable out of the gravity weight 5. Shorten the cable/rod with a cut-off wheel or metal saw at the marking. Take note of the specifications in the following illustration when shortening the cable. 6. Cable with gravity weight: Shift the cable according to the drawing into the gravity weight SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 65: Software Update

    Current sensor software as file You can find the actual sensor software as well as detailed infor- mation of the procedure in the download area on our homepage: www.siemens.com/sitranslg. You can find information about the installation in the download file. Caution: Instruments with approvals can be bound to certain software versions. Therefore make sure that the approval is still effective after a software update is carried out. You can find detailed information in the download area on our home- page: www.siemens.com/sitranslg. PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 66: How To Proceed If A Repair Is Necessary

    How to proceed if a repair is necessary If it is necessary to repair the instrument, please contact Siemens. You find the locations on «www.siemens.com/processautomation». SITRANS LG250 — Operating Instructions PBD-51041053…

  • Page 67: Dismount

    Pass the instrument directly on to a specialised recycling company and do not use the municipal collecting points. If you have no way to dispose of the old instrument properly, please contact us concerning return and disposal. PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 68: Supplement

    Ʋ Seal between housing and housing lid Silicone SI 850 R Ʋ Inspection window in housing cover Plastic housing: Polycarbonate (optional) Metal housing: Glass Ʋ Ground terminal 316L Ʋ Cable gland PA, stainless steel, brass Ʋ Sealing, cable gland Ʋ Blind plug, cable gland SITRANS LG250 — Operating Instructions PBD-51041053…

  • Page 69
    ±(2 mm + 0.05 % of the cable length) Lateral load Ʋ Rod: ø 8 mm (0.315 in) 10 Nm (7.38 lbf ft) Ʋ Rod: ø 12 mm (0.472 in) 30 Nm (22.13 lbf ft) PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 70
    Ʋ 2. FB Secondary Value 1 (filling height in %) Ʋ 3. FB Secondary Value 2 (distance value) Current value Ʋ Non-Ex and Ex ia instrument 10 mA, ±0.5 mA Ʋ Ex-d-ia instruments 16 mA, ±0.5 mA Resolution, digital < 1 mm (0.039 in) SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 71
    Probe end does not touch the vessel bottom Sensor parameter adjustment No gating out of false signals carried out Fig. 28: Measuring ranges — SITRANS LG250 Reference plane Probe length L Measuring range (default setting refers to the measuring range in water)
  • Page 72
    0,08 m 0,3 m 0,02 m (3.15 (11.811 » » (0.787 «) Fig. 29: Deviation SITRANS LG250 in rod version in water Dead zone (no measurement possible in this area) Probe length 15 mm (0.591 » 2 mm (0.079 «) -2 mm (-0.079…
  • Page 73
    (3.15 «) Fig. 32: Deviation SITRANS LG250 in cable version (ø 2 mm/0.079 in), in medium oil Dead zone (no measurement possible in this area) When using a centering weight, it is only possible to measure up to the upper edge of the cerntering weight.
  • Page 74
    (5.906 «) Fig. 33: Deviation SITRANS LG250 in cable version (ø 4 mm/0.157 in), in medium oil Dead zone (no measurement possible in this area) When using a centering weight, it is only possible to measure up to the upper edge of the cerntering weight.
  • Page 75
    «) (1.969 «) 0,2 m (7.874 «) Fig. 35: Deviation SITRANS LG250 in cable version (ø 4 mm/0.157 in, PFA-coated), in oil Dead zone (no measurement possible in this area) Probe length Non-repeatability ≤ ±1 mm Variables influencing measurement accuracy Temperature drift — Digital output ±3 mm/10 K relating to the max.
  • Page 76
    -20 … +150 °C (-4 … +302 °F) Ʋ FFKM (Kalrez 6375) — with tempera- -20 … +200 °C (-4 … +392 °F) ture adapter Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2). SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 77
    -40°C / -40°F Fig. 37: Ambient temperature — process temperature, version with temperature adapter Ambient temperature Process temperature (depending on the seal material) Aluminium housing Plastic housing Stainless steel housing, precision casting Stainless steel housing, electropolished PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 78
    180 m (590.6 ft) Ʋ Min. bending radius (at 25 °C/77 °F) 25 mm (0.984 in) Ʋ Diameter approx. 8 mm (0.315 in) Ʋ Colour — Non-Ex version Black Ʋ Colour — Ex-version Blue SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 79
    IP66/IP68 (0.2 bar) Type 6P polished Stainless steel, precision Single chamber IP66/IP68 (0.2 bar) Type 6P casting Double chamber IP66/IP67 Type 4X IP66/IP68 (0.2 bar) Type 6P Galvanic separation between electronics and metal housing parts PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 80: Device Communication Profibus Pa

    The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during opera- tion. The below block diagram below shows which data can be accessed by the PLC. When used with fulfilled housing protection IEC 61010-1 SITRANS LG250 — Operating Instructions PBD-51041053…

  • Page 81
    Fig. 38: SITRANS LG250: Block diagram with AI FB 1 … AI FB 3 OUT values TB Transducer Block FB 1 … FB 3 Function Block Module of the PA sensors For the cyclic data traffic, SITRANS LG250 provides the following modules: • AI FB1 (OUT) – Out value of the AI FB1 after scaling •…
  • Page 82
    -10 -11 -12 -13 -14 -15 -16 -17 -18 -19 -20 -21 -22 -23 Sign Significant Significant Exponent Significant (Exponent — 127) Value = (-1) (1 + Significant) Fig. 40: Data format of the measured value SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 83
    — high limited 0 x 8d good (non-cascade) — ac- Lo-Lo-Alarm tive critical alarm — low limited 0 x 8e good (non-cascade) — ac- Hi-Hi-Alarm tive critical alarm — high limited PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 84: Dimensions

    ½ NPT Fig. 42: Housing versions with protection rating IP66/IP68 (0.2 bar), (with integrated display and adjustment mod- ule the housing is 9 mm/0.35 in higher) Aluminium — single chamber Aluminium — double chamber SITRANS LG250 — Operating Instructions PBD-51041053…

  • Page 85
    Fig. 43: Housing versions with protection rating IP66/IP68 (0.2 bar), (with integrated display and adjustment mod- ule the housing is 9 mm/0.35 in higher) Stainless steel single chamber (electropolished) Stainless steel single chamber (precision casting) Stainless steel double chamber housing (precision casting) PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 86
    (0.79″) (0.79″) (0.79″) Fig. 44: SITRANS LG250, threaded version with gravity weight (all gravity weights with thread M8 for eye-bolt) Sensor length, see chapter «Technical data» Cable version ø 2 mm (0.079 in) with gravity weight Cable version ø 4 mm (0.157 in) with gravity weight…
  • Page 87
    SITRANS LG250, cable version with centering weight SW 36 (1.42″) (G¾, ¾ NPT) SW 41 (1.61″) (G1, 1 NPT) SW 46 (1.81″) (G1½, 1½ NPT) G¾, ¾ NPT, G1, 1 NPT, G1½, 1½ NPT ø 4 mm ø 4 mm (0.16″)
  • Page 88
    G1½, 1½ NPT ø 8 mm ø 12¨mm (0.32″) (0.47″) Fig. 46: SITRANS LG250, threaded version Sensor length, see chapter «Technical data» Rod version ø 8 mm (0.315 in) Rod version ø 12 mm (0.472 in) SITRANS LG250 — Operating Instructions…
  • Page 89: Trademark

    11.4 Trademark All the brands as well as trade and company names used are property of their lawful proprietor/ originator. PBD-51041053 SITRANS LG250 — Operating Instructions…

  • Page 90
    Event memory 54 Quick setup 29 Factory calibration date 47 False signal suppression 34 Fault Read out info 47 – Rectification 58 Repair 66 Fault rectification 58 Replacement parts Functional principle 9 – Rod components 12 – Spacer 12 SITRANS LG250 — Operating Instructions PBD-51041053…
  • Page 91
    Scaling unit 37 Sensor characteristics 47 Sensor status 39 Simulation 41 Software addressing 26, 31 Special parameters 47 Status bytes PA output value 83 Telegram configuration 82 Type label 8 Type of medium 32 Units 31 PBD-51041053 SITRANS LG250 — Operating Instructions…
  • Page 92
    For more information www.siemens.com/level www.siemens.com/weighing Siemens Canada Limited Subject to change without prior notice PD PA PI LW PBD-51041053 Rev. 7.0 1954 Technology Drive P.O. Box 4225 © Siemens AG 2020 Peterborough, ON K9J 7B1, Canada email: techpubs.smpi@siemens.com Printed in Canada www.siemens.com/processautomation…

Contents

1

1.1

Function …………………………………………………………………………………………………………… 5

1.2

Target group ……………………………………………………………………………………………………… 5

1.3

Symbols used……………………………………………………………………………………………………. 5

2

2.1

Authorised personnel …………………………………………………………………………………………. 6

2.2

Appropriate use …………………………………………………………………………………………………. 6

2.3

Warning about incorrect use ………………………………………………………………………………… 6

2.4

General safety instructions ………………………………………………………………………………….. 6

2.5

CE conformity ……………………………………………………………………………………………………. 6

2.6

2.7

2.8

Environmental instructions ………………………………………………………………………………….. 7

3

3.1

Configuration …………………………………………………………………………………………………….. 8

3.2

Principle of operation………………………………………………………………………………………….. 9

3.3

3.4

4

4.1

General instructions …………………………………………………………………………………………. 13

4.2

Mounting instructions ……………………………………………………………………………………….. 13

5

5.1

Preparing the connection ………………………………………………………………………………….. 21

5.2

Connection ……………………………………………………………………………………………………… 22

5.3

5.4

5.5

5.6

5.7

Supplementary electronics ………………………………………………………………………………… 26

5.8

Switch-on phase………………………………………………………………………………………………. 26

6

6.1

Objective ………………………………………………………………………………………………………… 28

6.2

SIL qualification ……………………………………………………………………………………………….. 28

6.3

Application area ………………………………………………………………………………………………. 28

6.4

6.5

Setup process …………………………………………………………………………………………………. 30

7

7.1

7.2

Adjustment system …………………………………………………………………………………………… 33

7.3

Parameter adjustment ………………………………………………………………………………………. 35

7.4

8

8.1

Connect the PC ……………………………………………………………………………………………….. 57

8.2

8.3

PBD-51041388

SITRANS LG250 — Operating Instructions

3

Specifications:

990/990661-sitrans_lg250.pdf file (27 Nov 2022)

Accompanying Data:

Siemens SITRANS LG250 Measuring Instruments, Radar PDF Operating Instructions Manual (Updated: Sunday 27th of November 2022 07:26:54 AM)

Rating: 4.5 (rated by 11 users)

Compatible devices: SITRANS FC410, ULTRAMAT 6F, MAG 1100 F, FIDAMAT 6, 5TT3 196, SENTRON PAC2200, Class 87, 7KT1 543.

Recommended Documentation:

Siemens SITRANS LG250: Text of Operating Instructions Manual

(Ocr-Read Version Summary of Contents, UPD: 27 November 2022)

  • 57, 57 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 8 Setup with PACTware 8.1 Connect the PC 3 1 2 Fig. 24: Connection of the PC directly to the sensor via the interface adapter 1 USB cable to the PC 2 Interface adapter 3 Sensor 1 3 2 5 4 Fig. 25: Connecting the PC via HART to the signal cable 1 Sensor 2 HART resistance 250 Ω (optional depending on processing) 3 A…

  • 31, 31 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Function test not required If the parameter check was successful, the adjustment is locked auto- matically and the instrument is again in safe operating state. Setup is then nished. Function test required Should a function test be necessary, the following message is displayed on the display and adjust…

  • 20, 20 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 1 2 1 2 Fig. 11: Fasten the probe 1 Measuring probe 2 Retaining sleeve In case of dicult installation conditions, the probe can be also mounted laterally. For this purpose, adapt the rod with rod extensions or bow-shaped segments. Let the probe length determine automatically by the instrument to …

  • 68, 68 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Measurement error during lling Fault description Error pattern Cause Rectication 3. Measured value re- mains in the area of the bottom during lling Level time 0 – Echo from the probe end larger than the product echo, for example, with products with ε r < 2.5 oil-based, solvents, etc. – Check par…

  • 52, 52 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Setup Menu item Default value Modied value Lock adjustment Locked Measurement loop name Sensor Units Distance unit: mm Temperature unit: °C Probe length Length of the probe Ex factory Type of medium Liquid Application Level, vessel Medium, dielectric constant Water-based, > 10 Superimposed gas …

  • 25, 25 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Contact pin Colour connection ca- ble in the sensor Terminal, electronics module Pin 1 Brown 5 Pin 2 White 6 Pin 3 Blue 7 Pin 4 Black 8 5.6 Wiring plan, Ex-d-ia double chamber housing 31 2 567 8 1 2 ( ) (-) + 4…20mA Fig. 17: Electronics compartment, double chamber housing 1 Internal connection to the t…

  • 89, 89 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 12.3 Trademark All the brands as well as trade and company names used are property of their lawful proprietor/ originator.

  • 6, 6 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 2 For your safety 2.1 Authorised personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the required personal protective equipment must always be worn.…

  • 64, 64 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Code Text mes- sage Cause Rectication F260 Error in the instrument settings – Error in the calibration car- ried out in the factory – Error in the EEPROM – Exchanging the electronics – Send instrument for repair F261 Error in the instrument settings – Error during setup – Error …

  • 37, 37 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 In this menu item, you can select the application. You can choose between level measurement and interface measurement. You can also choose between measurement in a vessel or in a bypass or standpipe. Note: The selection of the application has a considerable inuence on all other menu item…

  • 90, 90 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 INDEX A Accessories – Display and adjustment module 11 – External display and adjustment unit 11, 12 Adjustment – Max. adjustment 38, 39 – Min. adjustment 38, 39 Adjustment system 34 Application 37, 38 Application area 9 B Backlight 48 C Cable entry 21 Check signal 66 Conne…

  • 60, 60 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 9 Set up with other systems 9.1 DD adjustment programs Device descriptions as Enhanced Device Description (EDD) are available for DD adjustment programs such as, for example, AMS™ and PDM. 9.2 Communicator 375, 475 Device descriptions for the instrument are available as DD or EDD for parameter adjustment with the …

Siemens SITRANS LG250: Recommended Instructions

HCVR5104C Series, F25209, FEB30S5ASB, 2005 S2000

  • PM5 Panel MeterOptional Output AddendumAMALGAMATED INSTRUMENT CO ABN: 80 619 963 692Unit 5, 28 Leighton Place Hornsby Telephone: +61 2 9476 2244 e-mail: [email protected] 2077 Australia Facsimile: +61 2 9476 2902 Internet: www.aicpl.com.au …

    PM5 31

  • User Manual LT80 LED Light Meter Introduction Congratulations on your purchase of the Triplett LT80 LED Light Meter that measures light intensity from white LED light sources. The LT80 can also measure light from fluorescent, metal halide, high‐ pressure sodium, and incandescent sources, for reference only (unspecified accuracy). The LT80 …

    LT80 8

  • Digital High Frequency Analyser HF59B © Gigahertz Solutions GmbH, 90579 Langenzenn, Germany Revision 4.5 (December 2006) Page 1 HF59B HF Analyzer for Frequencies from 800 MHz to 2.5 GHz (to 3.3 GHz with additional tolerance; ready for Frequencies from 27 MHz with optional Antenna) Instruction Manual Revision 4.5 This manual will be continuously updated, improved and e …

    HF59B 19

  • Instructions for configuration and installation Ecometer P Ultrasonic level indicator for fast measurements with external power supply (09/2018) Proteus Ecometer P (Power) FR …

    Ecometer P 4

  • Preventive maintenancePreventive maintenancePreventive maintenancePreventive maintenanceDeLaval milk meter MM27BC1111 Task ScheduleTask ScheduleTask ScheduleTask ScheduleNo 1 Replace MM27BC gasketNo 1 Replace MM27BC gasketNo 1 Replace MM27BC gasketNo 1 Replace MM27BC gasketReplacement parts or kits:Art No: 91470502Required tools:WrenchNoNoNoNo Service taskService task …

    MM27BC 22

  • ISSPRO EV 2 1/16” Diesel Tachometers (R5501, R5503, R5504, R5591, R6501, R6503, R6504, R6591) 1.) Select a mounting location for the sensor assembly and the magnets according to the following: a. The sensor assembly must be mounted such that the magnets pass within 1/8” to ¼” of the end of thesensor as shown in the installation diagram on the back pa …

    R5503 2

  • PCE Americas Inc. 711 Commerce Way Suite 8 Jupiter FL-33458 USA From outside US: +1 Tel: (561) 320-9162 Fax: (561) 320-9176 [email protected] PCE Instruments UK Ltd. Units 12/13 Southpoint Business Park Ensign way Hampshire / Southampton United Kingdom, SO31 4RF From outside UK: +44 Tel: (0) 2380 98703 0 Fax: (0) 2380 98703 9 [email protected] www.pce-instruments.c …

    PCE-VA 20 12

  • USER GUIDE31-00438-01C7355B In-Duct IAQ MonitorINTRODUCTIONAbout This MonitorThis air quality monitor is specially designed for monitoring multiple air quality parameters in the air duct. The sensor is installed in the outdoor or return air duct. Real time monitoring parameters are particles (PM2.5 and PM10), carbon dioxide (CO2), TVOC, air temperature and relative humidity.The intelligent con …

    C7355B 12

  • Robert Bosch GmbHPower Tools Division70745 Leinfelden-EchterdingenGermanywww.bosch-pt.com1 609 92A 0K5 (2014.04) I / 93 WEUWEU WEUPTD 1de Originalbetriebsanleitungen Original instructionsfr Notice originalees Manual originalpt Manual originalit Istruzioni originalinl Oorspronkelijke gebruiksaanwijzingda Original brugsanvisningsv Bruksanvisning i originalno Original driftsinstruksf …

    PTD 1 92

  • ba75408e04 12/2005NitraLyt®NOANitraLyt®NOA/ATOperating ManualNitraLyt® nitrate combination electrodeNitraLyt®NOA reference electrode NitraLyt®NOA/AT exchange electrodeNitraLyt NOA/AT®NitraLyt NOA® …

    NitraLyt NOA 10

Additional Information:

Operating Impressions, Questions and Answers:

[Page 1] Siemens SITRANS LG250

Operating Instructions • 03/2014 Guided Wave Radar SITRANS LG250 4 … 20 mA/HART — two-wire Rod and cable probe With SIL qualication

[Page 2] Siemens SITRANS LG250

2 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424

[Page 3] Siemens SITRANS LG250

3 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-15042446201-EN-150424 Contents 1 About this document 1.1 Function ……………………………………………………………………………………………………………

[Page 4] Siemens SITRANS LG250

4 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 9 Set up with other systems 9.1 DD adjustment programs ………………………………………………………………………………….. 60 9.2 Communicator 375, 47…

[Page 5] Siemens SITRANS LG250

5 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 1 About this document 1.1 Function This operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc- tions…

[Page 6] Siemens SITRANS LG250

6 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 2 For your safety 2.1 Authorised personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by t…

[Page 7] Siemens SITRANS LG250

7 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 YoucanndtheCECerticateofConformityinthedownloadsection of our homepage. Electromagnetic compatibility Instruments in four-wire or Ex-d-ia …

[Page 8] Siemens SITRANS LG250

8 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 3 Product description 3.1 Conguration Thetypelabelcontainsthemostimportantdataforidenticationand use of the instrument: 2 1 5 3 6 4 7 8 11…

[Page 9] Siemens SITRANS LG250

9 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 – SafetyManual(SIL) – Testcerticatemeasuringaccuracy(optional) – Operating instructions manual «Display and adjustment mod- ule» (optional) …

[Page 10] Siemens SITRANS LG250

10 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 TS d1 h1 h2 d2 1 L2 L1 L3 Fig. 3: Interface measurement 1 Sensorreferenceplane(sealsurfaceoftheprocesstting) d1 Distance to the interface (HART value…

[Page 11] Siemens SITRANS LG250

11 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 The instrument is always preset to the application «Level measure- ment». For the interface measurement, you can select the requested output signal with the setup. 3.3 …

[Page 12] Siemens SITRANS LG250

12 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Youcanndadditionalinformationintheoperatinginstructions manual «LG Remote Interface». The LG Remote Interface is suitable for measured value…

[Page 13] Siemens SITRANS LG250

13 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 4 Mounting 4.1 General instructions Withinstrumentswiththreadedprocesstting,suitabletoolsmustbe applied for tightening the hexagon. Warning: The …

[Page 14] Siemens SITRANS LG250

14 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Fig. 4: Vessel with conical bottom Plastic vessel/Glass vessel The guided microwave principle requires a metallic surface on the processtting.Therefore,inplastic…

[Page 15] Siemens SITRANS LG250

15 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Higher sockets or sockets with a bigger diameter can generally be used. They can, however, increase the upper blocking distance (dead band). Check if this is relevant for your m…

[Page 16] Siemens SITRANS LG250

16 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Fig.8:Mountingofthesensorwithinowingmedium The reference plane for the measuring range of the sensors is the sealingsurfaceofthethreador�…

[Page 17] Siemens SITRANS LG250

17 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 When the SITRANS LG250 is used in bypass tubes, contact with the tube wall must be avoided. We recommend for this purpose a cable probe with centering weight. Caution: When moun…

[Page 18] Siemens SITRANS LG250

18 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 • A false signal suppression with installed sensor is generally rec- ommended to achieve the best possible accuracy. Standpipes or surge pipes are normally metal tubes with a di…

[Page 19] Siemens SITRANS LG250

19 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Microwavescanpenetratemanyplastics.Thisiswhyplastictubesare problematic for measurement applications. If durability is no problem, we recommend t…

[Page 20] Siemens SITRANS LG250

20 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 1 2 1 2 Fig. 11: Fasten the probe 1 Measuring probe 2 Retaining sleeve Incaseofdicultinstallationconditions,theprobecanbealso mounted laterall…

[Page 21] Siemens SITRANS LG250

21 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 5 Connecting to power supply 5.1 Preparing the connection Always keep in mind the following safety instructions: • Connect only in the complete absence of line voltage • I…

[Page 22] Siemens SITRANS LG250

22 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 equalisationcurrentscanowoverthecablescreenifthescreenis grounded on both ends. To avoid this, the cable screen in such applications must be …

[Page 23] Siemens SITRANS LG250

23 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 6. Insert the wire ends into the terminals according to the wiring plan Information: Solidcoresaswellasexiblecoreswithwireendsleevesare ins…

[Page 24] Siemens SITRANS LG250

24 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 567 8 4…20mA 1 2 + ( ) (-) 2 1 1 Fig.14:Electronicscompartmentwithdoublechamberhousing 1 Internal connection to the terminal compartment 2 For display a…

[Page 25] Siemens SITRANS LG250

25 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Contact pin Colour connection ca- ble in the sensor Terminal, electronics module Pin 1 Brown 5 Pin 2 White 6 Pin 3 Blue 7 Pin 4 Black 8 5.6 Wiring plan, Ex-d-ia double chamber h…

[Page 26] Siemens SITRANS LG250

26 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 34 1 2 Fig. 19: Top view of the plug connector 1 Pin 1 2 Pin 2 3 Pin 3 4 Pin 4 Contact pin Colour connection ca- ble in the sensor Terminal, electronics module Pin 1 Brown 5 P…

[Page 27] Siemens SITRANS LG250

27 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 • Internal check of the electronics • Indication of the instrument type, hardware and software version, measurement loop name on the display or PC • Indication of the st…

[Page 28] Siemens SITRANS LG250

28 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 6 Functional safety (SIL) 6.1 Objective In case of dangerous failures, processing facilities and machines can cause risks for persons, environment and property. The risk of such …

[Page 29] Siemens SITRANS LG250

29 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 The following inputs/outputs are permitted: • 4 … 20 mA current output 6.4 Safety concept of the parameterization The following tools are permitted for parameterization of t…

[Page 30] Siemens SITRANS LG250

30 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 All parameters changed by the operator are automatically stored temporarilysothattheycanbeveriedinthenextstep. Aftersetup,themodied…

[Page 31] Siemens SITRANS LG250

31 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Function test not required If the parameter check was successful, the adjustment is locked auto- matically and the instrument is again in safe operating state. Setupisthen�…

[Page 32] Siemens SITRANS LG250

32 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 In both cases the output current must correspond to the respective level. Measurethecurrentoutputandcomparethevaluewiththecalcu- lated current value….

[Page 33] Siemens SITRANS LG250

33 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 7 Set up with the display and adjustment module 7.1 Insert display and adjustment module The display and adjustment module can be inserted into the sensor and removed again at…

[Page 34] Siemens SITRANS LG250

34 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 – Movetothemenuoverview – Conrmselectedmenu – Edit parameter – Save value • [->] key: – Presentation, change measured value – Select li…

[Page 35] Siemens SITRANS LG250

35 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 7.3 Parameter adjustment Themainmenuisdividedintovesectionswiththefollowingfunc- tions: Setup: Settings, e.g. measurement loop name, medium, v…

[Page 36] Siemens SITRANS LG250

36 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 To prevent unintentional or unauthorized adjustment, the instrument is protected (locked) against all parameter changes while in normal operating condition. For each parameter ch…

[Page 37] Siemens SITRANS LG250

37 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 In this menu item, you can select the application. You can choose between level measurement and interface measurement. You can also choose between measurement in a vessel or in …

[Page 38] Siemens SITRANS LG250

38 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 This menu item is only available if you have selected interface meas- urement under the menu item «Application». In this menu item you can choose the type of medium of t…

[Page 39] Siemens SITRANS LG250

39 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Enter the suitable distance value in m for the empty vessel (e.g. distancefromtheangetotheprobeend)correspondingtotheper- centage value. The d…

[Page 40] Siemens SITRANS LG250

40 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Enter the respective distance value in m for the empty vessel cor- responding to the percentage value. Todampprocess-dependentmeasuredvalueuctuations,setan�…

[Page 41] Siemens SITRANS LG250

41 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 + h D — h Fig. 23: Vessel height and socket correction value D Vessel height +h Positive socket correction value -h Negative socket correction value Since scaling is very exten…

[Page 42] Siemens SITRANS LG250

42 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Since scaling is very extensive, scaling of the level value was divided into two menu items. In menu item «Level 2″youdenethescalingformatonthe�…

[Page 43] Siemens SITRANS LG250

43 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 In the menu item «Currentoutputmode» you determine the output characteristics and reaction of the current output in case of failure. The default setting is output…

[Page 44] Siemens SITRANS LG250

44 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 In the menu «HART variables 1″youcanhavetherstHARTvaluePV (primary value) and the second HART value SV (secondary value) of the sensor disp…

[Page 45] Siemens SITRANS LG250

45 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Note: Check the distance to the product surface, because if an incorrect (too large) value is entered, the existing level will be saved as a false signal. The level would then n…

[Page 46] Siemens SITRANS LG250

46 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 is required. If a function test is necessary, the following message is displayed. In this case, you have to carry out a function test. Function test During a function test, you ha…

[Page 47] Siemens SITRANS LG250

47 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Otherwise the instrument remains in the released and hence unsafe condition. If you have to interrupt the function test, you can leave the display and adjustment module of SITRA…

[Page 48] Siemens SITRANS LG250

48 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 The default setting for the displayed value 2 is the electronics tem- perature. Theintegratedbackgroundlightingcanbeswitchoviatheadjust- ment menu….

[Page 49] Siemens SITRANS LG250

49 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 In another window you can carry out a reset of the two peak values separately. The respective min. and max. measured values are saved in the sensor. The values are displayed in …

[Page 50] Siemens SITRANS LG250

50 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Select the requested simulation variable and set the requested value. Caution: During simulation, the simulated value is outputted as 4 … 20 mA cur- rent value and digital HART s…

[Page 51] Siemens SITRANS LG250

51 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 During the function test, the safety function must be treated as unsafe. Keepinmindthatthefunctiontestinuencesdownstreamconnected devices. You…

[Page 52] Siemens SITRANS LG250

52 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Setup Menu item Default value Modiedvalue Lock adjustment Locked Measurementloopname Sensor Units Distance unit: mm Temperature unit: °C Probe length Length of the pro…

[Page 53] Siemens SITRANS LG250

53 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Menu item Default value Modiedvalue Scaling interface — 100 % correspond to 100 Scaling interface — 0 % correspond to 0 Current output, output variable First HART variable (…

[Page 54] Siemens SITRANS LG250

54 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Menu item Default value Modiedvalue Devicememory-Measuredvaluememory-Start with measured value Not active Devicememory-Measuredvaluemem…

[Page 55] Siemens SITRANS LG250

55 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 In this menu item you gain access to the protected area where you can enter special parameters. In exceptional cases, individual parameterscanbemodiedinorder�…

[Page 56] Siemens SITRANS LG250

56 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 7.4 Saving the parameter adjustment data We recommended noting the adjusted data, e.g. in this operating instructions manual, and archiving them afterwards. They are thus availa…

[Page 57] Siemens SITRANS LG250

57 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 8 Setup with PACTware 8.1 Connect the PC 3 1 2 Fig.24:ConnectionofthePCdirectlytothesensorviatheinterfaceadapter 1 USBcableto�…

[Page 58] Siemens SITRANS LG250

58 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 8.2 Parameter adjustment with PACTware For parameter adjustment of the sensor via a Windows PC, the congurationsoftwarePACTwareandasuitableinstrumentdrive…

[Page 59] Siemens SITRANS LG250

59 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 8.3 Saving the parameter adjustment data We recommend documenting or saving the parameter adjustment data via PACTware. That way the data are available for multiple use or serv…

[Page 60] Siemens SITRANS LG250

60 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 9 Set up with other systems 9.1 DD adjustment programs Device descriptions as Enhanced Device Description (EDD) are availableforDDadjustmentprogramssuchas,f…

[Page 61] Siemens SITRANS LG250

61 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 10 Diagnostics and servicing 10.1 Maintenance If the device is used correctly, no maintenance is required in normal operation. When used in safety-instrumented systems (SIS), th…

[Page 62] Siemens SITRANS LG250

62 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Eventtypesare,forexample,parametermodications,statusand errormessagesaswellasswitchonandswitchotimes.Thedata…

[Page 63] Siemens SITRANS LG250

63 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 «Device status» in the indicating and adjustment module as well as in theDTMandEDD. The following table shows the error codes in the status message «Fail…

[Page 64] Siemens SITRANS LG250

64 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Code Text mes- sage Cause Rectication F260 Error in the instrument settings – Error in the calibration car- ried out in the factory – ErrorintheEEPROM – Exch…

[Page 65] Siemens SITRANS LG250

65 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Code Text mes- sage Cause Rectication S600 Impermissi- ble electronics temperature – Temperature of the pro- cessing electronics in the non-speciedsection – Check…

[Page 66] Siemens SITRANS LG250

66 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Code Text mes- sage Cause Rectication M504 Error on an device inter- face – Hardware defect – Exchanging the electronics – Send instrument for repair M505 no measured …

[Page 67] Siemens SITRANS LG250

67 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Error Cause Rectication Current sig- nal greater than 22 mA or less than 3.6 mA Electronics mod- ule in the sensor defective Exchange the instrument or send it in for repai…

[Page 68] Siemens SITRANS LG250

68 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Measurementerrorduringlling Fault description Error pattern Cause Rectication 3.Measuredvaluere- mains in the area of the bottomduringlling Level …

[Page 69] Siemens SITRANS LG250

69 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Order the replacement electronics module through the agency serving you. The electronics modules are adapted to the respective sensor. It is absolutely necessary that the factor…

[Page 70] Siemens SITRANS LG250

70 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Fig.36:Exchangecableorrod Information: Pleasemaintainthespeciedtorquesothatthemax.tensilestrength of the connection remains. 7. …

[Page 71] Siemens SITRANS LG250

71 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 8. Enter new probe length and then carry out a fresh adjustment (see «Setupprocedure,Carryingoutmin.adjustment-Carrying out max. adjustment»). …

[Page 72] Siemens SITRANS LG250

72 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 11 Dismount 11.1 Dismounting steps Warning: Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel, high temperatures, corrosive or toxi…

[Page 73] Siemens SITRANS LG250

73 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 12 Supplement 12.1 Technical data General data 316L corresponds to 1.4404 or 1.4435 Materials,wettedparts Ʋ Processtting(versionupto6bar) 316L and PP…

[Page 74] Siemens SITRANS LG250

74 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Processttings Ʋ Pipe thread, cylindrical (ISO 228 T1) G¾, G1, G1½ according to DIN 3852-A Ʋ American pipe thread, conical (ASMEB1.20.1) ¾ NPT, 1 NPT, 1½ NPT Ʋ F…

[Page 75] Siemens SITRANS LG250

75 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Ʋ Rod: ø 12 mm (0.472 in) 10 Nm (7.38 lbf ft) Torque for NPT cable glands and Conduit tubes Ʋ Plastic housing max. 10 Nm (7.376 lbf ft) Ʋ Aluminium/Stainless steel housing …

[Page 76] Siemens SITRANS LG250

76 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Starting current ≤10mAfor5msafterswitchingon,≤3.6mA Load see load diagram under Power supply Damping (63 % of the input variable), adjustable …

[Page 77] Siemens SITRANS LG250

77 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Ʋ Vessel metallic, ø 1 m (3.281 ft), centric installation, process ttingushwiththevesselceiling Ʋ Medium Water/Oil (dielectric constant ~2.0) 4) Ʋ Ins…

[Page 78] Siemens SITRANS LG250

78 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 L 2mm (0.079 «) 0 -2mm (-0.079 «) 15mm (0.591 «) -10mm (-0.591 «) 0,3 m (11.811 «) 0,15 m (5.906 «) 0,05 m (1.97 «) 0,07 m (2.756 &qu…

[Page 79] Siemens SITRANS LG250

79 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 L 0 -15mm (-0.591 «) 2mm (0.079 «) -2mm (-0.079 «) 15mm (0.591 «) 0,3 m (11.811 «) 0,15 m (5.906 «) 0,08 m (3.15 «) 0,05 m (1.969 &q…

[Page 80] Siemens SITRANS LG250

80 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Temperature drift — Digital output ±3 mm/10 K relating to the max. measuring range or max. 10 mm (0.394 in) Additional deviation through electromag- netic interference acc. to EN…

[Page 81] Siemens SITRANS LG250

81 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Process conditions Fortheprocessconditions,pleasealsonotethespecicationsonthetypelabel.Thelowestvalue always applies. Themeas…

[Page 82] Siemens SITRANS LG250

82 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 1 2 0°C (32°F) -40°C (-104°F) 55°C (131°F) 80°C (176°F) 200°C (392°F) 150°C (302°F) 3 4 -20°C (-68°F) Fig. 45: Ambient temperature — process temperature, version with…

[Page 83] Siemens SITRANS LG250

83 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Materials Ʋ Housing ABS Ʋ Inspection window Polyester foil Integrated clock Date format Day.Month.Year Time format 12 h/24 h Time zone Ex factory CET Electronics temperature m…

[Page 84] Siemens SITRANS LG250

84 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Housing material Version IP-protection class NEMAprotection Aluminium Single chamber IP 66/IP 68 (0.2 bar) NEMA6P Double chamber IP 66/IP 67 IP 66/IP 68 (0.2 bar) NEMA4X N…

[Page 85] Siemens SITRANS LG250

85 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Aluminium housing 21 ø 84 mm (3.31″) ~ 116 mm (4.57″) 120 mm (4.72″) M20x1,5 M20x1,5/ ½ NPT ~ 91 mm (3.58″) M16x1,5 ø 84 mm (3.31″) 124 mm (4.88″)…

[Page 86] Siemens SITRANS LG250

86 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 SITRANSLG250,cableversionwithgravityweight 1 2 3 L SW 36 (1. 42″) (G¾, ¾ NPT) SW 41 (1. 61″) (G1, 1 NPT) SW 46 (1. 81″) (G1½, 1½ NPT) G¾, �…

[Page 87] Siemens SITRANS LG250

87 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 1 Cableversionø2mm(0.079in)withgravityweight 2 Cableversionø4mm(0.157in)withgravityweight 3 Cableversionwith…

[Page 88] Siemens SITRANS LG250

88 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 SITRANSLG250,rodversion L SW 36 (1. 42″) (G¾, ¾ NPT) SW 41 (1. 61″) (G1, 1 NPT) SW 46 (1. 81″) (G1½, 1½ NPT) G¾, ¾ NPT, G1, 1 NPT, G1½, 1½ NPT 22…

[Page 89] Siemens SITRANS LG250

89 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 12.3 Trademark All the brands as well as trade and company names used are property of their lawful proprietor/ originator.

[Page 90] Siemens SITRANS LG250

90 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 INDEX A Accessories – Display and adjustment module 11 – External display and adjustment unit 11, 12 Adjustment – Max.adjustment38, 39 – Min.adjustment�…

[Page 91] Siemens SITRANS LG250

91 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 Repair 71 Replacement parts – Electronics module 12 – Rod extension 12 – Spacer 12 Reset 51 S Scaling measured value 41, 42 Sensor characteristics 55 Sensor status…

[Page 92] Siemens SITRANS LG250

Siemens AG Industry sector 1954 Technology Drive P.O. Box 4225 Peterborough. ON Canada K9J7B1 email: [email protected] www.siemens.com/processautomation Subject to change without prior notice PBD-51041388 Rev. 1.0 © Siemens AG 2015 For more …

Document’s Content and Additional Information Share Manual

Siemens SITRANS LG250 Operating instructions manual

  • Siemens
  • Radar
  • Operating instructions manual for Siemens SITRANS LG250
  • siemens-sitrans-lg250-operating-instructions-manual-84_manual.pdf
  • 84 |

Pages Preview:



Document Transcription:

  • 62 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 • Evaluation of fault messages, for example via the display and adjustment module • Checking the output signal • Treatment of measurement errors Further comprehensive diagnostics o …

  • 58 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 • Modicationofaparameter • Switch-onandswitch-otimes • Status messages (according to NE 107) • Error messages (according to NE 107) The data are read out …

  • 22 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 34 1 2 Fig. 13: View to the plug connector M12 x 1 1 Pin 1 2 Pin 2 3 Pin 3 4 Pin 4 Contact pin Colour connection ca- ble in the sensor Terminal, electronics module Pin 1 Brown 5 Pin 2 W …

See Details
Download

Siemens SITRANS LG250 Operating instructions manual

  • Siemens
  • Radar
  • Operating instructions manual for Siemens SITRANS LG250
  • siemens-sitrans-lg250-operating-instructions-manual-88_manual.pdf
  • 88 |

Pages Preview:



Document Transcription:

  • 86 PBD-51041056SITRANS LG250 — Operating Instructions 44573-EN-140321 INDEX A Accessories – Display and adjustment module 11 – External display and adjustment unit 11, 12 Adjustment – Max. adjustment 30, 31 – Min. adjustment 31, 32 Adjustment s …

  • 58 PBD-51041056SITRANS LG250 — Operating Instructions 44573-EN-140321 1 2 Level time 0 Fig. 22: The broken line 1 shows the real level, the continuous line 2 shows the level displayed by the sensor Note: • Wherever the sensor displays a constant value, the …

  • 25PBD-51041056 SITRANS LG250 — Operating Instructions 44573-EN-140321 – Conrmselectedmenu – Edit parameter – Save value • [->] key: – Presentation, change measured value – Select list entry – Select editing position • [+] …

See Details
Download

Siemens SITRANS LG250 Operating instructions manual

  • Siemens
  • Measuring Instruments
  • Operating instructions manual for Siemens SITRANS LG250
  • siemens-sitrans-lg250-operating-instructions-manual-92_manual.pdf
  • 92 |

Pages Preview:



Document Transcription:

  • 84 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 Housing material Version IP-protection class NEMAprotection Aluminium Single chamber IP 66/IP 68 (0.2 bar) NEMA6P Double chamber IP 66/IP 67 IP 66/IP 68 (0.2 bar) NEMA4X NEMA6P S …

  • 46 PBD-51041388SITRANS LG250 — Operating Instructions 46201-EN-150424 is required. If a function test is necessary, the following message is displayed. In this case, you have to carry out a function test. Function test During a function test, you have to test …

  • 37 PBD-51041388 SITRANS LG250 — Operating Instructions 46201-EN-150424 In this menu item, you can select the application. You can choose between level measurement and interface measurement. You can also choose between measurement in a vessel or in a bypass o …

See Details
Download

(Ocr-Read Summary of Contents of some pages of the Siemens SITRANS LG250 Document (Main Content), UPD: 11 April 2023)

  • 1, Operating Instructions • 04/2016 Guided Wave Radar SITRANS LG250 4 … 20 mA/HART — two-wire Coax probe With SIL qualication

  • 61, 61 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 The following table shows the error codes and text messages in the status message «Out of specication» and provides information on causes as well as corrective measures. Code Text message Cause Rectication DevSpec State in CMD 48 S601 Overlling – Level echo in the close range not available – Reduce level – 100 % adjustment: Increase value – Check mounting socket – Remove possible…

  • 79, 79 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 SITRANS LG250, coax version L SW 36 (1. 42″) (G¾, ¾ NPT) SW 41 (1. 61″) (G1, 1 NPT) SW 46 (1. 81″) (G1½, 1½ NPT) G¾, ¾ NPT, G1, 1 NPT, G1½, 1½ NPT 46 mm (1.81″) ø 21,3 mm (0.84″) L 22mm (0.86″) ø 42,2 mm (1.66″) SW 55 (2.17″) 51 mm (2.01″) G1½, 1½ NPT 1 2 Fig. 43: SITRANS LG250, threaded version L Sensor length, see chapter «Technical data…

  • 76, 76 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Permissible residual ripple — Ex-d-ia instrument Ʋ for 18 V< U B < 36 V ≤ 1 V e (16 … 400 Hz) Load resistor Ʋ Calculation (U B — U min )/0.022 A Ʋ Example — Non-Ex instrument with U B = 24 V DC (24 V — 9.6 V)/0.022 A = 655 Ω Electrical protective measures Protection rating Housing material Version IP-protection class NEMA protection Plastic Single chamber IP 66/IP 67 Type 4X Dou…

  • 77, 77 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 12.2 Dimensions Plastic housing ~ 69 mm (2.72″) ø 77 mm (3.03″) 114 mm (4.49″) M20x1,5/ ½ NPT ~ 86 mm (3.39″) M16x1,5 114 mm (4.49″) M20x1,5/ ½ NPT ø 77 mm (3.03″) 1 2 Fig. 40: Housing versions with protection rating IP 66/IP 67 — with integrated display and adjustment module the housing is 9 mm/0.35 in higher 1 Single chamber ver…

  • 35, 35 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 This menu item is only available if you have selected interface meas- urement under the menu item «Application». In this menu item you can choose the type of medium of the upper medium. You can enter the dielectric constant of the upper medium directly or have the value determined by the instrument. To do this you have to enter the measured or known distance to the i…

  • 67, Siemens SITRANS LG250 67 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 12 Supplement 12.1 Technical data General data 316L corresponds to 1.4404 or 1.4435 Materials, wetted parts Ʋ Process tting 316L and PEEK, Alloy C22 (2.4602) and PEEK Ʋ Process seal on the instrument side (rod leadthrough) FKM (SHS FPM 70C3 GLT), FFKM (Kalrez 6375), EPDM (A+P 75.5/KW75F), silicone FEP coated (A+P FEP-O-SEAL) Ʋ Process tting — for volatile substances such …

  • 38, 38 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 + h D — h Fig. 21: Vessel height and socket correction value D Vessel height +h Positive socket correction value -h Negative socket correction value In the menu item «Current output mode» you determine the output characteristics and reaction of the current output in case of failure. The default setting is output characteristics 4 … 20 mA, failure mode < 3.6 mA.…

  • 7, 7 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 You can nd the CE Certicate of Conformity in the download section of our homepage. Electromagnetic compatibility Instruments in four-wire or Ex-d-ia version are designed for use in an industrial environment. Nevertheless, electromagnetic interference from electrical conductors and radiated emissions must be taken into account, as is usual with class A instruments according to EN 61326- …

  • 14, Siemens SITRANS LG250 14 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 You can nd detailed information on the process conditions in chapter «Technical data» as well as on the type label. 4.2 Mounting instructions In vessels with conical bottom it can be advantageous to mount the sensor in the center of the vessel, as measurement is then possible nearly down to the lowest point of the bottom. Keep in mind that measurement all…

  • 13, Siemens SITRANS LG250 13 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 4 Mounting 4.1 General instructions On instruments with threaded process tting, the hexagon must be tightened with a suitable wrench. For the proper wrench size see chapter «Dimensions». Warning: The housing must not be used to screw the instrument in! Applying tightening force can damage internal parts of the housing. Protect your instrument against moisture ing…

  • 3, Siemens SITRANS LG250 3 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-16051746200-EN-160517 Contents 1 About this document 1.1 Function …………………………………………………………………………………………………………… 5 1.2 Target group ……………………………………………………………………………………………………… 5 1.3 Symbols used………………………………………………………….…

  • 23, 23 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 4…20mA 1 2 + ( ) (-) 2 1 Fig. 15: Terminal compartment, double chamber housing Ex d ia 1 Voltage supply, signal output 2 Ground terminal for connection of the cable screen 3 1 2 Fig. 16: View to the electronics compartment with DISADAPT for connection of the external display and adjustment unit 1 DISADAPT 2 Internal plug connection 3 Plug connector M12 x 1 34 1 2 Fig. 17: View …

  • 9, 9 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 – Safety Manual (SIL) – Test certicate measuring accuracy (optional) – Operating instructions manual «Display and adjustment mod- ule» (optional) – Supplementary instructions manual «Plug connector for con- tinuously measuring sensors» (optional) – Ex-specic «Safety instructions» (with Ex versions) – If necessary, further certicates 3.2 Principle of operation…

  • 27, 27 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 All parameters changed by the operator are automatically stored temporarily so that they can be veried in the next step. After setup, the modied parameters must be veried (conrm the correctness of the parameters). To do this, you rst have to enter the PIN. Here the adjustment is locked automatically. Then you carry out a comparison of two character strin…

  • 22, 22 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 34 1 2 Fig. 13: View to the plug connector M12 x 1 1 Pin 1 2 Pin 2 3 Pin 3 4 Pin 4 Contact pin Colour connection ca- ble in the sensor Terminal, electronics module Pin 1 Brown 5 Pin 2 White 6 Pin 3 Blue 7 Pin 4 Black 8 5.6 Wiring plan, Ex-d-ia double chamber housing 31 2 567 8 1 2 ( ) (-) + 4…20mA Fig. 14: Electronics compartment, double chamber housing 1 Interna…

  • 78, 78 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Stainless steel housing ~ 69 mm (2.72″) ø 77 mm (3.03″) 119 mm (4.69″) M20x1,5/ ½ NPT ~ 59 mm (2.32″) ø 80 mm (3.15″) 112 mm (4.41″) M20x1,5/ ½ NPT ~ 90 mm (3.54″) ø 84 mm (3.31″) 123 mm (4.84″) M20x1,5/ ½ NPT M16x1,5 321 Fig. 42: Housing versions with protection rating IP 66/IP 68 (0.2 bar) — with integrated display and adjustment module the ho…

  • 71, 71 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 Typical deviation — Total level interface measurement ± 5 mm (0.197 in) Typical deviation — Level measurement 6)7) See following diagrams L 0 -2 mm (-0.079″) 2 mm (0.079″) -10 mm (0.394″) 5 mm (0.197″) 0,15 m (5.906″) 0,03 m (1.181 «) 0,05 m (1.969 «) 1 Fig. 36: Deviation SITRANS LG250 in coax version in water 1 Dead band — n…

  • 69, 69 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 Output variable Output signal 4 … 20 mA/HART Range of the output signal 3.8 … 20.5 mA/HART (default setting) Fullled HART specication 7 Signal resolution 0.3 µA Failure signal current output (adjustable) ≥ 21 mA, ≤ 3.6 mA Max. output current 21.5 mA Starting current ≤ 10 mA for 5 ms after switching on, ≤ 3.6 mA Load see load diagram under Power supply Damping (63 % of the …

Contents

1

About this document ………………………………………………………………………………………………… 5

1.1

Function …………………………………………………………………………………………………………… 5

1.2

Target group ……………………………………………………………………………………………………… 5

1.3

Symbols used……………………………………………………………………………………………………. 5

2

For your safety …………………………………………………………………………………………………………. 6

2.1

Authorised personnel …………………………………………………………………………………………. 6

2.2

Appropriate use …………………………………………………………………………………………………. 6

2.3

Warning about incorrect use ………………………………………………………………………………… 6

2.4

General safety instructions ………………………………………………………………………………….. 6

2.5

EU conformity ……………………………………………………………………………………………………. 7

2.6

NAMUR recommendations …………………………………………………………………………………. 7

2.7

3

Product description ………………………………………………………………………………………………….. 8

3.1

Configuration …………………………………………………………………………………………………….. 8

3.2

Principle of operation………………………………………………………………………………………….. 9

3.3

3.4

Accessories…………………………………………………………………………………………………….. 12

4

Mounting ………………………………………………………………………………………………………………… 13

4.1

General instructions …………………………………………………………………………………………. 13

4.2

Mounting instructions ……………………………………………………………………………………….. 14

5

Connecting to power supply ……………………………………………………………………………………. 17

5.1

Preparing the connection ………………………………………………………………………………….. 17

5.2

Connecting ……………………………………………………………………………………………………… 18

5.3

5.4

5.5

5.6

Supplementary electronics ………………………………………………………………………………… 22

5.7

Switch-on phase………………………………………………………………………………………………. 22

6

6.1

6.2

Adjustment system …………………………………………………………………………………………… 24

6.3

6.4

6.5

7

Setup with PACTware ………………………………………………………………………………………………. 44

7.1

Connect the PC ……………………………………………………………………………………………….. 44

7.2

7.3

Set up with the quick setup ………………………………………………………………………………… 46

7.4

8

Set up with other systems ………………………………………………………………………………………. 48

8.1

DD adjustment programs ………………………………………………………………………………….. 48

8.2

Field Communicator 375, 475 ……………………………………………………………………………. 48

9

Diagnostics and servicing ………………………………………………………………………………………. 49

9.1

Maintenance …………………………………………………………………………………………………… 49

9.2

Diagnosis memory …………………………………………………………………………………………… 49

PBD-51041048

SITRANS LG250 — Operating Instructions

3

[Page 1] Siemens SITRANS LG250

Operating Instructions • 04/2016 Guided Wave Radar SITRANS LG250 4 … 20 mA/HART — two-wire Coax probe With SIL qualication

[Page 2] Siemens SITRANS LG250

2 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517

[Page 3] Siemens SITRANS LG250

3 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-16051746200-EN-160517 Contents 1 About this document 1.1 Function ……………………………………………………………………………………………………………

[Page 4] Siemens SITRANS LG250

4 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 9.1 DD adjustment programs ………………………………………………………………………………….. 56 9.2 Field Communicator 375, 475 ……………………

[Page 5] Siemens SITRANS LG250

5 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 1 About this document 1.1 Function This operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc- tions…

[Page 6] Siemens SITRANS LG250

6 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 2 For your safety 2.1 Authorised personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by t…

[Page 7] Siemens SITRANS LG250

7 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 YoucanndtheCECerticateofConformityinthedownloadsection of our homepage. Electromagnetic compatibility Instruments in four-wire or Ex-d-ia …

[Page 8] Siemens SITRANS LG250

8 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 3 Product description 3.1 Conguration Thetypelabelcontainsthemostimportantdataforidenticationand use of the instrument: 2 1 5 3 6 4 7 8 11…

[Page 9] Siemens SITRANS LG250

9 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 – Safety Manual (SIL) – Testcerticatemeasuringaccuracy(optional) – Operating instructions manual «Display and adjustment mod- ule» (optional) –…

[Page 10] Siemens SITRANS LG250

10 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 TS d1 h1 h2 d2 1 L2 L1 L3 Fig. 3: Interface measurement 1 Sensorreferenceplane(sealsurfaceoftheprocesstting) d1 Distance to the interface (HART value…

[Page 11] Siemens SITRANS LG250

11 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 The instrument is always preset to the application «Level measure- ment». For the interface measurement, you can select the requested output signal with the setup. 3.3 …

[Page 12] Siemens SITRANS LG250

12 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Youcanndadditionalinformationintheoperatinginstructions manual «LG Remote Interface». The LG Remote Interface is suitable for measured value…

[Page 13] Siemens SITRANS LG250

13 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 4 Mounting 4.1 General instructions Oninstrumentswiththreadedprocesstting,thehexagonmustbe tightened with a suitable wrench. For the proper wrenc…

[Page 14] Siemens SITRANS LG250

14 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Youcannddetailedinformationontheprocessconditionsinchapter «Technical data» as well as on the type label. 4.2 Mounting instructions I…

[Page 15] Siemens SITRANS LG250

15 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 Fig.5:Mountingofthesensorwithinowingmedium The reference plane for the measuring range of the sensors is the sealingsurfaceofthethreador…

[Page 16] Siemens SITRANS LG250

16 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 1 2 1 2 Fig. 6: Fasten the probe 1 Coaxprobe 2 Retaining sleeve

[Page 17] Siemens SITRANS LG250

17 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 5 Connecting to power supply 5.1 Preparing the connection Always keep in mind the following safety instructions: Warning: Connect only in the complete absence of line voltage. �…

[Page 18] Siemens SITRANS LG250

18 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Max. torque for all housings, see chapter «Technical data». If screened cable is required, we recommend connecting the cable screen on both ends to ground potential. In …

[Page 19] Siemens SITRANS LG250

19 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 Fig.7:Connectionsteps5and6-Singlechamberhousing Fig.8:Connectionsteps5and6-Doublechamberhousing 6. Insert the wire end…

[Page 20] Siemens SITRANS LG250

20 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 8. Connect the screen to the internal ground terminal, connect the external ground terminal to potential equalisation 9. Tighten the compression nut of the cable entry gland. Th…

[Page 21] Siemens SITRANS LG250

21 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 5 1 2 + ( ) (-) 678 4…20mADisplay 2 3 4 1 Fig. 11: Terminal compartment, double chamber housing 1 Voltage supply, signal output 2 For display and adjustment module or inter…

[Page 22] Siemens SITRANS LG250

22 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 34 1 2 Fig. 13: View to the plug connector M12 x 1 1 Pin 1 2 Pin 2 3 Pin 3 4 Pin 4 Contact pin Colour connection ca- ble in the sensor Terminal, electronics module Pin 1 Brown…

[Page 23] Siemens SITRANS LG250

23 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 4…20mA 1 2 + ( ) (-) 2 1 Fig.15:Terminalcompartment,doublechamberhousingExdia 1 Voltage supply, signal output 2 Ground terminal for connection of t…

[Page 24] Siemens SITRANS LG250

24 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Contact pin Colour connection ca- ble in the sensor Terminal, electronics module Pin 2 White 6 Pin 3 Blue 7 Pin 4 Black 8 5.7 Supplementary electronics To make a second measured …

[Page 25] Siemens SITRANS LG250

25 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 6 Functional safety (SIL) 6.1 Objective In case of dangerous failures, processing facilities and machines can cause risks for persons, environment and property. The risk of such…

[Page 26] Siemens SITRANS LG250

26 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 The following inputs/outputs are permitted: • 4 … 20 mA current output 6.4 Safety concept of the parameterization The following tools are permitted for parameterization of th…

[Page 27] Siemens SITRANS LG250

27 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 All parameters changed by the operator are automatically stored temporarilysothattheycanbeveriedinthenextstep. Aftersetup,themodied�…

[Page 28] Siemens SITRANS LG250

28 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Function test not required If the parameter check was successful, the adjustment is locked auto- matically and the instrument is again in safe operating state. Setupisthen…

[Page 29] Siemens SITRANS LG250

29 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 In both cases the output current must correspond to the respective level. Measure the current output and compare the value with the calcu- lated current value. You have to determ…

[Page 30] Siemens SITRANS LG250

30 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 7 Set up with the display and adjustment module 7.1 Insert display and adjustment module The display and adjustment module can be inserted into the sensor andremovedagain…

[Page 31] Siemens SITRANS LG250

31 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 7.2 Adjustment system 1 2 Fig. 20: Display and adjustment elements 1 LCdisplay 2 Adjustmentkeys • [OK] key: – Move to the menu overview – Conrmselected…

[Page 32] Siemens SITRANS LG250

32 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 After switching on, the SITRANS LG250 carries out a short self-test where the device software is checked. The output signal transmits a fault signal during the switch-on phase. Th…

[Page 33] Siemens SITRANS LG250

33 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 Note: For optimum adjustment of the measuring point, the individual sub- menu items in the main menu item «Setup» should be selected one after the other and provided wi…

[Page 34] Siemens SITRANS LG250

34 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 In this menu item, you can select the application. You can choose between level measurement and interface measurement. You can also choose between measurement in a vessel or in a…

[Page 35] Siemens SITRANS LG250

35 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 This menu item is only available if you have selected interface meas- urement under the menu item «Application». In this menu item you can choose the type of medium of …

[Page 36] Siemens SITRANS LG250

36 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Enter the suitable distance value in m for the empty vessel (e.g. distancefromtheangetotheprobeend)correspondingtotheper- centage value. The di…

[Page 37] Siemens SITRANS LG250

37 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 Enter the respective distance value in m for the empty vessel cor- responding to the percentage value. Todampprocess-dependentmeasuredvalueuctuations,setan…

[Page 38] Siemens SITRANS LG250

38 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 + h D — h Fig.21:Vesselheightandsocketcorrectionvalue D Vessel height +h Positivesocketcorrectionvalue -h Negativesocketcorrectionvalu…

[Page 39] Siemens SITRANS LG250

39 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 The default setting is min. current 3.8 mA and max. current 20.5 mA. Thefollowingcircumstancescauseinterferingreectionsandcan inuencethemeasure…

[Page 40] Siemens SITRANS LG250

40 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 To avoid possible errors during parameterization in a non-safe user environment,avericationprocedureisusedthatmakesitpossible to detect parameteri…

[Page 41] Siemens SITRANS LG250

41 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 your measurement loop. Determine the permissible tolerance for the deviation. If you have to interrupt the function, you can leave the SITRANS LG250 in the respective situation….

[Page 42] Siemens SITRANS LG250

42 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 In the main menu point «Display», the individual submenu points should be selected subsequently and provided with the correct parameters to ensure the optimum adjustmen…

[Page 43] Siemens SITRANS LG250

43 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 In this menu item, the device status is displayed. The respective min. and max. measured value is saved in the sen- sor. The two values are displayed in the menu item » Peak�…

[Page 44] Siemens SITRANS LG250

44 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 In another window you can carry out a reset of the two peak values separately. The menu item «Echocurve» shows the signal strength of the echoes over the measuring r…

[Page 45] Siemens SITRANS LG250

45 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 Information: The simulation is terminated automatically 60 minutes after the activa- tion of the simulation. With the menu item «Setup» the echo curve it is possible to …

[Page 46] Siemens SITRANS LG250

46 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 With a reset, certain parameter adjustments carried out by the user are reset. The following reset functions are available: Delivery status: Restoring the parameter settings at th…

[Page 47] Siemens SITRANS LG250

47 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 Menu item Default value Modiedvalue Min. adjustment — Level Distance: Probe length — take dead band into account Accept adjustment of the level measurement? No Max. adjustm…

[Page 48] Siemens SITRANS LG250

48 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Menu item Default value Modiedvalue Third HART variable (TV) Measurement certainty, level Fourth HART variable (QV) Electronics temperature Display Menu item Default value Mo…

[Page 49] Siemens SITRANS LG250

49 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 • Read from sensor: Read data from sensor and save in the display and adjustment module • Write to sensor: Save data from the display and adjustment mod- ule back into the …

[Page 50] Siemens SITRANS LG250

50 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Since scaling is very extensive, scaling of the interface value was divided into two menu items. In menu item «Interface 1 «youdenethescalingsizeand…

[Page 51] Siemens SITRANS LG250

51 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 In this menu item you can select the type and size of your probe from a list of all possible probes. This is necessary to adapt the electronics optimally to the probe. The senso…

[Page 52] Siemens SITRANS LG250

52 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 7.4 Saving the parameter adjustment data We recommended noting the adjusted data, e.g. in this operating instructions manual, and archiving them afterwards. They are thus availa…

[Page 53] Siemens SITRANS LG250

53 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 8 Setup with PACTware 8.1 Connect the PC 3 1 2 Fig.22:ConnectionofthePCdirectlytothesensorviatheinterfaceadapter 1 USBcableto�…

[Page 54] Siemens SITRANS LG250

54 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 8.2 Parameter adjustment with PACTware For parameter adjustment of the sensor via a Windows PC, the congurationsoftwarePACTwareandasuitableinstrumentdrive…

[Page 55] Siemens SITRANS LG250

55 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 8.3 Saving the parameter adjustment data We recommend documenting or saving the parameter adjustment data via PACTware. That way the data are available for multiple use or serv…

[Page 56] Siemens SITRANS LG250

56 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 9 Set up with other systems 9.1 DD adjustment programs Device descriptions as Enhanced Device Description (EDD) are available for DD adjustment programs such as, for example, AM…

[Page 57] Siemens SITRANS LG250

57 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 10 Diagnostics and servicing 10.1 Maintenance If the instrument is used correctly, no maintenance is required in normal operation. When used in safety-instrumented systems (SIS)…

[Page 58] Siemens SITRANS LG250

58 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 • Modicationofaparameter • Switch-onandswitch-otimes • Status messages (according to NE 107) • Error messages (according to NE 107) The data are…

[Page 59] Siemens SITRANS LG250

59 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 This status message is always active. It cannot be deactivated by the user. Function check: The instrument is in operation, the measured value is temporarily invalid (for exampl…

[Page 60] Siemens SITRANS LG250

60 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Code Text message Cause Rectication DevSpec State in CMD 48 F105 Measured value is determined – The instrument is still in the start phase, the measured value could not y…

[Page 61] Siemens SITRANS LG250

61 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 The following table shows the error codes and text messages in the status message «Outofspecication» and provides information on causes as well as corrective …

[Page 62] Siemens SITRANS LG250

62 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 • Evaluation of fault messages, for example via the display and adjustment module • Checking the output signal • Treatment of measurement errors Further comprehensive dia…

[Page 63] Siemens SITRANS LG250

63 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 Measurement error with constant level Fault description Error pattern Cause Rectication 1. Measured value shows a too low or too high level Level time 0 – Min./max. adju…

[Page 64] Siemens SITRANS LG250

64 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Measurement error during emptying Fault description Error pattern Cause Rectication 7. Measured value re- mains unchanged in the close range during emptying Level time 0 �…

[Page 65] Siemens SITRANS LG250

65 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 10.6 Software update The following components are required to update the sensor soft- ware: • Sensor • Voltage supply • HART modem • PC with PACTware • Currents…

[Page 66] Siemens SITRANS LG250

66 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 11 Dismount 11.1 Dismounting steps Warning: Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel or pipeline, high temperatures, cor- …

[Page 67] Siemens SITRANS LG250

67 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 12 Supplement 12.1 Technical data General data 316L corresponds to 1.4404 or 1.4435 Materials, wetted parts Ʋ Processtting 316L and PEEK, Alloy C22 (2.4602) and PEEK Ʋ …

[Page 68] Siemens SITRANS LG250

68 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Second Line of Defense (optional) Ʋ The Second Line of Defense (SLOD) is a second level of the process separation in the form of a gas-tight feedthrough in the lower part of t…

[Page 69] Siemens SITRANS LG250

69 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 Output variable Output signal 4 … 20 mA/HART Range of the output signal 3.8 … 20.5 mA/HART (default setting) FullledHARTspecication 7 Signal resolution 0.3 µA Fai…

[Page 70] Siemens SITRANS LG250

70 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Accuracy (according to DIN EN 60770-1) Process reference conditions according to DIN EN 61298-1 Ʋ Temperature +18 … +30 °C (+64 … +86 °F) Ʋ Relative humidity 45 … 75 % …

[Page 71] Siemens SITRANS LG250

71 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 Typical deviation — Total level interface measurement ± 5 mm (0.197 in) Typical deviation — Level measurement 6)7) See following diagrams L 0 -2 mm (-0.079″) 2 mm (0.079&qu…

[Page 72] Siemens SITRANS LG250

72 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Additional deviation through electromag- netic interference acc. to EN 61326 < ±10 mm (< ±0.394 in) Specicationsapplyalsotothecurrentoutput 8) Temperat…

[Page 73] Siemens SITRANS LG250

73 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 Process conditions Fortheprocessconditions,pleasealsonotethespecicationsonthetypelabel.Thelowestvalue always applies. Themeas…

[Page 74] Siemens SITRANS LG250

74 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 0°C / 32°F -40°C / -40°F 80°C / 176°F 35°C / 95°F 40°C / 104°F 30°C / 86°F 60°C / 140°F 200°C 392°F 150°C 302°F 100°C 212°F 50°C 122°F 80°C 176°F -20°C -4�…

[Page 75] Siemens SITRANS LG250

75 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 Display and adjustment module Display element Display with backlight Measured value indication Ʋ Number of digits 5 Ʋ Size of digits W x H = 7 x 13 mm Adjustment elements 4 ke…

[Page 76] Siemens SITRANS LG250

76 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Permissible residual ripple — Ex-d-ia instrument Ʋ for 18 V< U B < 36 V ≤1V e (16 … 400 Hz) Load resistor Ʋ Calculation (U B — U min )/0.022 A Ʋ Example…

[Page 77] Siemens SITRANS LG250

77 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 12.2 Dimensions Plastic housing ~ 69 mm (2.72″) ø 77 mm (3.03″) 114 mm (4.49″) M20x1,5/ ½ NPT ~ 86 mm (3.39″) M16x1,5 114 mm (4.49″) M20x1,5/ ½ NPT ø …

[Page 78] Siemens SITRANS LG250

78 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Stainless steel housing ~ 69 mm (2.72″) ø 77 mm (3.03″) 119 mm (4.69″) M20x1,5/ ½ NPT ~ 59 mm (2.32″) ø 80 mm (3.15″) 112 mm (4.41″) M20x1,5/ ½ NP…

[Page 79] Siemens SITRANS LG250

79 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 SITRANS LG250, coax version L SW 36 (1. 42″) (G¾, ¾ NPT) SW 41 (1. 61″) (G1, 1 NPT) SW 46 (1. 81″) (G1½, 1½ NPT) G¾, ¾ NPT, G1, 1 NPT, G1½, 1½ NPT 46 mm …

[Page 80] Siemens SITRANS LG250

80 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 12.3 Trademark All the brands as well as trade and company names used are property of their lawful proprietor/ originator.

[Page 81] Siemens SITRANS LG250

81 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517 INDEX A Accessories – Display and adjustment module 11 – External display and adjustment unit 11, 12 – Flanges 12 Adjustment – Max. adjustment 35, 36 – Min. adj…

[Page 82] Siemens SITRANS LG250

82 PBD-51041387SITRANS LG250 — Operating Instructions 46200-EN-160517 Sensor characteristics 51 Sensor status 43 SIL 25 Simulation 44 Special parameters 51 T Type label 8 Type of medium 33 U Units 33 Unlock adjustment 39 V Verify parameter …

[Page 83] Siemens SITRANS LG250

Notes 83 PBD-51041387 SITRANS LG250 — Operating Instructions 46200-EN-160517

[Page 84] Siemens SITRANS LG250

Siemens Canada Limited PD PA PI LW 1954 Technology Drive P.O. Box 4225 Peterborough, ON K9J 7B1, Canada email: [email protected] www.siemens.com/processautomation Subject to change without prior notice PBD-51041387 Rev. 3.0 © Siemens AG 2016…