Proline Promass F 300 Coriolis Flowmeter
EtherNet/IP
Operating Instructions Manual
BA01807O/06/EN/01.17
Valid as of version 01.00 zz (Device firmware)
71382409
MANUAL
Related Manuals for Endress+Hauser Proline Promass F 300
Summary of Contents for Endress+Hauser Proline Promass F 300
-
Page 1
MANUAL Proline Promass F 300 Coriolis Flowmeter EtherNet/IP Operating Instructions Manual BA01807O/06/EN/01.17 Valid as of version 01.00 zz (Device firmware) 71382409… -
Page 2
• The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser Sales Center will supply you with current information and updates to these instructions. Important All information and technical specifications in this documentation have been carefully checked and compiled by the author. -
Page 3: Table Of Contents
Proline Promass F 300 EtherNet/IP Table of contents Table of contents 5.2.2 Measuring devices with lifting lugs . . About this document ….6 5.2.3 Transporting with a fork lift .
-
Page 4
Table of contents Proline Promass F 300 EtherNet/IP Access to the operating menu via the local 10.5.4 Selecting and setting the medium . . display …… -
Page 5
13.2 Measuring and test equipment … 216 13.3 Endress+Hauser services ….216 Repairs ……217 14.1 General notes . -
Page 6: About This Document
About this document Proline Promass F 300 EtherNet/IP About this document Document function These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
-
Page 7: Communication Symbols
Proline Promass F 300 EtherNet/IP About this document 1.2.3 Communication symbols Symbol Meaning Wireless Local Area Network (WLAN) Communication via a wireless, local network. Light emitting diode is off. Light emitting diode is on. Light emitting diode is flashing. 1.2.4…
-
Page 8: Symbols In Graphics
• The W@M Device Viewer : Enter the serial number from the nameplate (www.endress.com/deviceviewer) • The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2-D matrix code (QR code) on the nameplate. For a detailed list of the individual documents along with the documentation code →…
-
Page 9: Supplementary Device-Dependent Documentation
Proline Promass F 300 EtherNet/IP About this document Document type Purpose and content of the document Transmitter Brief Operating Guides you quickly to the 1st measured value — Part 2 Instructions The Transmitter Brief Operating Instructions are aimed at specialists with responsibility for commissioning, configuring and parameterizing the measuring device (until the first measured value).
-
Page 10: Basic Safety Instructions
Basic safety instructions Proline Promass F 300 EtherNet/IP Basic safety instructions Requirements for the personnel The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task.
-
Page 11: Workplace Safety
Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
-
Page 12: Product Safety
It meets general safety standards and legal requirements. It also complies with the EU directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device.
-
Page 13: Protecting Access Via A Password
Proline Promass F 300 EtherNet/IP Basic safety instructions the motherboard). When hardware write protection is enabled, only read access to the parameters is possible. Hardware write protection is disabled when the device is delivered → 169. 2.7.2 Protecting access via a password Different passwords are available to protect write access to the device parameters or access to the device via the WLAN interface.
-
Page 14: Access Via Web Server
Basic safety instructions Proline Promass F 300 EtherNet/IP 2.7.4 Access via Web server The device can be operated and configured via a Web browser with the integrated Web server (→ 66). The connection is via the service interface (CDI-RJ45), the connection for EtherNet/IP signal transmission (RJ45 connector) or the WLAN interface.
-
Page 15: Product Description
Proline Promass F 300 EtherNet/IP Product description Product description The device consists of a transmitter and a sensor. The device is available as a compact version: The transmitter and sensor form a mechanical unit. Product design N ic te r e rg ö…
-
Page 16: Incoming Acceptance And Product
A0028673 and documents present? • If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center. • Depending on the device version, the CD-ROM might not be part of the delivery! The Technical Documentation is available via the Internet or via the Endress+Hauser…
-
Page 17: Product Identification
• Enter the serial number from the nameplates into the Endress+Hauser Operations App or scan the 2-D matrix code (QR code) on the nameplate with the Endress+Hauser Operations App: all the information for the measuring device is displayed. For an overview of the scope of the associated Technical Documentation, refer to the following: •…
-
Page 18: Transmitter Nameplate
Incoming acceptance and product identification Proline Promass F 300 EtherNet/IP 4.2.1 Transmitter nameplate 3 4 5 Order code: Ser. no.: Ext. ord. cd.: Date: A0029192 2 Example of a transmitter nameplate Manufacturing location Name of the transmitter Order code Serial number (ser.
-
Page 19: Sensor Nameplate
Proline Promass F 300 EtherNet/IP Incoming acceptance and product identification 4.2.2 Sensor nameplate Order code: Ser. no.: Ext. ord. cd.: Date: A0029199 3 Example of a sensor nameplate Name of the sensor Manufacturing location Order code Serial number (ser. no.) Extended order code (Ext.
-
Page 20
Incoming acceptance and product identification Proline Promass F 300 EtherNet/IP 4.2.3 Symbols on measuring device Symbol Meaning WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury. Reference to documentation Refers to the corresponding device documentation. -
Page 21: Storage And Transport
Proline Promass F 300 EtherNet/IP Storage and transport Storage and transport Storage conditions Observe the following notes for storage: ‣ Store in the original packaging to ensure protection from shock. ‣ Do not remove protective covers or protective caps installed on process connections.
-
Page 22: Measuring Devices With Lifting Lugs
Storage and transport Proline Promass F 300 EtherNet/IP A0029214 5.2.2 Measuring devices with lifting lugs CAUTION Special transportation instructions for devices with lifting lugs ‣ Only use the lifting lugs fitted on the device or flanges to transport the device.
-
Page 23: Installation
Proline Promass F 300 EtherNet/IP Installation Installation Installation conditions No special measures such as supports are necessary. External forces are absorbed by the construction of the device. 6.1.1 Mounting position Mounting location A0028772 To prevent measuring errors arising from accumulation of gas bubbles in the measuring tube, avoid the following mounting locations in the pipe: •…
-
Page 24
Installation Proline Promass F 300 EtherNet/IP A0028773 4 Installation in a down pipe (e.g. for batching applications) Supply tank Sensor Orifice plate, pipe restriction Valve Batching tank Ø orifice plate, pipe restriction [mm] [in] [mm] [in] ³⁄₈ 0.24 ½… -
Page 25
Proline Promass F 300 EtherNet/IP Installation Orientation Recommendation Horizontal orientation, transmitter at bottom Exceptions: → 5, 25 A0015590 Horizontal orientation, transmitter at side A0015592 Applications with low process temperatures may decrease the ambient temperature. To maintain the minimum ambient temperature for the transmitter, this orientation is recommended. -
Page 26: Requirements From Environment And Process
If operating outdoors: Avoid direct sunlight, particularly in warm climatic regions. You can order a weather protection cover from Endress+Hauser : → 219 System pressure It is important that cavitation does not occur, or that gases entrained in the liquids do not outgas.
-
Page 27
Proline Promass F 300 EtherNet/IP Installation The following device versions are recommended for versions with thermal insulation: • Version with extended neck for insulation: Order code for «Sensor option», option CG with an extended neck length of 105 mm (4.13 in). -
Page 28: Special Mounting Instructions
Installation Proline Promass F 300 EtherNet/IP Heating options If a fluid requires that no heat loss should occur at the sensor, users can avail of the following heating options: • Electrical heating, e.g. with electric band heaters • Via pipes carrying hot water or steam •…
-
Page 29
Proline Promass F 300 EtherNet/IP Installation DN 8 ( «)…150 (6″) DN 250 (10″) ⁄ RUPTURE DISK A0028903 Rupture disk label Rupture disk with 1/2″ NPT internal thread with 1» width across flat Transport protection Zero point adjustment All measuring devices are calibrated in accordance with state-of-the-art technology. -
Page 30: Mounting The Measuring Device
Installation Proline Promass F 300 EtherNet/IP Cover locking NOTICE Order code «Housing», option L «Cast, stainless»: The covers of the transmitter housing are provided with a borehole to lock the cover. The cover can be locked using screws and a chain or cable provided by the customer.
-
Page 31: Turning The Transmitter Housing
Proline Promass F 300 EtherNet/IP Installation 1. Ensure that the direction of the arrow on the nameplate of the sensor matches the flow direction of the fluid. 2. Install the measuring device or turn the transmitter housing so that the cable entries do not point upwards.
-
Page 32: Post-Installation Check
Installation Proline Promass F 300 EtherNet/IP – – – 3 mm A0030035 1. Depending on the device version: Loosen the securing clamp of the connection compartment cover. 2. Unscrew the connection compartment cover. 3. Turn the display module to the desired position: max. 8 × 45° in each direction.
-
Page 33: Electrical Connection
Proline Promass F 300 EtherNet/IP Electrical connection Electrical connection NOTICE The measuring device does not have an internal circuit breaker. ‣ For this reason, assign the measuring device a switch or power-circuit breaker so that the power supply line can be easily disconnected from the mains.
-
Page 34
Electrical connection Proline Promass F 300 EtherNet/IP Pulse/frequency/switch output Standard installation cable is sufficient. Relay output Standard installation cable is sufficient. Current input 0/4 to 20 mA Standard installation cable is sufficient. Status input Standard installation cable is sufficient. Cable diameter •… -
Page 35
Proline Promass F 300 EtherNet/IP Electrical connection Capacitance: core/shield Maximum 1 000 nF for Zone 1, Class I, Division 1 Maximum 24 µH/Ω for Zone 1, Class I, Division 1 Cable length Maximum 300 m (1 000 ft), see the following table Max. -
Page 36: Terminal Assignment
Electrical connection Proline Promass F 300 EtherNet/IP 7.1.3 Terminal assignment Transmitter: supply voltage, input/outputs The terminal assignment of the inputs and outputs depends on the individual order version of the device. The device-specific terminal assignment is documented on an adhesive label in the terminal cover.
-
Page 37: Preparing The Measuring Device
Proline Promass F 300 EtherNet/IP Electrical connection 7.1.6 Preparing the measuring device NOTICE Insufficient sealing of the housing! Operational reliability of the measuring device could be compromised. ‣ Use suitable cable glands corresponding to the degree of protection. 1. Remove dummy plug if present.
-
Page 38
Electrical connection Proline Promass F 300 EtherNet/IP Connecting the EtherNet/IP connector – – – 3 mm A0029813 1. Loosen the securing clamp of the connection compartment cover. 2. Unscrew the connection compartment cover. 3. Squeeze the tabs of the display module holder together. -
Page 39
Proline Promass F 300 EtherNet/IP Electrical connection 22 mm 24 mm N ic t e r e r g ö f f iz e t e n s io r ir A0033722 7. Push the cable through the cable entry . To ensure tight sealing, do not remove the sealing ring from the cable entry. -
Page 40
Electrical connection Proline Promass F 300 EtherNet/IP 22 mm 24 mm – A0033984 4. Connect the cable in accordance with the terminal assignment . Signal cable terminal assignment: The device-specific terminal assignment is documented on an adhesive label in the terminal cover. -
Page 41: Integrating The Transmitter Into A Network
Proline Promass F 300 EtherNet/IP Electrical connection 7.2.2 Integrating the transmitter into a network This section only presents the basic options for integrating the device into a network. For information on the procedure to follow to connect the transmitter correctly → 37.
-
Page 42
Electrical connection Proline Promass F 300 EtherNet/IP Integrating into a ring topology The device is integrated via the terminal connection for signal transmission (output 1) and the connection to the service interface (CDI-RJ45). Note the following when connecting: • Recommended cable: CAT5e, CAT6 or CAT7, with shielded connector •… -
Page 43: Connecting The Remote Display And Operating Module Dkx001
Proline Promass F 300 EtherNet/IP Electrical connection 7.2.3 Connecting the remote display and operating module DKX001 The remote display and operating module DKX001 is available as an optional extra → 219. • The remote display and operating module DKX001 is only available for the following housing versions, order code for «Housing»:…
-
Page 44: Special Connection Instructions
Electrical connection Proline Promass F 300 EtherNet/IP Special connection instructions 7.4.1 Connection examples EtherNet/IP A0028767 8 Connection example for EtherNet/IP Control system (e.g. PLC) Ethernet switch Observe cable specifications Device plug Transmitter EtherNet/IP: DLR (Device Level Ring) A0027544 Control system (e.g. PLC) Ethernet switch Observe cable specifications →…
-
Page 45
Proline Promass F 300 EtherNet/IP Electrical connection Current output 4-20 mA 4…20 mA A0028758 9 Connection example for 4-20 mA current output (active) Automation system with current input (e.g. PLC) Analog display unit: observe maximum load Transmitter 4…20 mA A0028759 … -
Page 46
Electrical connection Proline Promass F 300 EtherNet/IP Switch output A0028760 12 Connection example for switch output (passive) Automation system with switch input (e.g. PLC) Power supply Transmitter: Observe input values → 226 Relay output A0028760 13 Connection example for relay output (passive) Automation system with relay input (e.g. -
Page 47: Hardware Settings
Proline Promass F 300 EtherNet/IP Electrical connection Status input A0028764 15 Connection example for status input Automation system with status output (e.g. PLC) Power supply Transmitter: Observe input values Hardware settings 7.5.1 Setting the device address The IP address of the measuring device can be configured for the network via DIP switches.
-
Page 48: Activating The Default Ip Address
Electrical connection Proline Promass F 300 EtherNet/IP A0029635 1. Depending on the housing version, loosen the securing clamp or fixing screw of the housing cover. 2. Depending on the housing version, unscrew or open the housing cover and disconnect the local display from the main electronics module where necessary.
-
Page 49: Ensuring The Degree Of Protection
Proline Promass F 300 EtherNet/IP Electrical connection Ensuring the degree of protection The measuring device fulfills all the requirements for the IP66/67 degree of protection, Type 4X enclosure. To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following steps after the electrical connection: 1.
-
Page 50: Operation Options
Operation options Proline Promass F 300 EtherNet/IP Operation options Overview of operation options A0034513 Local operation via display module Computer with Web browser (e.g. Internet Explorer) or with operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) Field Xpert SFX350 or SFX370 Mobile handheld terminal Control system (e.g.
-
Page 51: Structure And Function Of The Operating Menu
Proline Promass F 300 EtherNet/IP Operation options Structure and function of the operating menu 8.2.1 Structure of the operating menu For an overview of the operating menu for experts: «Description of Device Parameters» document supplied with the device→ 255…
-
Page 52
Operation options Proline Promass F 300 EtherNet/IP Operating menu for operators and maintenances Language Operatation Language Parameter 1 Parameter n Submenu 1 Submenu n Setup Device tag Wizard 1 / Parameter 1 Wizard n / Parameter n Advanced setup Enter access code… -
Page 53: Operating Philosophy
Proline Promass F 300 EtherNet/IP Operation options 8.2.2 Operating philosophy The individual parts of the operating menu are assigned to certain user roles (operator, maintenance etc.). Each user role contains typical tasks within the device lifecycle. For custody transfer, once the device has been put into circulation or sealed, its operation is restricted.
-
Page 54: Access To The Operating Menu Via The Local Display
Operation options Proline Promass F 300 EtherNet/IP Menu/parameter User role and tasks Content/meaning Expert function-oriented Tasks that require detailed Contains all the parameters of the device and makes it possible to access knowledge of the function of the these parameters directly using an access code. The structure of this menu is…
-
Page 55
Proline Promass F 300 EtherNet/IP Operation options Status area The following symbols appear in the status area of the operational display at the top right: • Status signals→ 189 – F: Failure – C: Function check – S: Out of specification –… -
Page 56: Navigation View
Operation options Proline Promass F 300 EtherNet/IP Measurement channel numbers Symbol Meaning Measurement channel 1 to 4 The measurement channel number is displayed only if more than one channel is present for the same measured variable type (e.g. Totalizer 1 to 3).
-
Page 57
Proline Promass F 300 EtherNet/IP Operation options For more information about the icons in the menu, refer to the «Display area» section → 57 Status area The following appears in the status area of the navigation view in the top right corner: •… -
Page 58: Editing View
Operation options Proline Promass F 300 EtherNet/IP Wizard operation Symbol Meaning Switches to the previous parameter. Confirms the parameter value and switches to the next parameter. Opens the editing view of the parameter. 8.3.3 Editing view Numeric editor +0.000 Xx –…
-
Page 59
Proline Promass F 300 EtherNet/IP Operation options Text editor Xxxxxxx A B C D E F G H I J K M N O P Q R S T U V W A0034114 18 For entering text in parameters (e.g. tag name) -
Page 60: Operating Elements
Operation options Proline Promass F 300 EtherNet/IP Controlling data entries Symbol Meaning Move entry position Reject entry Confirm entry Delete character immediately to the left of the entry position Delete character immediately to the right of the entry position Clear all the characters entered 8.3.4…
-
Page 61: Opening The Context Menu
Proline Promass F 300 EtherNet/IP Operation options Operating key(s) Meaning Escape key combination (press keys simultaneously) In a menu, submenu • Pressing the key briefly: – Exits the current menu level and takes you to the next higher level. – If help text is open, closes the help text of the parameter.
-
Page 62: Navigating And Selecting From List
Operation options Proline Promass F 300 EtherNet/IP 8.3.6 Navigating and selecting from list Different operating elements are used to navigate through the operating menu. The navigation path is displayed on the left in the header. Icons are displayed in front of the individual menus.
-
Page 63: Calling The Parameter Directly
Proline Promass F 300 EtherNet/IP Operation options 8.3.7 Calling the parameter directly A parameter number is assigned to every parameter to be able to access a parameter directly via the onsite display. Entering this access code in the Direct access parameter calls up the desired parameter directly.
-
Page 64: Changing The Parameters
Operation options Proline Promass F 300 EtherNet/IP 8.3.9 Changing the parameters Parameters can be changed via the numeric editor or text editor. • Numeric editor: Change values in a parameter, e.g. specifications for limit values. • Text editor: Enter text in a parameter, e.g. tag name.
-
Page 65: Disabling Write Protection Via Access
Proline Promass F 300 EtherNet/IP Operation options 8.3.11 Disabling write protection via access code If the -symbol appears on the local display in front of a parameter, the parameter is write-protected by a user-specific access code and its value cannot be changed at the moment using local operation →…
-
Page 66: Access To The Operating Menu Via The Web Browser
Operation options Proline Promass F 300 EtherNet/IP Access to the operating menu via the Web browser 8.4.1 Function range Thanks to the integrated Web server, the device can be operated and configured via a Web browser and via a service interface (CDI-RJ45) or via a WLAN interface. The structure of the operating menu is the same as for the local display.
-
Page 67
Proline Promass F 300 EtherNet/IP Operation options Computer settings Settings Interface CDI-RJ45 WLAN User rights Appropriate user rights (e.g. administrator rights) for TCP/IP and proxy server settings are necessary (for adjusting the IP address, subnet mask etc.). Proxy server settings of the… -
Page 68: Establishing A Connection
Operation options Proline Promass F 300 EtherNet/IP Device WLAN interface IP address If the IP address of the device is not known: • The IP address can be read out via local operation: Diagnostics → Device information → IP address •…
-
Page 69
Proline Promass F 300 EtherNet/IP Operation options 4. If a 2nd network card is not used, close all the applications on the notebook. Applications requiring Internet or a network, such as e-mail, SAP applications, Internet or Windows Explorer. 5. Close any open Internet browsers. -
Page 70: Logging On
Operation options Proline Promass F 300 EtherNet/IP Starting the Web browser 1. Start the Web browser on the computer. 2. Enter the IP address of the Web server in the address line of the Web browser: 192.168.1.212 The login page appears.
-
Page 71: User Interface
Proline Promass F 300 EtherNet/IP Operation options 8.4.5 User interface A0029418 Function row Local display language Navigation area Header The following information appears in the header: • Device name • Device tag • Device status with status signal → 192 •…
-
Page 72: Disabling The Web Server
Operation options Proline Promass F 300 EtherNet/IP Navigation area If a function is selected in the function bar, the submenus of the function open in the navigation area. The user can now navigate through the menu structure. Working area Depending on the selected function and the related submenus, various actions can be performed in this area: •…
-
Page 73: Access To The Operating Menu Via The Operating Tool
Proline Promass F 300 EtherNet/IP Operation options 2. Close the Web browser. 3. If no longer needed: Reset modified properties of the Internet protocol (TCP/IP) → 68. If communication with the Web server was established via the default IP address 192.168.1.212, DIP switch No.
-
Page 74
Operation options Proline Promass F 300 EtherNet/IP A0033725 21 Options for remote operation via EtherNet/IP network: ring topology Automation system, e.g. «RSLogix» (Rockwell Automation) Workstation for measuring device operation: with Custom Add-On Profile for «RSLogix 5000» (Rockwell Automation) or with Electronic Data Sheet (EDS) Computer with Web browser (e.g. -
Page 75
Proline Promass F 300 EtherNet/IP Operation options A0027563 22 Connection via service interface (CDI-RJ45) Computer with Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for accessing the integrated device Web server or with «FieldCare», «DeviceCare» operating tool with COM DTM «CDI Communication TCP/IP»… -
Page 76
Operation options Proline Promass F 300 EtherNet/IP Degree of protection IP67 Available antennas • Internal antenna • External antenna (optional) In the event of poor transmission/reception conditions at the place of installation. Only one antenna active in each case! Max. -
Page 77: Fieldcare
FieldCare Function scope FDT-based plant asset management tool from Endress+Hauser. It can configure all smart field devices in a system and helps you manage them. By using the status information, it is also a simple but effective way of checking their status and condition.
-
Page 78: Devicecare
DeviceCare Function scope Tool to connect and configure Endress+Hauser field devices. The fastest way to configure Endress+Hauser field devices is with the dedicated «DeviceCare» tool. Together with the device type managers (DTMs) it presents a convenient, comprehensive solution. For details, see Innovation Brochure IN01047S Source for device description files See information →…
-
Page 79: System Integration
Proline Promass F 300 EtherNet/IP System integration System integration Overview of device description files 9.1.1 Current version data for the device Firmware version 01.00.zz • On the title page of the Operating Instructions • On the transmitter nameplate • Firmware version Diagnostics →…
-
Page 80: Overview Of System Files
System integration Proline Promass F 300 EtherNet/IP Overview of system files System files Version Description How to acquire Electronic Data Certified in accordance with the • www.endress.com → Download- Sheet (EDS following ODVA guidelines: Area system file) • Conformance test •…
-
Page 81
Proline Promass F 300 EtherNet/IP System integration Heartbeat monitoring Permanently assigned → fixed input assembly → 86 input group (Assem112) 96 byte Input assembly custom Configurable → → 86 (Assem101) 88 byte input group Output assembly fix Permanently assigned ←… -
Page 82: Input And Output Groups
System integration Proline Promass F 300 EtherNet/IP 9.4.2 Input and output groups Possible configurations Configuration 1: Exclusive Owner Multicast Input Assembly Fix Instance Size (byte) Min. RPI (ms) Input Assembly Configurable Configuration 0 x 64 – Output Assembly Fix O → T Configuration…
-
Page 83
Proline Promass F 300 EtherNet/IP System integration Configuration 7: Exclusive Owner Multicast Input Assembly Configurable Instance Size (byte) Min. RPI (ms) Input Assembly Configurable Configuration 0 x 69 – – Output Assembly Fix O → T Configuration 0 x 66 Input Assembly Fix T →… -
Page 84
System integration Proline Promass F 300 EtherNet/IP Description Byte Reference density 29-32 Totalizer 1 33-36 Totalizer 2 37-40 Totalizer 3 41-44 Diagnostic information via EtherNet/IP → 93 Mass flow fixed input assembly (Assem106), 32 byte Description Byte 1. File header (not visible) 2. -
Page 85
Proline Promass F 300 EtherNet/IP System integration Description Byte 3. Carrier mass flow 37-40 4. Target volume flow 41-44 5. Carrier volume flow 45-48 6. Target corrected volume flow 49-52 7. Carrier corrected volume flow 53-56 8. Concentration 57-60 9. Volume flow unit 61-62 10. -
Page 86
System integration Proline Promass F 300 EtherNet/IP Description Byte 13. Oil density unit 73-74 14. Water density unit 75-76 Only available with the Petroleum application package Heartbeat monitoring fixed input assembly (Assem112), 100 byte Description Byte 1. Mass flow fixed input assembly 1-32 2. -
Page 87
Proline Promass F 300 EtherNet/IP System integration Possible input values Possible input values 1 to 10: • Off • Temperature • Exciter current 0 • Mass flow • Carrier tube temperature • Exciter current 1 • Volume flow • Electronic temperature •… -
Page 88
System integration Proline Promass F 300 EtherNet/IP Description (format) Byte Value 17. Not used – 18. Control totalizer 1 (integer) • 32226 (0): Add • 32490 (1): Reset and stop 19. Control totalizer 2 (integer) • 32228 (2): Default value and stop •… -
Page 89
Proline Promass F 300 EtherNet/IP System integration Description (format) Byte Value 28. External reference density unit (integer) 29-30 • 32840 (240): kg/Nm • 32841 (240): kg/Nl • 32842 (240): g/Scm • 32843 (240): kg/Scm • 32844 (240): lb/Sft 29. Not used 31-32 –… -
Page 90
System integration Proline Promass F 300 EtherNet/IP Description (format) Bits Byte Offset Parameter 84 System units Dynamic viscosity unit Parameter 78 System units Concentration unit Parameter 82 System units Oil density unit Parameter 83 System units Water density unit Parameter 90… -
Page 91
Proline Promass F 300 EtherNet/IP System integration Description (format) Bits Byte Offset Parameter 22 Configurable input assembly Input assembly position 15 Parameter 23 Configurable input assembly Input assembly position 16 Parameter 24 Configurable input assembly Input assembly position 17 Parameter 25… -
Page 92
System integration Proline Promass F 300 EtherNet/IP Description (format) Bits Byte Offset Parameter 61 Diagnostic behavior Assign behavior for diagnostic information 302 None Parameter 74 Diagnostic behavior Assign behavior for diagnostic information 441 Parameter 75 Diagnostic behavior Assign behavior for diagnostic… -
Page 93: Diagnostic Information Via Ethernet/Ip
Proline Promass F 300 EtherNet/IP System integration Description (format) Bits Byte Offset 123. Parameter 162 Concentration Coefficient D1 124. Parameter 165 Concentration Coefficient D2 125. Parameter 168 Concentration Coefficient D3 126. Parameter 171 Concentration Coefficient D4 127. Parameter 55 Petroleum mode 128.
-
Page 94
System integration Proline Promass F 300 EtherNet/IP Status signal Short text Value Process temperature too high 16777413 Process temperature too low 16777414 Main electronic failure 16777428 Sensor temperature 16777429 Sensor temperature 16777430 Sensor connection 16777435 Sensor connection 16777436 Electronic failure… -
Page 95
Proline Promass F 300 EtherNet/IP System integration Status signal Short text Value Process temperature too high 33554629 Process temperature too low 33554630 Special event 13 33554719 Special event 10 33554768 Special event 11 33554769 Special event 12 33554770 Simulation diagnostic event… -
Page 96
System integration Proline Promass F 300 EtherNet/IP Status signal Short text Value Special event 11 134218065 Special event 12 134218066 Inhomogeneous 134218082 Tube damping too high 134218088 Monitoring failed 134218182 1089 Power on 268435545 1090 Configuration reset 268435546 1091 Configuration changed… -
Page 97
Proline Promass F 300 EtherNet/IP System integration Status signal Short text Value 1461 Failed: Sensor verification 268435917 1462 Failed: Sensor electronic module verific. 268435918… -
Page 98: Commissioning
Commissioning Proline Promass F 300 EtherNet/IP Commissioning 10.1 Function check Before commissioning the measuring device: ‣ Make sure that the post-installation and post-connection checks have been performed. • «Post-installation check» checklist→ 32 • «Post-connection check» checklist → 49 10.2…
-
Page 99: Configuring The Measuring Device
Proline Promass F 300 EtherNet/IP Commissioning X X X X X X X 20.50 Main menu 0104-1 Display language English Operation Setup Display language 0104-1 English à Deutsch Español Français Display language 0104-1 à English Deutsch Español Français Hauptmenü 0104-1…
-
Page 100
Commissioning Proline Promass F 300 EtherNet/IP X X X X X X X 20.50 Main menu 0104-1 Display language English Display/operat. Setup Main menu Display/operat. Setup Diagnostic / ../Setup Medium selection XXXXXXXXX XXXXXXXXX A0032222-EN 24 Taking the example of the local display Depending on the device version, not all submenus and parameters are available in every device. -
Page 101: Defining The Tag Name
Proline Promass F 300 EtherNet/IP Commissioning ‣ Low flow cut off → 139 ‣ Partially filled pipe detection → 140 ‣ Advanced setup → 141 10.5.1 Defining the tag name To enable fast identification of the measuring point within the system, you can enter a unique designation using the Device tag parameter and thus change the factory setting.
-
Page 102
Commissioning Proline Promass F 300 EtherNet/IP Volume flow unit → 102 Volume unit → 102 Corrected volume flow unit → 102 Corrected volume unit → 102 Density unit → 103 Reference density unit → 103 →… -
Page 103: Configuring The Communication
Proline Promass F 300 EtherNet/IP Commissioning Parameter Description Selection Factory setting Density unit Select density unit. Unit choose list Country-specific: • kg/l Result • lb/ft³ The selected unit applies for: • Output • Simulation process variable • Density adjustment (Expert menu) Reference density unit Select reference density unit.
-
Page 104
Commissioning Proline Promass F 300 EtherNet/IP Subnet mask → 104 Default gateway → 104 Parameter overview with brief description Parameter Description User interface / Selection / Factory setting User entry MAC address Displays the MAC address of the measuring Unique 12-digit character Each measuring device is given device. -
Page 105
Proline Promass F 300 EtherNet/IP Commissioning 10.5.4 Selecting and setting the medium The Select medium wizard submenu contains parameters that must be configured in order to select and set the medium. Navigation «Setup» menu → Select medium ‣ Medium selection Select medium →… -
Page 106: Interface
Commissioning Proline Promass F 300 EtherNet/IP Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry / User interface Select medium – Select medium type. • Liquid Liquid • Gas Select gas type The Gas option is selected in Select measured gas type.
-
Page 107: Displaying The I/O Configuration
Proline Promass F 300 EtherNet/IP Commissioning 10.5.5 Displaying the I/O configuration The I/O configuration submenu guides the user systematically through all the parameters in which the configuration of the I/O modules is displayed. Navigation «Setup» menu → I/O configuration ‣…
-
Page 108
Commissioning Proline Promass F 300 EtherNet/IP Navigation «Setup» menu → Current input ‣ Current input 1 to n Terminal number → 108 → 108 Signal mode 0/4 mA value → 108 20 mA value → 108 Current span →… -
Page 109: Configuring The Status Input
Proline Promass F 300 EtherNet/IP Commissioning 10.5.7 Configuring the status input The Status input submenu guides the user systematically through all the parameters that have to be set for configuring the status input. Navigation «Setup» menu → Status input ‣…
-
Page 110
Commissioning Proline Promass F 300 EtherNet/IP Navigation «Setup» menu → Current output ‣ Current output 1 to n Terminal number → 110 → 110 Signal mode Assign current output 1 to n → 111 Current span → 112 0/4 mA value →… -
Page 111
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description User interface / Factory setting Selection / User entry Assign current output 1 to n – Select process variable for • Off Mass flow current output. • Mass flow • Volume flow • Corrected volume flow •… -
Page 112
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description User interface / Factory setting Selection / User entry Current span – Select current range for • 4…20 mA NAMUR Country-specific: process value output and • 4…20 mA US • 4…20 mA NAMUR upper/lower level for alarm •… -
Page 113
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description User interface / Factory setting Selection / User entry Failure mode One of the following options is Define output behavior in • Min. Max. selected in the Assign current alarm condition. • Max. output parameter (→ 111): •… -
Page 114: Configuring The Pulse/Frequency
Commissioning Proline Promass F 300 EtherNet/IP 10.5.9 Configuring the pulse/frequency/switch output The Pulse/frequency/switch output wizard guides you systematically through all the parameters that can be set for configuring the selected output type. Navigation «Setup» menu → Advanced setup → Pulse/frequency/switch output ‣…
-
Page 115
Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Operating mode – Define the output as a pulse, • Pulse Pulse frequency or switch output. • Frequency • Switch Terminal number –… -
Page 116
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Pulse width In the Operating mode Define time width of the 0.05 to 2 000 ms 100 ms parameter, the Pulse option is output pulse. selected, and one of the… -
Page 117
Proline Promass F 300 EtherNet/IP Commissioning Measuring value at maximum → 120 frequency → 121 Failure mode Failure frequency → 121 Invert output signal → 121 Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User… -
Page 118
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Assign frequency output The Frequency option is Select process variable for • Off selected in the Operating frequency output. • Mass flow mode parameter (→ 114). -
Page 119
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Minimum frequency value In the Operating mode Enter minimum frequency. 0.0 to 10 000.0 Hz 0.0 Hz parameter, the Frequency option is selected, and one of… -
Page 120
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Measuring value at minimum In the Operating mode Enter measured value for Signed floating-point Depends on country frequency parameter, the Frequency minmum frequency. number and nominal… -
Page 121
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Failure mode In the Operating mode Define output behavior in • Actual value 0 Hz parameter, the Frequency alarm condition. • Defined value option is selected, and one of •… -
Page 122
Commissioning Proline Promass F 300 EtherNet/IP Configuring the switch output Navigation «Setup» menu → Pulse/frequency/switch output ‣ Pulse/frequency/switch output 1 to n Operating mode → 122 → 122 Terminal number Signal mode → 123 Switch output function →… -
Page 123
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Signal mode – Select the signal mode for the • Passive Passive PFS output. • Active Switch output function The Switch option is selected Select function for switch •… -
Page 124
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Assign limit • The Switch option is Select process variable for limit • Mass flow Mass flow selected in the Operating function. • Volume flow mode parameter. -
Page 125: 10.5.10 Configuring The Relay Output
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Switch-on value • In the Operating mode Enter measured value for the Signed floating-point Country-specific: parameter, the Switch switch-on point. number • 0 kg/h option is selected.
-
Page 126
Commissioning Proline Promass F 300 EtherNet/IP Assign status → 127 Switch-off value → 127 Switch-on value → 127 Failure mode → 128 Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Relay output function –… -
Page 127
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Assign limit In the Relay output function Select process variable for limit • Mass flow Mass flow parameter, the Limit option is function. • Volume flow selected. -
Page 128: 10.5.11 Configuring The Local Display
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Switch-on delay In the Relay output function Define delay for the switch-on 0.0 to 100.0 s 0.0 s parameter, the Limit option is of status output.
-
Page 129
Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry Format display A local display is provided. Select how measured values • 1 value, max. size 1 value, max. size are shown on the display. -
Page 130
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 1 display A local display is provided. Select the measured value that • Mass flow Mass flow is shown on the local display. • Volume flow •… -
Page 131
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Current output 1 • Current output 2 • Current output 3 • Pressure 0% bargraph value 1 A local display is provided. Enter 0% value for bar graph… -
Page 132
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 2 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •… -
Page 133
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation… -
Page 134
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 3 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •… -
Page 135
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation… -
Page 136
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry 100% bargraph value 3 A selection was made in the Enter 100% value for bar Signed floating-point Value 3 display parameter. graph display. number… -
Page 137
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry Value 4 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •… -
Page 138
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation… -
Page 139: 10.5.12 Configuring The Low Flow Cut Off
Proline Promass F 300 EtherNet/IP Commissioning 10.5.12 Configuring the low flow cut off The Low flow cut off wizard systematically guides the user through all the parameters that must be set to configure low flow cut off. Navigation «Setup» menu → Low flow cut off ‣…
-
Page 140: 10.5.13 Configuring The Partial Filled Pipe
Commissioning Proline Promass F 300 EtherNet/IP 10.5.13 Configuring the partial filled pipe detection The Partial filled pipe detection wizard guides you systematically through all parameters that have to be set for configuring the monitoring of the pipe filling. Navigation «Setup» menu → Partially filled pipe detection ‣…
-
Page 141: Advanced Settings
Proline Promass F 300 EtherNet/IP Commissioning 10.6 Advanced settings The Advanced setup submenu together with its submenus contains parameters for specific settings. Navigation to the «Advanced setup» submenu X X X X X X X 20.50 0104-1 Main menu Display language English Display/operat.
-
Page 142: Using The Parameter To Enter The Access Code
Commissioning Proline Promass F 300 EtherNet/IP ‣ Totalizer 1 to n → 144 ‣ Display → 147 ‣ WLAN settings → 158 ‣ Concentration ‣ Heartbeat setup ‣ Configuration backup → 160 ‣ → 161 Administration 10.6.1…
-
Page 143: Carrying Out A Sensor Adjustment
Proline Promass F 300 EtherNet/IP Commissioning Linear expansion coefficient → 143 Square expansion coefficient → 143 Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Corrected volume flow calculation – Select reference density for •…
-
Page 144: Configuring The Totalizer
Commissioning Proline Promass F 300 EtherNet/IP Navigation «Setup» menu → Advanced setup → Sensor adjustment ‣ Sensor adjustment Installation direction → 144 ‣ → 144 Zero point adjustment Parameter overview with brief description Parameter Description Selection Factory setting…
-
Page 145
Proline Promass F 300 EtherNet/IP Commissioning Navigation «Setup» menu → Advanced setup → Totalizer 1 to n ‣ Totalizer 1 to n Assign process variable → 145 → 145 Unit totalizer 1 to n Totalizer operation mode → 146 Failure mode →… -
Page 146
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection Factory setting Totalizer operation mode One of the following options is Select totalizer calculation • Net flow total Net flow total selected in the Assign process mode. • Forward flow total variable parameter •… -
Page 147: Carrying Out Additional Display Configurations
Proline Promass F 300 EtherNet/IP Commissioning 10.6.5 Carrying out additional display configurations In the Display submenu you can set all the parameters associated with the configuration of the local display. Navigation «Setup» menu → Advanced setup → Display ‣ Display Format display →…
-
Page 148
Commissioning Proline Promass F 300 EtherNet/IP Separator → 158 Backlight → 158… -
Page 149
Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry Format display A local display is provided. Select how measured values • 1 value, max. size 1 value, max. size are shown on the display. -
Page 150
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 1 display A local display is provided. Select the measured value that • Mass flow Mass flow is shown on the local display. • Volume flow •… -
Page 151
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Current output 1 • Current output 2 • Current output 3 • Pressure 0% bargraph value 1 A local display is provided. Enter 0% value for bar graph… -
Page 152
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 2 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •… -
Page 153
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation… -
Page 154
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 3 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •… -
Page 155
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation… -
Page 156
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 4 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •… -
Page 157
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation… -
Page 158: Wlan Configuration
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Header A local display is provided. Select header contents on local • Device tag Device tag display. • Free text Header text In the Header parameter, the Enter display header text.
-
Page 159
Proline Promass F 300 EtherNet/IP Commissioning WLAN IP address → 159 WLAN passphrase → 159 Assign SSID name → 159 SSID name → 160 Connection state → 160 Received signal strength → 160 Parameter overview with brief description… -
Page 160: Configuration Management
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry / User interface SSID name • The User-defined option is Enter the user-defined SSID Max. 32-digit EH_device selected in the Assign SSID name (max. 32 characters). character string designation_last 7 name parameter.
-
Page 161: Using Parameters For Device Administration
Proline Promass F 300 EtherNet/IP Commissioning Parameter Description User interface / Selection Factory setting Configuration management Select action for managing the device data in • Cancel Cancel the HistoROM backup. • Execute backup • Restore • Compare • Clear backup data Backup state Shows the current status of data saving or •…
-
Page 162
Commissioning Proline Promass F 300 EtherNet/IP ‣ Reset access code → 162 Device reset → 163 Using the parameter to define the access code Navigation «Setup» menu → Advanced setup → Administration → Define access code ‣ Define access code Define access code →… -
Page 163: Simulation
Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Description User interface / User entry Factory setting Operating time Indicates how long the device has been in Days (d), hours (h), minutes – operation. (m) and seconds (s) Reset access code Reset access code to factory settings.
-
Page 164
Commissioning Proline Promass F 300 EtherNet/IP Value current input 1 to n → 166 Current output 1 to n simulation → 166 Value current output 1 to n → 166 Frequency output simulation 1 to n → 166 Frequency value 1 to n →… -
Page 165
Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry / User interface Assign simulation process variable – Select a process variable for • Off the simulation process that is • Mass flow activated. -
Page 166
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry / User interface Status input simulation – Switch simulation of the status • Off input on and off. • On Input signal level In the Status input simulation Select the signal level for the •… -
Page 167: Protecting Settings From Unauthorized
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry / User interface Device alarm simulation – Switch the device alarm on and • Off off. • On Diagnostic event category – Select a diagnostic event • Sensor Process category.
-
Page 168
A reset code must be entered for this purpose. The user-specific access code can then be defined again afterwards. Via Web browser, FieldCare, DeviceCare (via CDI-RJ45 service interface), fieldbus For a reset code, contact your Endress+Hauser service organization. 1. Navigate to the Reset access code parameter (→ 163). -
Page 169: Write Protection Via Write Protection
Proline Promass F 300 EtherNet/IP Commissioning 2. Enter the reset code. The access code has been reset to the factory setting 0000. It can be redefined → 167. 10.8.2 Write protection via write protection switch Unlike parameter write protection via a user-specific access code, this allows write access to the entire operating menu — except for the «Contrast display»…
-
Page 170: Operation
Operation Proline Promass F 300 EtherNet/IP Operation 11.1 Reading the device locking status Device active write protection: Locking status parameter Operation → Locking status Function scope of the «Locking status» parameter Options Description None The access status displayed in the Access status parameter applies → 64. Only appears on local display.
-
Page 171: Measured Variables» Submenu
Proline Promass F 300 EtherNet/IP Operation ‣ Output values → 175 ‣ Totalizer → 173 11.4.1 «Measured variables» submenu The Measured variables submenu contains all the parameters needed to display the current measured values for each process variable.
-
Page 172
Operation Proline Promass F 300 EtherNet/IP Parameter overview with brief description Parameter Prerequisite Description User interface Mass flow – Displays the mass flow currently Signed floating-point measured. number Dependency The unit is taken from the Mass flow unit parameter (→ 102). -
Page 173: Totalizer» Submenu
Proline Promass F 300 EtherNet/IP Operation Parameter Prerequisite Description User interface Target mass flow With the following conditions: Displays the target fluid mass flow Signed floating-point • Order code for «Application package», currently measured. number option ED «Concentration» Dependency • The WT-% option or the User conc.
-
Page 174
Operation Proline Promass F 300 EtherNet/IP Navigation «Diagnostics» menu → Measured values → Input values ‣ Input values ‣ Current input 1 to n → 174 ‣ → 174 Status input 1 to n Input values of current input The Current input 1 to n submenu contains all the parameters needed to display the current measured values for every current input. -
Page 175: Output Values
Proline Promass F 300 EtherNet/IP Operation Parameter overview with brief description Parameter Description User interface Value status input Shows the current input signal level. • High • Low 11.4.4 Output values The Output values submenu contains all the parameters needed to display the current measured values for every output.
-
Page 176
Operation Proline Promass F 300 EtherNet/IP Output values for pulse/frequency/switch output The Pulse/frequency/switch output 1 to n submenu contains all the parameters needed to display the current measured values for every pulse/frequency/switch output. Navigation «Diagnostics» menu → Measured values → Output values → Pulse/frequency/switch output 1 to n ‣… -
Page 177: Adapting The Measuring Device To The Process
Proline Promass F 300 EtherNet/IP Operation Parameter overview with brief description Parameter Description User interface Switch status Shows the current relay switch status. • Open • Closed Switch cycles Shows number of all performed switch cycles. Positive integer Max. switch cycles number Shows the maximal number of guaranteed switch cycles.
-
Page 178: Function Scope Of The «Control Totalizer» Parameter
Operation Proline Promass F 300 EtherNet/IP Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry Control Totalizer 1 to n One of the following options is Control totalizer value. • Totalize Totalize selected in the Assign process •…
-
Page 179: Showing Data Logging
Proline Promass F 300 EtherNet/IP Operation 11.7 Showing data logging The Extended HistoROM application package must be enabled in the device (order option) for the Data logging submenu to appear. This contains all the parameters for the measured value history.
-
Page 180
Operation Proline Promass F 300 EtherNet/IP Logging delay → 183 Data logging control → 183 Data logging status → 183 Entire logging duration → 183 ‣ Display channel 1 ‣ Display channel 2 ‣ Display channel 3 ‣… -
Page 181
Proline Promass F 300 EtherNet/IP Operation Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry / User interface Assign channel 1 The Extended HistoROM Assign a process variable to • Off application package is logging channel. • Mass flow available. -
Page 182
Operation Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry / User interface • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation damping fluctuation 1 •… -
Page 183
Proline Promass F 300 EtherNet/IP Operation Parameter Prerequisite Description Selection / User Factory setting entry / User interface Logging delay In the Data logging Enter the time delay for 0 to 999 h parameter, the Not measured value logging. overwriting option is selected. Data logging control… -
Page 184: Diagnostics And Troubleshooting
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.1 General troubleshooting For local display Error Possible causes Solution Local display dark and no output Supply voltage does not match the Apply the correct supply voltage . signals value indicated on the nameplate.
-
Page 185
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting For output signals Error Possible causes Solution Signal output outside the valid Main electronics module is Order spare part → 217. range defective. Device shows correct value on local Configuration error… -
Page 186
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Error Possible causes Solution Apart from the active network • Make sure that no other network connection to the measuring device, connections are established by other network connections are also the computer (also no WLAN) being used. -
Page 187: Diagnostic Information Via Light Emitting
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Error Possible causes Solution Operation with FieldCare or Firewall of computer or network is Depending on the settings of the DeviceCare via CDI-RJ45 service preventing communication firewall used on the computer or in…
-
Page 188
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Color Meaning The EtherNet/IP address of the device has been assigned twice. Flashing red EtherNet/IP connection is in the «time out» mode. Flashing red/green The device restarts/self-test. Port 1 active: Not connected or no connection established. -
Page 189: Diagnostic Information On Local Display
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.3 Diagnostic information on local display 12.3.1 Diagnostic message Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic message in alternation with the operational display. Operational display in alarm condition…
-
Page 190
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic behavior Symbol Meaning Alarm • Measurement is interrupted. • Signal outputs and totalizers assume the defined alarm condition. • A diagnostic message is generated. Warning Measurement is resumed. The signal outputs and totalizers are not affected. A diagnostic message is generated. -
Page 191: Calling Up Remedial Measures
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.3.2 Calling up remedial measures X X X X X X X X X X X X X X 20.50 S801 Supply voltage Menu Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2…
-
Page 192: Diagnostic Information In The Web Browser
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP 12.4 Diagnostic information in the Web browser 12.4.1 Diagnostic options Any faults detected by the measuring device are displayed in the Web browser on the home page once the user has logged on.
-
Page 193: Calling Up Remedy Information
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.4.2 Calling up remedy information Remedy information is provided for every diagnostic event to ensure that problems can be rectified quickly. These measures are displayed in red along with the diagnostic event and the related diagnostic information.
-
Page 194: Calling Up Remedy Information
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Diagnostic code Diagnostic Diagnostic Status signal Short text behavior number ↓ ↓ ↓ Example Process limit A0013962 A0013958 NAMUR 3-digit number NE 107 12.5.2 Calling up remedy information Remedy information is provided for every diagnostic event to ensure that problems can be rectified quickly: •…
-
Page 195: Adapting The Diagnostic Information
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.7 Adapting the diagnostic information 12.7.1 Adapting the diagnostic behavior Each item of diagnostic information is assigned a specific diagnostic behavior at the factory. The user can change this assignment for specific diagnostic information in the Diagnostic behavior submenu.
-
Page 196
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 062 Sensor connection faulty 1. Check or replace sensor • 0x10000DB electronic module (ISEM) • 0x10000DC 2. If available: Check connection •… -
Page 197: Diagnostic Of Electronic
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 144 Measuring error too high 1. Check or change sensor 0x10001C7 2. Check process conditions Status signal Diagnostic behavior [from the…
-
Page 198
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 262 Sensor electronic connection faulty 1. Check or replace connection 0x1000149 cable between sensor electronic module (ISEM) and main Status signal… -
Page 199
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 276 I/O module 1 to n faulty 1. Restart device • 0x100007B 2. Change I/O module • 0x1000081 Status signal Diagnostic behavior… -
Page 200
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 372 Sensor electronic (ISEM) faulty 1. Restart device • 0x10000A1 2. Check if failure recurs • 0x10000C7 3. Replace sensor electronic module •… -
Page 201: Diagnostic Of Configuration
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 383 Memory content 1. Restart device 0x100016E 2. Delete T-DAT via ‘ R eset device’ parameter Status signal 3. Replace T-DAT…
-
Page 202
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 412 Processing download Download active, please wait 0x2000204 Status signal Diagnostic behavior Warning Diagnostic information Remedy instructions Coding of diagnostic information (hex) -
Page 203
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 443 Pulse output 1 to n 1. Check process • 0x800008C 2. Check pulse output settings • 0x8000121 Status signal Diagnostic behavior… -
Page 204
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 491 Current output 1 to n simulation Deactivate simulation 0x200000E Status signal Diagnostic behavior Warning Diagnostic information Remedy instructions Coding of diagnostic… -
Page 205: Diagnostic Of Process
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 520 I/O 1 to n hardware configuration invalid 1. Check I/O hardware 0x1000276 configuration 2. Replace wrong I/O module Status signal 3.
-
Page 206
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 830 Sensor temperature too high Reduce ambient temp. around the 0x80000C0 sensor housing Status signal Diagnostic behavior [from the Warning factory] Diagnostic behavior can be changed. -
Page 207
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 834 Process temperature too high Reduce process temperature 0x80000C5 Status signal Diagnostic behavior [from the Warning factory] Diagnostic behavior can be changed. -
Page 208
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 910 Tubes not oscillating 1. Check electronic 0x1000050 2. Inspect sensor Status signal Diagnostic behavior Alarm Diagnostic information Remedy instructions Coding of diagnostic… -
Page 209: Pending Diagnostic Events
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 943 API pressure out of specification 1. Check process pressure with 0x800037F selected API commodity group 2. Check API related parameters…
-
Page 210: 12.10 Diagnostic List
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Operating time from restart → 210 Operating time → 210 Parameter overview with brief description Parameter Prerequisite Description User interface Actual diagnostics A diagnostic event has occurred. Shows the current occured diagnostic…
-
Page 211: 12.11 Event Logbook
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.11 Event logbook 12.11.1 Reading out the event logbook A chronological overview of the event messages that have occurred is provided in the Events list submenu. Navigation path Diagnostics menu → Event logbook submenu → Event list / ../Eventlist…
-
Page 212: 12.11.3 Overview Of Information Events
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP 12.11.3 Overview of information events Unlike a diagnostic event, an information event is displayed in the event logbook only and not in the diagnostic list. Info number Info name I1000 ———(Device ok)
-
Page 213: 12.12 Resetting The Measuring Device
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Info number Info name I1514 Upload started I1515 Upload finished I1618 I/O module 2 replaced I1619 I/O module 3 replaced I1621 I/O module 4 replaced I1622 Calibration changed I1624 Reset all totalizers…
-
Page 214: 12.13 Device Information
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP 12.13 Device information The Device information submenu contains all parameters that display different information for device identification. Navigation «Diagnostics» menu → Device information ‣ Device information Device tag → 214 Serial number →…
-
Page 215: 12.14 Firmware History
«Manufacturer’ s information» document. The manufacturer’ s information is available: • In the Download Area of the Endress+Hauser web site: www.endress.com → Downloads • Specify the following details: –…
-
Page 216: Maintenance
→ 238. 13.2 Measuring and test equipment Endress+Hauser offers a wide variety of measuring and test equipment, such as W@M or device tests. Your Endress+Hauser Sales Center can provide detailed information on the services. List of some of the measuring and testing equipment: → 219 13.3…
-
Page 217: Repairs
• The measuring devices have a modular design. • Spare parts are grouped into logical kits with the associated Installation Instructions. • Repairs are carried out by Endress+Hauser Service or by appropriately trained customers. • Certified devices can only be converted to other certified devices by Endress+Hauser Service or at the factory.
-
Page 218: Disposal
Repairs Proline Promass F 300 EtherNet/IP 14.5 Disposal 14.5.1 Removing the measuring device 1. Switch off the device. WARNING Danger to persons from process conditions. ‣ Beware of hazardous process conditions such as pressure in the measuring device, high temperatures or aggressive fluids.
-
Page 219: Accessories
Various accessories, which can be ordered with the device or subsequently from Endress +Hauser, are available for the device. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
-
Page 220: For The Sensor
Is used to stabilize the temperature of the fluids in the sensor. Water, water vapor and other non-corrosive liquids are permitted for use as fluids. If using oil as a heating medium, please consult with Endress+Hauser. Heating jackets cannot be used with sensors fitted with a rupture disk.
-
Page 221: System Components
For details, see Operating Instructions BA00027S and BA00059S DeviceCare Tool for connecting and configuring Endress+Hauser field devices. For details, see Innovation brochure IN01047S 15.4 System components…
-
Page 222: Technical Data
Technical data Proline Promass F 300 EtherNet/IP Technical data 16.1 Application The measuring device is suitable for flow measurement of liquids and gases only. Depending on the version ordered, the measuring device can also measure potentially explosive, flammable, poisonous and oxidizing media.
-
Page 223: Input
Proline Promass F 300 EtherNet/IP Technical data 16.3 Input Measured variable Direct measured variables • Mass flow • Density • Temperature Calculated measured variables • Volume flow • Corrected volume flow • Reference density Measuring range Measuring ranges for liquids Measuring range full scale values …
-
Page 224
• Operating pressure to increase accuracy (Endress+Hauser recommends the use of a pressure measuring device for absolute pressure, e.g. Cerabar M or Cerabar S) •… -
Page 225
Proline Promass F 300 EtherNet/IP Technical data Current input 0/4 to 20 mA Current input 0/4 to 20 mA (active/passive) Current span • 4 to 20 mA (active) • 0/4 to 20 mA (passive) Resolution 1 µA Voltage drop Typically: 0.6 to 2 V for 3.6 to 22 mA (passive) Maximum input voltage ≤… -
Page 226: Output
Technical data Proline Promass F 300 EtherNet/IP 16.4 Output Output signal EtherNet/IP Standards In accordance with IEEE 802.3 Current output 0/4 to 20 mA Current output 0/4 to 20 mA Maximum output values 22.5 mA Current span Can be set to: •…
-
Page 227
Proline Promass F 300 EtherNet/IP Technical data Maximum output current 22.5 mA (active) Open-circuit voltage DC 28.8 V (active) Pulse width Adjustable: 0.05 to 2 000 ms Maximum pulse rate 10 000 Impulse/s Pulse value Adjustable Assignable measured • Mass flow variables •… -
Page 228
Technical data Proline Promass F 300 EtherNet/IP Relay output Function Switch output Version Relay output, galvanically isolated Switching behavior Can be set to: • NO (normally open), factory setting • NC (normally closed) Maximum switching • DC 30 V, 0.1 A capacity (passive) •… -
Page 229
Proline Promass F 300 EtherNet/IP Technical data Current output 0/4 to 20 mA 4 to 20 mA Failure mode Choose from: • 4 to 20 mA in accordance with NAMUR recommendation NE 43 • 4 to 20 mA in accordance with US •… -
Page 230
Technical data Proline Promass F 300 EtherNet/IP Interface/protocol • Via digital communication: EtherNet/IP • Via service interface – CDI-RJ45 service interface – WLAN interface Plain text display With information on cause and remedial measures Web server Plain text display With information on cause and remedial measures… -
Page 231: Power Supply
Proline Promass F 300 EtherNet/IP Technical data Configuration of the device • DIP switches on the electronics module for IP addressing (last octet) address • DHCP • Manufacturer-specific software (FieldCare) • Add-on Profile Level 3 for Rockwell Automation control systems •…
-
Page 232: Performance Characteristics
Technical data Proline Promass F 300 EtherNet/IP terminals Spring-loaded terminals: Suitable for strands and strands with ferrules. Conductor cross-section 0.2 to 2.5 mm (24 to 12 AWG). Cable entries • Cable gland: M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in) •…
-
Page 233
Proline Promass F 300 EtherNet/IP Technical data Density (cryogenic liquids) Order code for «Measuring tube material», option LA ±0.05 g/cm³ Temperature ±0.5 °C ± 0.005 · T °C (±0.9 °F ± 0.003 · (T – 32) °F) Zero point stability… -
Page 234
Technical data Proline Promass F 300 EtherNet/IP SI units 1:10 1:20 1:50 1:100 1:500 [mm] [kg/h] [kg/h] [kg/h] [kg/h] [kg/h] [kg/h] 2 000 6 500 18 000 1 800 45 000 4 500 2 250 70 000 7 000 3 500… -
Page 235
Proline Promass F 300 EtherNet/IP Technical data Base repeatability Design fundamentals → 237 Mass flow and volume flow (liquids) ±0.025 % o.r. (PremiumCal, for mass flow) ±0.05 % o.r. Mass flow (cryogenic liquids) Order code for «Measuring tube material», option LA ±0.175 % % o.r. -
Page 236
Technical data Proline Promass F 300 EtherNet/IP Wide-range density specification (special density calibration) If the process temperature is outside the valid range (→ 232) the measured error is ±0.00005 g/cm /°C (±0.000025 g/cm /°F) [kg/m ] [°C] [° ] F… -
Page 237: Installation
Proline Promass F 300 EtherNet/IP Technical data Design fundamentals o.r. = of reading, o.f.s. = of full scale value BaseAccu = base accuracy in % o.r., BaseRepeat = base repeatability in % o.r. MeasValue = measured value; ZeroPoint = zero point stability…
-
Page 238: Process
Technical data Proline Promass F 300 EtherNet/IP Temperature tables Observe the interdependencies between the permitted ambient and fluid temperatures when operating the device in hazardous areas. For detailed information on the temperature tables, see the separate document entitled «Safety Instructions» (XA) for the device.
-
Page 239
Proline Promass F 300 EtherNet/IP Technical data High-temperature version –50 to +350 °C (–58 to +662 °F) For nominal diameters DN 25 (1″), DN 50 (2″) and DN 80 (3″) Order code for «Measuring tube mat., wetted surface», option TT, Low-temperature version –196 to +150 °C (–320 to +302 °F) -
Page 240
Technical data Proline Promass F 300 EtherNet/IP Density 0 to 5 000 kg/m (0 to 312 lb/cf) Pressure-temperature An overview of the pressure-temperature ratings for the process connections is ratings provided in the «Technical Information» document Secondary containment For the Standard version with the temperature range –50 to +150 °C (–58 to +302 °F), the sensor housing is filled with dry nitrogen gas and protects the electronics and mechanics inside. -
Page 241
Proline Promass F 300 EtherNet/IP Technical data If the sensor is to be purged with gas (gas detection), it should be equipped with purge connections. Do not open the purge connections unless the containment can be filled immediately with a dry, inert gas. Use only low pressure to purge. Maximum pressure: 5 bar (72.5 psi). -
Page 242: 16.10 Mechanical Construction
Technical data Proline Promass F 300 EtherNet/IP 16.10 Mechanical construction Design, dimensions For the dimensions and installation lengths of the device, see the «Technical Information» document, «Mechanical construction» section. Weight All values (weight exclusive of packaging material) refer to devices with EN/DIN PN 40 flanges.
-
Page 243
Proline Promass F 300 EtherNet/IP Technical data Materials Transmitter housing Order code for «Housing»: • Option A «Aluminum, coated»: aluminum, AlSi10Mg, coated • Option B «Stainless, hygienic»: stainless steel, 1.4404 (316L) • Option L «Cast, stainless»: cast, stainless steel, 1.4409 (CF3M) similar to 316L Window material Order code for «Housing»:… -
Page 244
Technical data Proline Promass F 300 EtherNet/IP Order code for «Housing», option L «Cast, stainless» The various cable entries are suitable for hazardous and non-hazardous areas. Cable entry/cable gland Material Cable gland M20 × 1.5 Stainless steel, 1.4404 (316L) Adapter for cable entry with internal thread G ½»… -
Page 245
Proline Promass F 300 EtherNet/IP Technical data High-temperature version Flanges according to EN 1092-1 (DIN2501) / according to ASME B 16.5 / as per JIS B2220: – Stainless steel, 1.4404 (F316/F316L) – Alloy C22, 2.4602 (UNS N06022) List of all available process connections → 245… -
Page 246: 16.11 Operability
Technical data Proline Promass F 300 EtherNet/IP 16.11 Operability Languages Can be operated in the following languages: • Via local operation English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Chinese, Japanese, Korean, Bahasa (Indonesian), Vietnamese, Czech, Swedish • Via Web browser…
-
Page 247
Proline Promass F 300 EtherNet/IP Technical data Via remote display and operating module DKX001 The remote display and operating module DKX001 is available as an optional extra → 219. • The remote display and operating module DKX001 is only available for the following housing versions, order code for «Housing»:… -
Page 248
Technical data Proline Promass F 300 EtherNet/IP Dimensions Information on the dimensions: «Mechanical construction» section of the «Technical Information» document. Remote operation → 73 Service interface → 74 Supported operating tools Different operating tools can be used for local or remote access to the measuring device. -
Page 249
Proline Promass F 300 EtherNet/IP Technical data Supported functions Data exchange between the operating unit (such as a notebook for example) and the measuring device: – Upload the configuration from the measuring device (XML format, configuration backup) – Save the configuration to the measuring device (XML format, restore configuration) –… -
Page 250
Technical data Proline Promass F 300 EtherNet/IP Data backup Automatic • The most important device data (sensor and transmitter) are automatically saved in the DAT modules • If the transmitter or measuring device is replaced: once the T-DAT containing the… -
Page 251: 16.12 Certificates And Approvals
EU Directives. These are listed in the corresponding EU Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. C-Tick symbol The measuring system meets the EMC requirements of the «Australian Communications and Media Authority (ACMA)».
-
Page 252
For detailed information on the radio approval, see the Special Documentation → 256 Additional certification Marine approval Currently valid certificates are available: • In the Download Area of the Endress+Hauser Internet site: www.endress.com → Downloads • Specify the following details: Search area: Approval & Certificates→ Marine CRN approval Some device versions have CRN approval. -
Page 253: 16.13 Application Packages
The application packages can be ordered with the device or subsequently from Endress+Hauser. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
-
Page 254
Technical data Proline Promass F 300 EtherNet/IP Diagnostics functions Package Description Extended HistoROM Comprises extended functions concerning the event log and the activation of the measured value memory. Event log: Memory volume is extended from 20 message entries (standard version) to up to 100 entries. -
Page 255: 16.14 Accessories
• The W@M Device Viewer : Enter the serial number from the nameplate (www.endress.com/deviceviewer) • The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2-D matrix code (QR code) on the nameplate. Standard documentation…
-
Page 256
Technical data Proline Promass F 300 EtherNet/IP Device-dependent Safety instructions additional documentation Safety instructions for electrical equipment for hazardous areas. Contents Documentation code ATEX/IECEx Ex d/Ex de XA01405D ATEX/IECEx Ex ec XA01439D cCSAus XP XA01373D cCSAus Ex d/ Ex de… -
Page 257: Index
Proline Promass F 300 EtherNet/IP Index Index 0 … 9 Explanation ……61 Current consumption .
-
Page 258
Index Proline Promass F 300 EtherNet/IP Display area Field of application For operational display ….. 55 Residual risks ……11 In the navigation view . -
Page 259
Proline Promass F 300 EtherNet/IP Index System pressure ……26 Mounting dimensions Thermal insulation ……26 see Installation dimensions Vibrations . -
Page 260
Index Proline Promass F 300 EtherNet/IP Current output ……109 Current output (Wizard) ….109 Radio approval . -
Page 261
Proline Promass F 300 EtherNet/IP Index Sensor adjustment ….. . . 143 Value current output 1 to n ….175 Simulation . -
Page 262
Index Proline Promass F 300 EtherNet/IP Troubleshooting General ……. 184 TSE/BSE certificate of suitability . -
Page 264
The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currently in ef- fect. Otherwise, the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect. Contact information is subject to change.
(Ocr-Read Summary of Contents of some pages of the Endress+Hauser Proline Promass F 300 Document (Main Content), UPD: 15 September 2023)
-
216, Endress+Hauser Proline Promass F 300 Maintenance Proline Promass F 300 EtherNet/IP 216 13 Maintenance 13.1 Maintenance tasks No special maintenance work is required. 13.1.1 Exterior cleaning When cleaning the exterior of measuring devices, always use cleaning agents that do not attack the surface of the housing or the seals. 13.1.2 Interior cleaning Observe the following points for CIP and SIP cleaning: • Use only cleaning agents to which the process-wett…
-
8, About this document Proline Promass F 300 EtherNet/IP 8 1.2.6 Symbols in graphics Symbol Meaning 1, 2, 3, … Item numbers 1. , 2. , 3. , … Series of steps A, B, C, … Views A-A, B-B, C-C, … Sections — Hazardous area . Safe area (non-hazardous area) Flow direction 1.3 Documentation For an overview of the scope of the associated Technical Documentation, refer to the following: • The W@M Device Vie…
-
48, Electrical connection Proline Promass F 300 EtherNet/IP 48 1 2 3 4 5 6 7 8 128 64 32 16 8 4 2 1 IP Address setting (last octet) A0029635 1. Depending on the housing version, loosen the securing clamp or fixing screw of the housing cover. 2. Depending on the housing version, unscrew or open the housing cover and disconnect the local display from the main electronics module where necessary. 3. Se…
-
153, Proline Promass F 300 EtherNet/IP Commissioning 153 Parameter Prerequisite Description Selection / User entry Factory setting • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation damping fluctuation 1 • Signal asymmetry • Exciter current 0 • Exciter current 1 • HBSI • Totalizer 1 • Totalizer 2 • Totalizer 3 • Current …
-
169, Proline Promass F 300 EtherNet/IP Commissioning 169 2. Enter the reset code. The access code has been reset to the factory setting 0000. It can be redefined → 167. 10.8.2 Write protection via write protection switch Unlike parameter write protection via a user-specific access code, this allows write access to the entire operating menu — except for the «Contrast display» parameter — to be locked. The parameter values are no…
-
119, Proline Promass F 300 EtherNet/IP Commissioning 119 Parameter Prerequisite Description Selection / User interface / User entry Factory setting Minimum frequency value In the Operating mode parameter, the Frequency option is selected, and one of the following options is selected in the Assign frequency output parameter (→ 118): • Mass flow • Volume flow • Corrected volume flow • Target mass flow …
-
160, Commissioning Proline Promass F 300 EtherNet/IP 160 Parameter Prerequisite Description Selection / User entry / User interface Factory setting SSID name • The User-defined option is selected in the Assign SSID name parameter. • The WLAN access point option is selected in the WLAN mode parameter. Enter the user-defined SSID name (max. 32 characters). The user-defined SSID name may only be assigned once. If t…
-
172, Operation Proline Promass F 300 EtherNet/IP 172 Parameter overview with brief description Parameter Prerequisite Description User interface Mass flow – Displays the mass flow currently measured. Dependency The unit is taken from the Mass flow unit parameter (→ 102). Signed floating-point number Volume flow – Displays the volume flow currently calculated. Dependency The unit is taken from the Volume flow unit parameter (→ 102). Sig…
-
192, Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP 192 12.4 Diagnostic information in the Web browser 12.4.1 Diagnostic options Any faults detected by the measuring device are displayed in the Web browser on the home page once the user has logged on. 2 3 1 A0031056 1 Status area with status signal 2 Diagnostic information → 190 3 Remedy information with Service ID In addition, diagnostic events which have occurred can be shown in the Diagnostics menu: �…
-
235, Proline Promass F 300 EtherNet/IP Technical data 235 Base repeatability Design fundamentals → 237 Mass flow and volume flow (liquids) ±0.025 % o.r. (PremiumCal, for mass flow) ±0.05 % o.r. Mass flow (cryogenic liquids) Order code for «Measuring tube material», option LA ±0.175 % % o.r. Mass flow (gases) ±0.25 % o.r. Density (liquids) ±0.00025 g/cm 3 Density (cryogenic liquids) Order code for «Measuring tube material», option…
-
219, Proline Promass F 300 EtherNet/IP Accessories 219 15 Accessories Various accessories, which can be ordered with the device or subsequently from Endress +Hauser, are available for the device. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com. 15.1 Device-specific accessories 15.1.1 For the transmitter Accessories Description Trans…
-
96, System integration Proline Promass F 300 EtherNet/IP 96 Status signal No. Short text Value S 392 Special event 11 134218065 S 592 Special event 12 134218066 S 912 Inhomogeneous 134218082 S 948 Tube damping too high 134218088 S 944 Monitoring failed 134218182 I 1089 Power on 268435545 I 1090 Configuration reset 268435546 I 1091 Configuration changed 268435547 I 1110 Write protection switch changed 268435566 I 1111 Density adjust failure 2…
-
81, Proline Promass F 300 EtherNet/IP System integration 81 Heartbeat monitoring fixed input assembly 3) (Assem112) 96 byte → 86 Permanently assigned input group → Input assembly custom (Assem101) 88 byte → 86 Configurable input group → Output assembly fix (Assem102) 54 byte → 87 Permanently assigned output group ← Config assembly (Assem104) 2709 byte → 89 Permanently assigned configu…
-
22, Storage and transport Proline Promass F 300 EtherNet/IP 22 A0029214 5.2.2 Measuring devices with lifting lugs L CAUTION Special transportation instructions for devices with lifting lugs ‣ Only use the lifting lugs fitted on the device or flanges to transport the device. ‣ The device must always be secured at two lifting lugs at least. 5.2.3 Transporting with a fork lift If transporting in wood crates, the floor structure enables the crates to be lifted lengthwise or …
-
264, Endress+Hauser Proline Promass F 300 TechnipFMC.com © TechnipFMC 2017 All rights reserved. BA01807O/06/EN/01.17 TechnipFMC Measurement Solutions, Inc. 500 North Sam Houston Parkway West, Suite 100 Houston, Texas 77067 USA P:+1 281.260.2190 USA Operation 1602 Wagner Avenue Erie, Pennsylvania 16510 USA P:+1 814.898.5000 Germany Operation Smith Meter GmbH Regentstrasse 1 25474 Ellerbek, Germany P:+49 4101 304.0 The specications contained herein are subject to change…
-
99, Proline Promass F 300 EtherNet/IP Commissioning 99 X X X X X X XX X 20.50 Operation Setup Main menu 0104-1 Display language English Español Français Display language English Deutsch à 0104-1 à Español Français Display language English Deutsch 0104-1 Betrieb Setup Hauptmenü Sprache Deutsch 0104-1 XXXX 1. 2. 3. 4. A0029420 23 Taking the example of the local display 10.5 Configuring the measuring device • The Setup menu with its…
-
233, Endress+Hauser Proline Promass F 300 Proline Promass F 300 EtherNet/IP Technical data 233 Density (cryogenic liquids) Order code for «Measuring tube material», option LA ±0.05 g/cm³ Temperature ±0.5 °C ± 0.005 · T °C (±0.9 °F ± 0.003 · (T – 32) °F) Zero point stability DN Zero point stability [mm] [in] [kg/h] [lb/min] 8 ³⁄₈ 0.030 0.001 15 ½ 0.200 0.007 25 1 0.540 0.019 40 1½ 2.25 0.083 50 2 3.50 0.129 80 3 9.0 0.330 100 4 14.0 0.514 150 6 32.0 1.17 250 10 88.0 3.23 High-temperature version: ord…
-
24, Installation Proline Promass F 300 EtherNet/IP 24 1 2 3 4 5 A0028773 4 Installation in a down pipe (e.g. for batching applications) 1 Supply tank 2 Sensor 3 Orifice plate, pipe restriction 4 Valve 5 Batching tank DN Ø orifice plate, pipe restriction [mm] [in] [mm] [in] 8 ³⁄₈ 6 0.24 15 ½ 10 0.40 25 1 14 0.55 40 1½ 22 0.87 50 2 28 1.10 80 3 50 1.97 100 4 65 2.60 150 6 90 3.54 250 10 150 5.91 Orientation The direction of the arrow on the sensor nameplat…
-
164, Endress+Hauser Proline Promass F 300 Commissioning Proline Promass F 300 EtherNet/IP 164 Value current input 1 to n → 166 Current output 1 to n simulation → 166 Value current output 1 to n → 166 Frequency output simulation 1 to n → 166 Frequency value 1 to n → 166 Pulse output simulation 1 to n → 166 Pulse value 1 to n → 166 Switch output simulation 1 to n → 166 Switch status 1 to n → 166 Relay output 1 to n simu…
-
Page 1
MANUAL Proline Promass F 300 Coriolis Flowmeter EtherNet/IP Operating Instructions Manual BA01807O/06/EN/01.17 Valid as of version 01.00 zz (Device firmware) 71382409… -
Page 2
• The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser Sales Center will supply you with current information and updates to these instructions. Important All information and technical specifications in this documentation have been carefully checked and compiled by the author. -
Page 3: Table Of Contents
Proline Promass F 300 EtherNet/IP Table of contents Table of contents 5.2.2 Measuring devices with lifting lugs . . About this document ….6 5.2.3 Transporting with a fork lift .
-
Page 4
Table of contents Proline Promass F 300 EtherNet/IP Access to the operating menu via the local 10.5.4 Selecting and setting the medium . . display …… -
Page 5
13.2 Measuring and test equipment … 216 13.3 Endress+Hauser services ….216 Repairs ……217 14.1 General notes . -
Page 6: About This Document
About this document Proline Promass F 300 EtherNet/IP About this document Document function These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
-
Page 7: Communication Symbols
Proline Promass F 300 EtherNet/IP About this document 1.2.3 Communication symbols Symbol Meaning Wireless Local Area Network (WLAN) Communication via a wireless, local network. Light emitting diode is off. Light emitting diode is on. Light emitting diode is flashing. 1.2.4…
-
Page 8: Symbols In Graphics
• The W@M Device Viewer : Enter the serial number from the nameplate (www.endress.com/deviceviewer) • The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2-D matrix code (QR code) on the nameplate. For a detailed list of the individual documents along with the documentation code →…
-
Page 9: Supplementary Device-Dependent Documentation
Proline Promass F 300 EtherNet/IP About this document Document type Purpose and content of the document Transmitter Brief Operating Guides you quickly to the 1st measured value — Part 2 Instructions The Transmitter Brief Operating Instructions are aimed at specialists with responsibility for commissioning, configuring and parameterizing the measuring device (until the first measured value).
-
Page 10: Basic Safety Instructions
Basic safety instructions Proline Promass F 300 EtherNet/IP Basic safety instructions Requirements for the personnel The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task.
-
Page 11: Workplace Safety
Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
-
Page 12: Product Safety
It meets general safety standards and legal requirements. It also complies with the EU directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device.
-
Page 13: Protecting Access Via A Password
Proline Promass F 300 EtherNet/IP Basic safety instructions the motherboard). When hardware write protection is enabled, only read access to the parameters is possible. Hardware write protection is disabled when the device is delivered → 169. 2.7.2 Protecting access via a password Different passwords are available to protect write access to the device parameters or access to the device via the WLAN interface.
-
Page 14: Access Via Web Server
Basic safety instructions Proline Promass F 300 EtherNet/IP 2.7.4 Access via Web server The device can be operated and configured via a Web browser with the integrated Web server (→ 66). The connection is via the service interface (CDI-RJ45), the connection for EtherNet/IP signal transmission (RJ45 connector) or the WLAN interface.
-
Page 15: Product Description
Proline Promass F 300 EtherNet/IP Product description Product description The device consists of a transmitter and a sensor. The device is available as a compact version: The transmitter and sensor form a mechanical unit. Product design N ic te r e rg ö…
-
Page 16: Incoming Acceptance And Product
A0028673 and documents present? • If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center. • Depending on the device version, the CD-ROM might not be part of the delivery! The Technical Documentation is available via the Internet or via the Endress+Hauser…
-
Page 17: Product Identification
• Enter the serial number from the nameplates into the Endress+Hauser Operations App or scan the 2-D matrix code (QR code) on the nameplate with the Endress+Hauser Operations App: all the information for the measuring device is displayed. For an overview of the scope of the associated Technical Documentation, refer to the following: •…
-
Page 18: Transmitter Nameplate
Incoming acceptance and product identification Proline Promass F 300 EtherNet/IP 4.2.1 Transmitter nameplate 3 4 5 Order code: Ser. no.: Ext. ord. cd.: Date: A0029192 2 Example of a transmitter nameplate Manufacturing location Name of the transmitter Order code Serial number (ser.
-
Page 19: Sensor Nameplate
Proline Promass F 300 EtherNet/IP Incoming acceptance and product identification 4.2.2 Sensor nameplate Order code: Ser. no.: Ext. ord. cd.: Date: A0029199 3 Example of a sensor nameplate Name of the sensor Manufacturing location Order code Serial number (ser. no.) Extended order code (Ext.
-
Page 20
Incoming acceptance and product identification Proline Promass F 300 EtherNet/IP 4.2.3 Symbols on measuring device Symbol Meaning WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury. Reference to documentation Refers to the corresponding device documentation. -
Page 21: Storage And Transport
Proline Promass F 300 EtherNet/IP Storage and transport Storage and transport Storage conditions Observe the following notes for storage: ‣ Store in the original packaging to ensure protection from shock. ‣ Do not remove protective covers or protective caps installed on process connections.
-
Page 22: Measuring Devices With Lifting Lugs
Storage and transport Proline Promass F 300 EtherNet/IP A0029214 5.2.2 Measuring devices with lifting lugs CAUTION Special transportation instructions for devices with lifting lugs ‣ Only use the lifting lugs fitted on the device or flanges to transport the device.
-
Page 23: Installation
Proline Promass F 300 EtherNet/IP Installation Installation Installation conditions No special measures such as supports are necessary. External forces are absorbed by the construction of the device. 6.1.1 Mounting position Mounting location A0028772 To prevent measuring errors arising from accumulation of gas bubbles in the measuring tube, avoid the following mounting locations in the pipe: •…
-
Page 24
Installation Proline Promass F 300 EtherNet/IP A0028773 4 Installation in a down pipe (e.g. for batching applications) Supply tank Sensor Orifice plate, pipe restriction Valve Batching tank Ø orifice plate, pipe restriction [mm] [in] [mm] [in] ³⁄₈ 0.24 ½… -
Page 25
Proline Promass F 300 EtherNet/IP Installation Orientation Recommendation Horizontal orientation, transmitter at bottom Exceptions: → 5, 25 A0015590 Horizontal orientation, transmitter at side A0015592 Applications with low process temperatures may decrease the ambient temperature. To maintain the minimum ambient temperature for the transmitter, this orientation is recommended. -
Page 26: Requirements From Environment And Process
If operating outdoors: Avoid direct sunlight, particularly in warm climatic regions. You can order a weather protection cover from Endress+Hauser : → 219 System pressure It is important that cavitation does not occur, or that gases entrained in the liquids do not outgas.
-
Page 27
Proline Promass F 300 EtherNet/IP Installation The following device versions are recommended for versions with thermal insulation: • Version with extended neck for insulation: Order code for «Sensor option», option CG with an extended neck length of 105 mm (4.13 in). -
Page 28: Special Mounting Instructions
Installation Proline Promass F 300 EtherNet/IP Heating options If a fluid requires that no heat loss should occur at the sensor, users can avail of the following heating options: • Electrical heating, e.g. with electric band heaters • Via pipes carrying hot water or steam •…
-
Page 29
Proline Promass F 300 EtherNet/IP Installation DN 8 ( «)…150 (6″) DN 250 (10″) ⁄ RUPTURE DISK A0028903 Rupture disk label Rupture disk with 1/2″ NPT internal thread with 1» width across flat Transport protection Zero point adjustment All measuring devices are calibrated in accordance with state-of-the-art technology. -
Page 30: Mounting The Measuring Device
Installation Proline Promass F 300 EtherNet/IP Cover locking NOTICE Order code «Housing», option L «Cast, stainless»: The covers of the transmitter housing are provided with a borehole to lock the cover. The cover can be locked using screws and a chain or cable provided by the customer.
-
Page 31: Turning The Transmitter Housing
Proline Promass F 300 EtherNet/IP Installation 1. Ensure that the direction of the arrow on the nameplate of the sensor matches the flow direction of the fluid. 2. Install the measuring device or turn the transmitter housing so that the cable entries do not point upwards.
-
Page 32: Post-Installation Check
Installation Proline Promass F 300 EtherNet/IP – – – 3 mm A0030035 1. Depending on the device version: Loosen the securing clamp of the connection compartment cover. 2. Unscrew the connection compartment cover. 3. Turn the display module to the desired position: max. 8 × 45° in each direction.
-
Page 33: Electrical Connection
Proline Promass F 300 EtherNet/IP Electrical connection Electrical connection NOTICE The measuring device does not have an internal circuit breaker. ‣ For this reason, assign the measuring device a switch or power-circuit breaker so that the power supply line can be easily disconnected from the mains.
-
Page 34
Electrical connection Proline Promass F 300 EtherNet/IP Pulse/frequency/switch output Standard installation cable is sufficient. Relay output Standard installation cable is sufficient. Current input 0/4 to 20 mA Standard installation cable is sufficient. Status input Standard installation cable is sufficient. Cable diameter •… -
Page 35
Proline Promass F 300 EtherNet/IP Electrical connection Capacitance: core/shield Maximum 1 000 nF for Zone 1, Class I, Division 1 Maximum 24 µH/Ω for Zone 1, Class I, Division 1 Cable length Maximum 300 m (1 000 ft), see the following table Max. -
Page 36: Terminal Assignment
Electrical connection Proline Promass F 300 EtherNet/IP 7.1.3 Terminal assignment Transmitter: supply voltage, input/outputs The terminal assignment of the inputs and outputs depends on the individual order version of the device. The device-specific terminal assignment is documented on an adhesive label in the terminal cover.
-
Page 37: Preparing The Measuring Device
Proline Promass F 300 EtherNet/IP Electrical connection 7.1.6 Preparing the measuring device NOTICE Insufficient sealing of the housing! Operational reliability of the measuring device could be compromised. ‣ Use suitable cable glands corresponding to the degree of protection. 1. Remove dummy plug if present.
-
Page 38
Electrical connection Proline Promass F 300 EtherNet/IP Connecting the EtherNet/IP connector – – – 3 mm A0029813 1. Loosen the securing clamp of the connection compartment cover. 2. Unscrew the connection compartment cover. 3. Squeeze the tabs of the display module holder together. -
Page 39
Proline Promass F 300 EtherNet/IP Electrical connection 22 mm 24 mm N ic t e r e r g ö f f iz e t e n s io r ir A0033722 7. Push the cable through the cable entry . To ensure tight sealing, do not remove the sealing ring from the cable entry. -
Page 40
Electrical connection Proline Promass F 300 EtherNet/IP 22 mm 24 mm – A0033984 4. Connect the cable in accordance with the terminal assignment . Signal cable terminal assignment: The device-specific terminal assignment is documented on an adhesive label in the terminal cover. -
Page 41: Integrating The Transmitter Into A Network
Proline Promass F 300 EtherNet/IP Electrical connection 7.2.2 Integrating the transmitter into a network This section only presents the basic options for integrating the device into a network. For information on the procedure to follow to connect the transmitter correctly → 37.
-
Page 42
Electrical connection Proline Promass F 300 EtherNet/IP Integrating into a ring topology The device is integrated via the terminal connection for signal transmission (output 1) and the connection to the service interface (CDI-RJ45). Note the following when connecting: • Recommended cable: CAT5e, CAT6 or CAT7, with shielded connector •… -
Page 43: Connecting The Remote Display And Operating Module Dkx001
Proline Promass F 300 EtherNet/IP Electrical connection 7.2.3 Connecting the remote display and operating module DKX001 The remote display and operating module DKX001 is available as an optional extra → 219. • The remote display and operating module DKX001 is only available for the following housing versions, order code for «Housing»:…
-
Page 44: Special Connection Instructions
Electrical connection Proline Promass F 300 EtherNet/IP Special connection instructions 7.4.1 Connection examples EtherNet/IP A0028767 8 Connection example for EtherNet/IP Control system (e.g. PLC) Ethernet switch Observe cable specifications Device plug Transmitter EtherNet/IP: DLR (Device Level Ring) A0027544 Control system (e.g. PLC) Ethernet switch Observe cable specifications →…
-
Page 45
Proline Promass F 300 EtherNet/IP Electrical connection Current output 4-20 mA 4…20 mA A0028758 9 Connection example for 4-20 mA current output (active) Automation system with current input (e.g. PLC) Analog display unit: observe maximum load Transmitter 4…20 mA A0028759 … -
Page 46
Electrical connection Proline Promass F 300 EtherNet/IP Switch output A0028760 12 Connection example for switch output (passive) Automation system with switch input (e.g. PLC) Power supply Transmitter: Observe input values → 226 Relay output A0028760 13 Connection example for relay output (passive) Automation system with relay input (e.g. -
Page 47: Hardware Settings
Proline Promass F 300 EtherNet/IP Electrical connection Status input A0028764 15 Connection example for status input Automation system with status output (e.g. PLC) Power supply Transmitter: Observe input values Hardware settings 7.5.1 Setting the device address The IP address of the measuring device can be configured for the network via DIP switches.
-
Page 48: Activating The Default Ip Address
Electrical connection Proline Promass F 300 EtherNet/IP A0029635 1. Depending on the housing version, loosen the securing clamp or fixing screw of the housing cover. 2. Depending on the housing version, unscrew or open the housing cover and disconnect the local display from the main electronics module where necessary.
-
Page 49: Ensuring The Degree Of Protection
Proline Promass F 300 EtherNet/IP Electrical connection Ensuring the degree of protection The measuring device fulfills all the requirements for the IP66/67 degree of protection, Type 4X enclosure. To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following steps after the electrical connection: 1.
-
Page 50: Operation Options
Operation options Proline Promass F 300 EtherNet/IP Operation options Overview of operation options A0034513 Local operation via display module Computer with Web browser (e.g. Internet Explorer) or with operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) Field Xpert SFX350 or SFX370 Mobile handheld terminal Control system (e.g.
-
Page 51: Structure And Function Of The Operating Menu
Proline Promass F 300 EtherNet/IP Operation options Structure and function of the operating menu 8.2.1 Structure of the operating menu For an overview of the operating menu for experts: «Description of Device Parameters» document supplied with the device→ 255…
-
Page 52
Operation options Proline Promass F 300 EtherNet/IP Operating menu for operators and maintenances Language Operatation Language Parameter 1 Parameter n Submenu 1 Submenu n Setup Device tag Wizard 1 / Parameter 1 Wizard n / Parameter n Advanced setup Enter access code… -
Page 53: Operating Philosophy
Proline Promass F 300 EtherNet/IP Operation options 8.2.2 Operating philosophy The individual parts of the operating menu are assigned to certain user roles (operator, maintenance etc.). Each user role contains typical tasks within the device lifecycle. For custody transfer, once the device has been put into circulation or sealed, its operation is restricted.
-
Page 54: Access To The Operating Menu Via The Local Display
Operation options Proline Promass F 300 EtherNet/IP Menu/parameter User role and tasks Content/meaning Expert function-oriented Tasks that require detailed Contains all the parameters of the device and makes it possible to access knowledge of the function of the these parameters directly using an access code. The structure of this menu is…
-
Page 55
Proline Promass F 300 EtherNet/IP Operation options Status area The following symbols appear in the status area of the operational display at the top right: • Status signals→ 189 – F: Failure – C: Function check – S: Out of specification –… -
Page 56: Navigation View
Operation options Proline Promass F 300 EtherNet/IP Measurement channel numbers Symbol Meaning Measurement channel 1 to 4 The measurement channel number is displayed only if more than one channel is present for the same measured variable type (e.g. Totalizer 1 to 3).
-
Page 57
Proline Promass F 300 EtherNet/IP Operation options For more information about the icons in the menu, refer to the «Display area» section → 57 Status area The following appears in the status area of the navigation view in the top right corner: •… -
Page 58: Editing View
Operation options Proline Promass F 300 EtherNet/IP Wizard operation Symbol Meaning Switches to the previous parameter. Confirms the parameter value and switches to the next parameter. Opens the editing view of the parameter. 8.3.3 Editing view Numeric editor +0.000 Xx –…
-
Page 59
Proline Promass F 300 EtherNet/IP Operation options Text editor Xxxxxxx A B C D E F G H I J K M N O P Q R S T U V W A0034114 18 For entering text in parameters (e.g. tag name) -
Page 60: Operating Elements
Operation options Proline Promass F 300 EtherNet/IP Controlling data entries Symbol Meaning Move entry position Reject entry Confirm entry Delete character immediately to the left of the entry position Delete character immediately to the right of the entry position Clear all the characters entered 8.3.4…
-
Page 61: Opening The Context Menu
Proline Promass F 300 EtherNet/IP Operation options Operating key(s) Meaning Escape key combination (press keys simultaneously) In a menu, submenu • Pressing the key briefly: – Exits the current menu level and takes you to the next higher level. – If help text is open, closes the help text of the parameter.
-
Page 62: Navigating And Selecting From List
Operation options Proline Promass F 300 EtherNet/IP 8.3.6 Navigating and selecting from list Different operating elements are used to navigate through the operating menu. The navigation path is displayed on the left in the header. Icons are displayed in front of the individual menus.
-
Page 63: Calling The Parameter Directly
Proline Promass F 300 EtherNet/IP Operation options 8.3.7 Calling the parameter directly A parameter number is assigned to every parameter to be able to access a parameter directly via the onsite display. Entering this access code in the Direct access parameter calls up the desired parameter directly.
-
Page 64: Changing The Parameters
Operation options Proline Promass F 300 EtherNet/IP 8.3.9 Changing the parameters Parameters can be changed via the numeric editor or text editor. • Numeric editor: Change values in a parameter, e.g. specifications for limit values. • Text editor: Enter text in a parameter, e.g. tag name.
-
Page 65: Disabling Write Protection Via Access
Proline Promass F 300 EtherNet/IP Operation options 8.3.11 Disabling write protection via access code If the -symbol appears on the local display in front of a parameter, the parameter is write-protected by a user-specific access code and its value cannot be changed at the moment using local operation →…
-
Page 66: Access To The Operating Menu Via The Web Browser
Operation options Proline Promass F 300 EtherNet/IP Access to the operating menu via the Web browser 8.4.1 Function range Thanks to the integrated Web server, the device can be operated and configured via a Web browser and via a service interface (CDI-RJ45) or via a WLAN interface. The structure of the operating menu is the same as for the local display.
-
Page 67
Proline Promass F 300 EtherNet/IP Operation options Computer settings Settings Interface CDI-RJ45 WLAN User rights Appropriate user rights (e.g. administrator rights) for TCP/IP and proxy server settings are necessary (for adjusting the IP address, subnet mask etc.). Proxy server settings of the… -
Page 68: Establishing A Connection
Operation options Proline Promass F 300 EtherNet/IP Device WLAN interface IP address If the IP address of the device is not known: • The IP address can be read out via local operation: Diagnostics → Device information → IP address •…
-
Page 69
Proline Promass F 300 EtherNet/IP Operation options 4. If a 2nd network card is not used, close all the applications on the notebook. Applications requiring Internet or a network, such as e-mail, SAP applications, Internet or Windows Explorer. 5. Close any open Internet browsers. -
Page 70: Logging On
Operation options Proline Promass F 300 EtherNet/IP Starting the Web browser 1. Start the Web browser on the computer. 2. Enter the IP address of the Web server in the address line of the Web browser: 192.168.1.212 The login page appears.
-
Page 71: User Interface
Proline Promass F 300 EtherNet/IP Operation options 8.4.5 User interface A0029418 Function row Local display language Navigation area Header The following information appears in the header: • Device name • Device tag • Device status with status signal → 192 •…
-
Page 72: Disabling The Web Server
Operation options Proline Promass F 300 EtherNet/IP Navigation area If a function is selected in the function bar, the submenus of the function open in the navigation area. The user can now navigate through the menu structure. Working area Depending on the selected function and the related submenus, various actions can be performed in this area: •…
-
Page 73: Access To The Operating Menu Via The Operating Tool
Proline Promass F 300 EtherNet/IP Operation options 2. Close the Web browser. 3. If no longer needed: Reset modified properties of the Internet protocol (TCP/IP) → 68. If communication with the Web server was established via the default IP address 192.168.1.212, DIP switch No.
-
Page 74
Operation options Proline Promass F 300 EtherNet/IP A0033725 21 Options for remote operation via EtherNet/IP network: ring topology Automation system, e.g. «RSLogix» (Rockwell Automation) Workstation for measuring device operation: with Custom Add-On Profile for «RSLogix 5000» (Rockwell Automation) or with Electronic Data Sheet (EDS) Computer with Web browser (e.g. -
Page 75
Proline Promass F 300 EtherNet/IP Operation options A0027563 22 Connection via service interface (CDI-RJ45) Computer with Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for accessing the integrated device Web server or with «FieldCare», «DeviceCare» operating tool with COM DTM «CDI Communication TCP/IP»… -
Page 76
Operation options Proline Promass F 300 EtherNet/IP Degree of protection IP67 Available antennas • Internal antenna • External antenna (optional) In the event of poor transmission/reception conditions at the place of installation. Only one antenna active in each case! Max. -
Page 77: Fieldcare
FieldCare Function scope FDT-based plant asset management tool from Endress+Hauser. It can configure all smart field devices in a system and helps you manage them. By using the status information, it is also a simple but effective way of checking their status and condition.
-
Page 78: Devicecare
DeviceCare Function scope Tool to connect and configure Endress+Hauser field devices. The fastest way to configure Endress+Hauser field devices is with the dedicated «DeviceCare» tool. Together with the device type managers (DTMs) it presents a convenient, comprehensive solution. For details, see Innovation Brochure IN01047S Source for device description files See information →…
-
Page 79: System Integration
Proline Promass F 300 EtherNet/IP System integration System integration Overview of device description files 9.1.1 Current version data for the device Firmware version 01.00.zz • On the title page of the Operating Instructions • On the transmitter nameplate • Firmware version Diagnostics →…
-
Page 80: Overview Of System Files
System integration Proline Promass F 300 EtherNet/IP Overview of system files System files Version Description How to acquire Electronic Data Certified in accordance with the • www.endress.com → Download- Sheet (EDS following ODVA guidelines: Area system file) • Conformance test •…
-
Page 81
Proline Promass F 300 EtherNet/IP System integration Heartbeat monitoring Permanently assigned → fixed input assembly → 86 input group (Assem112) 96 byte Input assembly custom Configurable → → 86 (Assem101) 88 byte input group Output assembly fix Permanently assigned ←… -
Page 82: Input And Output Groups
System integration Proline Promass F 300 EtherNet/IP 9.4.2 Input and output groups Possible configurations Configuration 1: Exclusive Owner Multicast Input Assembly Fix Instance Size (byte) Min. RPI (ms) Input Assembly Configurable Configuration 0 x 64 – Output Assembly Fix O → T Configuration…
-
Page 83
Proline Promass F 300 EtherNet/IP System integration Configuration 7: Exclusive Owner Multicast Input Assembly Configurable Instance Size (byte) Min. RPI (ms) Input Assembly Configurable Configuration 0 x 69 – – Output Assembly Fix O → T Configuration 0 x 66 Input Assembly Fix T →… -
Page 84
System integration Proline Promass F 300 EtherNet/IP Description Byte Reference density 29-32 Totalizer 1 33-36 Totalizer 2 37-40 Totalizer 3 41-44 Diagnostic information via EtherNet/IP → 93 Mass flow fixed input assembly (Assem106), 32 byte Description Byte 1. File header (not visible) 2. -
Page 85
Proline Promass F 300 EtherNet/IP System integration Description Byte 3. Carrier mass flow 37-40 4. Target volume flow 41-44 5. Carrier volume flow 45-48 6. Target corrected volume flow 49-52 7. Carrier corrected volume flow 53-56 8. Concentration 57-60 9. Volume flow unit 61-62 10. -
Page 86
System integration Proline Promass F 300 EtherNet/IP Description Byte 13. Oil density unit 73-74 14. Water density unit 75-76 Only available with the Petroleum application package Heartbeat monitoring fixed input assembly (Assem112), 100 byte Description Byte 1. Mass flow fixed input assembly 1-32 2. -
Page 87
Proline Promass F 300 EtherNet/IP System integration Possible input values Possible input values 1 to 10: • Off • Temperature • Exciter current 0 • Mass flow • Carrier tube temperature • Exciter current 1 • Volume flow • Electronic temperature •… -
Page 88
System integration Proline Promass F 300 EtherNet/IP Description (format) Byte Value 17. Not used – 18. Control totalizer 1 (integer) • 32226 (0): Add • 32490 (1): Reset and stop 19. Control totalizer 2 (integer) • 32228 (2): Default value and stop •… -
Page 89
Proline Promass F 300 EtherNet/IP System integration Description (format) Byte Value 28. External reference density unit (integer) 29-30 • 32840 (240): kg/Nm • 32841 (240): kg/Nl • 32842 (240): g/Scm • 32843 (240): kg/Scm • 32844 (240): lb/Sft 29. Not used 31-32 –… -
Page 90
System integration Proline Promass F 300 EtherNet/IP Description (format) Bits Byte Offset Parameter 84 System units Dynamic viscosity unit Parameter 78 System units Concentration unit Parameter 82 System units Oil density unit Parameter 83 System units Water density unit Parameter 90… -
Page 91
Proline Promass F 300 EtherNet/IP System integration Description (format) Bits Byte Offset Parameter 22 Configurable input assembly Input assembly position 15 Parameter 23 Configurable input assembly Input assembly position 16 Parameter 24 Configurable input assembly Input assembly position 17 Parameter 25… -
Page 92
System integration Proline Promass F 300 EtherNet/IP Description (format) Bits Byte Offset Parameter 61 Diagnostic behavior Assign behavior for diagnostic information 302 None Parameter 74 Diagnostic behavior Assign behavior for diagnostic information 441 Parameter 75 Diagnostic behavior Assign behavior for diagnostic… -
Page 93: Diagnostic Information Via Ethernet/Ip
Proline Promass F 300 EtherNet/IP System integration Description (format) Bits Byte Offset 123. Parameter 162 Concentration Coefficient D1 124. Parameter 165 Concentration Coefficient D2 125. Parameter 168 Concentration Coefficient D3 126. Parameter 171 Concentration Coefficient D4 127. Parameter 55 Petroleum mode 128.
-
Page 94
System integration Proline Promass F 300 EtherNet/IP Status signal Short text Value Process temperature too high 16777413 Process temperature too low 16777414 Main electronic failure 16777428 Sensor temperature 16777429 Sensor temperature 16777430 Sensor connection 16777435 Sensor connection 16777436 Electronic failure… -
Page 95
Proline Promass F 300 EtherNet/IP System integration Status signal Short text Value Process temperature too high 33554629 Process temperature too low 33554630 Special event 13 33554719 Special event 10 33554768 Special event 11 33554769 Special event 12 33554770 Simulation diagnostic event… -
Page 96
System integration Proline Promass F 300 EtherNet/IP Status signal Short text Value Special event 11 134218065 Special event 12 134218066 Inhomogeneous 134218082 Tube damping too high 134218088 Monitoring failed 134218182 1089 Power on 268435545 1090 Configuration reset 268435546 1091 Configuration changed… -
Page 97
Proline Promass F 300 EtherNet/IP System integration Status signal Short text Value 1461 Failed: Sensor verification 268435917 1462 Failed: Sensor electronic module verific. 268435918… -
Page 98: Commissioning
Commissioning Proline Promass F 300 EtherNet/IP Commissioning 10.1 Function check Before commissioning the measuring device: ‣ Make sure that the post-installation and post-connection checks have been performed. • «Post-installation check» checklist→ 32 • «Post-connection check» checklist → 49 10.2…
-
Page 99: Configuring The Measuring Device
Proline Promass F 300 EtherNet/IP Commissioning X X X X X X X 20.50 Main menu 0104-1 Display language English Operation Setup Display language 0104-1 English à Deutsch Español Français Display language 0104-1 à English Deutsch Español Français Hauptmenü 0104-1…
-
Page 100
Commissioning Proline Promass F 300 EtherNet/IP X X X X X X X 20.50 Main menu 0104-1 Display language English Display/operat. Setup Main menu Display/operat. Setup Diagnostic / ../Setup Medium selection XXXXXXXXX XXXXXXXXX A0032222-EN 24 Taking the example of the local display Depending on the device version, not all submenus and parameters are available in every device. -
Page 101: Defining The Tag Name
Proline Promass F 300 EtherNet/IP Commissioning ‣ Low flow cut off → 139 ‣ Partially filled pipe detection → 140 ‣ Advanced setup → 141 10.5.1 Defining the tag name To enable fast identification of the measuring point within the system, you can enter a unique designation using the Device tag parameter and thus change the factory setting.
-
Page 102
Commissioning Proline Promass F 300 EtherNet/IP Volume flow unit → 102 Volume unit → 102 Corrected volume flow unit → 102 Corrected volume unit → 102 Density unit → 103 Reference density unit → 103 →… -
Page 103: Configuring The Communication
Proline Promass F 300 EtherNet/IP Commissioning Parameter Description Selection Factory setting Density unit Select density unit. Unit choose list Country-specific: • kg/l Result • lb/ft³ The selected unit applies for: • Output • Simulation process variable • Density adjustment (Expert menu) Reference density unit Select reference density unit.
-
Page 104
Commissioning Proline Promass F 300 EtherNet/IP Subnet mask → 104 Default gateway → 104 Parameter overview with brief description Parameter Description User interface / Selection / Factory setting User entry MAC address Displays the MAC address of the measuring Unique 12-digit character Each measuring device is given device. -
Page 105
Proline Promass F 300 EtherNet/IP Commissioning 10.5.4 Selecting and setting the medium The Select medium wizard submenu contains parameters that must be configured in order to select and set the medium. Navigation «Setup» menu → Select medium ‣ Medium selection Select medium →… -
Page 106: Interface
Commissioning Proline Promass F 300 EtherNet/IP Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry / User interface Select medium – Select medium type. • Liquid Liquid • Gas Select gas type The Gas option is selected in Select measured gas type.
-
Page 107: Displaying The I/O Configuration
Proline Promass F 300 EtherNet/IP Commissioning 10.5.5 Displaying the I/O configuration The I/O configuration submenu guides the user systematically through all the parameters in which the configuration of the I/O modules is displayed. Navigation «Setup» menu → I/O configuration ‣…
-
Page 108
Commissioning Proline Promass F 300 EtherNet/IP Navigation «Setup» menu → Current input ‣ Current input 1 to n Terminal number → 108 → 108 Signal mode 0/4 mA value → 108 20 mA value → 108 Current span →… -
Page 109: Configuring The Status Input
Proline Promass F 300 EtherNet/IP Commissioning 10.5.7 Configuring the status input The Status input submenu guides the user systematically through all the parameters that have to be set for configuring the status input. Navigation «Setup» menu → Status input ‣…
-
Page 110
Commissioning Proline Promass F 300 EtherNet/IP Navigation «Setup» menu → Current output ‣ Current output 1 to n Terminal number → 110 → 110 Signal mode Assign current output 1 to n → 111 Current span → 112 0/4 mA value →… -
Page 111
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description User interface / Factory setting Selection / User entry Assign current output 1 to n – Select process variable for • Off Mass flow current output. • Mass flow • Volume flow • Corrected volume flow •… -
Page 112
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description User interface / Factory setting Selection / User entry Current span – Select current range for • 4…20 mA NAMUR Country-specific: process value output and • 4…20 mA US • 4…20 mA NAMUR upper/lower level for alarm •… -
Page 113
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description User interface / Factory setting Selection / User entry Failure mode One of the following options is Define output behavior in • Min. Max. selected in the Assign current alarm condition. • Max. output parameter (→ 111): •… -
Page 114: Configuring The Pulse/Frequency
Commissioning Proline Promass F 300 EtherNet/IP 10.5.9 Configuring the pulse/frequency/switch output The Pulse/frequency/switch output wizard guides you systematically through all the parameters that can be set for configuring the selected output type. Navigation «Setup» menu → Advanced setup → Pulse/frequency/switch output ‣…
-
Page 115
Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Operating mode – Define the output as a pulse, • Pulse Pulse frequency or switch output. • Frequency • Switch Terminal number –… -
Page 116
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Pulse width In the Operating mode Define time width of the 0.05 to 2 000 ms 100 ms parameter, the Pulse option is output pulse. selected, and one of the… -
Page 117
Proline Promass F 300 EtherNet/IP Commissioning Measuring value at maximum → 120 frequency → 121 Failure mode Failure frequency → 121 Invert output signal → 121 Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User… -
Page 118
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Assign frequency output The Frequency option is Select process variable for • Off selected in the Operating frequency output. • Mass flow mode parameter (→ 114). -
Page 119
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Minimum frequency value In the Operating mode Enter minimum frequency. 0.0 to 10 000.0 Hz 0.0 Hz parameter, the Frequency option is selected, and one of… -
Page 120
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Measuring value at minimum In the Operating mode Enter measured value for Signed floating-point Depends on country frequency parameter, the Frequency minmum frequency. number and nominal… -
Page 121
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Failure mode In the Operating mode Define output behavior in • Actual value 0 Hz parameter, the Frequency alarm condition. • Defined value option is selected, and one of •… -
Page 122
Commissioning Proline Promass F 300 EtherNet/IP Configuring the switch output Navigation «Setup» menu → Pulse/frequency/switch output ‣ Pulse/frequency/switch output 1 to n Operating mode → 122 → 122 Terminal number Signal mode → 123 Switch output function →… -
Page 123
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Signal mode – Select the signal mode for the • Passive Passive PFS output. • Active Switch output function The Switch option is selected Select function for switch •… -
Page 124
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Assign limit • The Switch option is Select process variable for limit • Mass flow Mass flow selected in the Operating function. • Volume flow mode parameter. -
Page 125: 10.5.10 Configuring The Relay Output
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Switch-on value • In the Operating mode Enter measured value for the Signed floating-point Country-specific: parameter, the Switch switch-on point. number • 0 kg/h option is selected.
-
Page 126
Commissioning Proline Promass F 300 EtherNet/IP Assign status → 127 Switch-off value → 127 Switch-on value → 127 Failure mode → 128 Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Relay output function –… -
Page 127
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Assign limit In the Relay output function Select process variable for limit • Mass flow Mass flow parameter, the Limit option is function. • Volume flow selected. -
Page 128: 10.5.11 Configuring The Local Display
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Switch-on delay In the Relay output function Define delay for the switch-on 0.0 to 100.0 s 0.0 s parameter, the Limit option is of status output.
-
Page 129
Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry Format display A local display is provided. Select how measured values • 1 value, max. size 1 value, max. size are shown on the display. -
Page 130
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 1 display A local display is provided. Select the measured value that • Mass flow Mass flow is shown on the local display. • Volume flow •… -
Page 131
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Current output 1 • Current output 2 • Current output 3 • Pressure 0% bargraph value 1 A local display is provided. Enter 0% value for bar graph… -
Page 132
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 2 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •… -
Page 133
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation… -
Page 134
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 3 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •… -
Page 135
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation… -
Page 136
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry 100% bargraph value 3 A selection was made in the Enter 100% value for bar Signed floating-point Value 3 display parameter. graph display. number… -
Page 137
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry Value 4 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •… -
Page 138
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation… -
Page 139: 10.5.12 Configuring The Low Flow Cut Off
Proline Promass F 300 EtherNet/IP Commissioning 10.5.12 Configuring the low flow cut off The Low flow cut off wizard systematically guides the user through all the parameters that must be set to configure low flow cut off. Navigation «Setup» menu → Low flow cut off ‣…
-
Page 140: 10.5.13 Configuring The Partial Filled Pipe
Commissioning Proline Promass F 300 EtherNet/IP 10.5.13 Configuring the partial filled pipe detection The Partial filled pipe detection wizard guides you systematically through all parameters that have to be set for configuring the monitoring of the pipe filling. Navigation «Setup» menu → Partially filled pipe detection ‣…
-
Page 141: Advanced Settings
Proline Promass F 300 EtherNet/IP Commissioning 10.6 Advanced settings The Advanced setup submenu together with its submenus contains parameters for specific settings. Navigation to the «Advanced setup» submenu X X X X X X X 20.50 0104-1 Main menu Display language English Display/operat.
-
Page 142: Using The Parameter To Enter The Access Code
Commissioning Proline Promass F 300 EtherNet/IP ‣ Totalizer 1 to n → 144 ‣ Display → 147 ‣ WLAN settings → 158 ‣ Concentration ‣ Heartbeat setup ‣ Configuration backup → 160 ‣ → 161 Administration 10.6.1…
-
Page 143: Carrying Out A Sensor Adjustment
Proline Promass F 300 EtherNet/IP Commissioning Linear expansion coefficient → 143 Square expansion coefficient → 143 Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Corrected volume flow calculation – Select reference density for •…
-
Page 144: Configuring The Totalizer
Commissioning Proline Promass F 300 EtherNet/IP Navigation «Setup» menu → Advanced setup → Sensor adjustment ‣ Sensor adjustment Installation direction → 144 ‣ → 144 Zero point adjustment Parameter overview with brief description Parameter Description Selection Factory setting…
-
Page 145
Proline Promass F 300 EtherNet/IP Commissioning Navigation «Setup» menu → Advanced setup → Totalizer 1 to n ‣ Totalizer 1 to n Assign process variable → 145 → 145 Unit totalizer 1 to n Totalizer operation mode → 146 Failure mode →… -
Page 146
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection Factory setting Totalizer operation mode One of the following options is Select totalizer calculation • Net flow total Net flow total selected in the Assign process mode. • Forward flow total variable parameter •… -
Page 147: Carrying Out Additional Display Configurations
Proline Promass F 300 EtherNet/IP Commissioning 10.6.5 Carrying out additional display configurations In the Display submenu you can set all the parameters associated with the configuration of the local display. Navigation «Setup» menu → Advanced setup → Display ‣ Display Format display →…
-
Page 148
Commissioning Proline Promass F 300 EtherNet/IP Separator → 158 Backlight → 158… -
Page 149
Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry Format display A local display is provided. Select how measured values • 1 value, max. size 1 value, max. size are shown on the display. -
Page 150
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 1 display A local display is provided. Select the measured value that • Mass flow Mass flow is shown on the local display. • Volume flow •… -
Page 151
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Current output 1 • Current output 2 • Current output 3 • Pressure 0% bargraph value 1 A local display is provided. Enter 0% value for bar graph… -
Page 152
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 2 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •… -
Page 153
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation… -
Page 154
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 3 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •… -
Page 155
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation… -
Page 156
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 4 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •… -
Page 157
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation… -
Page 158: Wlan Configuration
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Header A local display is provided. Select header contents on local • Device tag Device tag display. • Free text Header text In the Header parameter, the Enter display header text.
-
Page 159
Proline Promass F 300 EtherNet/IP Commissioning WLAN IP address → 159 WLAN passphrase → 159 Assign SSID name → 159 SSID name → 160 Connection state → 160 Received signal strength → 160 Parameter overview with brief description… -
Page 160: Configuration Management
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry / User interface SSID name • The User-defined option is Enter the user-defined SSID Max. 32-digit EH_device selected in the Assign SSID name (max. 32 characters). character string designation_last 7 name parameter.
-
Page 161: Using Parameters For Device Administration
Proline Promass F 300 EtherNet/IP Commissioning Parameter Description User interface / Selection Factory setting Configuration management Select action for managing the device data in • Cancel Cancel the HistoROM backup. • Execute backup • Restore • Compare • Clear backup data Backup state Shows the current status of data saving or •…
-
Page 162
Commissioning Proline Promass F 300 EtherNet/IP ‣ Reset access code → 162 Device reset → 163 Using the parameter to define the access code Navigation «Setup» menu → Advanced setup → Administration → Define access code ‣ Define access code Define access code →… -
Page 163: Simulation
Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Description User interface / User entry Factory setting Operating time Indicates how long the device has been in Days (d), hours (h), minutes – operation. (m) and seconds (s) Reset access code Reset access code to factory settings.
-
Page 164
Commissioning Proline Promass F 300 EtherNet/IP Value current input 1 to n → 166 Current output 1 to n simulation → 166 Value current output 1 to n → 166 Frequency output simulation 1 to n → 166 Frequency value 1 to n →… -
Page 165
Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry / User interface Assign simulation process variable – Select a process variable for • Off the simulation process that is • Mass flow activated. -
Page 166
Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry / User interface Status input simulation – Switch simulation of the status • Off input on and off. • On Input signal level In the Status input simulation Select the signal level for the •… -
Page 167: Protecting Settings From Unauthorized
Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry / User interface Device alarm simulation – Switch the device alarm on and • Off off. • On Diagnostic event category – Select a diagnostic event • Sensor Process category.
-
Page 168
A reset code must be entered for this purpose. The user-specific access code can then be defined again afterwards. Via Web browser, FieldCare, DeviceCare (via CDI-RJ45 service interface), fieldbus For a reset code, contact your Endress+Hauser service organization. 1. Navigate to the Reset access code parameter (→ 163). -
Page 169: Write Protection Via Write Protection
Proline Promass F 300 EtherNet/IP Commissioning 2. Enter the reset code. The access code has been reset to the factory setting 0000. It can be redefined → 167. 10.8.2 Write protection via write protection switch Unlike parameter write protection via a user-specific access code, this allows write access to the entire operating menu — except for the «Contrast display»…
-
Page 170: Operation
Operation Proline Promass F 300 EtherNet/IP Operation 11.1 Reading the device locking status Device active write protection: Locking status parameter Operation → Locking status Function scope of the «Locking status» parameter Options Description None The access status displayed in the Access status parameter applies → 64. Only appears on local display.
-
Page 171: Measured Variables» Submenu
Proline Promass F 300 EtherNet/IP Operation ‣ Output values → 175 ‣ Totalizer → 173 11.4.1 «Measured variables» submenu The Measured variables submenu contains all the parameters needed to display the current measured values for each process variable.
-
Page 172
Operation Proline Promass F 300 EtherNet/IP Parameter overview with brief description Parameter Prerequisite Description User interface Mass flow – Displays the mass flow currently Signed floating-point measured. number Dependency The unit is taken from the Mass flow unit parameter (→ 102). -
Page 173: Totalizer» Submenu
Proline Promass F 300 EtherNet/IP Operation Parameter Prerequisite Description User interface Target mass flow With the following conditions: Displays the target fluid mass flow Signed floating-point • Order code for «Application package», currently measured. number option ED «Concentration» Dependency • The WT-% option or the User conc.
-
Page 174
Operation Proline Promass F 300 EtherNet/IP Navigation «Diagnostics» menu → Measured values → Input values ‣ Input values ‣ Current input 1 to n → 174 ‣ → 174 Status input 1 to n Input values of current input The Current input 1 to n submenu contains all the parameters needed to display the current measured values for every current input. -
Page 175: Output Values
Proline Promass F 300 EtherNet/IP Operation Parameter overview with brief description Parameter Description User interface Value status input Shows the current input signal level. • High • Low 11.4.4 Output values The Output values submenu contains all the parameters needed to display the current measured values for every output.
-
Page 176
Operation Proline Promass F 300 EtherNet/IP Output values for pulse/frequency/switch output The Pulse/frequency/switch output 1 to n submenu contains all the parameters needed to display the current measured values for every pulse/frequency/switch output. Navigation «Diagnostics» menu → Measured values → Output values → Pulse/frequency/switch output 1 to n ‣… -
Page 177: Adapting The Measuring Device To The Process
Proline Promass F 300 EtherNet/IP Operation Parameter overview with brief description Parameter Description User interface Switch status Shows the current relay switch status. • Open • Closed Switch cycles Shows number of all performed switch cycles. Positive integer Max. switch cycles number Shows the maximal number of guaranteed switch cycles.
-
Page 178: Function Scope Of The «Control Totalizer» Parameter
Operation Proline Promass F 300 EtherNet/IP Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry Control Totalizer 1 to n One of the following options is Control totalizer value. • Totalize Totalize selected in the Assign process •…
-
Page 179: Showing Data Logging
Proline Promass F 300 EtherNet/IP Operation 11.7 Showing data logging The Extended HistoROM application package must be enabled in the device (order option) for the Data logging submenu to appear. This contains all the parameters for the measured value history.
-
Page 180
Operation Proline Promass F 300 EtherNet/IP Logging delay → 183 Data logging control → 183 Data logging status → 183 Entire logging duration → 183 ‣ Display channel 1 ‣ Display channel 2 ‣ Display channel 3 ‣… -
Page 181
Proline Promass F 300 EtherNet/IP Operation Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry / User interface Assign channel 1 The Extended HistoROM Assign a process variable to • Off application package is logging channel. • Mass flow available. -
Page 182
Operation Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry / User interface • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation damping fluctuation 1 •… -
Page 183
Proline Promass F 300 EtherNet/IP Operation Parameter Prerequisite Description Selection / User Factory setting entry / User interface Logging delay In the Data logging Enter the time delay for 0 to 999 h parameter, the Not measured value logging. overwriting option is selected. Data logging control… -
Page 184: Diagnostics And Troubleshooting
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.1 General troubleshooting For local display Error Possible causes Solution Local display dark and no output Supply voltage does not match the Apply the correct supply voltage . signals value indicated on the nameplate.
-
Page 185
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting For output signals Error Possible causes Solution Signal output outside the valid Main electronics module is Order spare part → 217. range defective. Device shows correct value on local Configuration error… -
Page 186
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Error Possible causes Solution Apart from the active network • Make sure that no other network connection to the measuring device, connections are established by other network connections are also the computer (also no WLAN) being used. -
Page 187: Diagnostic Information Via Light Emitting
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Error Possible causes Solution Operation with FieldCare or Firewall of computer or network is Depending on the settings of the DeviceCare via CDI-RJ45 service preventing communication firewall used on the computer or in…
-
Page 188
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Color Meaning The EtherNet/IP address of the device has been assigned twice. Flashing red EtherNet/IP connection is in the «time out» mode. Flashing red/green The device restarts/self-test. Port 1 active: Not connected or no connection established. -
Page 189: Diagnostic Information On Local Display
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.3 Diagnostic information on local display 12.3.1 Diagnostic message Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic message in alternation with the operational display. Operational display in alarm condition…
-
Page 190
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic behavior Symbol Meaning Alarm • Measurement is interrupted. • Signal outputs and totalizers assume the defined alarm condition. • A diagnostic message is generated. Warning Measurement is resumed. The signal outputs and totalizers are not affected. A diagnostic message is generated. -
Page 191: Calling Up Remedial Measures
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.3.2 Calling up remedial measures X X X X X X X X X X X X X X 20.50 S801 Supply voltage Menu Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2…
-
Page 192: Diagnostic Information In The Web Browser
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP 12.4 Diagnostic information in the Web browser 12.4.1 Diagnostic options Any faults detected by the measuring device are displayed in the Web browser on the home page once the user has logged on.
-
Page 193: Calling Up Remedy Information
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.4.2 Calling up remedy information Remedy information is provided for every diagnostic event to ensure that problems can be rectified quickly. These measures are displayed in red along with the diagnostic event and the related diagnostic information.
-
Page 194: Calling Up Remedy Information
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Diagnostic code Diagnostic Diagnostic Status signal Short text behavior number ↓ ↓ ↓ Example Process limit A0013962 A0013958 NAMUR 3-digit number NE 107 12.5.2 Calling up remedy information Remedy information is provided for every diagnostic event to ensure that problems can be rectified quickly: •…
-
Page 195: Adapting The Diagnostic Information
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.7 Adapting the diagnostic information 12.7.1 Adapting the diagnostic behavior Each item of diagnostic information is assigned a specific diagnostic behavior at the factory. The user can change this assignment for specific diagnostic information in the Diagnostic behavior submenu.
-
Page 196
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 062 Sensor connection faulty 1. Check or replace sensor • 0x10000DB electronic module (ISEM) • 0x10000DC 2. If available: Check connection •… -
Page 197: Diagnostic Of Electronic
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 144 Measuring error too high 1. Check or change sensor 0x10001C7 2. Check process conditions Status signal Diagnostic behavior [from the…
-
Page 198
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 262 Sensor electronic connection faulty 1. Check or replace connection 0x1000149 cable between sensor electronic module (ISEM) and main Status signal… -
Page 199
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 276 I/O module 1 to n faulty 1. Restart device • 0x100007B 2. Change I/O module • 0x1000081 Status signal Diagnostic behavior… -
Page 200
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 372 Sensor electronic (ISEM) faulty 1. Restart device • 0x10000A1 2. Check if failure recurs • 0x10000C7 3. Replace sensor electronic module •… -
Page 201: Diagnostic Of Configuration
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 383 Memory content 1. Restart device 0x100016E 2. Delete T-DAT via ‘ R eset device’ parameter Status signal 3. Replace T-DAT…
-
Page 202
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 412 Processing download Download active, please wait 0x2000204 Status signal Diagnostic behavior Warning Diagnostic information Remedy instructions Coding of diagnostic information (hex) -
Page 203
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 443 Pulse output 1 to n 1. Check process • 0x800008C 2. Check pulse output settings • 0x8000121 Status signal Diagnostic behavior… -
Page 204
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 491 Current output 1 to n simulation Deactivate simulation 0x200000E Status signal Diagnostic behavior Warning Diagnostic information Remedy instructions Coding of diagnostic… -
Page 205: Diagnostic Of Process
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 520 I/O 1 to n hardware configuration invalid 1. Check I/O hardware 0x1000276 configuration 2. Replace wrong I/O module Status signal 3.
-
Page 206
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 830 Sensor temperature too high Reduce ambient temp. around the 0x80000C0 sensor housing Status signal Diagnostic behavior [from the Warning factory] Diagnostic behavior can be changed. -
Page 207
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 834 Process temperature too high Reduce process temperature 0x80000C5 Status signal Diagnostic behavior [from the Warning factory] Diagnostic behavior can be changed. -
Page 208
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 910 Tubes not oscillating 1. Check electronic 0x1000050 2. Inspect sensor Status signal Diagnostic behavior Alarm Diagnostic information Remedy instructions Coding of diagnostic… -
Page 209: Pending Diagnostic Events
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 943 API pressure out of specification 1. Check process pressure with 0x800037F selected API commodity group 2. Check API related parameters…
-
Page 210: 12.10 Diagnostic List
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Operating time from restart → 210 Operating time → 210 Parameter overview with brief description Parameter Prerequisite Description User interface Actual diagnostics A diagnostic event has occurred. Shows the current occured diagnostic…
-
Page 211: 12.11 Event Logbook
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.11 Event logbook 12.11.1 Reading out the event logbook A chronological overview of the event messages that have occurred is provided in the Events list submenu. Navigation path Diagnostics menu → Event logbook submenu → Event list / ../Eventlist…
-
Page 212: 12.11.3 Overview Of Information Events
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP 12.11.3 Overview of information events Unlike a diagnostic event, an information event is displayed in the event logbook only and not in the diagnostic list. Info number Info name I1000 ———(Device ok)
-
Page 213: 12.12 Resetting The Measuring Device
Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Info number Info name I1514 Upload started I1515 Upload finished I1618 I/O module 2 replaced I1619 I/O module 3 replaced I1621 I/O module 4 replaced I1622 Calibration changed I1624 Reset all totalizers…
-
Page 214: 12.13 Device Information
Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP 12.13 Device information The Device information submenu contains all parameters that display different information for device identification. Navigation «Diagnostics» menu → Device information ‣ Device information Device tag → 214 Serial number →…
-
Page 215: 12.14 Firmware History
«Manufacturer’ s information» document. The manufacturer’ s information is available: • In the Download Area of the Endress+Hauser web site: www.endress.com → Downloads • Specify the following details: –…
-
Page 216: Maintenance
→ 238. 13.2 Measuring and test equipment Endress+Hauser offers a wide variety of measuring and test equipment, such as W@M or device tests. Your Endress+Hauser Sales Center can provide detailed information on the services. List of some of the measuring and testing equipment: → 219 13.3…
-
Page 217: Repairs
• The measuring devices have a modular design. • Spare parts are grouped into logical kits with the associated Installation Instructions. • Repairs are carried out by Endress+Hauser Service or by appropriately trained customers. • Certified devices can only be converted to other certified devices by Endress+Hauser Service or at the factory.
-
Page 218: Disposal
Repairs Proline Promass F 300 EtherNet/IP 14.5 Disposal 14.5.1 Removing the measuring device 1. Switch off the device. WARNING Danger to persons from process conditions. ‣ Beware of hazardous process conditions such as pressure in the measuring device, high temperatures or aggressive fluids.
-
Page 219: Accessories
Various accessories, which can be ordered with the device or subsequently from Endress +Hauser, are available for the device. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
-
Page 220: For The Sensor
Is used to stabilize the temperature of the fluids in the sensor. Water, water vapor and other non-corrosive liquids are permitted for use as fluids. If using oil as a heating medium, please consult with Endress+Hauser. Heating jackets cannot be used with sensors fitted with a rupture disk.
-
Page 221: System Components
For details, see Operating Instructions BA00027S and BA00059S DeviceCare Tool for connecting and configuring Endress+Hauser field devices. For details, see Innovation brochure IN01047S 15.4 System components…
-
Page 222: Technical Data
Technical data Proline Promass F 300 EtherNet/IP Technical data 16.1 Application The measuring device is suitable for flow measurement of liquids and gases only. Depending on the version ordered, the measuring device can also measure potentially explosive, flammable, poisonous and oxidizing media.
-
Page 223: Input
Proline Promass F 300 EtherNet/IP Technical data 16.3 Input Measured variable Direct measured variables • Mass flow • Density • Temperature Calculated measured variables • Volume flow • Corrected volume flow • Reference density Measuring range Measuring ranges for liquids Measuring range full scale values …
-
Page 224
• Operating pressure to increase accuracy (Endress+Hauser recommends the use of a pressure measuring device for absolute pressure, e.g. Cerabar M or Cerabar S) •… -
Page 225
Proline Promass F 300 EtherNet/IP Technical data Current input 0/4 to 20 mA Current input 0/4 to 20 mA (active/passive) Current span • 4 to 20 mA (active) • 0/4 to 20 mA (passive) Resolution 1 µA Voltage drop Typically: 0.6 to 2 V for 3.6 to 22 mA (passive) Maximum input voltage ≤… -
Page 226: Output
Technical data Proline Promass F 300 EtherNet/IP 16.4 Output Output signal EtherNet/IP Standards In accordance with IEEE 802.3 Current output 0/4 to 20 mA Current output 0/4 to 20 mA Maximum output values 22.5 mA Current span Can be set to: •…
-
Page 227
Proline Promass F 300 EtherNet/IP Technical data Maximum output current 22.5 mA (active) Open-circuit voltage DC 28.8 V (active) Pulse width Adjustable: 0.05 to 2 000 ms Maximum pulse rate 10 000 Impulse/s Pulse value Adjustable Assignable measured • Mass flow variables •… -
Page 228
Technical data Proline Promass F 300 EtherNet/IP Relay output Function Switch output Version Relay output, galvanically isolated Switching behavior Can be set to: • NO (normally open), factory setting • NC (normally closed) Maximum switching • DC 30 V, 0.1 A capacity (passive) •… -
Page 229
Proline Promass F 300 EtherNet/IP Technical data Current output 0/4 to 20 mA 4 to 20 mA Failure mode Choose from: • 4 to 20 mA in accordance with NAMUR recommendation NE 43 • 4 to 20 mA in accordance with US •… -
Page 230
Technical data Proline Promass F 300 EtherNet/IP Interface/protocol • Via digital communication: EtherNet/IP • Via service interface – CDI-RJ45 service interface – WLAN interface Plain text display With information on cause and remedial measures Web server Plain text display With information on cause and remedial measures… -
Page 231: Power Supply
Proline Promass F 300 EtherNet/IP Technical data Configuration of the device • DIP switches on the electronics module for IP addressing (last octet) address • DHCP • Manufacturer-specific software (FieldCare) • Add-on Profile Level 3 for Rockwell Automation control systems •…
-
Page 232: Performance Characteristics
Technical data Proline Promass F 300 EtherNet/IP terminals Spring-loaded terminals: Suitable for strands and strands with ferrules. Conductor cross-section 0.2 to 2.5 mm (24 to 12 AWG). Cable entries • Cable gland: M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in) •…
-
Page 233
Proline Promass F 300 EtherNet/IP Technical data Density (cryogenic liquids) Order code for «Measuring tube material», option LA ±0.05 g/cm³ Temperature ±0.5 °C ± 0.005 · T °C (±0.9 °F ± 0.003 · (T – 32) °F) Zero point stability… -
Page 234
Technical data Proline Promass F 300 EtherNet/IP SI units 1:10 1:20 1:50 1:100 1:500 [mm] [kg/h] [kg/h] [kg/h] [kg/h] [kg/h] [kg/h] 2 000 6 500 18 000 1 800 45 000 4 500 2 250 70 000 7 000 3 500… -
Page 235
Proline Promass F 300 EtherNet/IP Technical data Base repeatability Design fundamentals → 237 Mass flow and volume flow (liquids) ±0.025 % o.r. (PremiumCal, for mass flow) ±0.05 % o.r. Mass flow (cryogenic liquids) Order code for «Measuring tube material», option LA ±0.175 % % o.r. -
Page 236
Technical data Proline Promass F 300 EtherNet/IP Wide-range density specification (special density calibration) If the process temperature is outside the valid range (→ 232) the measured error is ±0.00005 g/cm /°C (±0.000025 g/cm /°F) [kg/m ] [°C] [° ] F… -
Page 237: Installation
Proline Promass F 300 EtherNet/IP Technical data Design fundamentals o.r. = of reading, o.f.s. = of full scale value BaseAccu = base accuracy in % o.r., BaseRepeat = base repeatability in % o.r. MeasValue = measured value; ZeroPoint = zero point stability…
-
Page 238: Process
Technical data Proline Promass F 300 EtherNet/IP Temperature tables Observe the interdependencies between the permitted ambient and fluid temperatures when operating the device in hazardous areas. For detailed information on the temperature tables, see the separate document entitled «Safety Instructions» (XA) for the device.
-
Page 239
Proline Promass F 300 EtherNet/IP Technical data High-temperature version –50 to +350 °C (–58 to +662 °F) For nominal diameters DN 25 (1″), DN 50 (2″) and DN 80 (3″) Order code for «Measuring tube mat., wetted surface», option TT, Low-temperature version –196 to +150 °C (–320 to +302 °F) -
Page 240
Technical data Proline Promass F 300 EtherNet/IP Density 0 to 5 000 kg/m (0 to 312 lb/cf) Pressure-temperature An overview of the pressure-temperature ratings for the process connections is ratings provided in the «Technical Information» document Secondary containment For the Standard version with the temperature range –50 to +150 °C (–58 to +302 °F), the sensor housing is filled with dry nitrogen gas and protects the electronics and mechanics inside. -
Page 241
Proline Promass F 300 EtherNet/IP Technical data If the sensor is to be purged with gas (gas detection), it should be equipped with purge connections. Do not open the purge connections unless the containment can be filled immediately with a dry, inert gas. Use only low pressure to purge. Maximum pressure: 5 bar (72.5 psi). -
Page 242: 16.10 Mechanical Construction
Technical data Proline Promass F 300 EtherNet/IP 16.10 Mechanical construction Design, dimensions For the dimensions and installation lengths of the device, see the «Technical Information» document, «Mechanical construction» section. Weight All values (weight exclusive of packaging material) refer to devices with EN/DIN PN 40 flanges.
-
Page 243
Proline Promass F 300 EtherNet/IP Technical data Materials Transmitter housing Order code for «Housing»: • Option A «Aluminum, coated»: aluminum, AlSi10Mg, coated • Option B «Stainless, hygienic»: stainless steel, 1.4404 (316L) • Option L «Cast, stainless»: cast, stainless steel, 1.4409 (CF3M) similar to 316L Window material Order code for «Housing»:… -
Page 244
Technical data Proline Promass F 300 EtherNet/IP Order code for «Housing», option L «Cast, stainless» The various cable entries are suitable for hazardous and non-hazardous areas. Cable entry/cable gland Material Cable gland M20 × 1.5 Stainless steel, 1.4404 (316L) Adapter for cable entry with internal thread G ½»… -
Page 245
Proline Promass F 300 EtherNet/IP Technical data High-temperature version Flanges according to EN 1092-1 (DIN2501) / according to ASME B 16.5 / as per JIS B2220: – Stainless steel, 1.4404 (F316/F316L) – Alloy C22, 2.4602 (UNS N06022) List of all available process connections → 245… -
Page 246: 16.11 Operability
Technical data Proline Promass F 300 EtherNet/IP 16.11 Operability Languages Can be operated in the following languages: • Via local operation English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Chinese, Japanese, Korean, Bahasa (Indonesian), Vietnamese, Czech, Swedish • Via Web browser…
-
Page 247
Proline Promass F 300 EtherNet/IP Technical data Via remote display and operating module DKX001 The remote display and operating module DKX001 is available as an optional extra → 219. • The remote display and operating module DKX001 is only available for the following housing versions, order code for «Housing»:… -
Page 248
Technical data Proline Promass F 300 EtherNet/IP Dimensions Information on the dimensions: «Mechanical construction» section of the «Technical Information» document. Remote operation → 73 Service interface → 74 Supported operating tools Different operating tools can be used for local or remote access to the measuring device. -
Page 249
Proline Promass F 300 EtherNet/IP Technical data Supported functions Data exchange between the operating unit (such as a notebook for example) and the measuring device: – Upload the configuration from the measuring device (XML format, configuration backup) – Save the configuration to the measuring device (XML format, restore configuration) –… -
Page 250
Technical data Proline Promass F 300 EtherNet/IP Data backup Automatic • The most important device data (sensor and transmitter) are automatically saved in the DAT modules • If the transmitter or measuring device is replaced: once the T-DAT containing the… -
Page 251: 16.12 Certificates And Approvals
EU Directives. These are listed in the corresponding EU Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. C-Tick symbol The measuring system meets the EMC requirements of the «Australian Communications and Media Authority (ACMA)».
-
Page 252
For detailed information on the radio approval, see the Special Documentation → 256 Additional certification Marine approval Currently valid certificates are available: • In the Download Area of the Endress+Hauser Internet site: www.endress.com → Downloads • Specify the following details: Search area: Approval & Certificates→ Marine CRN approval Some device versions have CRN approval. -
Page 253: 16.13 Application Packages
The application packages can be ordered with the device or subsequently from Endress+Hauser. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
-
Page 254
Technical data Proline Promass F 300 EtherNet/IP Diagnostics functions Package Description Extended HistoROM Comprises extended functions concerning the event log and the activation of the measured value memory. Event log: Memory volume is extended from 20 message entries (standard version) to up to 100 entries. -
Page 255: 16.14 Accessories
• The W@M Device Viewer : Enter the serial number from the nameplate (www.endress.com/deviceviewer) • The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2-D matrix code (QR code) on the nameplate. Standard documentation…
-
Page 256
Technical data Proline Promass F 300 EtherNet/IP Device-dependent Safety instructions additional documentation Safety instructions for electrical equipment for hazardous areas. Contents Documentation code ATEX/IECEx Ex d/Ex de XA01405D ATEX/IECEx Ex ec XA01439D cCSAus XP XA01373D cCSAus Ex d/ Ex de… -
Page 257: Index
Proline Promass F 300 EtherNet/IP Index Index 0 … 9 Explanation ……61 Current consumption .
-
Page 258
Index Proline Promass F 300 EtherNet/IP Display area Field of application For operational display ….. 55 Residual risks ……11 In the navigation view . -
Page 259
Proline Promass F 300 EtherNet/IP Index System pressure ……26 Mounting dimensions Thermal insulation ……26 see Installation dimensions Vibrations . -
Page 260
Index Proline Promass F 300 EtherNet/IP Current output ……109 Current output (Wizard) ….109 Radio approval . -
Page 261
Proline Promass F 300 EtherNet/IP Index Sensor adjustment ….. . . 143 Value current output 1 to n ….175 Simulation . -
Page 262
Index Proline Promass F 300 EtherNet/IP Troubleshooting General ……. 184 TSE/BSE certificate of suitability . -
Page 264
The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currently in ef- fect. Otherwise, the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect. Contact information is subject to change.
Download Operating instructions manual of Endress+Hauser Proline Promass F 300 Measuring Instruments for Free or View it Online on All-Guides.com.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
MANUAL
BA01807O/06/EN/01.17
Valid as of version 01.00 zz (Device rmware)
71382409
Proline Promass F 300 Coriolis Flowmeter
EtherNet/IP
Operating Instructions Manual
K
e
e
p
c
o
v
e
r
h
t
i
g
t
w
h
i
l
e
S
p
a
n
n
u
n
g
ö
f
f
n
e
n