Руководство по эксплуатации sicam

  • Contents

  • Table of Contents

  • Troubleshooting

  • Bookmarks

Quick Links

SICAM

Fault Passage Indicator

V01.20

Manual

E50417-H1040-C580-A7

Preface

Open Source Software

Table of Contents

Delivery

Introduction

Product Specification

Device Functions

Troubleshooting

Index

1

2

3

4

5

loading

Related Manuals for Siemens SICAM

Summary of Contents for Siemens SICAM

  • Page 1
    Preface Open Source Software Table of Contents SICAM Delivery Fault Passage Indicator Introduction Product Specification V01.20 Device Functions Manual Troubleshooting Index E50417-H1040-C580-A7…
  • Page 2
    Document version: E50417-H1040-C580-A7.00 Trademarks Edition: 11.2019 SIPROTEC, DIGSI, SIGRA, SIGUARD, SIMEAS SAFIR, SICAM, Version of the product described: V01.20 and MindSphere are trademarks of Siemens. Any unauthor- ized use is prohibited.
  • Page 3: Preface

    Preface Purpose of the Manual This manual describes the functions and operation of SICAM FPI device. In particular, you will find: • Compilation of the Technical Data 3.1.1 Technical Data • Information regarding the configuration of the device and a description of the device functions 4.1.1 Device Functions…

  • Page 4
    Qualified electrical engineering personnel in the sense of this document are people who can demonstrate technical qualifications as electrical technicians. These persons may commission, isolate, ground and label devices, systems and circuits according to the standards of safety engineering. SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 5
    Caution, risk of electric shock Caution, risk of danger, ISO 7000, 0434 Protective Insulation, IEC 60417, 5172, Safety Class II devices Guideline 2002/96/EC for electrical and electronic devices Guideline for the Eurasian Market SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 6
    SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 7: Open Source Software

    License Conditions provide for it you can order the source code of the Open Source Software from your Siemens sales contact – against payment of the shipping and handling charges – for a period of at least 3 years after purchase of the product. We are liable for the product including the Open Source Software contained in it pursuant to the license conditions applicable to the product.

  • Page 8
    SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 9: Table Of Contents

    2.1.11 Installation of Phase Sensors ………………23 2.1.12 Installation of Ground Sensor………………25 2.1.13 Mounting of Ground Sensor on Shielded Cable…………27 2.1.14 Replacing the SICAM FPI Battery……………….28 2.1.15 Environmental Protection Hints………………29 2.1.16 Terminal Diagram………………….30 2.1.17 Dimensional Drawings………………..31 Product Specification……………………..33 Technical Data……………………

  • Page 10
    Table of Contents 4.1.7 Battery Health Condition………………..47 4.1.8 Blinking Lamp Output………………..47 4.1.9 Binary Outputs………………….47 Troubleshooting……………………….49 Troubleshooting………………….. 50 Index…………………………..51 SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 11: Delivery

    Delivery Delivery SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…

  • Page 12: Delivery

    ICAO-TI/IATA-DGR: UN 3091 lithium metal batteries contained in equipment, 9, preconditions of Section II PI 970 met The lithium metal cell for SICAM FPI (as a spare part) is also subject to the special provision SP188 mentioned above, but classified according to: •…

  • Page 13: Introduction

    Introduction Overview SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…

  • Page 14: Overview

    SICAM FPI. In this condition, the corre- sponding LEDs blink. SICAM FPI is used as a fault detection and indication unit. SICAM FPI is used in the feeder and distribution automation of secondary medium-voltage systems that ranges from typically 10 kV to 36 kV.

  • Page 15: Hardware Components

    • Push Button — Push button is used for resetting the device manually (RST) and for executing the function check (FN.CHK) and battery check (BATT.CHK). SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…

  • Page 16: Features

    Binary outputs X3 and X4 Phase faults L1, L2, L3 optical input Remote reset input X1 (dry contact) Features 2.1.3 The salient features of SICAM FPI are: • Self-sustained — Using long-life lithium battery • Safe — Complies with the IEC 61010-1 safety standards •…

  • Page 17: Applications

    The device is used in 50-Hz/60-Hz networks. • The device is primarily intended for radial or open ring medium-voltage cable networks. 2.1.5 MLFB (Ordering Code) Table 2-1 SICAM FPI Selection and Ordering Data Description Versions Order no. 10 11 12 13 14 15 16 SICAM FPI, non-directional 6 M D 2 3 1 0 — 0 □…

  • Page 18: Sicam Fpi Variants

    With 1 ground-fault sensor (for E), Plastic fibre-optic cable (3 m in length) SICAM FPI Variants 2.1.6 The following tables show the list of SICAM FPI variants that can be ordered based on the standard MLFB. Table 2-2 SICAM FPI Variants (Type 1 Series) MLFB…

  • Page 19
    Introduction 2.1 Overview Table 2-3 SICAM FPI Variants (Type 2 Series) MLFB Phase Input Ground Input BO Sensor Type (Quantity) 6MD2310-0AE00-0AA0 3 phase + 1 ground 6MD2310-0BF00-0AA0 3 phase 6MD2310-0CG00-0AA0 1 ground 6MD2310-0DE00-0AA0 3 phase + 1 ground 6MD2310-0EG00-0AA0 1 ground Based on the device MLFB, the front view and rear view of the device varies.
  • Page 20: Device Installation

    2.1.7 Device Installation The SICAM FPI device is intended for indoor installation in an RMU panel. Execute the following procedure to install and mount the device in RMU: Create a slot of dimensions measuring 92+0.8 mm x 45+0.8 mm (W x H) to house the device in RMU ²…

  • Page 21: Commissioning

    Confirm that the correct DIP switch settings have been configured to meet the application requirements. Post-Installation and Commissioning 2.1.9 Procede as follows after installation and commissioning of the device. To use SICAM FPI for the first time, pull out the battery isolation tab to activate the device as shown in ² Figure 2-10.

  • Page 22
    [dw_fpidipswtool-global, 1, en_US] Figure 2-11 Changing DIP Switch Settings At the rear side of SICAM FPI, remove the stickers placed on the locknut of the optical inputs (L1, L2, L3, ² and E). If SICAM FPI is not responding even after pulling out the battery isolation tab, this may be due to passiva- ²…
  • Page 23: Preparing The Sensors For Installation

    Before installing the sensors on the underground cables, disconnect the power to the respective cables. Installation of Phase Sensors 2.1.11 To install the phase sensor, follow the procedure: Loosen the M4 fixing bolts on both sides using a 7-mm wrench. ² SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…

  • Page 24
    Flux concentrator bracket Core cable M4 fixing bolts Rotary switch for selecting fault-current threshold limit Gland Locknut Plastic fibre-optic cable Repeat the procedures mentioned before for installing the other phase sensors. ² SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 25: Installation Of Ground Sensor

    The plastic fibre-optic cable should be inserted into the gland till it contacts the internal component at both the ends of sensor and the device. The locknut should be fixed tightly. NOTE Siemens recommends using the following color sequence for the strip color fibre-optic cables supplied along with the SICAM FPI. •…

  • Page 26
    Rotary switch for selecting fault-current threshold limit Gland Locknut Plastic fibre-optic cable The following figure shows how SICAM FPI is connected with phase sensors and ground sensor via the plastic fibre-optic cable. SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 27: Mounting Of Ground Sensor On Shielded Cable

    Introduction 2.1 Overview [dw_fpiphaearsens-280314, 2, —_—] Figure 2-15 SICAM FPI Connected with Phase and Ground Sensors Phase conductor in a 3-core cable construction Phase conductor Phase sensor Plastic fibre-optic cable Locknut Gland Ground sensor Mounting of Ground Sensor on Shielded Cable 2.1.13…

  • Page 28: Replacing The Sicam Fpi Battery

    Always ensure that the exposed shield area is sealed to avoid any damage and stress. Replacing the SICAM FPI Battery 2.1.14 You can replace the SICAM FPI battery when it is damaged or exhausted. To replace the battery, procede as follows: Remove the SICAM FPI front cover with the help of a screwdriver.

  • Page 29: Environmental Protection Hints

    When disposing of or transferring a mobile storage device, Siemens strongly recommends physically destroying it or completely deleting data from the mobile storage device by using a commercially available computer data erasing software.

  • Page 30: Terminal Diagram

    Terminal Diagram 2.1.16 The terminal diagram shows the terminal number and terminal blocks of the 6MD2310-0AX00-0AA0 (X repre- sents the type of sensors) variant of SICAM FPI. [dw_fpirearv-210114-01, 2, —_—] Figure 2-18 Terminal Diagram Table 2-4 Terminals Specification and Recommended Lugs…

  • Page 31: Dimensional Drawings

    Introduction 2.1 Overview Dimensional Drawings 2.1.17 This section shows the dimensional drawings and different views of SICAM FPI. [dw_sicam-fpi_frbtv, 1, en_US] Figure 2-19 Front View [dw_fpirearv-210114-01, 2, —_—] Figure 2-20 Rear View SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…

  • Page 32
    SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 33: Product Specification

    Product Specification Technical Data Type Testing SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…

  • Page 34: Technical Data

    Internal battery Lithium battery (Li-SOCl ) type Standard AA cell size/3.6 V/2400 mAh Expected shelf life of the SICAM FPI with battery installed is at least 10 years, including > 2000 hours of flashing time in active mode (fault indication mode)

  • Page 35
    Humidity range 0 to 95 %, non-condensing Altitude above sea level Maximum up to 2000 m General Minimum and maximum operating temperature of -55 °C and +85 °C connected plastic fibre-optic cable SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 36: Type Testing

    Cat. III shorted Battery terminals 3.5 kV, 50 Hz Cat. III shorted SICAM FPI is classified into overvoltage category III and pollution degree 2 as per the device safety standard IEC 61010-1. Table 3-3 Environmental Test Type Test Reference Requirement…

  • Page 37
    Requirement IP Tests IP 50 IEC 60529 SICAM FPI indicator front IP 20 SICAM FPI indicator rear IP 67 SICAM FPI sensor — phase and ground Table 3-4 Routine/Production Test Type Test Reference Requirement Production test IEEE 495 Clause number. 4.2.1 and 4.2.2 SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 38
    SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 39: Device Functions

    Device Functions Description SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…

  • Page 40: Description

    4.1 Description Description Device Functions 4.1.1 This section describes the functions of SICAM FPI. Fault Detection 4.1.2 Phase Detection Single Fault — In the L1, L2, L3 phase, if single fault is detected and the fault current persists for greater than or equal to the set response time, the respective LED blinks to indicate a single fault (1 blink/s) and the phase binary output contact changes its state from open contact to close contact.

  • Page 41
    LED and the binary output remains latched. NOTE To operate the momentary fault reset, connect the NC contact of the incoming circuit breaker/bus supply to the AC 230 V input (X5). SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 42
    For example, set the DIP 3 to OFF, DIP 4 to ON, and DIP 5 to OFF to get the response time as 80 ms. By default, the factory response-time setting is 40 ms. The following table shows the response time settings of the device. SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 43
    If the battery voltage is low, the binary output contact X3 switches from open to close 5 times (open time/cycle: 1 s and close time/ cycle: 1 s), thus indicating the low battery status. SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 44
    To apply the changes in the DIP switch settings, run the complete function test by pressing the push button for less than 3 s. The following diagrams show the DIP switch settings label for the different device variants. SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 45
    [dw_fpivariant2-280314, 1, —_—] Figure 4-4 6MD2310-0BX00-0AA0 — 3 Phase, 1 Binary Output with 3 Phase Sensors [dw_fpivariant3-280314, 1, —_—] Figure 4-5 6MD2310-0CX00-0AA0 — 1 Ground, 1 Binary Output with 1 Ground Sensor SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 46
    Auto-reset time (RST TM) 6 — 7 Fault indication on binary output (FUNC SEL) X3, X4 Low battery configuration on binary output (FUNC Disabled SEL) Sensors plastic fibre-optic cable test (FUNC SEL) Disabled SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 47: Fault Indication

    When the ground-fault is detected, both the binary outputs change their position from open to close and from close to open and remain in that position until the device is reset. SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…

  • Page 48
    SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…
  • Page 49: Troubleshooting

    Troubleshooting Troubleshooting SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…

  • Page 50: Troubleshooting

    Troubleshooting 5.1 Troubleshooting Troubleshooting This section provides the common problems of SICAM FPI and the recommended solution to resolve the problem. Observations Action • The device is not responding Remove the housing screw and ensure that the paper strip inserted between the battery and battery-clip during shipment is removed.

  • Page 51: Index

    Commissioning 21 Current sensors 14 Installation Current threshold 14 Ground sensor 0 , 25 Phase sensors 23 Installation of SICAM FPI 20 Default factory settings 46 Device Description 14 Device functions 40 LEDs 15 Dimensions 34 Locknut 0 , 25, 25…

  • Page 52
    Ring main unit 20 Rotary switch 14 Routine/Production Test 36 SCADA 47 Sensors 17 Single fault 40 Spare part 17 Technical data 34 Terminal diagram 30 Troubleshooting 50 Type testing 36 Variants 18 SICAM, Fault Passage Indicator, Manual E50417-H1040-C580-A7, Edition 11.2019…

Предложите, как улучшить StudyLib

(Для жалоб на нарушения авторских прав, используйте

другую форму
)

Ваш е-мэйл

Заполните, если хотите получить ответ

Оцените наш проект

1

2

3

4

5

Table of Contents for Siemens SICAM RTU:

  • Table of Contents 14 SICAM RTUs, SICAM AK 3 User Manual Edition 07.2016, DC2-028-2.03 4.1.5.2 System-Technical Settings ……………………………………………………….. 189 4.1.5.2.1 Communication…………………………………………………………………… 189 4.1.5.2.2 Periphery …………………………………………………………………………… 189 4.1.5.3 Process-Technical Settings ………………………………………………………. 190 4

  • System Components 94 SICAM RTUs, SICAM AK 3 User Manual Edition 07.2016, DC2-028-2.03 2.2.1.4 LED Display Details about the meaning of the LEDs can be found in chapter Service, section Operation And Display Elements — Basic System Elements.

  • Installation SICAM RTUs, SICAM AK 3 User Manual 53 DC2-028-2.03, Edition 07.2016 Cable Circuitry Connection Board – ISDN Modem GND RXD RI 1 2 3 4 5 6 7 8 9 1 -/N 2 +/P 3 4 5 6 12-48VDC; 12-34 VAC (IDW90LV) DSR CTS RTS DCD DTP TXD Modem Westermo IDW-90 1 CTS 2 3 4 5 6 7 8 RTS DSR TXD RXD GND DCD DTR CP-2016 CP-2019 7 8 RX- n.c. RX+ n.c. n.c. n.c. TX- TX+ 1 2 3 4 5 6 7 8 RX- n.c. RX+ n.c. n

  • System Components 100 SICAM RTUs, SICAM AK 3 User Manual Edition 07.2016, DC2-028-2.03 2.4 Protocol Elements The hardware of the protocol elements, namely serial interface modules (SIM), can be in- stalled on the basic system element. There protocol element itself have neither a front panel nor LEDs to display status and functions. Therefore they use the LEDs and front panel of the basic system elements. The meaning of these LED displa

  • Service 224 SICAM RTUs, SICAM AK 3 User Manual Edition 07.2016, DC2-028-2.03 · W…warning Signals that the system features restricted functionality or availability (e.g. outage of mi- nute pulse, but quartz accuracy still sufficient) · T…test Signals that a function for test purposes has been affected specifically (e.g. block of input information items in the function diagram) You find further details on the diagnosis functions in the SICAM TOOLBOX II Online Help, chapter «Diagnosis». You

  • Licensing Agreement 260 SICAM RTUs, SICAM AK 3 User Manual Edition 07.2016, DC2-028-2.03 — End of document —

  • Installation SICAM RTUs, SICAM AK 3 User Manual 37 DC2-028-2.03, Edition 07.2016 1.3.1.2 Removing Front Panel Proceed as follows: · Open the screws • of the front panel which you want to remove. · Take hold of the front panel at the screws and remove it ‚. 1.3.2 Installation Caution Before the installation of a module the peripheral cable (CM-2890) must already be fitted. Warning Left and right of the boards DI-2114, DI-2115 and DO-2211 an insulation plate must be installed. One insula

  • System Components SICAM RTUs, SICAM AK 3 User Manual 159 DC2-028-2.03, Edition 07.2016 2.8.1.2 Block Diagram

  • System Components 126 SICAM RTUs, SICAM AK 3 User Manual Edition 07.2016, DC2-028-2.03 2.5.4.2 Block Diagram Warning An insulation plate must be installed left and right of the module DO-2111. One insulation plate is included to this board. Further can be ordered with following number: Insulation plate double-Euro format T12-001 / 6MF13010CA010AA0 Insulation plate holder ………………. TC2-099 / (4 pieces per insulation plate) 6MF13133CA000AA0 There

  • Service 220 SICAM RTUs, SICAM AK 3 User Manual Edition 07.2016, DC2-028-2.03 You find the basic connection possibilities in section 3.2, Connect Engineering PC with a Tar- get System. Following you find some application examples. Local Connection Directly Local Connection via Ethernet SICAM AK PS -2 63x CP -2 016 D I — 2110 DI- 21 10 CP — 20 19 DO- 22 10 AI — 230 1 A I- 23 00 SICAM AK PS-26 3x Ethernet (TCP/IP) SICAM T

  • Automation Units and Automation Networks 242 SICAM RTUs, SICAM AK 3 User Manual Edition 07.2016, DC2-028-2.03 6.1.1.5 SICAM AK 3 — SICAM AK 3 PE, electrical and optical Basic unit SICAM AK 3 to SICAM TM peripheral elements, electrically and optically connected · To one basic system element CP-2016/CPCX26 or CP-2019/PCCX26 one bus line with max. 16 peripheral elements can be connected. · Depending on the slot of the basic system element the socket connector for th

  • System Components 158 SICAM RTUs, SICAM AK 3 User Manual Edition 07.2016, DC2-028-2.03 2.8 Bus Interface Modules 2.8.1 CM-0843 The bus interface module CM-0843 serves for the electrical connection of up to 4 remotely in- stalled SICAM TM peripheral elements. 2.8.1.1 Front Panel

Questions, Opinions and Exploitation Impressions:

You can ask a question, express your opinion or share our experience of Siemens SICAM RTU device using right now.

Мониторинг и оптимизация электрических режимов дуговых печей АСУ электрической части энергообъектов Диспетчеризация электроснабжения промышленных

ЭНКС-1 ЭНМИ ЭНКС-3 ES-PDC БКВ ЭНКС-2 ЭНКС-3м ЭНМВ Система телемеханики ЭНТМ ES-Энергия ENMU ЭНИП-2

Каталог CPC 100.pdf Каталог ПТК ЭКРА.pdf Каталог POCON.pdf Каталог ПТК EVICON.pdf Каталог СПП.pdf ЭКРА

БЭ2502 ШЭ2607 ШЭ1110-ШЭ1113 БЭ2704 ОС и ПО ШЭЭ 24Х, ЭКРА 24Х (управление присоединением) ЭКРА217

Шкаф ДФЗ с трёхфазным отключением ШЭМ 2601 102.pdf Шкаф управления выкл ШЭМ 2601 501.pdf

Протокол наладки ШМЗТ2-10 БКЖИ.018-10.02.doc Протокол наладки ШМЗТ2-10 БКЖИ.018-10.04.doc Протокол наладки ШМСУ-10 БКЖИ.032-10.doc Протокол наладки

БКЖИ.656457.024-06РЭ ШМ35-06 изм0.pdf КЖИ.656457.024-39РЭ ШМ35-39 изм0.pdf БКЖИ.656455.006 РЭ ШМ35.pdf БКЖИ.656457.018-36РЭ ШМЗТ2-36 изм0.pdf БКЖИ.656457.033-03.01РЭ ШМ35-ВС3

Оперативная блокировка ШМОБ Защиты линии ШМЗЛ Защиты трансформатора ШМЗТ Защиты шин и ошиновки ШМЗШ

Типовые проекты БЭМП 1 БКЖИ.656316.001-10.40 РЭ2 БЭМП 1-10 изм1.pdf БКЖИ.656316.001-20.02 РЭ2 БЭМП 1-20 изм6.pdf

Свидетельства и ЗАКи Высоковольтная аппаратура Шкафы и панели Ретрофит Программное обеспечение ЧЭАЗ Дополнительное оборудование

SIMEAS R Power Quality_Catalog_2014_EN.pdf SICAM MMU SICAM_Q100 SICAM_Q80 SICAM T SICAM P50-55 (7KG85) SICAM

7SD600 7SS600 7SJ600 7SV600 7RW600 7VH600 7SN600 7SJ602 7SJ601

7SJ46x_Руководство_ru.pdf 7SJ45_46_Application.pdf 7SJ46_Catalog_SIP_E7.pdf 7SJ45x_Manual_en.pdf 7SJ45_Catalog_SIP_E7.pdf FAQ_E_7SJ45_46.pdf 7SJ46x_Manual_en.pdf

7SC80 7SK80 7RW80 7SJ80 7SD80 7SJ81 7SK81 Остальная информация

6MD613 7SS52 7SA522 7SJ66 7SJ62_64 6MD66 7UT613_63 6MD665 7VU683 7SJ63 7SJ61 7SD61 7UT612 7UM62

Системное описание_SIPROTEC4_DIGSI4_RU.pdf DIGSI_MANUAL_CFC (Руководство)_RU.pdf DIGSI_STARTUP (Руководство)_RU.pdf DIGSI CFC Руководство пользователя_RU.pdf Типы информации в DIGSI4.pdf

7XV5652_Преобразователь RS232 – оптика_Manual.pdf 7XV5653_Двухканальный преобразователь дискретных сигналов_Manual.pdf 7XV5673 Блок расширения входов-выходов 7XV5450_Звездообразный разветвитель_Manual.pdf

IEC61850_Realization_of_circuit_breakers_and_switches.pdf Indication_of_switch_key_position.zip Down_Hour_Counter.zip + Applications_SIPROTEC_complete_en.pdf Communicationtest.zip 7SV60_appl1.pdf 7SJ6x_Enhanced_Reverse_Interlocking.pdf Blinking_LED.zip 7SD_7SA_App_diff_0001_01_backreflection_en.pdf 7UT6_Appl.3ph.BB.en_001.02 NM.pdf Easy_interlocking.zip 7SJ6x_Appl_AR_CLP.pdf

(Ocr-Read Summary of Contents of some pages of the Siemens SICAM AK Document (Main Content), UPD: 14 April 2023)

  • 47, Redundancy via SCA-RS SICAM RTUs, SICAM AK Redundancy Unrestricted 47 DC2-026-2.07, Edition 10.2016 1.3.1.3 Redundant AUs, Voting by SCA-RS, Distance higher than 200 m Implemented with the third party product MOXA Nport Server: • SCA-RS is connected to SICAM AK via the socket connector SYS-IO on the SICAM AK • Redundancy synchronization of functional diagrams and periphery is carried out via free sel…

  • 88, Redundancy via CP-6010 88 Unrestricted SICAM RTUs, SICAM AK Redundancy Edition 10.2016, DC2-026-2.07 2.2 CP-6010 (Redundancy Voter) 2.2.1 Power Supply and Firmware Each module CP-6010 is supplied with voltage via a module PS-663x. The mounting takes place on a DIN rail. Once the respective CP-6010 is supplied with voltage, LEDs on the front panel indicate the readiness for operation and errors, as well as the communication states of the Ether…

  • 82, Redundancy via SCA-RS 82 Unrestricted SICAM RTUs, SICAM AK Redundancy Edition 10.2016, DC2-026-2.07 OPM, Edit image: Overview of the various combinations of attributes for the parameter setting of specific redundancy status information messages, necessary parameters are marked with an “X”: Return_inform_function_(RED) BSE_(RED) PRE_(RED) redundancy state X irrelevant for global redundancy switchover X irre…

  • 86, Redundancy via CP-6010 86 Unrestricted SICAM RTUs, SICAM AK Redundancy Edition 10.2016, DC2-026-2.07 2.1 Overview 2.1.1 System Components The SICAM AK Redundancy is an integrated functionality of SICAM AK which monitors the internally generated hardware, firmware and communication related errors. It monitors the error conditions of 2 systems SICAM AK and sends the switchover messages to ensure the availability of 1 active system. The SICAM AK Redundancy system consists of: …

  • 133, Configuration of SICAM AK and CP-6010 SICAM RTUs, SICAM AK Redundancy Unrestricted 133 DC2-026-2.07, Edition 10.2016 Addr. Message Line by line switch over Global switch- over IOA IOA hex IOA 1 IOA 2 IOA 3 System element +80 A/P control System element 80 C14 81 51 81 0 0 +81 A/P control System element 81 C15 82 52 82 0 0 +82 A/P control System element 82 C16 83 53 83 0 0 +83 A/P control S…

  • 18, Redundancy via SCA-RS 18 Unrestricted SICAM RTUs, SICAM AK Redundancy Edition 10.2016, DC2-026-2.07 Example for CPU-Redundancy: FUD is running, for instance, on both C-CPUs of the AU. Synchronization mode is HSL with singular Ax-PEs. Example for AE-redundancy with singular AX-PE-Bus. Periodical data points from the PEs are detected automatically over the HSL and used by the passive CPU. Spontaneous data points are copied from the active CPU…

  • 164, Configuration of SICAM AK and CP-6010 164 Unrestricted SICAM RTUs, SICAM AK Redundancy Edition 10.2016, DC2-026-2.07 Addr. Message Line by line switch over Global switch- over IOA IOA hex IOA 1 IOA 2 IOA 3 System element +1310 priority 14 1311 51F 31 5 0 +1311 priority 15 1312 520 32 5 0 +1312 priority 0 System element 82 C16 1313 521 33 5 0 +1313 priority 1 1314 522 34 5 0 +1314 priority 2 1315 523 35 5 0 +1315 priority 3 1316 524…

  • 98, Siemens SICAM AK Redundancy via CP-6010 98 Unrestricted SICAM RTUs, SICAM AK Redundancy Edition 10.2016, DC2-026-2.07 2.4.2 Parameterization 2.4.2.1 Logon Start the web browser of your PC, enter the default IP address of your target system ( http://172.16.0.3) into the address field, and confirm with the enter key. If the connection to the target system is established, the login page is opened. For the entrance into the targe…

  • 70, Redundancy via SCA-RS 70 Unrestricted SICAM RTUs, SICAM AK Redundancy Edition 10.2016, DC2-026-2.07 • Take the expansion PCB and guide it towards the backplane from below ; ensure correct plug connection between both PCB’s  • Screw the expansion PCB firmly to the mounting rack  • Remove the screws for the connection PCB ; there are 2 on both the backplane and expansion PCB • Rotate the connection PCB to the pos…

  • 10, Table of Contents 10 Unrestricted SICAM RTUs, SICAM AK Redundancy Edition 10.2016, DC2-026-2.07 1.5.2.1 Fitting Power Supply in CM-2834 …………………………………………………….65 1.5.2.1.1 Installing 1 st Power Supply …………………………………………………………65 1.5.2.1.2 Installing 2 nd Power Supply ………………………………………………………..65 …

  • 79, Redundancy via SCA-RS SICAM RTUs, SICAM AK Redundancy Unrestricted 79 DC2-026-2.07, Edition 10.2016 Switch-over disabled: cannot be used for application-related voting With CPU redundancy and global switchover with SCA-RS it is possible to prevent the switchover through modified priorities. That is necessary, if e.g. an application is not running synchronously. The block can be set by means of use…

  • 32, Redundancy via SCA-RS 32 Unrestricted SICAM RTUs, SICAM AK Redundancy Edition 10.2016, DC2-026-2.07 Necessary modules and cables Designation Item Number / MLFB Base unit SICAM AK CP-2017 processing and communication Processing and communication element CP-2017/PCCX25 CM-2838 connection communication (CP-2017) BC2-017 / 6MF10130CA170AA0 BC2-838 / 6MF10130CJ380AA0 SM-2556/ETA2 BC2-556 / 6MF10130CF560AA0 CM-2860 patch plug standard V28…

  • 59, Redundancy via SCA-RS SICAM RTUs, SICAM AK Redundancy Unrestricted 59 DC2-026-2.07, Edition 10.2016 • In the OPM system technique select the node Address of the redundant BSE’s under C4:CP-2017/PCCX25 • Enter the following data (valid for BSE and AU redundancy) Column name/ Parameter Description/Value Comment Red_sync reg-Nr. Region number of the other element of the redundancy pa…

  • 158, Configuration of SICAM AK and CP-6010 158 Unrestricted SICAM RTUs, SICAM AK Redundancy Edition 10.2016, DC2-026-2.07 Addr. Message Line by line switch over Global switch- over IOA IOA hex IOA 1 IOA 2 IOA 3 System element +1046 priority 6 1047 417 23 4 0 +1047 priority 7 1048 418 24 4 0 +1048 priority 8 1049 419 25 4 0 +1049 priority 9 1050 41A 26 4 0 +1050 priority 10 1051 41B 27 4 0 +1051 priority 11 1052 41C 28 4 0 +1052 priorit…

  • 1, Siemens SICAM AK Unrestricted DC2-026-2.07 SICAM RTUs SICAM AK Redundan cy Preface , Table of Contents Redundancy via SCA -RS 1 Redundancy via CP -6010 2 SICAM RTUs AK3: Redundancy in one Rack 3 Configuration of SICAM AK and CP-6010 A

  • 161, Configuration of SICAM AK and CP-6010 SICAM RTUs, SICAM AK Redundancy Unrestricted 161 DC2-026-2.07, Edition 10.2016 Addr. Message Line by line switch over Global switch- over IOA IOA hex IOA 1 IOA 2 IOA 3 System element +1178 priority 10 1179 49B 155 4 0 +1179 priority 11 1180 49C 156 4 0 +1180 priority 12 1181 49D 157 4 0 +1181 priority 13 1182 49E 158 4 0 +1182 priority 14 1183 49F 159 4 0 +1183 priority 15 1184 4A0 16…

  • 110, Siemens SICAM AK Redundancy via CP-6010 110 Unrestricted SICAM RTUs, SICAM AK Redundancy Edition 10.2016, DC2-026-2.07 Note If you have a different configuration in SICAM AK, you must parameterize the corresponding system elements in the topology. 2.5.2.2 Process-Technical Settings For the functionality “global switchover”, you must create the control and return information signals in the Process Technique. Create the signals in the Process Technique for both …

  • 90, Siemens SICAM AK Redundancy via CP-6010 90 Unrestricted SICAM RTUs, SICAM AK Redundancy Edition 10.2016, DC2-026-2.07 2.2.2.1 Behavior Meaning of represented symbols in the following: Symbol Status  active  inactive § flashes regularly  flickers (data exchange) LEDs on the front panel show different states that are determined by the utilized firmware. The placement of the LEDs comprises: • System display Display of the system states • …