Pcc3201 руководство по эксплуатации

  • 8/18/2019 Operator Manual PCC 3201

    1/90

    English – Original Instructions 11-2009 0908-0104 (Issue 4)

    Operator Manual

    with PowerCommand™ Control 3201

  • 8/18/2019 Operator Manual PCC 3201

    2/90

  • 8/18/2019 Operator Manual PCC 3201

    3/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    FOREWORD

    The purpose of this manual is to provide the users with sound,
    general information. It is for guidance andassistance with
    recommendations for correct and safe procedures. Cummins Power
    Generation Limited

    cannot accept any liability whatsoever for problems arising as a
    result of following recommendations in thismanual.

    The information contained within the manual is based on
    information available at the time of going to print. Inline with
    Cummins Power Generation Limited policy of continuous development
    and improvement,information may change at any time without notice.
    The users should therefore ensure that beforecommencing any work,
    they have the latest information available.

    Users are respectfully advised that it is their responsibility
    to employ competent persons to carry out anyinstallation work in
    the interests of good practice and safety. Consult your Authorised
    Distributor for furtherinstallation information. It is essential
    that the utmost care is taken with the application, installation
    andoperation of any diesel engine due to their potentially
    dangerous nature. Careful reference should also bemade to other
    Cummins Power Generation Limited literature, in particular the
    Health and Safety Manual(0908-0110-00) and the Engine Manual.

    Should you require further assistance contact: —

    Cummins Power Generation1400 73

    rd Avenue NE

    MinneapolisMN 55432USA

    Tel:+1 (763) 574-5000

    Fax:+1 (763) 574-5298

    e-mail:[email protected] 

    Cummins Power GenerationColumbus AvenueManston
    ParkManstonRamsgateKent CT12 5BFUnited Kingdom

    Tel:+44 (0) 1843 255000

    Fax:+44 (0) 1843 255902

    e-mail:[email protected] 

    Cummins Power Generation10 Toh Guan Road #07-01TT International
    TradeparkSingapore 608838

    Tel: (65) 6417 2388

    Fax:(65) 6417 2399

    e-mail: [email protected] 

    Web: www.cumminspower.com 
    Web: www.cumminspower.com 
    Web: www.cumminspower.com 

    Cummins Power Generation35A/1/2, ErandawanaPune 411 038India

    Tel.: (91 020) 3024 8600Fax: (91 020) 6602 8090

    e-mail:[email protected] 

    Cummins Power GenerationRua Jati, 310 — CumbicaGuarulhos
    –SPBrazilCEP: 07180-900

    Tel.: (55 11) 2186 4195Fax: (55 11) 2186 4729

    e-mail: [email protected]  

    Web: www.cumminspower.com 
    Web: www.cumminspower.com 

    mailto:[email protected]:[email protected]:[email protected]://www.cumminspower.com/http://www.cumminspower.com/http://www.cumminspower.com/http://www.cumminspower.com/http://www.cumminspower.com/mailto:[email protected]:[email protected]://www.cumminspower.com/http://www.cumminspower.com/http://www.cumminspower.com/http://www.cumminspower.com/http://www.cumminspower.com/mailto:[email protected]:[email protected]://www.cumminspower.com/http://www.cumminspower.com/http://www.cumminspower.com/mailto:cpg.apmktg@cummins.commailto:[email protected]:[email protected]

  • 8/18/2019 Operator Manual PCC 3201

    4/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    This is a Blank Page

  • 8/18/2019 Operator Manual PCC 3201

    5/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Contents Page i

    CONTENTS

    Section Title Page

    Schedule of Abbreviations
    ……………………………………………………………………………………………………………….i 

    1  Safety 1-1 1.1  Warning, Caution and Note
    Styles Used In This
    Manual……………………………………………………
    1-1 1.2 
    Warnings…………………………………………………………………………………………………………………….
    1-1 1.3  General Information
    ……………………………………………………………………………………………………..
    1-1 1.4  Generator Plant Safety
    Code…………………………………………………………………………………………
    1-1 


    Introduction……………………………………………………………………………………………………………………..2-1 2.1 
    General 2-1 2.2  Generating Set
    Identification………………………………………………………………………………………….
    2-1 2.3   After Sales
    Services……………………………………………………………………………………………………..
    2-2 2.3.1  Maintenance
    ………………………………………………………………………………………………………….
    2-2 2.3.2

    Warranty
    ……………………………………………………………………………………………………………….
    2-2 

    2.3.3  Spares
    ………………………………………………………………………………………………………………….
    2-2 2.3.4  Overseas
    ………………………………………………………………………………………………………………
    2-2 2.3.5   Additional
    Literature………………………………………………………………………………………………..
    2-2 

    3  System
    Overview……………………………………………………………………………………………………………..
    3-1 3.1  Generator Components – Typical Generator Set
    ……………………………………………………………..
    3-1 3.1.1   AC Supply and Isolation
    ………………………………………………………………………………………….
    3-2 3.1.2  Control
    System………………………………………………………………………………………………………
    3-2 3.1.3 
    Engine…………………………………………………………………………………………………………………..3-2 3.1.4 
     Alternator
    ………………………………………………………………………………………………………………
    3-2 3.1.5  Generator Rating
    ……………………………………………………………………………………………………
    3-2 3.1.6  Generator Set
    Construction……………………………………………………………………………………..3-2 3.1.7

    Fuel
    System…………………………………………………………………………………………………………..
    3-3 

    3.1.8  Cooling
    System………………………………………………………………………………………………………
    3-3 3.1.9  Engine Exhaust (Option)
    …………………………………………………………………………………………
    3-3 3.1.10  DC Electrical
    System………………………………………………………………………………………………
    3-3 3.1.11   Alarm Module
    (Option)…………………………………………………………………………………………….
    3-4 3.1.12  Sensors/Senders
    ……………………………………………………………………………………………………
    3-4 3.2  Heaters 3-5 3.2.1  Heater Supply
    and Isolation
    …………………………………………………………………………………….
    3-5 3.2.2  Engine Heater
    (Option)……………………………………………………………………………………………
    3-5 3.2.3   Alternator Heater (Option)
    ……………………………………………………………………………………….
    3-5 3.2.4  Control Panel Heater
    (Option)………………………………………………………………………………….
    3-5 3.3  Mains Powered Battery Charger
    (Option)………………………………………………………………………..
    3-6 

    3.3.1 

    Operation………………………………………………………………………………………………………………
    3-6 

    3.3.2 

    Boost Charge
    (Option)…………………………………………………………………………………………….
    3-6 

    4  Control
    System………………………………………………………………………………………………………………..
    4-1 4.1  Control System
    Description……………………………………………………………………………………………
    4-1 4.1.1  Control Panel Power ON/OFF Modes
    ……………………………………………………………………….4-2 4.1.2 
    Control Panel — Front Panel
    ……………………………………………………………………………………..
    4-3 4.1.3  Control Panel — Operator Panel
    ………………………………………………………………………………..
    4-4 4.1.4  Control Panel — Switch
    Panel……………………………………………………………………………………
    4-4 4.2  Menu Display and
    Switches…………………………………………………………………………………………..
    4-6 4.2.1  Graphical
    Display……………………………………………………………………………………………………
    4-6 4.2.2  Menu
    Buttons…………………………………………………………………………………………………………
    4-6 4.3  Menu Units Selection
    ……………………………………………………………………………………………………
    4-7 

    4.3.1 

    Local/Remote
    Field…………………………………………………………………………………………………
    4-7 

    4.4 

    Main
    Menu…………………………………………………………………………………………………………………..
    4-8 

    4.4.1   Adjust Button
    …………………………………………………………………………………………………………
    4-8 

  • 8/18/2019 Operator Manual PCC 3201

    6/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page ii Contents

    4.4.2  Set-up Button
    …………………………………………………………………………………………………………4-8 4.4.3 
     _\_ Button (Paralleling applications
    only)……………………………………………………………………4-9 4.4.4 
    Power Trans Button (PTC applications
    only)………………………………………………………………4-9 4.5 
    Engine Data Submenus
    ………………………………………………………………………………………………4-10 4.6 
     Alternator Data
    Submenus…………………………………………………………………………………………..4-11 4.6.1 
    Voltage L–L and
    L–N…………………………………………………………………………………………….4-11 4.6.2

     Amps…………………………………………………………………………………………………………………..4-11 

    4.6.3  Frequency
    ……………………………………………………………………………………………………………4-11 4.6.4 
     AVR Duty Cycle
    ……………………………………………………………………………………………………4-11 4.6.5 
    kW, kVA and
    PF……………………………………………………………………………………………………4-11 4.7 
    Control Submenu
    ……………………………………………………………………………………………………….4-12 4.7.1 
    Local Control Submenu Function
    ……………………………………………………………………………4-12 4.7.2 
    Remote Control Submenu
    Functions……………………………………………………………………….4-13 4.7.3 
    Local/Remote Control Submenu
    Function………………………………………………………………..
    4-13 4.8  History/About
    Submenus……………………………………………………………………………………………..
    4-14 4.8.1 
    History…………………………………………………………………………………………………………………4-14 4.8.2 
     About…………………………………………………………………………………………………………………..4-14 4.8.3 
    Fault
    History…………………………………………………………………………………………………………
    4-14 

    4.9 

     Adjust
    Sub-menu………………………………………………………………………………………………………..4-16 

    4.10 

    Parallel Data Submenu
    ……………………………………………………………………………………………….4-17 

    4.10.1  Parallel Data Status Line
    ……………………………………………………………………………………….4-17 4.11 
    Password
    Menu………………………………………………………………………………………………………….4-18 4.12 
    Power Transfer Main
    Menu………………………………………………………………………………………….4-19 4.12.1 
    PTC Status
    Line……………………………………………………………………………………………………4-20 4.12.2 
    Utility (PWR TRAN) Submenus
    ………………………………………………………………………………4-21 4.12.3 
    Status (PWR TRAN)
    Submenus……………………………………………………………………………..
    4-22 4.12.4  Transfer Control (PWR TRAN)
    Submenu…………………………………………………………………
    4-23 4.12.5  Generator Set (PWR TRAN) Submenus
    ………………………………………………………………….4-24 

    5  Operation 5-1 5.1  Safety 5-1 

    5.2 

    Introduction………………………………………………………………………………………………………………….5-1 

    5.3 

    Maintenance………………………………………………………………………………………………………………..5-1 

    5.4  Operating
    Recommendations…………………………………………………………………………………………5-2 5.4.1 
    Running-in……………………………………………………………………………………………………………..5-2 5.4.2 
    No Load
    Operation………………………………………………………………………………………………….5-2 5.4.3 
    Exercise
    Period………………………………………………………………………………………………………
    5-2 5.4.4  Low Operating
    Temperatures…………………………………………………………………………………..5-2 5.4.5 
    High Operating Temperatures
    ………………………………………………………………………………….
    5-2 5.4.6  Operating Conditions for Prime, Standby and
    Continuous Power Ratings.
    …………………….5-3 5.4.7  De-Rating
    Factors…………………………………………………………………………………………………..
    5-4 5.5  Generator Set Operation
    ……………………………………………………………………………………………….5-5 5.5.1 
    Sequence of
    Operation……………………………………………………………………………………………5-5 5.6 
    Starting 5-5 

    5.6.1 

    Pre-start
    Checks…………………………………………………………………………………………………….5-6 5.6.2 
    Starting at Switch Panel (Manual Mode)
    ……………………………………………………………………
    5-8 

    5.6.3  Starting at Remote Operator Panel (Auto Mode)
    ………………………………………………………5-10 5.6.4 
    Starting from Remote Location (Switch or Device) (Auto
    Mode)…………………………………. 5-10 5.6.5 
    Exercise
    Start……………………………………………………………………………………………………….5-11 5.6.6 
    Cold Starting with
    Loads………………………………………………………………………………………..5-11 5.7 
    Running at Idle (Manual)
    ……………………………………………………………………………………………..5-12 5.8 
    Stopping
    ……………………………………………………………………………………………………………………5-13 5.8.1 
    Emergency Stop (Code 1434)
    ………………………………………………………………………………..
    5-13 5.8.2  Stopping at Switch Panel (Manual
    Mode)…………………………………………………………………5-13 5.8.3 
    Stopping at Remote Operator Panel (Auto
    Mode)……………………………………………………..
    5-13 5.8.4  Stopping from Remote Location (Switch or
    Device) (Auto
    Mode)………………………………..5-14 5.9 
    Optional Power Transfer Control (PTC)
    Operation………………………………………………………….5-15 

    5.9.1 

    PCC3201/PTC – Normal Operation Sequences
    ……………………………………………………….5-15 5.9.2 
    Test Switch
    ………………………………………………………………………………………………………….5-15 

  • 8/18/2019 Operator Manual PCC 3201

    7/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Contents Page iii


    Maintenance…………………………………………………………………………………………………………………….
    6-1 6.1  Locking the Generator Set Out of Service
    ……………………………………………………………………….6-2 6.1.1 
    Introduction……………………………………………………………………………………………………………
    6-2 6.1.2  Immobilising the Generator Set for Safe
    Working……………………………………………………….
    6-3 6.2  General
    ………………………………………………………………………………………………………………………
    6-3 6.3  Daily or Refuelling Maintenance
    Procedures……………………………………………………………………
    6-6 6.3.1

    General
    Information………………………………………………………………………………………………..
    6-6 

    6.3.2  Engine Operation
    Report…………………………………………………………………………………………
    6-6 6.4  Cooling
    System……………………………………………………………………………………………………………
    6-6 6.4.1  Coolant Level — Check
    …………………………………………………………………………………………….
    6-7 6.4.2  Cooling Fan —
    Inspect………………………………………………………………………………………………
    6-8 6.4.3  Drive Belt — Inspect
    …………………………………………………………………………………………………
    6-8 6.4.4  Radiator —
    Check…………………………………………………………………………………………………….
    6-8 6.5  Engine
    Oil……………………………………………………………………………………………………………………
    6-9 6.5.1  Engine Oil Level – Check
    ………………………………………………………………………………………..
    6-9 6.6  Fuel System
    ………………………………………………………………………………………………………………
    6-10 6.6.1  Fuel Level
    ……………………………………………………………………………………………………………
    6-10 6.6.2  Fuel/Water Separator — Drain
    …………………………………………………………………………………
    6-10 

    6.7 

    Fluid Containment
    ………………………………………………………………………………………………………
    6-11 

    6.8 

    Hoses and Fuel Lines —
    Check……………………………………………………………………………………..
    6-11 

    6.9  Exhaust
    System…………………………………………………………………………………………………………
    6-12 6.10  Generator Set Output — AC Electric
    System……………………………………………………………………
    6-12 6.11  DC Electrical System
    ………………………………………………………………………………………………….
    6-12 

    7  Troubleshooting
    ………………………………………………………………………………………………………………
    7-1 7.1 
    Introduction………………………………………………………………………………………………………………….
    7-1 7.2  Control Unit DC Power
    Supply……………………………………………………………………………………….
    7-1 7.3  Safety
    Considerations…………………………………………………………………………………………………..
    7-2 7.4  Fault
    Finding………………………………………………………………………………………………………………..
    7-3 7.5  Status Indicators
    ………………………………………………………………………………………………………….
    7-3 7.5.1  Not In Auto Indicator
    ……………………………………………………………………………………………….
    7-3 

    7.5.2 

    Shutdown Status
    Indicator……………………………………………………………………………………….
    7-3 

    7.5.3 

    Warning Status Indicator
    …………………………………………………………………………………………
    7-3 

    7.6  Reading Fault Codes
    ……………………………………………………………………………………………………
    7-4 7.6.1  Reading Fault Codes Using Graphical Display
    (Optional) ……………………………………………
    7-4 7.6.2  Reading Fault Codes Using Warning/Shutdown
    Indicators ………………………………………….
    7-4 7.7  Line Circuit Breaker
    (Optional)……………………………………………………………………………………….
    7-6 7.8  Control and Diagnostics Via Network or PC
    (Laptop)………………………………………………………..
    7-6 7.9  Fault Codes
    …………………………………………………………………………………………………………………
    7-6 7.9.1  Category A Fault Codes
    ………………………………………………………………………………………….
    7-6 7.9.2  Category B Fault Codes
    ………………………………………………………………………………………….
    7-6 7.9.3  Category C Fault
    Codes………………………………………………………………………………………….
    7-6 7.9.4  Category D Fault
    Codes………………………………………………………………………………………….
    7-6 7.9.5  Category E Fault Codes
    ………………………………………………………………………………………….
    7-6 

  • 8/18/2019 Operator Manual PCC 3201

    8/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page iv Contents

    CONTENTS (continued)

    Illustrations

    Figure Title Page

    Figure 2-1  Typical Generator Set Rating
    Plate…………………………………………………………………….
    2-1 Figure 3-1  Typical Generator Set (C450 to
    C550)………………………………………………………………..
    3-1 Figure 3-2   Alarm Module Front
    Panel…………………………………………………………………………………3-4 Figure
    4-1  Control Panel Assembly (Full Featured)
    ……………………………………………………………..
    4-3 Figure 4-2  Graphical Display and Menu Selection
    Buttons……………………………………………………
    4-6 Figure 4-3  Units
    Submenu………………………………………………………………………………………………..4-7 Figure
    4-4  System Control Main Menus A and B
    …………………………………………………………………
    4-8 Figure 4-5  Engine Data Sub-menus
    …………………………………………………………………………………4-10 Figure
    4-6   Alternator Data
    Sub-menus……………………………………………………………………………..4-11 Figure
    4-7  Local Control
    Sub-menu………………………………………………………………………………….
    4-12 

    Figure 4-8 

    Control
    Sub-menu………………………………………………………………………………………….4-13 Figure
    4-9  History/About Sub-menus
    ……………………………………………………………………………….4-15 

    Figure 4-10   Adjust
    Sub-menu……………………………………………………………………………………………4-16 Figure
    4-11  Bus Data
    Sub-menu……………………………………………………………………………………….4-17 Figure
    4-12  Password
    Menu……………………………………………………………………………………………..4-18 Figure
    4-13  Power Transfer Main
    Menu……………………………………………………………………………..4-19 Figure
    4-14  Utility
    Sub-menu…………………………………………………………………………………………….4-21 Figure
    4-15  Status (PWR TRANS)
    Submenus…………………………………………………………………….
    4-22 Figure 4-16  Transfer Control Submenus
    …………………………………………………………………………….4-23 Figure
    4-17  Genset
    Submenus………………………………………………………………………………………….4-24 Figure
    5-1  Normal Start/Run/Stop
    Sequences…………………………………………………………………….
    5-9 Figure 7-1  Front Control Panel (Full-Featured)
    ……………………………………………………………………
    7-5 

    Tables

    Table No. Title Page

    Table 5-1  Manual
    Run…………………………………………………………………………………………………..
    5-16 Table 5-2  Utility Power
    Fail…………………………………………………………………………………………….
    5-17 Table 5-3  Exercise with load
    ………………………………………………………………………………………….
    5-18 Table 7-1  Warning and Shutdown Fault Codes
    ………………………………………………………………….
    7-7 Table 7-2  Troubleshooting Procedures for Fault Codes
    ……………………………………………………
    7-10 

    Supplementary Publications

    The Supplementary Publications appropriate to your system will
    also be supplied with the system. Whereappropriate the
    corresponding Instruction Manual(s) will also be supplied with any
    accessory that you order.

    Title Publication No

    Lead Acid Battery
    ………………………………………………………………………………………………………..0908-0101-00Battery
    Charger
    ………………………………………………………………………………………………………..0908-0102-00Radiator
    Information
    ……………………………………………………………………………………………………….0908-0107-00Health
    and Safety (Diesel Generator
    sets)…………………………………………………………………………0908-0110-00

  • 8/18/2019 Operator Manual PCC 3201

    9/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Schedule of Abbreviations Page i

    Schedule of Abbreviations AC Alternating Current MCB
    Miniature Circuit Breaker

     ACB Air Circuit Breaker MCCB Moulded Case Circuit
    Breaker

     ACH Anti-Condensation Heaters MF Mains Failed ATS
    Automatic Transfer Switch MFSS Master First Start Sensor

     AVR Automatic Voltage Regulator MR Mains Returned

    MST Mains Sensing Transformer

    BHP Brake Horsepower MSU Mains Sensing Unit

    BMS Building Management System MV Medium Voltage

    BST Busbar Sensing Transformer

    NEC Neutral Earthing Contact

    CB Circuit Breaker 

    CCA Cold Cranking Amps PCC3201 PowerCommand™

     Control System

    CHP Combined Heat and Power PF Power Factor  

    COP Continuous Power Rating PFC Power Factor Controller

    CT Current Transformer PLC Programmable Logic
    Controller 

      PMG Permanent Magnet Generator  

    dB(A) Unit of noise level PRP Prime Power Rating

    DC Direct Current PSU Power Supply Unit

    DIP Dual In-line Package PT/CT Potential Transformer /Current
    Transformer

    DMC Digital Master Control PTC Power Transfer Control

    DMSU Demand Load Standby Unit

    EMCU Engine Monitoring and Control Unit QCC Quadrature Current
    Control

    EMF Electromotive ForceEPU Engine Protection Unit RFI Radio
    Frequency Interference

      RMS Root Mean Square

    FSS First Start Sensor RPM Revolutions Per Minute

    RTD Resistance Temperature Detector 

    GCP Generator Control Panel

    Genset Generator Set V Volts

    GKWT Global Kilowatt Transducer VAC Volts, Alternating
    Current

    VCB Vacuum Circuit Breaker

    HV High Voltage VDC Volts, Direct Current

    VF Volt-freeIC Integrated Circuit VT Voltage Transformer

    I/O Input / Output

    kVA Apparent Power 

    kVAR Reactive Power 

    kW Active / Real Power

    kWh Unit of electrical energy or work

    LED Light-Emitting Diode

    LTA Low Temperature Aftercooling

    LTP Limited Time Power RatingLV Low Voltage

  • 8/18/2019 Operator Manual PCC 3201

    10/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page ii Schedule of Abbreviations

    This is a Blank Page

  • 8/18/2019 Operator Manual PCC 3201

    11/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 1 – Preliminary and Safety Page 1-1

    SECTION 1 – PRELIMINARY AND SAFETY

    1 Safety

    1.1 Warning, Caution and Note Styles Used In This ManualThe
    following safety styles found throughout this manual indicate
    potentially hazardous conditionsto the operator, service personnel
    or the equipment.

    WARNING: WARNS OF A HAZARD THAT MAY RESULT IN SEVERE
    PERSONALINJURY OR DEATH.

    Caution: Warns of a hazard or an unsafe practice that can result
    in product or propertydamage.

    Note:  A short piece of text giving information that
    augments the current text.

    1.2 Warnings

    WARNING: IT IS IMPORTANT TO READ AND UNDERSTAND ALL SAFETY
    NOTICESPROVIDED IN THIS MANUAL. IMPROPER OPERATION OR
    MAINTENANCECOULD RESULT IN A SERIOUS ACCIDENT OR DAMAGE TO
    THEEQUIPMENT, CAUSING INJURY OR DEATH.

    1.3 General Information

    This manual should form part of the documentation package
    supplied by Cummins PowerGeneration Limited with specific generator
    sets. In the event that this manual has been supplied in

    isolation please refer to the other Cummins Power Generation
    Limited literature, in particular theHealth and Safety Manual
    (0908-0110-00) and the engine manual relevant to your generator
    set.

    Note: It is in the user’s interest to read and understand all
    Health and Safety informationtogether with all Warnings and
    Cautions contained within the documentation relevant tothe
    generator set and its operation and maintenance.

    1.4 Generator Plant Safety Code

    Before operating the generator set, read this manual and become
    familiar with it and theequipment. Safe and efficient operation can
    be achieved only if the equipment is properly operatedand
    maintained. Many accidents are caused by failure to follow
    fundamental rules andprecautions.

    WARNING: LIFTING AND REPOSITIONING ON THE GENERATOR SET MUST
    ONLY BECARRIED OUT USING SUITABLE LIFTING EQUIPMENT, SHACKLES
    ANDSPREADER BARS IN ACCORDANCE WITH LOCAL GUIDELINES ANDLEGISLATION
    BY SUITABLY TRAINED AND EXPERIENCED PERSONNEL.INCORRECT LIFTING CAN
    RESULT IN SEVERE PERSONAL INJURY,DEATH AND/OR EQUIPMENT DAMAGE. FOR
    MORE INFORMATIONCONTACT YOUR AUTHORISED DISTRIBUTOR.

  • 8/18/2019 Operator Manual PCC 3201

    12/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 1-2 Section 1– Preliminary and Safety

    This is a Blank Page

  • 8/18/2019 Operator Manual PCC 3201

    13/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 2 – Introduction Page 2-1

    SECTION 2 — INTRODUCTION

    2 Introduction

    2.1 GeneralBefore any attempt is made to operate the generator
    set, the user should take time to read thismanual and to
    familiarise him or herself with the Warnings and Operating
    Procedures.

     A generator set must be operated and maintained properly
    if you are to expect safe and reliableoperation. The manual
    includes a maintenance schedule and a troubleshooting guide.

    The engine manual is included with the set. Where there is
    conflicting information, this manualtakes precedence over the
    engine manual.

    2.2 Generating Set Identification

    Each generating set is provided with a Generating Set Rating
    Plate similar to that shown below.This provides information unique
    to the set.

    Figure 2-1 Typical Generator Set Rating Plate

  • 8/18/2019 Operator Manual PCC 3201

    14/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 2-2 Section 2– Introduction

    2.3 After Sales Services

    We offer a full range of after sales services as follows:

    2.3.1 Maintenance

    WARNING: INCORRECT SERVICE OR PARTS REPLACEMENT CAN RESULT
    INSEVERE PERSONAL INJURY, DEATH, AND/OR EQUIPMENT DAMAGE.SERVICE
    PERSONNEL MUST BE TRAINED AND EXPERIENCED TOPERFORM ELECTRICAL
    AND/OR MECHANICAL SERVICE.

    For customers who wish to have their generator sets expertly
    serviced at regular intervals theCustomer Service Department offers
    a complete maintenance contract package. This covers allitems
    subject to routine maintenance and includes a detailed report on
    the condition of thegenerator set. In addition, this can be linked
    to a 24-hour call-out arrangement, providingassistance 365 days a
    year if necessary. Specialist engineers are available to maintain
    optimumperformance levels from customer’s generator sets, and it is
    recommended that maintenance

    tasks are only undertaken by trained and experienced engineers
    provided by the CustomerService Department

    2.3.2 Warranty

     All generator sets have a twelve months warranty from the
    commissioning date as standard.Extended warranty coverage is also
    available. In the event of a breakdown prompt assistance
    cannormally be given by factory trained service engineers with
    facilities to undertake all minor andmany major repairs to
    equipment on site.

    For further warranty details contact your authorised
    distributor.

    2.3.3 Spares

     An extensive Spare Parts Department is available for any
    emergency breakdown and for theengineer who carries out his own
    routine maintenance. Please contact your authorised
    CumminsDistributor.

    Please quote Plant Nos., Serial Nos., and Part Nos. when
    ordering spares.

    2.3.4 Overseas

     Agents and representatives in almost 100 countries
    throughout the world offer installation and aftersales service for
    the equipment provided. Your authorised distributor can provide the
    name andaddress of the agent for your specific location.

    2.3.5 Additional LiteratureShould you require further, more
    detailed information regarding the engine or alternator
    pleasecontact your authorised distributor.

    Please quote Plant Nos. and Serial Nos.

  • 8/18/2019 Operator Manual PCC 3201

    15/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 3 – System Overview Page 3-1

    SECTION 3 – SYSTEM OVERVIEW

    3 System Overview

    3.1 Generator Components – Typical Generator SetThe main
    components of a Typical Generator Set are shown below and referred
    to within thissection. Refer to the Engine Manual for location of
    other components, e.g. oil filler, dipstick, etc.

    Data sheets are also available if additional, specific
    information is required. Contact yourauthorised distributor.

    Various options are listed although they may not be available
    for all models.

    Figure 3-1 Typical Generator Set (C450 to C550)

    KEY OPTIONS

    1. Alternator Batteries and Tray

    2. Control Housing Circuit Breaker Entrance Box

    3. Control Panel Electric Fuel Transfer Pump

    4. Air Cleaner Engine Coolant Heater

    5. Engine Sump Drain Pump

    6. Radiator

    7. Bed Frame

    1

    2

    3

    45

    6

    7

  • 8/18/2019 Operator Manual PCC 3201

    16/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 3-2 Section 3 – System Overview

    3.1.1 AC Supply and Isolation

    It is the sole responsibility of the customer to provide the AC
    power supply and the means toisolate the AC input to the terminal
    box. Refer to the wiring diagram supplied with the
    generatorset.

    Note:  A separate disconnecting device is required by BS EN
    12601:2001.

    WARNING: THE DISCONNECTING DEVICE IS NOT PROVIDED AS PART OF
    THEGENERATOR SET AND CUMMINS POWER GENERATION LIMITEDACCEPTS NO
    RESPONSIBILITY FOR PROVIDING THE MEANS OFISOLATION.

    3.1.2 Control System

    The control system is a micro-processor based control unit for
    monitoring and protecting thegenerator set (see Section 4) and can
    provide automatic paralleling. All indicators,
    controlswitches/buttons and the digital display are on the face of
    the control panel as illustrated inFigure 4-1.

    The control system provides fuel control and engine speed
    governing, main alternator voltageoutput regulation, and complete
    generator set control and monitoring. The control also monitorsthe
    health of the engine, alternator and auxiliary systems
    continuously, via an array of sensors andsenders located on the
    generator set, and will affect an Automatic Shutdown if a serious
    faultoccurs.

    3.1.3 Engine

     All generator sets employ a 4-stroke, water-cooled engine
    and incorporate a governor control andfull engine protection
    system. Refer to the Generating Set Rating Plate for engine type
    and ratingdetails.

    For further information refer to the engine manual supplied with
    this manual.

    3.1.4 Alternator

     All generator sets use AC alternators of a brushless,
    rotating field design, which eliminates themaintenance associated
    with slip rings and brushes. Refer to the Generating Set Rating
    Plate foralternator type and rating details.

    3.1.5 Generator Rating

    For details of your generator rating refer to the Generating Set
    Rating Plate.

    3.1.6 Generator Set ConstructionMost generator sets are
    constructed as a single module with the engine and alternator
    connectedthrough a coupling chamber with resilient mountings to
    form one unit. The engine and alternatorare mounted on a bedframe
    on resilient mounts. This results in one unit of immense
    strength andrigidity, with accurate alignment between the engine
    and alternator, and effective damping ofengine vibration.

  • 8/18/2019 Operator Manual PCC 3201

    17/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 3 – System Overview Page 3-3

    3.1.7 Fuel System

     A fuel tank incorporated into the base frame can be
    provided. Alternately free standing main tankswith stands providing
    450, 900 and 1350 litre capacity are available as options.

    Note: Where spillage containment is not part of Cummins supply,
    it is the responsibility of theinstaller to provide the necessary
    containment to prevent contamination of theenvironment, especially
    water courses/sources.

    3.1.7.1 Fuel Transfer Pumps (Option)

    Free standing fuel tanks can be filled manually using an
    optional hand fuel transfer pump.

     Alternatively, fuel tanks can be filled automatically
    using an electrical fuel transfer pump. Thispump, which is supplied
    complete with starter, operates under the control of Low and High
    FuelLevel switches fitted to the tank.

    On automatically filled systems, the tank filler cap is replaced
    with an overflow/breather connectionto allow piping to a safe area
    or return to a bulk tank.

    3.1.7.2 Fuel / Water SeparatorsSet-mounted fuel/water separators
    are fitted as standard to provide protection for the engine
    fuelinjection system as water-free fuel supplies cannot be
    guaranteed.

    3.1.8 Cooling System

    The engine cooling system consists of a radiator and pusher fan,
    mechanically driven water pumpand a thermostat. The fan drives air
    through the radiator and removes surface heat from theengine and
    alternator.

    The alternator has its own internal cooling fan.

    3.1.9 Engine Exhaust (Option)WARNING: EXHAUST PIPES AND CHARGE
    AIR PIPES ARE VERY HOT AND THEY

    CAN CAUSE SEVERE PERSONAL INJURY OR DEATH FROM DIRECTCONTACT OR
    FROM FIRE HAZARD.

    Exhaust systems, which are optional and supplied in loose form,
    reduce engine noise toacceptable levels and pipe exhaust gases to
    an area where they will not present a hazard.Industrial and
    residential types are available as options. Flexible bellows are
    also available as anoption.

    3.1.10 DC Electrical System

     A 24 volt battery system provides multi-attempt engine
    starting and DC power for the generator setcontrol system.

    3.1.10.1 Battery System

    Battery type, size and voltage are selected to suit the
    generator set capacity and application onordering.

    3.1.10.2 Charge Alternator

     An engine driven charge alternator is provided as standard
    to maintain the battery in a chargedcondition when the engine is
    running.

    3.1.10.3 Mains Powered Battery Charger (Option)

    Optional single phase, mains powered battery chargers, which can
    be panel or wall mounted, areavailable to maintain the battery in a
    charged condition when the generator set is not running.

  • 8/18/2019 Operator Manual PCC 3201

    18/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 3-4 Section 3 – System Overview

    Red Lens

     Amber Lens

    Green Lens

    Horn

    Toggle Switch

    3.1.11 Alarm Module (Option)

    The front panel comprises a warning horn, three indicator
    lights, and one toggle-switch, and hasthe ability to provide
    warnings audibly and/or visually.

    Figure 3-2 Alarm Module Front Panel

    The toggle-switch provides the user with the ability to enable
    or silence the horn. The green or theamber LED will illuminate to
    indicate the active mode of the toggle-switch, whilst the red LED
    will

    illuminate if the alarm has been activated.

    The three indicator lights provide the following
    information:

    LED Label Text English

    Red Alarm Actuated Alarm Actuated

    Green Enabled Enabled

     Amber Silenced Silenced

    3.1.12 Sensors/Senders

    Various generator set parameters are measured by sensors,
    senders, RTDs etc. and the resultingsignals are received by the
    control.

    Engine mounted sensors are able to monitor the following
    systems:

    •  Cooling system

    •  Fuel

    •  Lube oil

    •  Miscellaneous areas

    Optional alternator mounted sensors are able to monitor the
    following parameter:

    •  Winding temps

  • 8/18/2019 Operator Manual PCC 3201

    19/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 3 – System Overview Page 3-5

    3.2 Heaters

    Caution: Heater(s) must not be energised if the coolant system
    has been drained.

    3.2.1 Heater Supply and Isolation

     A heater supply is required for the operation of the
    engine and alternator heaters. See Section3.1.1.

     A separate disconnecting device is required by BS EN
    12601:2001.

    Note: This disconnecting device is not provided as part of the
    generator set.

    Note: It is the sole responsibility of the customer to provide
    the power supply and the meansto isolate the AC input to the
    terminal box. Cummins Power Generation Limited acceptsno
    responsibility for providing the means of isolation.

    WARNING: THE AC SUPPLY TO THE TERMINAL BOX MUST BE ISOLATED
    BEFORE

    ATTEMPTING TO GAIN ACCESS TO THE TERMINAL BOX.

    Caution: Remove AC power to the heater before disconnecting
    battery leads. Heater willrun continuously without DC power and can
    overheat and damage heater.

    3.2.2 Engine Heater (Option)

    The engine heater is designed to keep the engine coolant warm
    when the engine is shut down. Itheats and circulates the coolant
    within the engine, reducing start-up time and engine wear causedby
    cold starts. The heater is controlled by an associated thermostat,
    but is locked out at enginestart.

    WARNING: ALWAYS ISOLATE THE SUPPLY TO THE ENGINE HEATER /
    THERMOSTATBEFORE CARRYING OUT ANY MAINTENANCE ON THE ENGINE.
    ALWAYSISOLATE THE GENERATOR SET PRIOR TO ANY MAINTENANCE.

    Caution: The engine heater is in no way intended to protect the
    engine and coolingsystem from freezing in sub zero conditions. If
    there is any danger from freezing,then a suitable antifreeze agent
    must be added to the cooling system.

    3.2.3 Alternator Heater (Option)

    The alternator heater is designed to keep the alternator free of
    condensation when the generatorset is not running. During cool and
    humid conditions, condensation can form within the alternator,which
    can result in insulation degradation, leading to failure, and a
    possible shock hazard. The

    heater is locked out at engine start.

    WARNING: ALWAYS ISOLATE THE ALTERNATOR HEATER FROM THE AC
    SUPPLYBEFORE WORKING ON THE ALTERNATOR OR HEATER.

    3.2.4 Control Panel Heater (Option)

    The control panel heater provides a means of
    humidity/temperature control within the control boxinterior. It
    protects the components and ensures their effectiveness when the
    generator set issubjected to varying ambient air conditions during
    extended periods of non-use. The heater islocked out at engine
    start.

    WARNING: ALWAYS ISOLATE THE CONTROL PANEL HEATER FROM THE
    ACSUPPLY BEFORE WORKING ON THE CONTROL PANEL OR HEATER.

  • 8/18/2019 Operator Manual PCC 3201

    20/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 3-6 Section 3 – System Overview

    3.3 Mains Powered Battery Charger (Option)

    Caution: Isolate the charger before disconnecting the
    battery

    3.3.1 Operation

    This unit maintains the battery in a fully charged condition
    without over-charging. The unit alsoprovides rapid charging, when
    necessary, at a current up to the rated output.

    The charger’s electronic control circuit allows the charger to
    be left in circuit during engine crankingand to operate in parallel
    with the charge alternator.

    The charger will supply current to the battery system when the
    battery terminal voltage is equal tothe set float voltage, at which
    point only a trickle charge current is present. When the
    batterybecomes discharged due to a load being present and the
    terminal voltage falls, the charger willagain supply current to
    restore the voltage of the battery to the float voltage.

    Should a charge fail condition occur for longer than ten seconds
    then the charge fail relay will

    energise, and its contact close. Charger operation is indicated
    by a red LED.

    Note: The LED will light even if the charger output fuse is
    blown.

    3.3.2 Boost Charge (Option)

    During trickle charging, not all cells in the battery receive
    the same charge and over a period ofseveral months this may affect
    battery performance. It is therefore normal to give batteries
    aregular charge at their full rate  to return all cells to
    full capacity. This is referred to as BoostCharging (also known as
    equalise charging).

    If the charger is fitted with a Boost Charge switch, the Boost
    position should be selected atintervals detailed by the battery
    manufacturer (normally around every six months).

    Caution:  Batteries should not be left on Boost Charge for
    extended periods as this willresult in excessive water consumption
    and gassing and may impair battery performance.

  • 8/18/2019 Operator Manual PCC 3201

    21/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 4 – Control System Page 4-1

    SECTION 4 – CONTROL SYSTEM

    4 Control System

    4.1 Control System Description

    The main control panel consists of two panels, the Operator
    Panel and the Switch Panel. Theseand their associated equipment are
    located in the Control Housing, which is mounted at the rear ofthe
    generator set.

    Dependent on site requirements the Operator Panel may be mounted
    in the control panelassembly (full-featured) as shown in Figure
    4-1, or it may be contained in a separate enclosureand mounted
    remotely of the control panel assembly. In this latter case, the
    panel may be situatedup to 1.2km (4,000ft) away from the generator
    set.

    Note: The function of several buttons on the Operator Panel will
    vary dependent on thelocation of the Operator Panel (remote or
    local of the Control Panel assembly). If the

    function differs, it is noted as either Remote or Local Operator
    Panel in the description.The control system is a micro-processor
    based control unit for monitoring and protecting thegenerator set
    and can provide automatic paralleling. All indicators, control
    switches/buttons andthe digital display are on the face of the
    control panel as illustrated in Figure 4-1.

    The control system provides fuel control and engine speed
    governing, main alternator voltageoutput regulation, and complete
    generator set control and monitoring. The control also monitorsthe
    health of the engine, alternator and auxiliary systems
    continuously, via an array of sensors andsenders located on the
    generator set, and will affect an Automatic Shutdown if a serious
    faultoccurs.

    There are two fault level signals generated by the control
    system as follows:

    1. Warning:  signals an imminent or non-fatal fault for the
    engine. The control provides

    an indication only for this condition.2. Shutdown:  signals
    a potentially fatal fault for the engine. The control will
    automatically

    take the engine off-load and shut it down immediately, without a
    cooling down run.

    The control system operates on 24V DC battery power. The
    auxiliary equipment operates on LV AC power. The history data
    is stored in non-volatile memory and will not be deleted due to
    loss ofbattery power.

    In addition to the many control and annunciation functions, the
    PCC 3201 can be easily upgradedto communicate over a
    PowerCommand

    ™ Network, or to work as part of a paralleling system.

  • 8/18/2019 Operator Manual PCC 3201

    22/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 4-2 Section 4 – Control System

    4.1.1 Control Panel Power ON/OFF Modes

    The power on/off modes of the control panel and operating
    software are Power On, Screen Saverand Sleep/Awake.

    Power On ModeIn this mode, power is continuously supplied to the
    control panel. The control’s operating softwareand control panel
    LEDs/graphical display will remain active until the Screen Saver
    mode isactivated.

    Screen Saver Mode

    Power to the graphical display will be removed after ten minutes
    (generator set not running orrunning). The ten minute timer resets
    and begins after each control panel action (any button orswitch
    selection) or signal received by the operating software. The bottom
    LEDs of the Analogue AC Metering Panel (bar graphs) may remain
    on during Screen Saver mode, indicating that theoperating software
    is active (Awake mode).

    When a Warning signal is sensed by the control, (for example,
    Low Coolant Temp), a warningmessage will be displayed. The control
    will remain active until the Fault Acknowledge button ispressed to
    clear the warning message and start the ten minute timer.

    Sleep/Awake Mode

    In the Sleep mode, the control’s operating software is inactive
    and the LEDs and the graphicaldisplay on the control panel are all
    off. Sleep mode is a feature that is used to reduce batterypower
    consumption when the control is in the Auto mode and is not being
    used.

    When all conditions are met (i.e., no unacknowledged faults,
    Screen Saver Mode is active, andOff/Manual/Auto switch is in the
    Auto position) the Sleep mode will be activated.

    The operating software is initialised and the control panel LEDs
    and graphical display are turnedon in response to one of the
    following:

    •  Moving/pressing any control panel switch/button

    •  A remote start input signal (generator set in Auto
    mode)

    •  Customer fault 2 or 3 only (Shutdown or Warning
    indicator is on)

    To activate the control and view the menu display without
    starting the generator set, press anybutton on the control
    panel.

    The InPower service tool is required to enable or disable the
    Sleep mode. When shipped from thefactory, the Sleep mode is
    disabled. When disabled, the operating software will always
    remainactive (Awake mode) when the control is in Auto mode.

    Note: The InPower service tool is required in order to select
    the desired mode.Contact your authorised distributor for
    assistance.

  • 8/18/2019 Operator Manual PCC 3201

    23/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 4 – Control System Page 4-3

    4.1.2 Control Panel — Front Panel

    Figure 4-1 Control Panel Assembly (Full Featured)

    1. Analogue AC metering panel 7. Off/Manual/Auto switch (mode
    switch)

    2. Emergency stop push switch (This is a Key Switch)

    3. Status indicators 8. Manual Run/Stop button &
    indicator

    4. Fault acknowledge button 9. Graphical display

    5. Panel lamp/lamp test button 10. Display menu selection
    buttons (1 of 6)

    6. Exercise button & indicator

    SWITCH PANEL 

    OPERATOR PANEL 

    1 2

    3

    4

    5

    6

    78910

  • 8/18/2019 Operator Manual PCC 3201

    24/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 4-4 Section 4 – Control System

    4.1.3 Control Panel — Operator Panel

    The operator panel contains the following components:

    Analogue AC Metering Panel:

    This panel simultaneously displays 3–phase line-to-line AC volts
    and current, kW, power factorand frequency.

    The meter panel is composed of a series of LEDs that are
    configured in bar graphs for eachfunction. The LEDs are colour
    coded, with green indicating normal range values, amber forWarning
    levels and red for Shutdown conditions.

    Scales for each function are in % of nominal values. Resolution
    is 1% for values close to nominal,and increases for values further
    from nominal.

    Graphical Display:

    The graphical display is capable of displaying up to nine lines
    of data with approximately 27characters per line. The display is
    used to view the menus of the menu–driven operating system.

    (Refer to the menu trees later in this section). The display is
    also used to show Warning andShutdown messages/error codes, modes
    of operation (Figure 4-2) and system actions, such asWarning,
    De-rate, Shutdown, etc.

    Display Menu Selection Buttons:

    Six momentary buttons—three on each side of the graphical
    display window—are used to navigatethrough the system control menus
    and to adjust generator set parameters. The button is activewhen
    the message adjacent to the button is highlighted (displayed in
    inverse video).

    4.1.4 Control Panel — Switch Panel

    WARNING: SOME PANEL INTERNAL COMPONENTS MAY HAVE LIVE
    EXPOSED

    TERMINATIONS EVEN IF THE GENERATOR SET IS NOT RUNNING.ISOLATE
    ALL EXTERNAL ELECTRICAL SUPPLIES PRIOR TO ACCESS OFTHE CONTROL
    PANEL.

    The switch panel contains the following components:

    Emergency Stop Button:

    Push the button in for Emergency Shutdown of the engine. If the
    engine is not running, pushingthe button in will prevent the
    starting of the engine, regardless of the start signal source
    (local orremote).

    To reset:

    •  Pull, or twist and pull, the button out.

    •  Turn the Off/Manual/Auto switch to Off (O).

    •  Press the front panel Fault Acknowledge button.

    •  Select Manual or Auto, as required.

    Caution: Ensure that the cause of the emergency is fully
    investigated and remediedbefore an emergency stop Reset, and
    generator set Start are attempted.

    Note: Emergency Stop shutdown status can be reset only at the
    operator control panel.

  • 8/18/2019 Operator Manual PCC 3201

    25/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 4 – Control System Page 4-5

    Remote Start Indicator:

    This green lamp is lit whenever the control is receiving a
    Remote Run signal. When this lamp isflashing, it indicates a load
    demand stop mode.

    Not in Auto Indicator:

    This red lamp flashes continuously when the Off/Manual/Auto
    switch is not in the Auto position.(If it is in the Auto position
    and the lamp is flashing, this indicates that a service is
    required).

    Shutdown Status Indicator:

    This red lamp is lit whenever the control detects a Shutdown
    condition. The generator set cannotbe started when this lamp is on.
    After the condition is corrected, Shutdown indicators can be
    resetby turning the Off/Manual/Auto switch to the Off (O) position,
    and pressing the Fault Acknowledgebutton.

    Dependent upon the specific fault that occurs, the engine may or
    may not shut down immediately. A fault that could cause engine
    damage causes an immediate engine shutdown (bypasses
    enginecool–down sequence). All other faults would allow the engine
    to run during the cool–down

    sequence before engine shutdown. In this case, the Shutdown
    Status Indicator blinks during thecooldown period.

    Warning Status Indicator:

    This yellow lamp is lit whenever the control detects a Warning
    condition. After the condition iscorrected, warning indicators can
    be reset by pressing the Fault Acknowledge button. (It is
    notnecessary to stop the generator set if the fault becomes
    inactive during generator set operation).

    Fault Acknowledge:

    Press this button to acknowledge Warning and Shutdown messages
    after the fault has beencorrected.

    To acknowledge a Warning message, the Off/Manual/Auto switch can
    be in any position. (It is not

    necessary to stop the generator set to acknowledge an inactive
    Warning condition). Toacknowledge a Shutdown message with this
    button, the Off/Manual/Auto switch must be in the Off(O)
    position.

    This button is also used to blink a fault code if the Shutdown
    or Warning Status Indicator is lit.(This function is used when the
    control does not contain a graphical display). Refer to
    ReadingFault Codes in Section 7 -Troubleshooting, which describes
    how to use this button for interpretingfault codes.

    Panel Lamp/Lamp Test Button:

    Press this button to turn the panel lamp on or off.

    Press and hold down this button for a minimum of three seconds
    to turn all control panel LEDs on,to make sure all lamps
    illuminate. The illumination will shut off after releasing the
    button.

    Exercise Button:

    Press this button to initiate a pre-programmed exercise
    sequence. The Off/Manual/Auto switch isused in conjunction with
    this button to enable this function (refer to Section 5.6.5
    Exercise Start).

    Manual Run/Stop Button:

    This button starts and stops the set locally and will bypass
    Time Delay to Start and Stopsequences. The Off/Manual/Auto switch
    must be in the Manual position to enable this button.

  • 8/18/2019 Operator Manual PCC 3201

    26/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 4-6 Section 4 – Control System

    Off/Manual/Auto Switch:

    Manual position enables the use of the switch panel Manual
    Run/Stop button.

    Auto position enables start/stop control of the engine from
    a remote location. (Disables the use ofthe switch panel Manual
    Run/Stop button).

    Off (O) position prevents the starting of the generator set
    (local or remote). If moved to Off (O)  during set operation,
    an immediate engine shutdown will be initiated (bypasses cool–down
    timers).This hot shutdown should be avoided, if possible, to help
    reduce unnecessary engine wear. Hotshutdowns are logged by the
    system software.

     A key function is provided to prevent unauthorised
    operation of the switch.

    4.2 Menu Display and Switches

    Figure 4-2 shows the graphical display and the menu selection
    buttons.

    4.2.1 Graphical Display

    The graphical display is capable of displaying up to nine lines
    of data with approximately 27characters per line. The display is
    used to view the menus of the menu–driven operating system.(Refer
    to the menu trees later in this section). The display is also used
    to show the followingsystem information:

    •  State Line — modes of operation, such as Stopped,
    Time Delay to Start, Warm Up at Idle, etc.(see Figure 4-1), and
    paralleling operations, such as Standby, Dead BUS Close,
    Synchronise,etc.

    •  Action Line  — system actions, such as Warning,
    De-rate, Shutdown Cool–down andShutdown, and fault codes.

    •  Description Line — Fault code/status messages.

    Figure 4-2 Graphical Display and Menu Selection Buttons

    4.2.2 Menu Buttons

    Six momentary buttons — three on each side of the graphical
    display window — are used to navigatethrough the system control
    menus and to adjust generator set parameters. The button is
    activewhen the message or symbol adjacent to the switch is
    highlighted (displayed in inverse video). Thedisplayed message or
    symbol indicates the function of the button.

    Note: In the graphical display, the symbol indicates that
    selecting the adjacent buttoncauses the operating program to go to
    the next menu display—as shown in the menudiagrams.

    In the graphical display, the symbol indicates that selecting
    the adjacent button

    causes the operating program to go back to the previous menu
    display.

    STATE LINE

     ACTION LINE

    DESCRIPTION LINE

    MENU DISPLAY AREA

    GRAPHICALDISPLAY

    MENUBUTTONS

    MENUBUTTONS

  • 8/18/2019 Operator Manual PCC 3201

    27/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 4 – Control System Page 4-7

    In the graphical display, the symbol indicates that selecting
    the adjacent buttoncauses the operating program to go back to Main
    Menu A (Figure 4-4).

    4.3 Menu Units Selection

    During any control panel operation, you can change how units are
    displayed by pressing the twolower menu buttons (one on each side
    of display). When pressing these two buttonssimultaneously, the
    unit’s submenus will appear (Figure 4-3). After selecting the
    desired units,press the ENTER button in this submenu to change
    and save the selections.

    Note: Use the + button to select the desired option for
    each field. Use the arrow ( → ) button tomove to the next
    field. Selected field is highlighted.

    Figure 4-3 Units Submenu

    4.3.1 Local/Remote Field

    This selection must be set to Local, when the graphical display
    is mounted on the generator setfront control panel, or Remote when
    mounted remotely from the generator set.

    The Local/Remote selection determines which buttons in the
    Control submenu (Section 4.7) areactive (displayed).

    Temp: Used to select °F or °C for temperature readings.

    Pressure Fluid: Used to select PSI, KPa, BAR or IN for pressure
    readings.

    Pressure Gas: Used to select INHG or MMHG for pressure
    readings.

    Flow Air: Used to select CFM or CMM for airflow readings.

    LOCATION LOCAL

    TEMPΕF

    PRESS FLD PSIPRESS GAS INHG

    ENTER

    +

    → 

  • 8/18/2019 Operator Manual PCC 3201

    28/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 4-8 Section 4 – Control System

    4.4 Main Menu

    Figure 4-4 shows the main menus (Menu A and Menu B) of the
    system control. The two mainmenus are used to divide the system
    submenus into major categories, such as, Engine Data,

     Alternator Data, Control, etc.To view system data, simply
    press the appropriate menu button to select the category.
    Afterpressing the desired menu button, refer to the following pages
    for detailed information related tothe selected category.

    Note: The numerical information shown in the following figures
    is for example only. They donot necessarily reflect the information
    for your specific generator set.

    Figure 4-4 System Control Main Menus A and B

    Note: In the following figures, the boxed/highlighted field
    indicates that the adjacent menubutton is active. Also, the
    submenus are shown in the order in which they are displayedwhen
    scrolling up , or down .

    4.4.1 Adjust Button

    The Adjust submenu is intended for competent site personnel
    only. Note that a password may beassigned to allow only authorised
    operators to modify this data.

    4.4.2 Set-up Button

    The Set-up submenu is described in the Service manual and is
    intended for competent servicepersonnel only. For this reason, a
    password must be entered before this data can be
    modified. 

    Note: PTC – The PTC Setup submenu is intended for qualified
    service and site personnelonly. Password is provided, but can be
    changed after installation to prevent un-authorised
    modifications,

    Note: The Adjust and Set-up submenus can be viewed, but not
    modified without entering thecorrect passwords.

    MENUBUTTONS 

    MENUBUTTONS

    MENU A

    ENGINE

    HISTORY/ABOUT

    MENUB 

    ALTERNATORCONTROL

    MORE>

    POWER TRAN or_\_ 

    MENU B

    BACK

  • 8/18/2019 Operator Manual PCC 3201

    29/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 4 – Control System Page 4-9

    4.4.3 _\_ Button (Paralleling applications only)

    When displayed, indicates that the feature for generator set
    paralleling applications is enabled.This button is used to open and
    close the generator set circuit breaker (CB). The symbol
    indicatesif the CB is opened or closed.Opened  _\_,  push
    to close.Closed  _-_,  push to open.

    With the control panel Off/Manual/Auto switch in the Auto
    position, the opening and closing of theCB is controlled by the
    control system software. The CB symbol will indicate an open or
    closedCB, but the button will be inactive when the control is in
    Auto.

    In the Manual position, the CB can only be closed by using this
    button. When manually closed andthe CB opens, it must be closed
    again by using this button. To close the CB, press and hold
    thebutton until the symbol indicates a closed CB. (CB close will
    occur only when set-up conditionsallow — dead bus or generator set
    synchronised with bus).

    4.4.4 Power Trans Button (PTC applications only)

    When displayed, indicates that the Power Transfer Control
    feature is enabled.

    Refer to Section 4-12 for submenu description.

  • 8/18/2019 Operator Manual PCC 3201

    30/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 4-10 Section 4 – Control System

    4.5 Engine Data Submenus

    If you press the Engine Data button in Menu A, the Engine Data
    submenus will appear(Figure 4-5).

    The first submenu displays general information that applies to
    all generator sets (coolant temp, oilpressure, etc.) The data in
    the remaining submenu(s) will vary according to the type and number
    ofsensors provided with the engine.

    Figure 4-5 Engine Data Sub-menus

    COOLANT TEMP 180ΕF

    ENGINE SPEED 1800 RPMBATTERY 29.1 VDCOIL PRESSURE 75 PSI

    OIL TEMP 210Ε

    F

    MANF TEMP 75ΕFMANF PRESS ABS 180 INHGOUT PRESS ABS 180
    PSIAMBIENT PRESS 88 INHG

    ENGINE DATA

  • 8/18/2019 Operator Manual PCC 3201

    31/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 4 – Control System Page 4-11

    4.6 Alternator Data Submenus

    If the Alternator Data button in Menu A is pressed, the
    Alternator Data submenus will appear(Figure 4-6).

    4.6.1 Voltage L–L and L–N

    Indicates voltage Line–to–Line, and Line–to–Neutral. Note that
    the Line–to–Neutral column will notbe displayed for a
    3-phase/3-wire system. Accuracy 1%.

    The voltages Line–to–Line (L1, L2 and L3) are measured between
    L1 to L2, L2 to L3 and L3 to L1,respectively.

    Figure 4-6 Alternator Data Sub-menus

    4.6.2 Amps

     All phases. Accuracy 1%.

    4.6.3 Frequency

    Generator set output frequency.

    4.6.4 AVR Duty Cycle

    Displays voltage regulator (drive) level in percentage of
    maximum.

    4.6.5 kW, kVA and PF

    Displays generator set kW and kVA output (average and individual
    phase, and direction of flow)and power factor with leading/lagging
    indication. Accuracy 5%.

    Note: The PF reading will contain an asterisk if the power
    factor is leading (e.g., *.30).

    kW kVA PF

    L1 350 500 .80L2 350 500 .80L3 350 500 .80TOT 1050 1500 .80

    V L-L L-N AMPSL1 480 277 1340L2 480 277 1290L3 480 277
    1260FREQUENCY 60.0HZAVR DUTY CYCLE 10.3%

    ALTERNATOR DATA

  • 8/18/2019 Operator Manual PCC 3201

    32/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 4-12 Section 4 – Control System

    4.7 Control Submenu

    If the Control button in Menu A is pressed, the Control submenu
    will appear(Figure 4-7).

    4.7.1 Local Control Submenu Function

    When the Operator panel (Figure 4-1) is mounted on the control
    panel assembly, the Run ModeIdle/Rated button is active
    (displayed).

    Note: In remote applications (Figure 4-8) this button is not
    displayed.

    The shaded area in Figure 4-7 displays the selected/active mode
    of operation, (Idle or Rated).

    Note: Run Mode Idle/Run at Rated Button: Refer to Section 5.7
    for a complete description ofthe Run at Idle mode.

    Figure 4-7 Local Control Sub-menu

    + RUN MODE IDLE

    CONTROL(Local)

    ENABLE SYNC

    BARGRAPH TEST

  • 8/18/2019 Operator Manual PCC 3201

    33/90

  • 8/18/2019 Operator Manual PCC 3201

    34/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 4-14 Section 4 – Control System

    4.8 History/About Submenus

    Pressing the History/About button in Menu A will reveal the
    History/About submenus (Figure 4-9).

    4.8.1 HistoryThe control maintains a data log of the number of
    engine starts and number of operating hours forthe engine and
    control, and the megawatt and maximum torque hours of the generator
    set. Thisinformation is stored in non-volatile memory and will not
    be deleted due to loss of battery power.

    4.8.2 About

    The About submenus provide the following generator set
    information:

    •  Generator set model and wattage (kW/MW)

    •  Output voltage and WYE, DELTA or SINGLE

    •  Frequency 50 or 60 Hz

    •  Rating: Standby, Prime or Base

    •  Version level of the controller and panel operating
    software

    4.8.3 Fault History

    The control maintains a data log of all fault conditions as they
    occur, and time stamps them withthe control and engine operating
    hours.

    Up to 32 (unacknowledged) fault codes can be stored in control
    panel memory. Following Faultacknowledgement and correction, it is
    deleted from the control panel memory. However, it remainsin a data
    log that maintains the fault code history. (The InPower service
    tool is required to view thisdata log).

    The Fault History display line: 1 of 24 indicates that 24 faults
    are recorded and that the mostrecent fault (1) detected by the
    controller is displayed.

    The Occurrences display line: In this example, 5 indicates
    that this is the fifth occurrence of thisfault. (The InPower
    service tool is required to review the last four faults of this
    code).

    Note: The Occurrences number is incremented for each new
    occurrence of the same fault.The controller must detect that the
    original sensed fault is corrected before it willincrement the
    occurrence number for that fault.

    For example, when a Low Oil Pressure fault is detected, the
    controller will incrementthe Occurrences number by 1. This fault
    will remain active until the controller detectsthat the fault is
    corrected. An active fault will prevent the controller from
    incrementingthe Occurrences number each time the engine is started.
    When the controller detects

    that the oil pressure is normal the fault will become inactive,
    allowing the occurrencesnumber to be incremented for the next
    detected Low Oil Pressure fault.

  • 8/18/2019 Operator Manual PCC 3201

    35/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 4 – Control System Page 4-15

    Figure 4-9 History/About Sub-menus

    STARTS533

    ENGINE HOURS 1236CONTROL HOURS 7879KWHRS

    890

    HRS@%MAX TORQUE

    12345@0-9 23455@50-5912345@10-19 12345@60-6912345@20-29
    12345@70-7912345@30-39 12345@80-89

    MODEL 1750DQKBVOLTAGE 416 WYEFREQUENCY 60RATING STANDBY

    CONTROLLER VERSIONRTOP DN30008.DFABATS FEB 15 1999OT PANEL
    VERSIONRTOP 1.12BATS 1.04

    FAULT HISTORY 1 OF 24

    CNTL HOURS 459

    OCCURRENCES 5ENGINE HOURS 334FAULT CODE 1437

    (FAULT DESCRIPTION)

    HISTORY/ABOUT

  • 8/18/2019 Operator Manual PCC 3201

    36/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 4-16 Section 4 – Control System

    4.9 Adjust Sub-menu

    If the Adjust button in Menu B is pressed, the Adjust submenu
    will appear(Figure 4-10).

    The Adjust submenu is intended for qualified service personnel
    and site personnel only and mayrequire a USER  password.
    If a password is required, the USER  password menu will
    appear whenyou try to modify the Adjust submenu. (Refer to Password
    Menu in Section 4.11 to enterpassword).

    Changes are automatically saved when you exit this menu.

    Note: Use the + and —  buttons to increase or
    decrease the values in the following fields. Usethe arrow
    ( → ) button to move the cursor within a field or to the
    next field. Selected fieldis highlighted.

    •  START DELAY: This delay applies only to remote starting
    in the Auto mode.The Start Delay adjustment range is 0 to 300
    seconds. 

    •  STOP DELAY:  This delay applies only to remote
    stopping in the Auto

    mode. The Stop Delay adjustment range is 0 to
    600seconds. 

    •  VOLTAGE:  Used to adjust the output voltage
    ±5%.

    •  FREQUENCY:  Used to adjust the frequency ±3 Hz.

    •  VOLTAGE/SPEED DROOP:  These two sub-menus apply to
    a generator set that has theparalleling option enabled and is
    configured to operate indroop mode. These adjustments must be
    performed bytechnically qualified personnel only. 

    Figure 4-10 Adjust Sub-menu

    ADJUST:START DELAY 5 SECSTOP DELAY 11 SECVOLTAGE 208 1.2 %FREQ
    60.0 HZ -0.0 HZ

    — 

    ADJUST:STANDBY

    VOLTAGE DROOP OFFBUS L1 480 VPOWER FACTOR 0.80VOLT 4.99 %

    6

    — 

    ADJUST:STANDBYSPEED DROOP OFFBUS FREQ 60.0 HZTOTAL KW 300 HZFRE
    60.0 0.40 HZ

    — 

    ADJUST

  • 8/18/2019 Operator Manual PCC 3201

    37/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 4 – Control System Page 4-17

    4.10 Parallel Data Submenu

    If the Parallel Data button in Menu B is pressed, the Parallel
    Data submenu will appear(Figure 4-11). This menu is displayed in
    paralleling applications only.

    4.10.1 Parallel Data Status Line

    The top line of the graphical display is used to indicate the
    following Parallel Data status:

    •  STANDBY: Indicates no paralleling activity is
    occurring. 

    •  DEAD BUS CLOSE: Indicates first generator set in system
    to close to bus. 

    •  SYNCHRONISE: Generator set is synchronising to
    bus. 

    •  LOAD SHARE: Generator set has closed to bus and is
    sharing load with othergenerator sets in system. 

    •  LOAD GOVERN: Generator set closed to bus in parallel
    with utility (mains). 

    Figure 4-11 Bus Data Sub-menu

    BUS Voltage L–L: The BUS voltage Line–to–Line (L1, L2 and
    L3) is measured between L1 to L2,L2 to L3 and L3 to L1,
    respectively.

    BUS/GEN HZ: BUS/GEN hertz.

    BUS/GEN SYNC STATUS:  The bottom line of the graphical
    display is used to indicate thefollowing BUS/GEN Sync status:

    •  NOT SYNCHRONIZING:  Generator set is in service
    mode that does not allow auto syncfeature. 

    •  SYNCHRONIZING: Generator set is synchronising to
    bus.

    •  READY TO CLOSE: In manual mode, push circuit breaker
    close button to closebreaker.

    •   _\_ Button: (Paralleling applications only). Used
    to open and close thegenerator set circuit breaker (CB). The symbol
    indicates if theCB is opened or closed.Opened  _\_ , push
    to close.Closed  _-_ , push to open.

    With the control panel Off/Manual/Auto switch in the Auto
    position, the opening and closing of theCB is controlled by the
    control system software. The CB symbol will indicate an open or
    closedCB, but the button will be inactive when the control is in
    Auto.

    In the Manual position, the CB must be closed by this button.
    When manually closed and the CB

    opens, it must be closed again by using this button. To close
    the CB, press and hold the buttonuntil the symbol indicates a
    closed CB. (CB close will occur only when set-up conditions allow
    -dead bus or generator synchronised with bus).

    LOAD GOVERNV BUS GENL1 480 480L2 480 480L3 480 480HZ 60.1
    60.1DEG – 122 NOT SYNCHRONIZING

     _\_ 

    PARALLEL DATA

  • 8/18/2019 Operator Manual PCC 3201

    38/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 4-18 Section 4 – Control System

    4.11 Password Menu

    When viewing the Adjust submenu, pressing either the +  or
    —  button will display the Passwordmenu (Figure 4-12) if a
    User password is assigned to this field. After entering the
    correct

    password, the system will allow you to modify the submenu. To
    prevent unauthorised adjustment,the entered password is valid for
    only ten minutes after the last button is pressed.

    Note:  Application Password is intended only for competent
    service personnel to allowadjustment of Set-up submenu
    parameters.

    To enter the password:

    1. Display Adjust submenu.

    2. Press either the + or —  button within the
    displayed submenu. The Password menu appears.(Adjustment is allowed
    if Password menu does not appear).

    3. Press the + and — button to select the first
    character of the User password (A-Z or 0-9).

    4. Press the → button to select the next character field.
    Selected character field is highlighted.

    5. Repeat steps 3 and 4 to enter remaining password
    characters.6. Press the Enter button after entering the password.
    The Adjust submenu will re-appear.

    7. Exit Adjust submenu to save changes.

    Figure 4-12 Password Menu

    ENTER USER PASSWORD(OR)

    ENTER APPLICATIONPASSWORD

    xxxxxxxx

    ENTER+ 

    → 

    + OR — BUTTON

    — 

  • 8/18/2019 Operator Manual PCC 3201

    39/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 4 – Control System Page 4-19

    4.12 Power Transfer Main Menu

    If you press the Power Trans button in Menu A, the Power
    Transfer main menu will appear(Figure 4–13).

    Note: The Power Transfer Control (PTC) feature must be enabled
    to display this menu.

    The PTC feature enables the PCC3201 to monitor the utility
    voltage (mains) and frequency forfailure, and control the opening
    and closing of the contacts (circuit breakers) for the utility (S1)
    andthe generator set (S2).

    If utility fails, the control will initiate the starting
    sequence (Figure 5–1), open S1 and close S2 tothe load. When
    utility returns, the load is retransferred to the utility (S1
    closes and S2 opens) andthe control initiates the generator set
    shutdown sequence.

    The symbol displayed in the middle of the Power Transfer main
    menu indicates whichbreaker (utility or generator set) is
    closed/opened to the load. The symbol shown in

    Figure 4-13 indicates that the utility breaker is closed and
    supplying power to the load.

    The Power Transfer main menu also indicates if the utility and
    the generator set are available toaccept load. When the control
    detects that either source is ready to accept load, Utility
    and/orGenset will be displayed in inverse video.

    The Power Transfer main menu has four submenu groups:

    •  Utility

    •  Status

    •  Transfer Control

    •  Genset

    To view system data, simply press the appropriate menu button to
    select the category. Afterpressing the desired menu button, refer
    to the following pages for detailed information related tothe
    selected category.

    Figure 4-13 Power Transfer Main Menu

    MENUBUTTONS 

    MENUBUTTONS

    PTC STATUS LINE

    DEG – 123 SYNCHRONIZING

    STATUS

    TRANSFER CONTROL

      UTILITY 

    GENSET

  • 8/18/2019 Operator Manual PCC 3201

    40/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 4-20 Section 4 – Control System

    4.12.1 PTC Status Line

    The top line of the graphical display is used to indicate the
    following PTC status:

    •  NOT ENABLED: PTC is not enabled. Control panel
    switch in O (Off) position.

    •  MANUAL:  Control panel switch is in Manual
    position. All PTC actions or generator setstart/stop actions are
    manually controlled.

    •  NORMAL UTIL: Load is connected to the utility.

    •  RETRAN: Retransfer of load to utility.

    •  RETRAN OVRD:  Immediate retransfer of load to
    utility due to generator set fault (e.g.,warning, derate, or
    shutdown with cooldown fault). The retransfer timer is ignored as
    is theretransfer inhibit.

    •  EMERG TEST:  Emergency Test sequence initiated
    through Remote Start switch withemergency start sequence enabled
    (TB8–3 terminal opened). Emergency test mode meansthat the
    generator set will continue to run even if a generator set warning
    or derate faultoccurs. This test can be performed with or without
    load (refer to Section 5.9). See Table 5–3

    for sequence of operation.•  TEST: Test sequence
    initiated through Remote Start switch with emergency start
    sequence

    disabled (TB8–3 terminal closed). Test mode is non–emergency,
    which means that aretransfer to utility will occur if any problems
    occur with the generator set while testing withload. This test can
    be performed with or without load (refer to Section 5.9). See Table
    5–3 forsequence of operation.

    •  EXERCISE: Exercise sequence initiated through
    control panel. This test can be performedwith or without load
    (refer to Section 5.9). A retransfer to utility will occur if any
    problemsoccur with the generator set during the exercise sequence.
    See Table 5–3 for sequence ofoperation.

    •  UTILITY FAIL: Utility has failed. (Initiates
    transfer of load to generator set if Off/Manual/Autoswitch is in
    Auto.)

  • 8/18/2019 Operator Manual PCC 3201

    41/90

    Generator Set Control System Publication
    0908-0104PowerCommand

    ™Control 3201 Issue 4 – 11-2009

    Section 4 – Control System Page 4-21

    4.12.2 Utility (PWR TRAN) Submenus

    If the Utility button in the Power Transfer Main menu is
    pressed, the Utility submenu will appear(Figure 4–14).

    •  Voltage L–L and L–N: Indicates utility voltage
    Line–to–Line and Line–to–Neutral. Note thatthe Line–to–Neutral
    column will not be displayed for a 3 phase/3 wire system. Accuracy
    1%.The voltage Line–to–Line (L1, L2 and L3) are measured between L1
    to L2, L2 to L3 and L3 toL1, respectively.

    •  Amps: L2 only. Accuracy 1%.

    •  Frequency: Utility frequency.

    •  kW, kVA and PF: Displays (L2 only) utility kW and
    kVA output (average and direction of flow)and power factor with
    leading/lagging indication. Accuracy 5%.

    Note: The PF reading will contain an asterisk if the power
    factor is leading(for example, *.30).

    Figure 4-14 Utility Sub-menu

    UTILITY:V L-L L-N AMPSL1 480 277L2 480 277 1320L3 480
    277FREQUENCY 60.0HZ

    UTILITY

    UTILITY:kWL kVA PF

    L1L2 125 175 .96L3TOT

  • 8/18/2019 Operator Manual PCC 3201

    42/90

    Publication 0908-0104 Generator Set Control SystemIssue 4 –
    11-2009 PowerCommand

    ™Control 3201

    Page 4-22 Section 4 – Control System

    4.12.3 Status (PWR TRAN) Submenus

    If the St

File Specifications:

951/951506-powercommand_3201.pdf file (14 Aug 2023)

Accompanying Data:

CUMMINS PowerCommand 3201 Controller PDF Service Manual (Updated: Monday 14th of August 2023 06:46:11 AM)

Rating: 4.1 (rated by 64 users)

Compatible devices: PowerComand 1301, PS0500, PowerCommand 3100, AvK MA330, Stamford MX322, PowerCommand FT-10, PowerCommand 3.3, PowerCommand 2.2.

Recommended Documentation:

Service Manual (Text Version):

(Ocr-Read Summary of Contents of some pages of the CUMMINS PowerCommand 3201 Document (Main Content), UPD: 14 August 2023)

  • CUMMINS PowerCommand 3201 User Manual

  • CUMMINS PowerCommand 3201 User Guide

  • CUMMINS PowerCommand 3201 PDF Manual

  • CUMMINS PowerCommand 3201 Owner’s Manuals

Recommended: 18H0500 — Z 54 Color Jetprinter Inkjet Printer, BE-32, CX 10, PL36PC50EC

Links & Tools

  • Metron, Inc. Date: 09/22/04 Approved: MH DOC#: 605 Revision: B Date: 06/14/06 Approved: MH Page: 1 of 24 MANUAL FOR MODEL MP300 to MP700 ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROLLERS Starting Serial No. «MA» T …

    MP300 24

  • Operator: Save these instructions for future use!FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.INSTALLATION INSTRUCTIONSTYPE 1127 HOT WATER CONTROL Surface Type — S.P.D.T.THESE CONTROLS MUST BE INSTALLE …

    1127 8

  • PBlack Red White [S[Specificationpecification]]MC-9200H/AFunction Auto recognition of cellPeak current 200 ASize 105 x 50x 36 mmWeight 325 gCell  LiPo 6-14 cells 22.2 〜 51.8 VBEC 5 〜 8 V / 10 ABrushless motor MC-9200H/AReceiverLEDTo CH3To free port Not useTo free port To drive battery Throt …

    MC-9200H/A 2

  • 1 ,17(5$&7,9(:+,7(%2$5’INTERACTIVE WHITE BOARD PC MODULE IWB-PC02 …

    IWB-PC02 9

Operating Impressions, Questions and Answers:

  • Service Manual

    Controller PowerCommand 3201

    English Original Instructions2010$7 (Issue )

  • iTable of Contents

    SECTION TITLE PAGE

    1. Introduction 1-1. . . . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
    . . .

    ABOUT THIS MANUAL 1-1. . . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . . . . . . . . . . TEST EQUIPMENT 1-1. . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
    . . . . HOW TO OBTAIN SERVICE 1-1. . . . . . . . . . . . . . . . .
    . . . . . . . . . . . . . . . . . . . .

    2. Control Operation 2-1. . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
    .

    GENERAL 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . . . . SEQUENCE OF
    OPERATION 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . CONTROL PANEL POWER ON/OFF MODES 2-1. . . . . . .
    . . . . . . . . . . . . . . CONTROL PANEL ASSEMBLY 2-4. . . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . . . . . READING FAULT
    CODES 2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . MENU DISPLAY AND SWITCHES 2-7. . . . . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . LANGUAGE/UNITS
    SELECTION MENU 2-8. . . . . . . . . . . . . . . . . . . . . . . . .
    . MAIN MENU 2-9. . . . . . . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . . . ENGINE SUBMENUS
    2-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . ALTERNATOR SUBMENUS 2-12. . . . . . . . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . . CONTROL SUBMENU
    2-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . HISTORY/ABOUT SUBMENUS 2-14. . . . . . . . . . .
    . . . . . . . . . . . . . . . . . . . . . . HISTORY/ABOUT SUBMENUS
    (CONT.) 2-15. . . . . . . . . . . . . . . . . . . . . . . . .
    PARALLEL DATA SUBMENU 2-16. . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . . . . . POWER TRANSFER MAIN/SUBMENUS 2-17. . .
    . . . . . . . . . . . . . . . . . . . . . . UTILITY (PWR TRAN)
    SUBMENUS 2-19. . . . . . . . . . . . . . . . . . . . . . . . . . .
    . . STATUS (PWR TRAN) SUBMENUS 2-20. . . . . . . . . . . . . . . .
    . . . . . . . . . . . . . TRANSFER CONTROL (PWR TRAN) SUBMENU 2-21.
    . . . . . . . . . . . . . . . . GENSET (PWR TRAN) SUBMENUS 2-22. .
    . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3. Control Calibration and Adjustment 3-1. . . . . . . . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . . .

    GENERAL 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . . . . PARALLELING and
    NONPARALLELING 3-1. . . . . . . . . . . . . . . . . . . . . . . . .
    SOFTWARE CALIBRATIONS 3-1. . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . . . . . . MODIFYING SETUP/ADJUST SUBMENUS 3-1.
    . . . . . . . . . . . . . . . . . . . . . . . SETUP MENUS 3-3. . .
    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . . GOVERNING/VOLT REG SUBMENU 3-4. . . . . . . .
    . . . . . . . . . . . . . . . . . . . . . CUSTOMER FAULTS SUBMENUS
    3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
    CALIBRATION SUBMENUS 3-8. . . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . . . . . . ISOLATED BUS SUBMENUS 3-11. . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UTILITY
    SUBMENUS 3-17. . . . . . . . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . . . . . . POWER TRANSFER CONTROL MAIN MENUS
    3-19. . . . . . . . . . . . . . . . . . . UTILITY SENSORS SUBMENUS
    3-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
    GENSET SENSORS SUBMENUS 3-22. . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . . TIMERS SUBMENU 3-24. . . . . . . . . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
    TEST/EXERCISE SUBMENU 3-26. . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . . . . . ADJUST SUBMENU 3-28. . . . . . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
    CALIBRATION PROCEDURE 3-29. . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . . . . .

  • ii

    SECTION TITLE PAGECONTROL BOX WIRING 3-31. . . . . . . . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . . . . . RUN RELAYS
    (K11, K12, K13) 3-33. . . . . . . . . . . . . . . . . . . . . . . .
    . . . . . . . . . . ALARM RELAY (K16) 3-34. . . . . . . . . . . . .
    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MAGNETIC
    SPEED PICKUP UNIT (MPU) INSTALLATION 3-35. . . . . . . . .

  • vIMPORTANT SAFETY INSTRUCTIONS

    SAVE THESE INSTRUCTIONS This manual containsimportant
    instructions that should be followed duringinstallation and
    maintenance of the generator set andbatteries.

    Before operating the generator set (genset), read theOperators
    Manual and become familiar with it and theequipment. Safe and
    efficient operation can beachieved only if the equipment is
    properly operatedand maintained. Many accidents are caused by
    failureto follow fundamental rules and precautions.

    The following symbols, found throughout this manual,alert you to
    potentially dangerous conditions to the oper-ator, service
    personnel, or the equipment.

    This symbol warns of immediatehazards which will result in
    severe personal in-jury or death.

    WARNING This symbol refers to a hazard or un-safe practice which
    can result in severe person-al injury or death.

    CAUTION This symbol refers to a hazard or un-safe practice which
    can result in personal injuryor product or property damage.

    FUEL AND FUMES ARE FLAMMABLE

    Fire, explosion, and personal injury or death can resultfrom
    improper practices.

    DO NOT fill fuel tanks while engine is running, un-less tanks
    are outside the engine compartment.Fuel contact with hot engine or
    exhaust is a potentialfire hazard.

    DO NOT permit any flame, cigarette, pilot light,spark, arcing
    equipment, or other ignition sourcenear the generator set or fuel
    tank.

    Fuel lines must be adequately secured and free ofleaks. Fuel
    connection at the engine should bemade with an approved flexible
    line. Do not use zinccoated or copper fuel lines with diesel
    fuel.

    Be sure all fuel supplies have a positive shutoffvalve.

    Be sure battery area has been well-ventilated priorto servicing
    near it. Lead-acid batteries emit a highlyexplosive hydrogen gas
    that can be ignited by arc-ing, sparking, smoking, etc.

    EXHAUST GASES ARE DEADLY

    Provide an adequate exhaust system to properlyexpel discharged
    gases away from enclosed orsheltered areas and areas where
    individuals arelikely to congregate. Visually and audibly
    inspectthe exhaust daily for leaks per the maintenanceschedule.
    Make sure that exhaust manifolds are se-cured and not warped. Do
    not use exhaust gases toheat a compartment.

    Be sure the unit is well ventilated. Engine exhaust and some of
    its constituents are

    known to the state of California to cause cancer,birth defects,
    and other reproductive harm.

    MOVING PARTS CAN CAUSE SEVEREPERSONAL INJURY OR DEATH

    Keep your hands, clothing, and jewelry away frommoving
    parts.

    Before starting work on the generator set, discon-nect battery
    charger from its AC source, then dis-connect starting batteries,
    negative () cable first.This will prevent accidental starting.

    Make sure that fasteners on the generator set aresecure. Tighten
    supports and clamps, keep guardsin position over fans, drive belts,
    etc.

    Do not wear loose clothing or jewelry in the vicinity ofmoving
    parts, or while working on electrical equip-ment. Loose clothing
    and jewelry can becomecaught in moving parts.

    If adjustment must be made while the unit is run-ning, use
    extreme caution around hot manifolds,moving parts, etc.

    DO NOT OPERATE IN FLAMMABLE ANDEXPLOSIVE ENVIRONMENTS

    Flammable vapor can cause an engine to overspeed andbecome
    difficult to stop, resulting in possible fire, explo-sion, severe
    personal injury and death. Do not operate agenset where a flammable
    vapor environment can becreated by fuel spill, leak, etc., unless
    the genset isequipped with an automatic safety device to block the
    airintake and stop the engine. The owners and operators ofthe
    genset are solely responsible for operating the gen-set safely.
    Contact your authorized Cummins PowerGeneration distributor for
    more information.

  • vi

    ELECTRICAL SHOCK CAN CAUSESEVERE PERSONAL INJURY OR DEATH

    Remove electric power before removing protectiveshields or
    touching electrical equipment. Use rub-ber insulative mats placed
    on dry wood platformsover floors that are metal or concrete when
    aroundelectrical equipment. Do not wear damp clothing(particularly
    wet shoes) or allow skin surface to bedamp when handling electrical
    equipment. Do notwear jewelry. Jewelry can short out electrical
    con-tacts and cause shock or burning.

    Use extreme caution when working on electricalcomponents. High
    voltages can cause injury ordeath. DO NOT tamper with
    interlocks.

    Follow all applicable state and local electricalcodes. Have all
    electrical installations performed bya qualified licensed
    electrician. Tag and lock openswitches to avoid accidental
    closure.

    DO NOT CONNECT GENERATOR SET DIRECT-LY TO ANY BUILDING
    ELECTRICAL SYSTEM.Hazardous voltages can flow from the generator
    setinto the utility line. This creates a potential for
    elec-trocution or property damage. Connect onlythrough an approved
    isolation switch or an ap-proved paralleling device.

    GENERAL SAFETY PRECAUTIONS

    Coolants under pressure have a higher boiling pointthan water.
    DO NOT open a radiator or heat ex-changer pressure cap while the
    engine is running.To prevent severe scalding, let engine cool
    downbefore removing coolant pressure cap. Turn capslowly, and do
    not open it fully until the pressure hasbeen relieved.

    Used engine oils have been identified by some stateor federal
    agencies as causing cancer or reproduc-tive toxicity. When checking
    or changing engine oil,take care not to ingest, breathe the fumes,
    or con-tact used oil.

    Keep multi-class ABC fire extinguishers handy.Class A fires
    involve ordinary combustible materialssuch as wood and cloth; Class
    B fires, combustibleand flammable liquid fuels and gaseous fuels;
    ClassC fires, live electrical equipment. (ref. NFPA No. 10).

    Make sure that rags or combustible material are notleft on or
    near the generator set.

    Make sure generator set is mounted in a manner toprevent
    combustible materials from accumulatingunder or near the unit.

    Remove all unnecessary grease and oil from theunit. Accumulated
    grease and oil can cause over-heating and engine damage which
    present a poten-tial fire hazard.

    Keep the generator set and the surrounding areaclean and free
    from obstructions. Remove any de-bris from the set and keep the
    floor clean and dry.

    Do not work on this equipment when mentally orphysically
    fatigued, or after consuming any alcoholor drug that makes the
    operation of equipment un-safe.

    Substances in exhaust gases have been identifiedby some state or
    federal agencies as causing can-cer or reproductive toxicity. Take
    care not to breathor ingest or come into contact with exhaust
    gases.

    Do not store any flammable liquids, such as fuel,cleaners, oil,
    etc., near the generator set. A fire orexplosion could result.

    Wear hearing protection when near an operatinggenerator set.

    To prevent serious burns, avoid contact with hotmetal parts such
    as radiator system, turbo chargersystem and exhaust system.

    KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE

  • 1-1

    1. Introduction

    ABOUT THIS MANUAL

    This manual provides PowerCommand Control3201 (PCC) calibration
    and adjustment proce-dures, control operation, alternator test and
    repairprocedures.

    Operating and maintenance instructions are in theapplicable
    Operators Manual.

    Read Important Safety Instructions and carefullyobserve all
    instructions and precautions in thismanual.

    TEST EQUIPMENTTo perform the test procedures in this manual,
    thefollowing test equipment must be available True RMS meter for
    accurate measurement of

    small AC and DC voltages. Battery Hydrometer Jumper Leads
    Tachometer or Frequency Meter Wheatstone Bridge or Digital Ohmmeter
    Variac Load Test Panel Megger or Insulation Resistance Meter
    InPower Service Tool (PC based genset ser-

    vice tool)

    HOW TO OBTAIN SERVICEAlways give the complete Model,
    Specification andSerial number of the generator set as shown on
    thenameplate when seeking additional service infor-mation or
    replacement parts. The nameplate is lo-cated on the side of the
    generator output box.

    WARNING Incorrect service or replacement ofparts can result in
    severe personal injury ordeath, and/or equipment damage. Service
    per-sonnel must be trained and experienced to per-form electrical
    and mechanical service. Readand follow Important Safety
    Instructions, onpages iii and iv.

  • 1-2

    THIS PAGE LEFT INTENTIONALLY BLANK

  • 2-1

    2. Control Operation

    GENERAL

    The following describes the function and operationof the
    PowerCommand Control 3200 (PCC). All in-dicators, control
    switches/buttons and graphicaldisplay are located on the face of
    the control panelas illustrated in Figure 2-1.

    Normally, generator set configuration options areset at the
    factory. When a new control is installed ona generator set or when
    parts are replaced, the con-trol must be configured for that
    generator set. Setupand calibration procedures are described in
    Sec-tion 3.

    SEQUENCE OF OPERATION

    When the PowerCommand control is in the AUTOmode, it will cause
    the generator set to start on re-ceiving a signal from a remote
    device. The controlwill initiate a starter cranking signal and
    verify thatthe engine is rotating. The control will provide
    suffi-cient fuel to the engine to accelerate to start discon-nect
    speed. On reaching that speed, the control willramp the generator
    set to idle (warm-up) or ratedspeed and voltage.

    On reaching rated speed and voltage, the controlchecks the
    system bus voltage. If no bus voltage is

    present, it will wait for a pulse from a remote MasterFirst
    Start Sensor. On receiving that pulse, the con-trol will signal the
    paralleling breaker to close.

    If bus voltage is present, the control will check forproper
    phase rotation, adjust the generator set tothe bus voltage and
    frequency level, and then syn-chronize the generator set to the
    system bus. Whena synchronous condition is achieved, the control
    willsend a signal to close the paralleling breaker.

    When the paralleling breaker is closed, the genera-tor set will
    assume its proportional share of the totalload on the system
    bus.

    CONTROL PANEL POWER ON/OFFMODES

    The power on/off modes of the control panel and op-erating
    software are Power On, Screen Saver andSleep/Awake.

    Power On Mode: In this mode, power is continu-ously supplied to
    the control panel. The controlsoperating software and control panel
    LEDs/graphi-cal display will remain active until the Screen
    Savermode is activated.

  • 2-2

    Screen Saver Mode: Power to the graphical dis-play will be
    removed after 10 minutes (generator setnot running or running). The
    10 minute timer resetsand begins after each control panel action
    (any but-ton or switch selection) or signal received by the
    op-erating software. The bottom LEDs of the AnalogAC Metering Panel
    (bar graphs) may remain on dur-ing Screen Saver mode, indicating
    that the operat-ing software is active (Awake mode).

    When a Warning signal is sensed by the PCC (forexample, low
    coolant temp), the control will displaythe warning message. The
    control will remain activeuntil the Fault Acknowledge button is
    pressed toclear the warning message and start the 10
    minutetimer.

    Sleep/Awake Mode: In the Sleep mode, the con-trols operating
    software is inactive and the LEDsand the graphical display on the
    control panel are alloff. Sleep mode is a feature that is used to
    reducebattery power consumption when the control is notbeing
    used.

    In Off mode, Sleep mode is activated when thereare no
    unacknowledged faults and Screen Savermode is active.

    In Auto mode, Sleep mode can be enabled or dis-abled. When
    shipped from the factory, it is disabled.You can enable Sleep mode
    by making thesechanges:

    Use InPower service tool to set Auto Sleep En-able to Sleep in
    Auto.

    Set switch S1 on the Genset/Paralleling Cardto Sleep/Off. This
    switch is located next to con-nector J8 and relay K9.

    If these conditions are not met, Sleep mode is dis-abled in Auto
    mode.

    The graphical display can enter Screen Saver modeeven if Sleep
    mode is disabled.

    If Sleep mode is enabled in Auto mode, Sleep modeis activated
    when there are no unacknowledgedfaults and Screen Saver mode is
    active.

    The operating software is initialized and the controlpanel LEDs
    and graphical display are turned on inresponse to one of the
    following:

    Moving/pressing any control panel switch/but-ton. (If Sleep mode
    is enabled in Auto mode,the control will remain asleep if Sleep
    modewas previously active in Off mode.)

    Receiving a remote start input signal (genera-tor set in Auto
    mode)

    Receiving an active DCD signal on the RS-232port.

    Modem RI latch becoming active. Digital display waking up.
    Lonworks (backplane) wakeup becoming ac-

    tive.

    Customer fault 2 or 3 only (shutdown or warn-ing indicator is
    on).

    Dial Out process becoming active.To activate the control and
    view the menu displaywithout starting the generator set, press any
    buttonon the control panel.

  • 2-3

    DISPLAY MENUSELECTION BUTTONS

    (1 of 6)

    0/MANUAL/AUTOSWITCH

    REMOTE START,NOT IN AUTO,SHUTDOWN,

    WARNINGSTATUS INDICATORS

    GRAPHICALDISPLAY

    ANALOG ACMETERING

    PANEL

    OPERATOR PANEL SWITCH PANEL

    MANUAL RUN/STOP BUTTON& INDICATOR

    EXERCISEBUTTON &INDICATOR

    FAULTACKNOWLEDGE

    BUTTON

    PANEL LAMP/LAMP TEST

    BUTTON

    EMERGENCYSTOP PUSH

    BUTTON

    0

    FIGURE 2-1. CONTROL PANEL ASSEMBLY (FULL-FEATURED)

  • 2-4

    CONTROL PANEL ASSEMBLY

    The control panel assembly (Figure 2-1) consist oftwo panels,
    the Operator Panel and the Switch Pan-el.

    Dependent on site requirements, the Operator Pan-el is either
    mounted on the control panel assembly(full-featured) as shown in
    Figure 2-1 or containedin a separate enclosure and mounted remotely
    ofthe control panel assembly.

    The function of several buttons on the control panelwill vary
    dependent on the location of the controlpanel (remote or local of
    the control panel assem-bly). If the function differs, it is noted
    as either re-mote or local operator panel in the button
    de-scription.

    Operator Panel

    The operator panel contains the following compo-nents:

    Analog AC Metering Panel: This panel simulta-neously displays
    3-phase line to line AC volts andcurrent, kW, power factor and
    frequency.

    The meter panel is composed of a series of LEDs,that are
    configured in bar graphs for each function.The LEDs are color
    coded, with green indicatingnormal range values, amber for warning
    levels andred for shutdown conditions.

    Scales for each function are in % of nominal values.Resolution
    is 1% for values close to nominal, and in-creases at values further
    from nominal.

    Graphical Display: The graphical display is capa-ble of
    displaying up to 9-lines of data with approxi-mately 27 characters
    per line. The display is used toview the menus of the menu-driven
    operating sys-tem.

    The top three lines of the graphical display containthe
    following control information in the order de-scribed:

    State Line modes of operation, such asStopped, Time Delay To
    Start, Warm Up AtIdle, etc. (see Figure 2-2), and paralleling
    op-erations, such as Standby, Dead BUS Close,Synchronize, Load
    Share and Load Govern.

    Action Line system actions, such as Warning,Derate, Shutdown
    Cool-down and Shutdown,and fault codes.

    Description Line Fault code messages.Display Menu Selection
    Buttons: Six momentarybuttonsthree on each side of the graphical
    dis-play windoware used to navigate through the sys-tem control
    menus and to adjust generator set pa-rameters. The button is active
    when the messageadjacent to the button is highlighted (displayed in
    in-verse video).

  • 2-5

    Switch Panel

    The switch panel contains the following compo-nents:

    Emergency Stop Button: Push the button in foremergency shutdown
    of the engine. If the engine isnot running, pushing the button in
    will prevent thestarting of the engine, regardless of the start
    signalsource (local or remote).

    To reset:1. Pull the button out.2. Move the 0/Manual/Auto switch
    to 0. 3. Press the front panel Fault Acknowledge

    button.4. Select Manual or Auto, as required.

    Remote Start Indicator: This green lamp is litwhenever the
    control is receiving a remote run sig-nal. When flashing, it
    indicates a load demand stopmode.

    Not in Auto Indicator: This red lamp flashes con-tinuously when
    the 0/Manual/Auto switch is not inthe Auto position. (If in Auto
    position and lamp isflashing, service is required.)

    Shutdown Status Indicator: This red lamp is litwhenever the
    control detects a shutdown condition.The generator set can not be
    started when this lampis on. After the condition is corrected,
    shutdown in-dicators can be reset by turning the
    0/Manual/Autoswitch to the 0 position, and pressing the Fault
    Ac-knowledge button.

    Dependent upon the specific fault that occurs, theengine may or
    may not shut down immediately. Afault that could cause engine
    damage, causes animmediate engine shutdown (bypasses
    enginecool-down sequence). All other faults would allowthe engine
    to run during the cool-down sequencebefore engine shutdown. In this
    case, the ShutdownStatus Indicator blinks during the cooldown
    period.

    Warning Status Indicator: This yellow lamp is litwhenever the
    control detects a warning condition.After the condition is
    corrected, warning indicatorscan be reset by pressing the Fault
    Acknowledgebutton. (It is not necessary to stop the generator setif
    the fault becomes inactive during genset opera-tion.)

    Fault Acknowledge: Press this button to acknowl-edge warning and
    shutdown messages after thefault has been corrected.

    To acknowledge a Warning message, the 0/Manu-al/Auto switch can
    be in any position. (It is not nec-essary to stop the generator set
    to acknowledge aninactive Warning condition.) To acknowledge
    ashutdown message with this button, the 0/Manual/Auto switch must
    be in the 0 (Off) position.

    This button is also used to blink a fault code if theShutdown or
    Warning Status Indicator is lit. (Thisfunction is used when the
    control does not contain agraphical display.) Refer to Reading
    Fault Codes inthis section, which describes how to use this
    buttonfor interpreting fault codes.

    Panel Lamp/Lamp Test Button: Press this buttonto turn on or off
    the panel lamp. Press and holddown this button for three seconds or
    more to turnall control panel LEDs on to make sure all lamps
    illu-minate. The illumination will shut off after releasingthe
    button.

    Exercise Button: Press this button to initiate a pre-programmed
    exercise sequence. To start the exer-cise sequence, press and hold
    down the Exercisebutton and move the O/Manual/Auto switch fromAuto
    to Manual and back to Auto or from Manual toAuto.

    Manual Run/Stop Button: This button starts andstops the set
    locally and will bypass Time Delay toStart and Stop sequences. The
    0/Manual/Autoswitch must be in the Manual position to enable
    thisbutton.

    0/Manual/Auto Switch: Manual position enablesthe use of the
    switch panel Manual Run/Stop but-ton.

    Auto position enables start/stop control of the en-gine from a
    remote location. (Disables the use of theswitch panel Manual
    Run/Stop button.)

    0 (Off) position prevents the starting of the set (localor
    remote). If moved to 0 during set operation, willcause an immediate
    engine shutdown (bypassescool-down timers). This hot shutdown
    should beavoided, if possible, to help prolong the life of
    theengine. Hot shutdowns are logged by the systemsoftware.

  • 2-6

    READING FAULT CODES

    If the genset contains the optional graphical displayand a fault
    occurs, the fault code/message will bedisplayed in the display
    Description Line (Figure2-2). If the control does not contain the
    graphicaldisplay, the fault code is read from the Warning
    andShutdown status indicators.

    Reading Fault codes Using Warning/ShutdownIndicators: If the
    Warning or Shutdown status indi-cator is lit, press and hold the
    Fault Acknowledgebutton and release after one second or more.
    Afterone second, the Shutdown lamp will begin to blinkthe active
    fault code(s) as follows.

    The Warning lamp is used to indicate the start of anew code. The
    Warning lamp will remain on for 2seconds, followed by the Shutdown
    lamp blinkingthe fault code. This sequence occurs three times
    foreach code. The fourth flash of the Warning lamp in-dicates the
    beginning of the second fault code.

    There are distinct pauses between repetitions of thecode blink
    transmissions of the Shutdown lamp.

    A three digit fault code is indicated by three sets ofblinks
    separated by a two second pause. The firstset corresponds to the
    hundreds position, the sec-ond to the tens position and the third
    to the ones dig-it. Example for Code No. 213:

    Shutdown LED:blink-blink-pause-blink-pause-blink-blink-blink

    Warning LED:blink (2 seconds)

    The light will display the fault codes (active or inac-tive) in
    succession, starting with the most recent. Upto 32 (unacknowledged)
    fault codes can be storedin control panel memory.

    To return the control to the most recent fault code,press and
    release the Fault Acknowledge button(less than one second) and
    repeat procedure.

    When the fault code is acknowledged and cor-rected, the recorded
    fault will be deleted from theLED fault log, but will remain in a
    data log that main-tains a fault code history. (The InPower service
    toolis required to view this data log.)

  • 2-7

    MENU DISPLAY AND SWITCHES

    Figure 2-2 shows the graphical display and themenu selection
    buttons.

    Graphical Display: The graphical display is capa-ble of
    displaying up to 9-lines of data with approxi-mately 27 characters
    per line. The display is used toview the menus of the menu-driven
    operating sys-tem. Refer to the menu trees later in this
    section.The display is also used to show the following sys-tem
    information:

    State Line modes of operation, such asStopped, Time Delay To
    Start, Warm Up AtIdle, etc., and paralleling operations, such
    asStandby, Dead BUS Close, Synchronize, etc.

    Action Line system actions, such as Warning,Derate, Shutdown
    Cool-down and Shutdown,and fault codes.

    Description Line Fault code/status mes-sages.

    Menu Buttons: Six momentary buttonsthree oneach side of the
    graphical display windowareused to navigate through the system
    control menusand to adjust generator set parameters. The buttonis
    active when the message or symbol adjacent tothe switch is
    highlighted (displayed in inverse vid-eo). The displayed message or
    symbol indicatesthe function of the button.

    In the graphical display, the symbol indicatesthat selecting the
    adjacent button causes the operat-ing program to go to the next
    menu displayasshown in the menu diagrams.

    In the graphical display, the symbol indicatesthat selecting the
    adjacent button causes the operat-ing program to go back to the
    previous menu display.

    In the graphical display, the symbol indicatesthat selecting the
    adjacent button causes the operat-ing program to go back to Main
    Menu A (Figure 2-4).

    STATE LINE

    ACTION LINE

    MENU DISPLAYAREA

    GRAPHICALDISPLAY

    MENUBUTTONS

    DESCRIPTION LINE

    MENUBUTTONS

    FIGURE 2-2. GRAPHICAL DISPLAY AND MENU SELECTION BUTTONS

  • 2-8

    LANGUAGE/UNITS SELECTION MENU

    During any control panel operation, you can selectone of three
    languages and change how units aredisplayed by pressing the two
    lower menu buttons(one on each side of display). When pressing
    thesetwo buttons simultaneously, the language/unitsmenu will appear
    (Figure 2-3). After making desiredselections, press the ENTER
    button in this menu tochange and save the selections.

    Use the + buttons to select the desired option foreach field.
    Use the arrow () button to move to thenext field. Selected field is
    highlighted.

    Language: Used to select desired language (de-fault =
    English).

    Location: This selection must be set to Local whenthe graphical
    display is mounted on the generatorset front control panel or
    Remote when mounted re-motely from the generator set.

    The Local/Remote selection determines which but-tons in the
    Control submenu (page 2-13) are active(displayed).

    Temp: Used to select F or C for temperature read-ings.

    Pressure Fluid: Used to select PSI, KPA, BAR orIN for pressure
    readings.

    Pressure Gas: Used to select INHG or MMHG forpressure
    readings.

    Flow Air: Used to select CFM or CMM for air flowreadings.

    ENTER

    LANGUAGEENGLISHLOCATIONLOCAL

    TEMP FPRESS FLDPSI

    PRESS GASINHGFLOW AIRCFM

    +

    FIGURE 2-3. LANGUAGE/UNITS MENU

  • 2-9

    MAIN MENU

    Figure 2-4 shows the main menus (Menu A andMenu B) of the system
    control. The two main menusare used to divide the system submenus
    into majorcategories, such as, Engine Data, Alternator
    Data,Control, etc.

    To view system data, simply press the appropriatemenu button to
    select the category. After pressingthe desired menu button, refer
    to the page numbershown in Figure 2-4 for detailed information
    relatedto the selected category.

    In the following figures, the boxed/highlighted fieldindicates
    that the adjacent menu button is active.Also, the submenus are
    shown in the order in whichthey are displayed when scrolling up or
    down .

    Adjust Button

    The Adjust submenu is intended for qualified sitepersonnel only.
    Note that a password may be as-signed to allow only authorized
    operators to modifythis data. (Password is not required if not
    assigned.)

    Setup Button

    The Setup submenu is described in Section 3.

    The Adjust and Setup submenus can be viewed,but not modified
    without entering the correct pass-words.

    _\_ Button (Paralleling Applications Only)

    When displayed, indicates that the feature for gen-erator set
    paralleling applications is installed. Thisbutton is used to open
    and close the generator setcircuit breaker (CB). The symbol
    indicates if the CBis opened or closed. Opened _\_, push to
    close.Closed __, push to open.

    With the control panel 0/Manual/Auto switch in theAuto position,
    the opening and closing of the CB iscontrolled by the control
    system software. The CBsymbol will indicate an open or closed CB,
    but thebutton will be inactive when the control is in Auto.

    In the Manual position, the CB can only be closedby using this
    button. When manually closed and theCB opens, it must be closed
    again by using this but-ton. To close the CB, press and hold the
    button untilthe symbol indicates a closed CB. (CB close will oc-cur
    only when setup conditions allow dead bus orgenerator synchronized
    with bus.)

    Power Trans Button (Power TransferControl Applications Only)

    When displayed, indicates that the Power TransferControl (PTC)
    feature is installed. Refer to page2-17 for PTC Data submenu
    description. The PTCsetup submenu is described in Section 3.

  • 2-10

    ENGINE

    ALTERNATOR

    CONTROL

    MORE>>

    POWER TRAN or _\_

    HISTORY/ABOUT

    PAGE2-11

    PAGE2-12

    PAGE2-13

    PAGE2-14

    Page2-9

    MENUB

    GRAPHICALDISPLAY

    MENUBUTTONS

    MENUBUTTONS

    SETUP

    ADJUST

    PARALLEL DATA

    BACK

  • 2-11

    ENGINE SUBMENUS

    If you press the ENGINE button in Menu A, the En-gine submenus
    will appear (Figure 2-5).

    The first submenu displays general information thatapplies to
    all gensets (coolant temp, oil pressure,etc.) The data in the
    remaining submenu(s) will varyaccording to the type and number of
    sensors pro-vided with the engine.

    COOLANT TEMP 180 FOIL PRESSURE 75PSI

    ENGINE SPEED 1800RPMBATTERY 29.1VDC

    MANF TEMP 75 FMANF PRESS ABS 180INHGRAIL PRESS ABS 180PSIPUMP
    PRESS ABS 291PSIFUEL INLET TEMP 172 FCOOLANT PRESSURE 59PSI

    ENGINE

    BLOWBY FLOW 25CFMTIMING PRESS 50PSIAFTERCOOLER TEMP 76 FAMBIENT
    PRESS 88INHG

    FIGURE 2-5. ENGINE SUBMENUS

  • 2-12

    ALTERNATOR SUBMENUS

    If you press the ALTERNATOR button in Menu A,the Alternator Data
    submenus will appear (Figure2-6).

    Voltage L-L and L-N: Indicates voltage Line-toLine and
    Line-to-Neutral. Note that the Line-to-Neu-tral column will not be
    displayed for a 3 phase/3 wiresystem. Accuracy 1%.

    The voltage Line-to-Line (L1, L2 and L3) are mea-sured between
    L1 to L2, L2 to L3 and L3 to L1, re-spectively.

    Amps: All phases. Accuracy 1%.

    Frequency: Generator set output frequency.

    AVR DUTY CYCLE: Displays voltage regulator(drive) level in
    percentage of maximum.

    kW, kVA and PF: Displays generator set kW andkVA output (average
    and individual phase, and di-rection of flow) and power factor with
    leading/lag-ging indication. Accuracy 5%.

    The PF reading will contain an asterisk if the powerfactor is
    leading (for example,*.30).

    kW kVA PFL1 350 500 .80L2 350 500 .80L3 350 500 .80TOT1050 1500
    .80

    ALTERNATOR

    V L-L L-NAMPSL1 480 2771340L2 480 2771290L3 480 2771260

    FREQUENCY60.0 HZAVR DUTY CYCLE10.3 %

    FIGURE 2-6. ALTERNATOR SUBMENUS

  • 2-13

    CONTROL SUBMENU

    If you press the CONTROL button in Menu A, theControl submenu
    will appear (Figure 2-7).

    Local CONTROL Submenu Function

    When the operator panel is mounted on the controlpanel assembly,
    the Run Mode Idle/Rated button isactive (displayed). Note in Figure
    2-7 that this but-ton is not displayed in remote applications.

    The shaded area in Figure 2-7 displays the se-lected/active mode
    of operation, either IDLE orRATED.

    Remote CONTROL Submenu Functions

    When the operator panel (Figure 2-1) is mountedremotely of the
    control panel assembly, the menubuttons in the Control submenu are
    used to performthe following remote operations. (To activate
    thesemenu buttons for remote/local use, refer to page2-8.)

    The 0/Manual/Auto switch must be in the Auto posi-tion to
    activate the Remote Menu Buttons of the Con-trol submenu.

    Remote START or STOP Button: This button isused to start and
    stop the generator set when theoperator panel is mounted in a
    remote location.

    When the generator set is operating, Stop will bedisplayed for
    this button and Start will be displayedwhen not operating.

    When the generator set is operating in the RemoteStart mode,
    removing the Remote Start commanddoes not shut off the engine if
    the load is 10 per cent,the cooldown timer is set to zero, and the
    control isconfigured for a single unit (not in parallel). The
    gen-erator set continues to operate until it runs out offuel, the
    Estop button is used, or the load is re-moved.

    Fault Acknowledge Button: Used to reset inactiveWarning
    messages, not Shutdown messages.

    Local/Remote CONTROL SubmenuFunction

    Bargraph Test: The function of this button remainsthe same and
    is not dependent on operator panellocation. This button
    sequentially lights the LEDs totest the bar graph display.

    Enable Sync: Displayed in paralleling applicationsonly. Intended
    for service personnel to turn off thesynchronizer for
    troubleshooting/testing purposes.

    CONTROL(Remote)

    START GENSET

    FAULT ACKNOWLEDGE

    CONTROL(Local)

    + RUN MODE IDLE

    BARGRAPH TEST

    BARGRAPH TEST

    ENABLE SYNC

    ENABLE SYNC

    FIGURE 2-7. CONTROL SUBMENU

  • 2-14

    HISTORY/ABOUT SUBMENUS

    If you press the HISTORY/ABOUT button in MenuA, the
    History/About submenus will appear (Figure2-8).

    HISTORY: The control maintains a data log of thenumber of engine
    starts and number of operatinghours for the engine and control, and
    the megawattand maximum torque hours of the generator set.This
    information is stored in non-volatile memoryand will not be deleted
    due to loss of battery power.

    ABOUT: The About submenus provide the follow-ing generator set
    information.

    Genset model and wattage (kW/MW) Output voltage and WYE, DELTA
    or SINGLE Frequency 50 or 60 Hz Rating: Standby, Prime or Base
    Version level of the controller and panel operat-

    ing software.

    STARTS 533ENGINE HOURS1236CONTROL HOURS7879KWHRS 890

    HISTORY/ABOUT

    HISTORY-HRS@ %MAX
    TORQUE12345@0-923455@50-5912345@10-1912345@60-6912345@20-2912345@70-7912345@30-3912345@80-89

    MODEL 1750DQKBVOLTAGE416 WYE

    FREQUENCY60RATINGSTANDBY

    CONTROLLER VERSIONRTOPDN30008.DFABATSAPR 23 1999

    OP PANEL VERSIONRTOP1.09 AUG 17 1999

    BATS1.02 MAY 6 1999

    CONTINUED TO NEXT PAGE

    FIGURE 2-8. HISTORY/ABOUT SUBMENUS

  • 2-15

    HISTORY/ABOUT SUBMENUS (CONT.)

    FAULT HISTORY: The control maintains a data logof all fault
    conditions as they occur, and time stampsthem with the control and
    engine operating hours.

    Up to 32 (unacknowledged) fault codes can bestored in control
    panel memory. After the fault is ac-knowledged and corrected, the
    recorded fault willbe deleted from the control panel memory, but
    willremain in a data log that maintains a fault code his-tory. (The
    InPower service tool is required to viewthis data log.)

    The Fault History display line: 1 of 24 indicates that24 faults
    are recorded and that the most recent fault(1) detected by the
    controller is displayed.

    The Occurrences display line: In this example, 5 in-dicates that
    this is the fifth occurrence of this fault.(The InPower service
    tool is required to review thelast four faults of this code.)

    The Occurrences number is incremented for eachnew occurrence of
    the same fault. The controllermust detect that the original sensed
    fault is cor-rected before it will increment the occurrence num-ber
    for that fault.

    For example, when a Low Oil Pressure fault is de-tected, the
    controller will increment the Occurrencesnumber by 1. This fault
    will remain active until thefault is acknowledged and the
    controller detects thatthe fault is corrected. An active fault will
    prevent thecontroller from incrementing the Occurrences num-ber
    each time the engine is started. When the con-troller detects that
    the oil pressure is normal the faultwill become inactive, allowing
    the occurrences num-ber to be incremented for the next detected Low
    OilPressurefault.

    FAULT HISTORY: 1 OF 24CNTL HOURS459OCCURRENCES5ENGINE
    HOURS334FAULT CODE1437(FAULT DESCRIPTION)

    HISTORY/ABOUT (CONT.)

    +

    FIGURE 2-8. HISTORY/ABOUT SUBMENUS (CONT.)

  • 2-16

    PARALLEL DATA SUBMENUIf you press the PARALLEL DATA button in
    MenuB, the Parallel Data submenu will appear (Figure2-9). This menu
    is displayed in paralleling applica-tions only.

    PARALLEL DATA STATUS LINE: The top line ofthe graphical display
    is used to indicate the follow-ing PARALLEL DATA status:

    STANDBY: Indicates no paralleling activity isoccurring at
    present.

    DEAD BUS CLOSE: Indicates first genset insystem to close to
    bus.

    SYNCHRONIZE: Genset is synchronizing tobus.

    LOAD SHARE: Genset has closed to bus andis sharing load with
    other gensets in system.

    LOAD GOVERN: Genset closed to bus in par-allel with utility
    (mains).

    BUS Voltage L-L: The BUS voltage Line-to-Line(L1, L2 and L3) are
    measured between L1 to L2, L2to L3 and L3 to L1, respectively.

    BUS/GEN HZ: BUS/GEN hertz.

    BUS/GEN SYNC STATUS: The bottom line of thegraphical display is
    used to indicate the followingBUS/GEN Sync status:

    NOT SYNCHRONIZING: Genset is in servicemode that does not allow
    auto sync feature.(Selected via InPower service tool deactivateto
    allow synchronization.)

    SYNCHRONIZING: Genset is synchronizing tobus.

    READY TO CLOSE: In manual mode, push cir-cuit breaker close
    button to close breaker.

    _\_ Button: Used to open and close the generatorset circuit
    breaker (CB). The symbol indicates if theCB is opened or closed.
    Opened _\_, push to close.Closed __, push to open.

    With the control panel 0/Manual/Auto switch in theAuto position,
    the opening and closing of the CB iscontrolled by the control
    system software. The CBsymbol will indicate an open or closed CB,
    but thebutton will be inactive when the control is in Auto.

    In the Manual position, the CB must be closed bythis button.
    When manually closed and the CBopens, it must be closed again by
    using this button.To close the CB, press and hold the button until
    thesymbol indicates a closed CB. (CB close will occuronly when
    setup conditions allow dead bus orgenerator synchronized with
    bus.)

    _\_

    V BUS GENL1 480 480L2 480 480L3 480 480HZ60.1 60.1

    DEG 122 NOT SYNCHRONIZING

    PARALLEL DATA

    LOAD GOVERN

    FIGURE 2-9. BUS DATA SUBMENU

  • 2-17

    POWER TRANSFER MAIN/SUBMENUS

    If you press the POWER TRANS button in MenuA, the Power Transfer
    main menu will appear (Fig-ure 2-10). The Power Transfer Control
    (PTC) fea-ture must be installed to display this menu.

    The PTC feature enables the PCC to monitor theutility voltage
    (mains) and frequency for failure andcontrol the opening and
    closing of the contacts (cir-cuit breakers) for the utility (S1)
    and the genset(S2).

    If utility fails, the control will initiate the genset start-ing
    sequence, open S1 and close S2 to the load.When utility returns,
    the load is retransferred to theutility (S1 closes/S2 opens) and
    the control initiatesthe genset shutdown sequence.

    The symbol displayed in the middle of the Pow-er Transfer main
    menu indicates which breaker(utility or genset) is closed/opened to
    the load. Thesymbol presently shown indicates that the
    utilitybreaker is closed and supplying power to the load.

    The Power Transfer main menu also indicates if theutility and
    the generator set are available to acceptload. When the control
    detects that either source isready to accept load, UTILITY and/or
    GENSET willbe displayed in inverse video.

    The Power Transfer main menu has four submenugroups. Refer to
    the page numbers shown in Figure2-10 for the Power Transfer submenu
    descriptions.

  • 2-18

    PTC Status Line

    The top line of the graphical display is used to indi-cate the
    following PTC status:

    NOT ENABLED: PTC is not enabled. Controlpanel switch in O (Off)
    position.

    MANUAL: Control panel switch is in Manualposition. All PTC
    actions or genset start/stopactions are manually controlled.

    NORMAL UTIL: Load is connected to the util-ity.

    RETRAN: Retransfer of load to utility. RETRAN OVRD: Immediate
    retransfer of load

    to utility due to genset fault (e.g., warning, der-ate, or
    shutdown w/cooldown fault). The re-transfer timer is ignored as is
    the retransfer in-hibit.

    EMERG TEST: Emergency Test sequence ini-tiated through Remote
    Start switch with emer-gency start sequence enabled (TB8-3
    terminalopened). Emergency test mode means that

    the genset will continue to run even if a gensetwarning or
    derate fault occurs. This test can beperformed with or without load
    (refer to TEST/EXERCISE submenu in Section 3).

    TEST: Test sequence initiated through RemoteStart switch with
    emergency start sequencedisabled (TB8-3 terminal closed). Test mode
    isnon-emergency, which means that a retransferto utility will occur
    if any problems occur withthe genset while testing with load. This
    test canbe performed with or without load (refer toTEST/EXERCISE
    submenu in Section 3).

    EXERCISE: Exercise sequence initiatedthrough control panel. This
    test can be per-formed with or without load (refer to
    TEST/EX-ERCISE submenu in Section 3). A retransfer toutility will
    occur if any problems occur with thegenset during the exercise
    sequence.

    UTILITY FAIL: Utility has failed. (Initiatestransfer of load to
    genset if O/MANUAL/AUTOswitch is in AUTO.)

    UTILITY

    STATUS

    TRANSFER CONTROL

    GENSET

    PAGE2-19

    PAGE2-20

    PAGE2-21

    MENUA

    PAGE2-22

    MENUBUTTONS

    MENUBUTTONS

    DEG 123 SYNCHRONIZING

    PTC STATUS LINE

    FIGURE 2-10. POWER TRANSFER MAIN MENU

  • 2-19

    UTILITY (PWR TRAN) SUBMENUS

    If you press the Utility button in the Power TransferMain menu,
    the Utility submenus will appear (Fig-ure 2-11).

    Voltage L-L and L-N: Indicates utility voltage Line-to Line and
    Line-to-Neutral. Note that the Line-to-Neutral column will not be
    displayed for a 3 phase/3wire system. Accuracy 1%.

    The voltage Line-to-Line (L1, L2 and L3) are mea-sured between
    L1 to L2, L2 to L3 and L3 to L1, re-spectively.

    Amps: L2 only. Accuracy 1%.

    Frequency: Utility frequency.

    kW, kVA and PF: Displays (L2 only) utility kW andkVA output
    (average and direction of flow) and pow-er factor with
    leading/lagging indication. Accuracy5%.

    The PF reading will contain an asterisk if the powerfactor is
    leading (for example, *.30).

    UTILITY:kW kVA PF

    L1L2 125 175 .96L3TOT

    UTILITY

    UTILITY:V L-L L-NAMPS

    L1480 277L2 480 2771320

    L3480 277FREQUENCY60.0 HZ

    FIGURE 2-11. UTILITY SUBMENUS

  • 2-20

    STATUS (PWR TRAN) SUBMENUS

    If you press the Status button in the Power Trans-fer Main menu,
    the Status submenus will appear(Figure 2-12).

    Connected: Indicates which source(s) is con-nected to the
    load.

    Available: Indicates when the correspondingsources have
    acceptable output voltage and fre-quency. Both can be available
    simultaneously.

    Volt L12: Indicates utility and generator set Line 1 toLine 2
    voltage.

    HZ: Utility and generator set output frequency.

    KW L2: Utility and generator set Phase B (L2) kWoutput.

    Transfer Inhibit: This feature is used to controlload transfer
    to the genset. When activated, loadtransfer to the genset will not
    take place if the utilityfails.

    Transfer inhibit is controlled by connecting a remotecontact
    between TB3-57 and TB3-58. Closing thecontact enables the feature
    and opening the con-tact disables it. When enabled, the event is
    dis-played on the graphical display.

    Retransfer Inhibit: This feature is used to preventthe PTC from
    automatically transferring the loadback to the utility. When
    activated, load transfer willnot take place unless the genset fails
    (RetransferInhibit is ignored if the genset fails).

    Retransfer inhibit is controlled by connecting a re-mote contact
    between TB3-64 and TB3-65. Closingthe contact enables the feature
    and opening thecontact disables it. When enabled, the event is
    dis-played on the graphical display.

    TRAN INHOFFRETRAN INHON

    STATUS

    UTILGENCONNECTEDYESNOAVAILABLEYESNOVOLT L12 4800

    HZ 60.00.0KW L2 4560

    FIGURE 2-12. STATUS SUBMENUS

  • 2-21

    TRANSFER CONTROL (PWR TRAN) SUBMENU

    If you press the TRANSFER CONTROL button inthe Power Transfer
    Main menu, the Transfer Con-trol submenu will appear (Figure
    2-13).

    The symbol displayed in the middle of theTRANSFER CONTROL
    submenu indicates whichbreaker (utility or genset) is closed/opened
    to theload. The symbol presently shown indicates that theutility
    breaker is closed and supplying power to theload.

    During genset operation in the manual mode, youcan manually
    transfer/retransfer load between theutility and the genset. To
    transfer load, press the ap-propriate CB ENABLE button (Utility or
    Genset).

    Example (Figure 2-13)

    In the example in Figure 2-13, the CB ENABLE but-ton for Utility
    was pressed. (If the CB ENABLEbutton for the Genset was pressed,
    ENABLEGEN CB would be displayed in the second subme-nu, allowing
    you to open or close the genset circuitbreaker.)

    After pressing the utility CB ENABLE button, thesecond submenu
    will be displayed allowing you toeither CANCEL or ENABLE the
    entered selection.

    Pressing the CANCEL button will return the displayto the
    previous menu.

    Pressing the ENABLE button will display the thirdsubmenu. With
    this submenu displayed you can re-turn to the second submenu
    without opening theutility circuit breaker (press

  • 2-22

    GENSET (PWR TRAN) SUBMENUS

    If you press the Genset button in the Power Trans-fer Main menu,
    the Genset submenus will appear(Figure 2-14).

    Voltage L-L and L-N: Indicates voltage Line-toLine and
    Line-to-Neutral. Note that the Line-to-Neu-tral column will not be
    displayed for a 3 phase/3 wiresystem. Accuracy 1%.

    The voltage Line-to-Line (L1, L2 and L3) are mea-sured between
    L1 to L2, L2 to L3 and L3 to L1, re-spectively.

    Amps: All phases. Accuracy 1%.

    Frequency: Generator set output frequency.

    kW, kVA and PF: Displays generator set kW andkVA output (average
    and individual phase, and di-rection of flow) and power factor with
    leading/lag-ging indication. Accuracy 5%.

    The PF reading will contain an asterisk if the powerfactor is
    leading (for example,*.30).

    GENSET:kW kVA PF

    L1 100 150 .97L2 125 175 .96L3 150 200 .95TOT375 525 .96

    GENSET

    GENSET:V L-L L-NAMPSL1 480 2771320L2 480 2771320L3 480
    2771320

    FREQUENCY60.0 HZ

    FIGURE 2-14. GENSET SUBMENUS

  • 3-1

    3. Control Calibration and Adjustment

    GENERALThis section contains calibration and
    adjustmentprocedures for the generator set control.

    PARALLELING AND NONPARALLELINGIf the generator set was purchased
    for a parallingapplication but will be used for a nonparalling
    ap-plication, entering the checksum data into the Data-plate
    Checksum dialog in InPower is not re-quired. However, the
    Adjustments Paralleling Paralleling Level must be set to Basic.

    SOFTWARE CALIBRATIONSIf the base card has software assembly A026
    F566v1.0 on the U33 flash memory chip, you must usethe latest
    software calibration for the control. If youload an earlier
    software calibration onto a base cardwith software assembly A026
    F566 v1.0, the soft-ware calibration will fail, and the board will
    lock uppermanent-ly.

    FIGURE 3-1. U33 FLASH MEMORY CHIP

    CAUTION If the base card has software as-sembly A026 F566 v1.0
    on the U33 flash memorychip, you must use the latest software
    calibra-tion for the control, or the board will lock up
    per-manently.

    MODIFYING SETUP/ADJUST SUBMENUS

    The Setup and Adjust submenus allow you to cali-brate the
    graphical display meters and to adjustsystem parameters, customer
    defined faults, gen-erator set voltage/frequency and paralleling
    ap-plications.

    CAUTION Improper calibration or adjustmentof the control can
    cause equipment malfunctionor damage. Calibration and adjustment
    must beperformed by technically qualified personnelonly.

    The Setup submenus are intended for qualified ser-vice personnel
    only. The Adjust submenu is in-tended for qualified service and
    site personnel only.For this reason, a password must be entered
    beforethis data can be modified. The Setup and Adjustsubmenus can
    be viewed, but not modified withoutentering the correct
    password.

    Saving Menu Changes

    Changes are automatically saved when the menu isexited.

  • 3-2

    PASSWORD Menu

    To allow the site personnel to modify only the Adjustsubmenu and
    not the Setup submenus, two pass-words are assigned within the
    system software. AnApplication password is used for the Setup
    sub-menus and a User password is used for the Adjustsubmenu.

    The two passwords are assigned during the initialinstallation of
    the generator set (via InPower) andwill vary between sites. The
    installer must makesure that the passwords are available to the
    ap-propriate personnel.

    When the generator set is first installed, the Applica-tion and
    User password are both set to GENSET toallow initial modification
    of the Setup and Adjustsubmenus. Assign new passwords when site
    instal-lation is complete.

    When viewing the Adjust menu, pressing the + or button will
    display the User Password menu.

    When viewing a Setup menu, pressing the + or button will always
    display the Application Passwordmenu.

    After entering the correct password, the system willallow you to
    modify the submenus. To help prevent

    unauthorized adjustment, the entered password isvalid for 10
    minutes after the last button is pressed(i.e., the password will
    need to be reentered afterthe ten minute timeout.

    Entering Password

    To enter the password:

    1. Display submenu to modify.

    2. Press either the + or button within the dis-played submenu.
    The Password menu ap-pears.

    3. Press the + and button to select the first char-acter of the
    password (AZ or 09). (Enter Ap-plication password for Setup
    submenus; En-ter User password for Adjust submenu.)

    4. Press the button to select the next characterfield. Selected
    character field is highlighted.

    5. Repeat steps 3 and 4 to enter remaining pass-word
    characters.

    6. Press the Enter button after entering the pass-word. The
    submenu selected in step 1 will re-appear.

    7. After making desired changes to submenu, exitsubmenu to save
    changes.

    + OR BUTTON

    ENTER

    ENTER APPLICATION PASSWORD

    +

    XXXXXXXX

    + OR BUTTON

    ENTER

    ENTER USER PASSWORD

    +

    XXXXXXXX

    SETUP SUBMENU PASSWORD MENU ADJUST SUBMENU PASSWORD MENU

    FIGURE 3-2. PASSWORD MENUS

  • 3-3

    SETUP MENUS

    Figure 3-3 shows the main menus (Menu A andMenu B) of the system
    control and the two Setupmenus.

    The Setup procedure is intended for qualified ser-vice personnel
    only. The APPLICATION passwordmust be entered to modify the Setup
    submenufields. Refer to PASSWORD Menu in this section toenter
    password and to save menu changes.

    To display the two Setup menus, press the

    MORE>> button in Menu A and then the SETUPbutton in Menu
    B.

    To view system data or to adjust system parame-ters, press the
    appropriate Setup menu button todisplay the desired Setup
    submenu(s). Refer to thepage number shown in Figure 3-3 for
    detailed infor-mation related to the selected submenu(s).

    CAUTION Improper calibration or adjustmentof the control can
    cause equipment malfunctionor damage. Calibration and adjustment
    must beperformed by technically qualified personnelonly.

    GOVERNING/VOLT REG

    CUSTOMER FAULTS

    CALIBRATION

    ISOLATED BUS

    UTILITY

    ENGINE

    ALTERNATOR

    CONTROL

    MORE>>

    POWER TRAN or _\_

    HISTORY/ABOUT SETUP

    ADJUST

    PARALLEL DATA

    BACK

  • 3-4

    GOVERNING/VOLT REG SUBMENU

    If you press the GOVERNING/VOLT REG buttonin the Setup menu, the
    Governing/Volt Regulatorsubmenu will appear (Figure 3-4).

    Use the + and buttons to increase or decrease thevalues in the
    following fields. Use the arrow () but-ton to move the cursor
    within a field or to the nextfield. Exit menu to safe changes.

    GOV GAIN: If the gain adjustment is set too high,engine speed
    will hunt or oscillate. If gain is set toolow, the engine will
    respond too slowly to changes inload and overspeed may result.
    (Gain should be re-duced to 80% for paralleling installations.)

    AVR GAIN: If the gain adjustment is set too high,output voltage
    will be unstable. If gain is set too low,the output voltage will
    respond sluggishly tochanges in load and overshoot may result.

  • 3-5

    GOVERNING/VOLT REG

    GOV GAIN80%AVR GAIN100%

    +

    FIGURE 3-4. GOVERNING/VOLT REG SUBMENU

  • 3-6

    CUSTOMER FAULTS SUBMENUS

    If you press the CUSTOMER FAULTS button inthe Setup menu, the
    Customer Faults submenuswill appear (Figure 3-5).

    There are a total of four customer fault inputs.(Faults 3 and 4
    paralleling only.) The message dis-played at the bottom of the menu
    can be modifiedfor each of these faults in addition to selecting
    thefollowing operating parameters for each fault.

    Enable On or Off Active Closed or Open Response Shutdown,
    Cooldown, Derate or

    Warning

    Shutdown: Genset will immediately shutdown. Normally used for
    engine faults.

    Cooldown: Cooldown sequence will be initi-ated before shutdown.
    Should not be used forengine faults.

    Derate: Used to lower kW output of genset forwarnings such as
    pre-high coolant tempera-ture, etc. Paralleling application
    controller willreduce precentage of kW load sharing on theset.
    Non-paralleling application controller will

    lower percentage of kW load by operating loadshed relay
    contacts.Warning: Display message, genset continuesto operate.

    The Enable and the Active fields apply to the Fault 1and 4
    submenus only.

    With the Active field selected, pressing the + or buttons will
    toggle the selection between CLOSEDand OPEN. Use same operation for
    remaining fieldselections.

    To enter the desired customer fault message, pressthe or button
    to display the submenu that con-tains the customer fault message (1
    through 4) to bechanged. Use the button to scroll down throughthe
    menu selections to the editable fault message(bottom menu
    line).

    Use the button to move to each character posi-tion within the
    fault message line.

    With the desired character position selected, use +or buttons to
    select the appropriate character.

    If these messages are changed, you should notethese changes in
    the Troubleshooting section of theOperators manual for this
    generator set.

  • 3-7

    CUSTOMER FAULTS

    CUSTOMER FAULT1:ENABLE ONACTIVE CLOSEDRESPONSEWARNING

    ***CUSTOMER FAULT1 ******************

    +

    CONTINUES THROUGH TWOADDITIONAL MENUS FOR ATOTAL OF FOUR
    POSSIBLE

    CUSTOMER FAULT MESSAGES

    +

    CUSTOMER FAULT2:

    RESPONSEWARNING

    ***CUSTOMER FAULT2 ******************

    FIGURE 3-5. CUSTOMER FAULTS SUBMENUS

  • 3-8

    CALIBRATION SUBMENUS

    If you press the CALIBRATION button in the Setupmenu, the
    Calibration submenus will appear (Fig-ure 3-6).

    Use the + and buttons to increase or decrease thevalues in the
    following fields. Use the arrow () but-ton to move the cursor
    within a field or to the nextfield. Exit menu to safe changes.

    The Calibration submenus allow you to calibrate thecontrol with
    the reading from a calibrated meter.Calibration is accomplished by
    using this section of

    the menu software to adjust the display so that itmatches the
    reading taken on an accurate, recentlycalibrated meter.

    Calibration is normally only required when replac-ing certain
    circuit cards. Refer to the CalibrationProcedure in this section
    which contains a list of thecards that require control
    calibration.

    When performing Bus Voltage Calibration from thegraphical
    display, the genset must be off and the Buslive. If the genset is
    running, it will synchronize to theBus.

  • 3-9

    CALIBRATION

    VOLTAGE CALIBRATIONL1 480-X.X%L2 480-X.X%L3 480-X.X%

    +

    CURRENT CALIBRATIONL1 234-X.X%L2 123-X.X%L3 562-X.X%

    +

    BUS VOLTAGE CALIBRATIONL1 480 -X.X%L2 480 -X.X%L3 480 -X.X%

    +

    FIGURE 3-6. CALIBRATION SUBMENUS

  • 3-10

    ISOLATED BUS / UTILITY Submenus(Paralleling Application)

    The Isolated BUS submenus (Figure 3-7) and theUtility submenus
    (Figure 3-8) adjust the control pa-rameters for generator set
    protection, synchroniz-ing and load sharing for both isolated bus
    and utility(mains) paralleling applications. Utility (mains)
    par-allel applications may require adjustment of boththe Isolated
    BUS and Utility submenus.

    Always perform ISO BUS calibration before UtilityBUS
    calibration.

    The sync check (permissive) function is operationalin both
    automatic and manual (RUN) modes. Thecontrol will make sure that
    the generator set is atproper voltage, within the defined sync
    check win-dow for the defined period of time and that phaserotation
    is correct. When all criteria are met, the par-alleling breaker is
    closed automatically by the con-trol (auto mode), or by operation
    of the breakerclose switch by the operator (manual mode).

    The synchronizing function of the control is enabledwhen the
    control has brought the generator set to90% of rated speed and
    voltage, and has sensedthat bus voltage is available. The control
    automati-cally adjusts the generator set speed and voltage tomatch
    the bus frequency and voltage. The controlcan force the generator
    set to match bus voltage

    and frequency in a range of minus 40% to plus 10%of normal bus
    conditions. When the parallelingbreaker has closed, the control
    will bring the gener-ator set back to normal voltage and
    frequency.

    When the generator set is paralleled to anothergenerator set,
    the control provides automatic loadsharing functions for both real
    (kW) and reactive(kVAR) loads. Load sharing is proportional
    betweengenerator sets based on their standby ratings. If
    twogenerator sets of different sizes are paralleled, theywill
    assume the same percentage of the systemload automatically. This
    can easily be verified on thekW Load LED bar graph on the front of
    the controlpanel.

    When the utility paralleling mode is enabled and thegenerator
    set paralleling breaker is closed, the gen-erator set will assume
    load based on external ana-log input signal. The input signal must
    be calibratedfrom 05 VDC. When the signal is at 0.5 to 1 VDC,the
    control will operate the generator at no load inparallel with the
    utility (mains) source. At 4.5 VDCand greater, the control will
    operate the generatorset at 110% of the generator set base load
    setting.When the load govern signal is between 1 VDC and4.5 VDC the
    control will operate the generator set ata load level which is
    determined by a linear relation-ship between the kW reference and
    the load governsignal.

  • 3-11

    ISOLATED BUS SUBMENUS

    If you press the ISOLATED BUS button in the Set-up menu, the
    Isolated BUS submenus will appear(Figure 3-7).

    Use the + and buttons to increase or decrease thevalues in the
    following fields. Use the arrow () but-ton to move the cursor
    within a field or to the nextfield. Exit menu to safe changes.

    SYNC TIME LIMIT: This parameter adjusts the timedelay in seconds
    before the Fail To Synchronizealarm will operate.

    REVERSE PWR LMT: Adjusts the reverse powerset point. For
    PowerCommand generator sets, atypical set point is 10-15%.

    REVERSE PWR TIME: Adjusts the reverse powerfunction time delay.
    A typical time delay which is

    suitable for PowerCommand generator sets is 3seconds.

    Lower reverse power set points can result in nui-sance reverse
    power shutdown faults.

    PERM WIN-PHASE: Adjusts the width of the per-missive
    (sync-check) acceptance window. The ad-justment range is from five
    to twenty electrical de-grees. Recommended set point is 20 degrees
    forisolated bus applications, and 15 degrees for utility(mains)
    paralleling applications.

    PERM WIN-TIME: Adjusts the time period (in sec-onds) for which
    the generator set must be synchro-nized with the system bus, before
    a breaker closesignal is issued by the PowerCommand
    control.Available range is 0.5 to 5 seconds. Recommendedvalue for
    PowerCommand generator sets is 0.5seconds for isolated bus
    applications.

  • 3-12

    ISOLATED BUS

    ISOLATED BUS:SYNC TIME LIMIT 120SEC

    REV PWR LMT 10%REV PWR TIME 3SECPERM WIN-PH 20DEGPERM WIN-TIME
    .5SEC

    +

    CONTINUED TO NEXT PAGE

    FIGURE 3-7. ISO BUS SUBMENUS

  • 3-13

    Adjusting the control for a smaller sync-check win-dow or longer
    time delay will cause synchronizingtime to be extended.

    SYNC GAIN: The sync gain adjustment controlshow quickly the
    governor will respond to try to mini-mize the bus/generator phase
    difference. Increas-ing the gain speeds up the response. If the
    gain istoo high instability can result.

    KW Balance and KVAR Balance changes should beequally shared
    among all generator sets.

    KW BALANCE: This function adjusts the kW loadsharing function of
    the generator set. Before adjust-ing this value, all generator set
    calibrations shouldbe performed. If the total load on the system is
    notshared proportionately, the kW Balance can beused to adjust the
    generator set for more preciseload sharing. Increasing the kW
    Balance value willcause the generator set to reduce the percentage
    ofthe total kW load on that set.

    KVAR BALANCE: This function adjusts the kVARload sharing
    function of the generator set. Beforeadjusting this value, all
    generator set calibrationsshould be performed. If the total load on
    the systemis not shared proportionately, the kVAR balance canbe
    used to adjust the generator set for more preciseload sharing.
    Increasing the kVAR balance valuewill cause the generator set to
    reduce the percent-age of the total kVAR load on that set.

    KW GAIN: Adjusts the rate of change of kW load onthe generator
    set. With a constant load on the sys-tem, if the generator set load
    is constantly chang-ing, reduce the gain adjustment on the
    generatorset. This also allows modification of the rate of
    loadassumption on transient load change.

    KVAR GAIN: Adjusts the rate of change of kVARload on the
    generator set. With a constant load onthe system, if the generator
    set load is constantlychanging, reduce the gain adjustment on the
    gener-ator set. This also allows modification of the rate ofload
    assumption on transient load change.

  • 3-14

    ISOLATED BUS (CONT.)

    ISOLATED BUS:SYNC GAIN 1.0KW BALANCE 0.3

    KVAR BALANCE 1.2KW GAIN 1.0KVAR GAIN 1.0

    +

    CONTINUED TO NEXT PAGE

    FIGURE 3-7. ISO BUS SUBMENUS (CONT.)

  • 3-15

    1ST FAIL TIME: Time delay in seconds after a sig-nal from the
    first start master is not sensed by thePCC that a FIRST START FAIL
    warning is dis-played.

    RAMP UNLOAD TIME: When a load demand stopinput is sensed the
    load is ramped down from thepresent load level on the set to the
    ramp unload lev-el in the time specified in seconds.

    RAMP UNLOAD LEVEL: The load demand rampunload function will ramp
    the load down from the

    present level on the set to this level before openingthe set
    circuit breaker. Value shown is in % of gensetstandby rating.

    RAMP LOAD TIME: When the load demand stopsignal is removed the
    load is ramped from 0kW tothe load share level in the specified
    time after thecircuit breaker closes.

    LOSS FIELD TIME: Adjusts the loss of field func-tion time delay.
    A typical delay which is suitable forPowerCommand generator sets is
    2 seconds.

  • 3-16

    ISOLATED BUS (CONT.)

    ISOLATED BUS:1ST FAIL TIME 12SECRAMP UNLD 20SEC

    RAMP UNLD LEVEL 10%RAMP LOAD TIME 3SECLOSS FIELD 20SEC

    +

    FIGURE 3-7. ISO BUS SUBMENUS (CONT.)

  • 3-17

    UTILITY SUBMENUS

    If you press the UTILITY button in the Setupmenu, the Utility
    submenus will appear (Figure 3-8).

    Use the + and buttons to increase or decrease thevalues in the
    following fields. Use the arrow () but-ton to move the cursor
    within a field or to the nextfield. Exit menu to safe changes.

    BASE LOAD (%): This controls the maximum kWload level that the
    generator set will operate at whenparalleled with the utility
    (mains). The value shownindicates the steady state load on the
    generator asa percent of the generator set standby rating.

    Check generator set ratings for maximum load levelat which the
    generator set should operate whenparalleled with the utility
    (mains). Extended opera-tion at load levels in excess of the
    generator set rat-ing can cause abnormal engine wear or
    prematureengine failure.

    PF LEVEL: Adjusts the power factor that the gener-ator set will
    run at when paralleled to the utility(mains). Recommended setting
    is 1.0.

    RAMP LOAD TIME: This is the ramp time frompresent set load to
    level determined by the load setanalog input. This is active when
    the control first en-ters the load govern mode.

    RAMP UNLOAD TIME: This is the ramp time frompresent set load to
    0 kW. This ramp is active whenthe load set analog input is less
    than 0.5 volts.

    MODE MULTIPLE/SINGLE: This controls wheth-er the set is to
    operate as part of a multiple set orsingle set (PLTE or PLTF)
    system. (Refer to LOADDEMAND SHUTDOWN and SINGLE MODE EN-ABLE
    function descriptions in wiring diagram,page 5-8.)

    KW GOVERN GAIN: This controls the rate that thegenerator set kW
    load is increased after the genera-tor set has closed to the system
    bus when utility(mains) paralleled. Decreasing this value will
    resultin slower loading of the generator set.

    KVAR GOVERN GAIN: This controls the rate thatthe generator set
    kVAR load is increased after thegenerator set has closed to the
    system bus whenutility (mains) paralleled. Decreasing this value
    willresult in slower loading of the generator set.

  • 3-18

    UTILITY

    UTILITY:BASE LOAD 80%PF LEVEL 1.00RAMP LOAD 3RAMP UNLD 20MODE
    MULTIPLE

    +

    UTILITY:KW GOVERN GAIN 1.00KVAR GOVERN GAIN1.00

    +

    FIGURE 3-8. UTILITY SUBMENUS

  • 3-19

    POWER TRANSFER CONTROL MAINMENUS

    If you press the POWER TRANSFER SETUP but-ton in the Setup menu
    2 in Figure 3-3, the two mainmenus of the optional Power Transfer
    Control(PTC) feature will appear (Figure 3-9).

    To adjust PTC system parameters, press the ap-propriate PTC main
    menu button and refer to thepage number shown in Figure 3-9 for
    detailed infor-mation related to the submenu selected.

    UTILITY SENSORS

    GENSET SENSORS

    TIMERS

    PAGE3-13

    PAGE3-15

    PAGE3-17

    NEXTMENU

    TEST/EXERCISE PAGE3-18

    PTC MAIN MENU 1

    PTC MAIN MENU 2

    FIGURE 3-9. PTC SETUP MAIN MENUS

  • 3-20

    UTILITY SENSORS SUBMENUS

    If you press the UTILITY SENSORS button in thePTC Main Menu 1,
    the Utility Sensors submenuswill appear (Figure 3-10).

    The following field descriptions show the valid fieldentries and
    default value (shown in parenthesis) foreach field.

    Use the + and buttons to increase or decrease thevalues in the
    following fields. Use the arrow () but-ton to move the cursor
    within a field or to the nextfield. Exit menu to save changes.

    U PT VOLT LL: Enter the value of the utility line-to-line
    voltage which yields 100% voltage at the termi-nals of the utility
    (bus) PT module.

    Range: 115000V, adjustable by standard nominalvoltage values,
    100V, 10V and 1V increments (1V).

    The 100% voltages for each of the four possible util-ity (bus)
    PT modules are as follows, based on mod-ule dash number:01 = 208
    volts LL02 = 416 volts LL03 = 600 volts LL04 = 120 volts LL

    Example 1: Nominal Utility voltage is 480V. Thismeans that
    utility (bus) PT module number 02should be used. The voltage which
    will yield 100%volts at this PT module is 416 per the above
    table.Thus enter 416V.

    Example 2: Nominal Utility voltage is 4160V. A pri-mary stage
    transformer with a ratio of 4200/240 isused. This means that
    utility (bus) PT module num-ber 01 should be used. The voltage
    which will yieldthe 100% volts (208V from above table) is
    calcu-lated as follows:

    208 x (4200/240) = 3640. Thus enter 3640V.

    U NOM VOLT LL: Enter the nominal utility line-to-line voltage.
    For example, 480, 4160, etc.. Range:115000 V, adjustable by
    standard nominal voltagevalues, 100V, 10V and 1V increments
    (1V).

    U CT RATIO: Enter the CT Ratio of the Utility L2 CT.This is the
    Ratio to 1 Amp. Range: 118000 (1A).

    CAUTION This CT must be rated for 1 Ampoutput (e.g. NOT 5 Amp).
    Be sure CT secondarycircuit has burden resistor or a shorting
    jumperin place before putting power through the CT.Example: CT
    Ratio = 2650:1. Thus enter 2650.

    U SENSOR TYPE: Enter the line-to-line (L-N) for 3phase
    line-neutral voltage sensing or line-to-line(L-L) for 3 phase
    line-line voltage sensing. This ap-plies to both the utility
    undervoltage and overvol-tage sensors. Range: LL, LN (LN).

    U : Enter utility connection type.Range: Delta, Wye (Wye).

    U UNLOADED KW: Enter the kW on utility Line 2 atwhich the
    utility is considered as unloaded. This isthe L2 kW level at which
    a closed transition softtransfer will disconnect from the
    utility.

    UTILITY UNDERVOLTAGE: Non-adjustable field,always enabled.

    UTILITY OVERVOLTAGE, FREQUENCY: Used toenable or disable menu
    function. Choose Enabledor Disabled (Enabled).

    UV PICKUP: Enter a number between 85 and100% of the nominal
    voltage (90%).

    UV DROP OUT: Enter a number between 75 and98% of the
    under-voltage pick-up percentage(90%).

    UV DELAY: Enter a time between 0.1 and 5.0 sec-onds (0.5
    seconds).

    UV MIN PHASE: Displays the lowest line voltage ofthe three
    utility phases.

  • 3-21

    OV PICKUP: This adjusts the over-voltage pickupas a percentage
    of the over-voltage drop-out. Entera number between 95 and 99%
    (95%).

    OV DROP OUT: Enter a percentage between 105and 135% of the
    nominal voltage (110%).

    OV DELAY: Enter a range between 0 and 120 sec-onds (3
    seconds).

    OV MAX PHASE: Displays the highest line voltageof the three
    utility phases.

    CENTER (FREQ): Enter a frequency between 45and 65 Hz (60
    Hz).

    PICK UP (FREQ): Enter a percentage between 5and 20% of the
    nominal frequency (10%).

    DROP OUT (FREQ): Enter a percentage between1 and 5% of the
    nominal frequency (1%).

    DELAY (FREQ): Enter a time between 0.1 and 15.0seconds (5.0
    seconds).

    FREQUENCY: This field displays the sensed utilityline
    frequency.

    UTILITY SENSORS

    UPT VOLT LL 416UNOM VOLT LL 480UCT RATIO: 1 1000USENSOR TYPE
    LL

    UUNLOADED KW 50 KW

    +

    UTILITY UV:ENABLED%VLL

    PICK UP 95475DROP OUT 85465

    DELAY 0.5 SMIN PHASE 470

    +

    UTILITY OV:DISABLED%VLL

    PICK UP 95487DROP OUT 110490

    DELAY 3.0 SMAX PHASE485

    +

    UTILITY FREQ:DISABLEDCENTER 60HZPICK UP 10%DROP OUT 1%DELAY
    1.0S

    FREQUENCY60.5HZ

    +

    FIGURE 3-10. UTILITY SENSORS SUBMENUS

  • 3-22

    GENSET SENSORS SUBMENUS

    If you press the GENSET SENSORS button in thePTC Main Menu 1,
    the Genset Sensors submenuswill appear (Figure 3-11).

    The following field descriptions show the valid fieldentries and
    default value (shown in parenthesis) foreach field.

    Use the + and buttons to increase or decrease thevalues in the
    following fields. Use the arrow () but-ton to move the cursor
    within a field or to the nextfield. Exit menu to save changes.

    G NOM VOLT LL: Non-adjustable field, displayscurrent setting of
    genset nominal voltage. (See Ad-just submenu to adjust the output
    voltage 5%.)G SENSOR TYPE: Enter the line-to-line (L-N) for 3phase
    line-neutral voltage sensing or line-to-line(L-L) for 3 phase
    line-line voltage sensing. This ap-plies to both the genset
    undervoltage and overvol-tage sensors. Range: LL, LN (LN).

    G BASE LOAD: Enter the maximum load the gen-set will carry
    during a closed transition. Range:0100% (80%).

    G RAMP LOAD: Enter the ramp time for the gensetramp load rate
    during a closed transition soft loadtransfer. Ramp rate is +100%kW
    divided by thistime setting. Range: 0900 seconds (20 sec).

    G RAMP UNLOAD: Enter the ramp time for thegenset ramp unload
    rate during a closed transtionsoft load retransfer. Ramp rate is
    100%kW dividedby this time setting. Range: 0900 seconds
    (20sec).

    G UNLOADED KW: Enter the %kW (based onstandby rating) that the
    genset is considered un-loaded. This is the %kW level at which a
    closed tran-sition soft retransfer will disconnect from the
    gen-set. Range: 0100% (5%).

    GEN UNDERVOLTAGE: Non-adjustable field, al-ways enabled.

    GEN OVERVOLTAGE, FREQUENCY: Used to en-able or disable menu
    function. Choose Enabled orDisabled (Enabled).

    UV PICKUP: Enter a number between 85 and100% of the nominal
    voltage (90%).

    UV DROP OUT: Enter a number between 75 and98% of the
    under-voltage pick-up percentage(90%).

    UV DELAY: Enter a time between 0.1 and 5.0 sec-onds (4
    seconds).

    UV MIN PHASE: Displays the lowest line voltage ofthe three
    genset phases.

  • 3-23

    OV PICKUP: This adjusts the over-voltage pickupas a percentage
    of the over-voltage drop-out. Entera number between 95 and 99%
    (95%).

    OV DROP OUT: Enter a percentage between 105and 135% of the
    nominal voltage (110%).

    OV DELAY: Enter a range between 0 and 120 sec-onds (3
    seconds).

    OV MAX PHASE: Displays the highest line voltageof the three
    genset phases.

    CENTER (FREQ): Enter a frequency between 45and 65 Hz (60
    Hz).

    PICK UP (FREQ): Enter a percentage between 5and 20% of the
    nominal frequency (10%).

    DROP OUT (FREQ): Enter a percentage between1 and 5% of the
    nominal frequency (1%).

    DELAY (FREQ): Enter a time between 0.1 and 15.0seconds (5.0
    seconds).

    FREQUENCY: Displays the sensed genset line fre-quency.

    GENSET SENSORS

    GNOM VOLT LL 480GSENSOR TYPE LLGBASE LOAD 80.0%GRAMP LOAD 20
    SGRAMP UNLOAD 20 SGUNLOADED KW 5 %

    +

    GEN UV: ENABLED%VLL

    PICK UP 95475DROP OUT 85465

    DELAY 1.0 SMIN PHASE 470

    +

    GEN OV: DISABLED%VLL

    PICK UP 95487DROP OUT 110490

    DELAY 8.0 SMAX PHASE485

    +

    GEN FREQ:DISABLEDCENTER 59HZPICK UP 12%DROP OUT 2%DELAY 5.0S

    FREQUENCY60.0HZ

    +

    FIGURE 3-11. GENSET SENSORS SUBMENUS

  • 3-24

    TIMERS SUBMENU

    If you press the TIMERS button in the PTC MainMenu 1, the Timers
    submenu will appear (Figure3-12).

    The following field descriptions show the valid fieldentries and
    default value (shown in parenthesis) foreach field.

    Use the + and buttons to increase or decrease thevalues in the
    following fields. Use the arrow () but-ton to move the cursor
    within a field or to the nextfield. Exit menu to save changes.

    START DELAY: Sets time delay for genset enginestart. Prevents
    nuisance genset starting during briefpower interruptions.

    Enter a range from 0 to 300 seconds (0 seconds).

    STOP DELAY: Sets the time delay for engine cool-down following a
    re-transfer. This stop delay worksin conjunction with and is
    activated at the same timeas the normal cooldown timer. (Will
    extend normalcooldown timer if entered time is greater.)

    Enter a time from 0 to 600 seconds (0 seconds).

    TRANSFER: In a Normal to Emergency transferthis function allows
    the genset to stabilize beforethe load is applied. Enter a time
    from 0 to 120 sec-onds (10 seconds).

    RETRANSFER: In a Emergency to Normal transferthis function
    allows the utility to stabilize before theload is applied.

    Enter a time from 0 to 1800 seconds (600 seconds).

    PGM TRANSIT: Sets the time delay for Pro-grammed Transition. A
    setting of 0.0 disables theprogram.

    Enter a time from 0 to 60 seconds (0 seconds).

    MAX PARALLEL: Sets the maximum time duringclosed transition that
    utility and genset can be paral-leled.

    Enter a time from 0 to 1800 seconds (20 seconds).

  • 3-25

    TIMERS

    START DELAY60SSTOP DELAY60STRANSFER 10SRETRANSFER900SPGM
    TRANSIT5SMAX PARALLEL30S

    +

    FIGURE 3-12. TIMERS SUBMENU

  • 3-26

    TEST/EXERCISE SUBMENU

    If you press the TEST/EXERCISE button in thePTC Main Menu 2, the
    Test/Exercise submenu willappear (Figure 3-13).

    The following field descriptions show the valid fieldentries and
    default value (shown in parenthesis) foreach field.

    Use the + and buttons to increase or decrease thevalues in the
    following fields. Use the arrow () but-ton to move the cursor
    within a field or to the nextfield. Exit menu to save changes.

    MODE: Indicates the generator set application typefor PTC
    option.

    OT-PGM TRAN Open transition load transfer.CT-MOMENT Closed
    transition load transferwith momentary (

  • 3-27

    TEST/EXERCISE

    MODE CT-SOFT

    TEST WITH LOADOFFEXER WITH LOADOFF

    +

    FIGURE 3-13. TIMERS SUBMENU

  • 3-28

    ADJUST SUBMENU

    Figure 3-14 shows the main menus (Menu A andMenu B) of the
    system control and the Adjust sub-menu.

    To display the Adjust submenu, press the MORE>>button in
    Menu A and then the ADJUST button inMenu B.

    The Adjust submenus are intended for qualifiedservice personnel
    and site personnel only and mayrequire a USER password. If a
    password is re-quired, the USER password menu will appear whenyou
    try to modify the Adjust submenus. (Refer toPASSWORD Menu in this
    section to enter pass-word.

    Changes are automatically saved when you exitthis menu.

    If the generator set is operating in parallel with asystem bus,
    the voltage and frequency adjustments

    are disabled to prevent inadvertent misadjustmentof the
    paralleling load sharing functions.

    Use the + and buttons to increase or decrease thevalues in the
    following fields. Use the arrow () but-ton to move the cursor
    within a field or to the nextfield. Exit menu to safe changes.

    START DELAY: This delay applies only to remotestarting in the
    Auto mode. The Start Delay adjust-ment range is 0 to 300
    seconds.

    STOP DELAY: This delay applies only to remotestopping in the
    Auto mode. The Stop Delay adjust-ment range is 0 to 600
    seconds.

    VOLTAGE: Used to adjust the output voltage 5%.

    FREQUENCY: Used to adjust the frequency 3 Hz.

    VOLTAGE/SPEED DROOP: These two submenusapply to a genset that
    has the paralleling option andis configured to operate in droop
    mode.

    ENGINE

    ALTERNATOR

    CONTROL

    MORE>>

    _\_

    HISTORY/ABOUT

    SETUP

    ADJUST

    BUS DATA

    BACK

  • 3-29

    CALIBRATION PROCEDURE

    There are several circuit cards/modules that, whenremoved and
    replaced, require you to recalibratethe control panel display for
    genset voltage and cur-rent and bus voltage.

    Note that the type of calibration to perform varies foreach
    card. The letters A, B and C are used to desig-nate which of the
    following three calibration proce-dures are required for each
    card/module.

    Genset/Parallel board (A, B & C) PT/CT board (A & B) Bus
    PT (C) CTs (B)

    WARNING Contacting high voltage compo-nents can cause
    electrocution, resulting in se-vere personal injury or death.
    Calibration andadjustment must be performed by technicallyqualified
    personnel only. Read and observe allWARNINGS and CAUTIONS in your
    generatorset manuals.

    CAUTION Improper calibration or adjustmentof the PowerCommand
    control can causeequipment malfunction or damage. Calibrationand
    adjustment must be performed by techni-cally qualified personnel
    only.

    Use a calibrated RMS multimeter for accurate mea-surements.

    (A) Genset Voltage Display Calibration

    The PowerCommand control automatically synchro-nizes to the
    system bus when bus voltage is avail-able and the genset is
    running. Consequently, it isnot possible to calibrate the genset
    output voltage

    display of the genset that is running when the bus isenergized.
    If it is necessary to adjust the output volt-age display of the
    genset that is running, the InPowerservice tool must be used to
    switch off the synchro-nizer function of the control.

    1. Display the Voltage Calibration submenu(Page 3-6).

    2. With the genset OFF, attach a calibrated volt-meter to the AC
    output from L1 to L2. (L1 toNeutral for single phase
    alternators.)

    3. Start the genset and allow it to reach normaloperating
    speed.

    4. Calibrate voltage reading for L1 so that thereading on the
    display agrees with the cali-brated voltmeter.

    5. Shut the generator set OFF.6. Repeat steps 2 through 5 for L2
    and L3. (In step

    2 attach meter to the AC output from L2 to L3 tocalibrate L2 and
    L3 to L1 to calibrate L3.)

    7. Exit menu to safe changes.

    (B) Genset Ammeter Display Calibration

    1. Display the Current Calibration submenu(Page 3-6).

    2. With the genset OFF, attach a calibrated am-meter to L1.

    3. Start the genset and allow it to reach normaloperating
    speed.

    4. Load the genset to maximum rated kVA atrated voltage.

    5. Calibrate the reading for L1 current so that thereading on
    the display agrees with calibratedammeter.

    6. Repeat steps 2 through 5 for L2 and L3. (In step2, attach
    meter to L2 to calibrate L2 current andL3 to calibrate L3
    current.)

    7. Exit menu to safe changes.

  • 3-30

    (C) Bus Voltage Calibration

    The PowerCommand control automatically synchro-nizes to the
    system bus when bus voltage is avail-able and the genset is
    running. Consequently, it isnot possible to calibrate the genset
    bus voltage dis-play of the genset that is running when the bus is
    en-ergized. If it is necessary to adjust the bus voltagedisplay of
    the genset that is running, the InPowerservice tool must be used to
    switch off the synchro-nizer function of the control.

    1. Display the Bus Voltage Calibration submenu(Page 3-6).

    2. With all gensets OFF, attach a calibrated volt-

    meter to TB1-A (L1) and TB1-B (L2) of the busPT module (Figure
    3-15).

    3. Start another genset and allow it to reach nor-mal operating
    speed and voltage. Connect op-erating genset to the bus.

    4. Calibrate the voltage reading for Bus Volts L1so that the
    reading on the display matches thereading on the calibrated
    meter.

    5. Shut the generator set OFF.6. Repeat steps 2 through 5 for
    Bus Volts L2 and

    L3. (In step 2 attach meter to the AC outputfrom L2 to L3 to
    calibrate L2; L3 to L1 to cali-brate L3.)

    7. Exit menu to safe changes.

    TB1-A (L1)

    CONTROLBOX DOOR

    TB1-B (L2)

    TB1-C (L3)

    FIGURE 3-15. BUS PT MODULE

  • 3-31

    CONTROL BOX WIRING

    The generator set control box assembly, which canbe located on
    either side of the genset, containsconnection points for remote
    control and monitoroptions.

    Customer monitor/control connections are at-tached to terminal
    blocks TB3 and TB8 (see Figure

    3-16). Optional equipment such as a remote annun-ciator panel,
    sensing devices used to monitor gen-set operation, remote
    start/stop switches, controlbox heater, and etc. are also attached
    to these ter-minal blocks. Driver signals for customer
    suppliedrelays are also provided for several alarm and shutdown
    conditions. Refer to Customer Connectionsdiagram in Section 7.

  • 3-32

    TB8

    CARDCAGE

    OPTIONALSHUTDOWN

    ALARM RELAY K16

    OPTIONALRUN RELAYS

    K11, K12 & K13

    CONTROL WIRINGACCESS

    FIGURE 3-16. CONTROL BOX ASSEMBLY INTERIOR

  • 3-33

    RUN RELAYS (K11, K12, K13)

    The optional run relays are rail mounted inside thecontrol box
    (Figure 3-16). The rail mount allows youto easily remove and
    replace the snap-on relays.The generator set can be equipped with
    one, two orthree run relays.

    The three-pole, double-throw run relays (Figure3-17) are used to
    control auxiliary equipment such

    as fans, pumps and motorized air dampers. The runrelays are
    energized when the generator set reach-es operating speed.

    The contacts are rated:

    10 amps at 28 VDC or 120 VAC, 80%PF 6 amps at 240 VAC, 80%PF 3
    amps at 480/600 VAC, 80%PF

    CUSTOMERCONNECTIONS

    TB3-7(GND)

    TB3-5(SWITCHED B+)

    NO

    COIL

    COM

    NC

    K11, K12, K13

    K11RUN RELAY

    K11, K12, K13

    K11, K12, K13

    K12RUN RELAY

    K13RUN RELAY

    NO

    NC

    NO

    NC

    FIGURE 3-17. OPTIONAL RUN RELAYS (K11, K12, K13)

  • 3-34

    ALARM RELAY (K16)

    The optional alarm relay is rail mounted inside thecontrol box
    (Figure 5-2). The rail mount allows youto easily remove and replace
    the snap-on relay.

    The three-pole, double-throw alarm relay (Figure5-4) is often
    used to energize warning devices such

    as audible alarms. Any generator set shutdown willenergize the
    alarm relay.

    The contacts are rated:

    10 amps at 28 VDC or 120 VAC, 80%PF 6 amps at 240 VAC, 80%PF 3
    amps at 480/600 VAC, 80%PF

    CUSTOMERCONNECTIONS

    TB3-18(GND)

    TB3-17(COM ALARM)

    NO

    COIL

    COM

    NC

    K16

    K16

    K16

    K16SHUTDOWN ALARM

    FIGURE 3-18. OPTIONAL ALARM RELAY (K16)

  • 3-35

    MAGNETIC SPEED PICKUP UNIT (MPU)INSTALLATION

    To install the MPU sensor, bar the engine until agear tooth on
    the flywheel lines up in the center of

    the mounting hole. Thread the sensor in gently byhand until it
    just touches the gear tooth. Back it outone quarter turn and set
    the locknut.

    CAUTION Do not use fan blade to bar over en-gine. That can
    damage blades and cause prop-erty damage and personal injury.

  • 3-36

    MAGNETICPIC

Published on December 2016 | Categories: Documents | Downloads: 330 | Comments: 0 | Views: 830

Service Manual
Controller
PowerCommand

3201

English − Original Instructions 9−2010 A034T572 (Issue 1)
i
Table of Contents
SECTION TITLE PAGE
1. Introduction 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ABOUT THIS MANUAL 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TEST EQUIPMENT 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HOW TO OBTAIN SERVICE 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Control Operation 2-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GENERAL 2-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SEQUENCE OF OPERATION 2-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONTROL PANEL POWER ON/OFF MODES 2-1 . . . . . . . . . . . . . . . . . . . . .
CONTROL PANEL ASSEMBLY 2-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
READING FAULT CODES 2-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MENU DISPLAY AND SWITCHES 2-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LANGUAGE/UNITS SELECTION MENU 2-8 . . . . . . . . . . . . . . . . . . . . . . . . . .
MAIN MENU 2-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ENGINE SUBMENUS 2-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ALTERNATOR SUBMENUS 2-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONTROL SUBMENU 2-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HISTORY/ABOUT SUBMENUS 2-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HISTORY/ABOUT SUBMENUS (CONT.) 2-15 . . . . . . . . . . . . . . . . . . . . . . . . .
PARALLEL DATA SUBMENU 2-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
POWER TRANSFER MAIN/SUBMENUS 2-17 . . . . . . . . . . . . . . . . . . . . . . . . .
UTILITY (PWR TRAN) SUBMENUS 2-19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STATUS (PWR TRAN) SUBMENUS 2-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TRANSFER CONTROL (PWR TRAN) SUBMENU 2-21 . . . . . . . . . . . . . . . . .
GENSET (PWR TRAN) SUBMENUS 2-22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. Control Calibration and Adjustment 3-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GENERAL 3-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PARALLELING and NON−PARALLELING 3-1 . . . . . . . . . . . . . . . . . . . . . . . . .
SOFTWARE CALIBRATIONS 3-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MODIFYING SETUP/ADJUST SUBMENUS 3-1 . . . . . . . . . . . . . . . . . . . . . . . .
SETUP MENUS 3-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GOVERNING/VOLT REG SUBMENU 3-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CUSTOMER FAULTS SUBMENUS 3-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CALIBRATION SUBMENUS 3-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ISOLATED BUS SUBMENUS 3-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UTILITY SUBMENUS 3-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
POWER TRANSFER CONTROL MAIN MENUS 3-19 . . . . . . . . . . . . . . . . . . .
UTILITY SENSORS SUBMENUS 3-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GENSET SENSORS SUBMENUS 3-22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TIMERS SUBMENU 3-24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TEST/EXERCISE SUBMENU 3-26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUST SUBMENU 3-28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CALIBRATION PROCEDURE 3-29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii
SECTION TITLE PAGE
CONTROL BOX WIRING 3-31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RUN RELAYS (K11, K12, K13) 3-33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ALARM RELAY (K16) 3-34 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MAGNETIC SPEED PICKUP UNIT (MPU) INSTALLATION 3-35 . . . . . . . . .

v
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS − This manual contains
important instructions that should be followed during
installation and maintenance of the generator set and
batteries.
Before operating the generator set (genset), read the
Operator’s Manual and become familiar with it and the
equipment. Safe and efficient operation can be
achieved only if the equipment is properly operated
and maintained. Many accidents are caused by failure
to follow fundamental rules and precautions.
The following symbols, found throughout this manual,
alert you to potentially dangerous conditions to the oper-
ator, service personnel, or the equipment.
This symbol warns of immediate
hazards which will result in severe personal in-
jury or death.
WARNING This symbol refers to a hazard or un-
safe practice which can result in severe person-
al injury or death.
CAUTION This symbol refers to a hazard or un-
safe practice which can result in personal injury
or product or property damage.
FUEL AND FUMES ARE FLAMMABLE
Fire, explosion, and personal injury or death can result
from improper practices.
 DO NOT fill fuel tanks while engine is running, un-
less tanks are outside the engine compartment.
Fuel contact with hot engine or exhaust is a potential
fire hazard.
 DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source
near the generator set or fuel tank.
 Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be
made with an approved flexible line. Do not use zinc
coated or copper fuel lines with diesel fuel.
 Be sure all fuel supplies have a positive shutoff
valve.
 Be sure battery area has been well-ventilated prior
to servicing near it. Lead-acid batteries emit a highly
explosive hydrogen gas that can be ignited by arc-
ing, sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
 Provide an adequate exhaust system to properly
expel discharged gases away from enclosed or
sheltered areas and areas where individuals are
likely to congregate. Visually and audibly inspect
the exhaust daily for leaks per the maintenance
schedule. Make sure that exhaust manifolds are se-
cured and not warped. Do not use exhaust gases to
heat a compartment.
 Be sure the unit is well ventilated.
 Engine exhaust and some of its constituents are
known to the state of California to cause cancer,
birth defects, and other reproductive harm.
MOVING PARTS CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH
 Keep your hands, clothing, and jewelry away from
moving parts.
 Before starting work on the generator set, discon-
nect battery charger from its AC source, then dis-
connect starting batteries, negative (−) cable first.
This will prevent accidental starting.
 Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards
in position over fans, drive belts, etc.
 Do not wear loose clothing or jewelry in the vicinity of
moving parts, or while working on electrical equip-
ment. Loose clothing and jewelry can become
caught in moving parts.
 If adjustment must be made while the unit is run-
ning, use extreme caution around hot manifolds,
moving parts, etc.
DO NOT OPERATE IN FLAMMABLE AND
EXPLOSIVE ENVIRONMENTS
Flammable vapor can cause an engine to overspeed and
become difficult to stop, resulting in possible fire, explo-
sion, severe personal injury and death. Do not operate a
genset where a flammable vapor environment can be
created by fuel spill, leak, etc., unless the genset is
equipped with an automatic safety device to block the air
intake and stop the engine. The owners and operators of
the genset are solely responsible for operating the gen-
set safely. Contact your authorized Cummins Power
Generation distributor for more information.
vi
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH
 Remove electric power before removing protective
shields or touching electrical equipment. Use rub-
ber insulative mats placed on dry wood platforms
over floors that are metal or concrete when around
electrical equipment. Do not wear damp clothing
(particularly wet shoes) or allow skin surface to be
damp when handling electrical equipment. Do not
wear jewelry. Jewelry can short out electrical con-
tacts and cause shock or burning.
 Use extreme caution when working on electrical
components. High voltages can cause injury or
death. DO NOT tamper with interlocks.
 Follow all applicable state and local electrical
codes. Have all electrical installations performed by
a qualified licensed electrician. Tag and lock open
switches to avoid accidental closure.
 DO NOT CONNECT GENERATOR SET DIRECT-
LY TO ANY BUILDING ELECTRICAL SYSTEM.
Hazardous voltages can flow from the generator set
into the utility line. This creates a potential for elec-
trocution or property damage. Connect only
through an approved isolation switch or an ap-
proved paralleling device.
GENERAL SAFETY PRECAUTIONS
 Coolants under pressure have a higher boiling point
than water. DO NOT open a radiator or heat ex-
changer pressure cap while the engine is running.
To prevent severe scalding, let engine cool down
before removing coolant pressure cap. Turn cap
slowly, and do not open it fully until the pressure has
been relieved.
 Used engine oils have been identified by some state
or federal agencies as causing cancer or reproduc-
tive toxicity. When checking or changing engine oil,
take care not to ingest, breathe the fumes, or con-
tact used oil.
 Keep multi-class ABC fire extinguishers handy.
Class A fires involve ordinary combustible materials
such as wood and cloth; Class B fires, combustible
and flammable liquid fuels and gaseous fuels; Class
C fires, live electrical equipment. (ref. NFPA No. 10).
 Make sure that rags or combustible material are not
left on or near the generator set.
 Make sure generator set is mounted in a manner to
prevent combustible materials from accumulating
under or near the unit.
 Remove all unnecessary grease and oil from the
unit. Accumulated grease and oil can cause over-
heating and engine damage which present a poten-
tial fire hazard.
 Keep the generator set and the surrounding area
clean and free from obstructions. Remove any de-
bris from the set and keep the floor clean and dry.
 Do not work on this equipment when mentally or
physically fatigued, or after consuming any alcohol
or drug that makes the operation of equipment un-
safe.
 Substances in exhaust gases have been identified
by some state or federal agencies as causing can-
cer or reproductive toxicity. Take care not to breath
or ingest or come into contact with exhaust gases.
 Do not store any flammable liquids, such as fuel,
cleaners, oil, etc., near the generator set. A fire or
explosion could result.
 Wear hearing protection when near an operating
generator set.
 To prevent serious burns, avoid contact with hot
metal parts such as radiator system, turbo charger
system and exhaust system.
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
1-1
1. Introduction
ABOUT THIS MANUAL
This manual provides PowerCommand

Control
3201 (PCC) calibration and adjustment proce-
dures, control operation, alternator test and repair
procedures.
Operating and maintenance instructions are in the
applicable Operator’s Manual.
Read Important Safety Instructions and carefully
observe all instructions and precautions in this
manual.

TEST EQUIPMENT
To perform the test procedures in this manual, the
following test equipment must be available
 True RMS meter for accurate measurement of
small AC and DC voltages.
 Battery Hydrometer
 Jumper Leads
 Tachometer or Frequency Meter
 Wheatstone Bridge or Digital Ohmmeter
 Variac
 Load Test Panel
 Megger or Insulation Resistance Meter
 InPower Service Tool (PC based genset ser-
vice tool)
HOW TO OBTAIN SERVICE
Always give the complete Model, Specification and
Serial number of the generator set as shown on the
nameplate when seeking additional service infor-
mation or replacement parts. The nameplate is lo-
cated on the side of the generator output box.
WARNING Incorrect service or replacement of
parts can result in severe personal injury or
death, and/or equipment damage. Service per-
sonnel must be trained and experienced to per-
form electrical and mechanical service. Read
and follow Important Safety Instructions, on
pages iii and iv.
1-2
THIS PAGE LEFT INTENTIONALLY BLANK
2-1
2. Control Operation
GENERAL
The following describes the function and operation
of the PowerCommand

Control 3200 (PCC). All in-
dicators, control switches/buttons and graphical
display are located on the face of the control panel
as illustrated in Figure 2-1.
Normally, generator set configuration options are
set at the factory. When a new control is installed on
a generator set or when parts are replaced, the con-
trol must be configured for that generator set. Setup
and calibration procedures are described in Sec-
tion 3.
SEQUENCE OF OPERATION
When the PowerCommand control is in the AUTO
mode, it will cause the generator set to start on re-
ceiving a signal from a remote device. The control
will initiate a starter cranking signal and verify that
the engine is rotating. The control will provide suffi-
cient fuel to the engine to accelerate to start discon-
nect speed. On reaching that speed, the control will
ramp the generator set to idle (warm-up) or rated
speed and voltage.
On reaching rated speed and voltage, the control
checks the system bus voltage. If no bus voltage is
present, it will wait for a pulse from a remote Master
First Start Sensor. On receiving that pulse, the con-
trol will signal the paralleling breaker to close.
If bus voltage is present, the control will check for
proper phase rotation, adjust the generator set to
the bus voltage and frequency level, and then syn-
chronize the generator set to the system bus. When
a synchronous condition is achieved, the control will
send a signal to close the paralleling breaker.
When the paralleling breaker is closed, the genera-
tor set will assume it’s proportional share of the total
load on the system bus.
CONTROL PANEL POWER ON/OFF
MODES
The power on/off modes of the control panel and op-
erating software are Power On, Screen Saver and
Sleep/Awake.
Power On Mode: In this mode, power is continu-
ously supplied to the control panel. The control’s
operating software and control panel LEDs/graphi-
cal display will remain active until the Screen Saver
mode is activated.
2-2
Screen Saver Mode: Power to the graphical dis-
play will be removed after 10 minutes (generator set
not running or running). The 10 minute timer resets
and begins after each control panel action (any but-
ton or switch selection) or signal received by the op-
erating software. The bottom LEDs of the Analog
AC Metering Panel (bar graphs) may remain on dur-
ing Screen Saver mode, indicating that the operat-
ing software is active (Awake mode).
When a “Warning” signal is sensed by the PCC (for
example, low coolant temp), the control will display
the warning message. The control will remain active
until the Fault Acknowledge button is pressed to
clear the warning message and start the 10 minute
timer.
Sleep/Awake Mode: In the Sleep mode, the con-
trol’s operating software is inactive and the LEDs
and the graphical display on the control panel are all
off. Sleep mode is a feature that is used to reduce
battery power consumption when the control is not
being used.
In Off mode, Sleep mode is activated when there
are no unacknowledged faults and Screen Saver
mode is active.
In Auto mode, Sleep mode can be enabled or dis-
abled. When shipped from the factory, it is disabled.
You can enable Sleep mode by making these
changes:
 Use InPower service tool to set Auto Sleep En-
able to Sleep in Auto.
 Set switch S1 on the Genset/Paralleling Card
to Sleep/Off. This switch is located next to con-
nector J8 and relay K9.
If these conditions are not met, Sleep mode is dis-
abled in Auto mode.
The graphical display can enter Screen Saver mode
even if Sleep mode is disabled.
If Sleep mode is enabled in Auto mode, Sleep mode
is activated when there are no unacknowledged
faults and Screen Saver mode is active.
The operating software is initialized and the control
panel LEDs and graphical display are turned on in
response to one of the following:
 Moving/pressing any control panel switch/but-
ton. (If Sleep mode is enabled in Auto mode,
the control will remain asleep if Sleep mode
was previously active in Off mode.)
 Receiving a remote start input signal (genera-
tor set in Auto mode)
 Receiving an active DCD signal on the RS-232
port.
 Modem RI latch becoming active.
 Digital display waking up.
 Lonworks (backplane) wakeup becoming ac-
tive.
 Customer fault 2 or 3 only (shutdown or warn-
ing indicator is on).
 Dial Out process becoming active.
To activate the control and view the menu display
without starting the generator set, press any button
on the control panel.
2-3
DISPLAY MENU
SELECTION BUTTONS
(1 of 6)
0/MANUAL/AUTO
SWITCH
REMOTE START,
NOT IN AUTO,
SHUTDOWN,
WARNING
STATUS INDICATORS
GRAPHICAL
DISPLAY
ANALOG AC
METERING
PANEL
OPERATOR PANEL SWITCH PANEL
MANUAL RUN/
STOP BUTTON
& INDICATOR
EXERCISE
BUTTON &
INDICATOR
FAULT
ACKNOWLEDGE
BUTTON
PANEL LAMP/
LAMP TEST
BUTTON
EMERGENCY
STOP PUSH
BUTTON
0
FIGURE 2-1. CONTROL PANEL ASSEMBLY (FULL-FEATURED)
2-4
CONTROL PANEL ASSEMBLY
The control panel assembly (Figure 2-1) consist of
two panels, the Operator Panel and the Switch Pan-
el.
Dependent on site requirements, the Operator Pan-
el is either mounted on the control panel assembly
(full-featured) as shown in Figure 2-1 or contained
in a separate enclosure and mounted remotely of
the control panel assembly.
The function of several buttons on the control panel
will vary dependent on the location of the control
panel (remote or local of the control panel assem-
bly). If the function differs, it is noted as either “re-
mote” or “local operator panel” in the button de-
scription.
Operator Panel
The operator panel contains the following compo-
nents:
Analog AC Metering Panel: This panel simulta-
neously displays 3-phase line to line AC volts and
current, kW, power factor and frequency.
The meter panel is composed of a series of LEDs,
that are configured in bar graphs for each function.
The LEDs are color coded, with green indicating
normal range values, amber for warning levels and
red for shutdown conditions.
Scales for each function are in % of nominal values.
Resolution is 1% for values close to nominal, and in-
creases at values further from nominal.
Graphical Display: The graphical display is capa-
ble of displaying up to 9-lines of data with approxi-
mately 27 characters per line. The display is used to
view the menus of the menu-driven operating sys-
tem.
The top three lines of the graphical display contain
the following control information in the order de-
scribed:
 State Line − modes of operation, such as
Stopped, Time Delay To Start, Warm Up At
Idle, etc. (see Figure 2-2), and paralleling op-
erations, such as Standby, Dead BUS Close,
Synchronize, Load Share and Load Govern.
 Action Line − system actions, such as Warning,
Derate, Shutdown Cool-down and Shutdown,
and fault codes.
 Description Line − Fault code messages.
Display Menu Selection Buttons: Six momentary
buttons—three on each side of the graphical dis-
play window—are used to navigate through the sys-
tem control menus and to adjust generator set pa-
rameters. The button is active when the message
adjacent to the button is highlighted (displayed in in-
verse video).
2-5
Switch Panel
The switch panel contains the following compo-
nents:
Emergency Stop Button: Push the button in for
emergency shutdown of the engine. If the engine is
not running, pushing the button in will prevent the
starting of the engine, regardless of the start signal
source (local or remote).
To reset:
1. Pull the button out.
2. Move the 0/Manual/Auto switch to 0.
3. Press the front panel Fault Acknowledge
button.
4. Select Manual or Auto, as required.
Remote Start Indicator: This green lamp is lit
whenever the control is receiving a remote run sig-
nal. When flashing, it indicates a load demand stop
mode.
Not in Auto Indicator: This red lamp flashes con-
tinuously when the 0/Manual/Auto switch is not in
the Auto position. (If in Auto position and lamp is
flashing, service is required.)
Shutdown Status Indicator: This red lamp is lit
whenever the control detects a shutdown condition.
The generator set can not be started when this lamp
is on. After the condition is corrected, shutdown in-
dicators can be reset by turning the 0/Manual/Auto
switch to the 0 position, and pressing the Fault Ac-
knowledge button.
Dependent upon the specific fault that occurs, the
engine may or may not shut down immediately. A
fault that could cause engine damage, causes an
immediate engine shutdown (bypasses engine
cool-down sequence). All other faults would allow
the engine to run during the cool-down sequence
before engine shutdown. In this case, the Shutdown
Status Indicator blinks during the cooldown period.
Warning Status Indicator: This yellow lamp is lit
whenever the control detects a warning condition.
After the condition is corrected, warning indicators
can be reset by pressing the Fault Acknowledge
button. (It is not necessary to stop the generator set
if the fault becomes inactive during genset opera-
tion.)
Fault Acknowledge: Press this button to acknowl-
edge warning and shutdown messages after the
fault has been corrected.
To acknowledge a Warning message, the 0/Manu-
al/Auto switch can be in any position. (It is not nec-
essary to stop the generator set to acknowledge an
inactive Warning condition.) To acknowledge a
shutdown message with this button, the 0/Manual/
Auto switch must be in the 0 (Off) position.
This button is also used to blink a fault code if the
Shutdown or Warning Status Indicator is lit. (This
function is used when the control does not contain a
graphical display.) Refer to Reading Fault Codes in
this section, which describes how to use this button
for interpreting fault codes.
Panel Lamp/Lamp Test Button: Press this button
to turn on or off the panel lamp. Press and hold
down this button for three seconds or more to turn
all control panel LEDs on to make sure all lamps illu-
minate. The illumination will shut off after releasing
the button.
Exercise Button: Press this button to initiate a pre-
programmed exercise sequence. To start the exer-
cise sequence, press and hold down the Exercise
button and move the O/Manual/Auto switch from
Auto to Manual and back to Auto or from Manual to
Auto.
Manual Run/Stop Button: This button starts and
stops the set locally and will bypass Time Delay to
Start and Stop sequences. The 0/Manual/Auto
switch must be in the Manual position to enable this
button.
0/Manual/Auto Switch: Manual position enables
the use of the switch panel Manual Run/Stop but-
ton.
Auto position enables start/stop control of the en-
gine from a remote location. (Disables the use of the
switch panel Manual Run/Stop button.)
0 (Off) position prevents the starting of the set (local
or remote). If moved to 0 during set operation, will
cause an immediate engine shutdown (bypasses
cool-down timers). This hot shutdown should be
avoided, if possible, to help prolong the life of the
engine. Hot shutdowns are logged by the system
software.
2-6
READING FAULT CODES
If the genset contains the optional graphical display
and a fault occurs, the fault code/message will be
displayed in the display Description Line (Figure
2-2). If the control does not contain the graphical
display, the fault code is read from the Warning and
Shutdown status indicators.
Reading Fault codes Using Warning/Shutdown
Indicators: If the Warning or Shutdown status indi-
cator is lit, press and hold the Fault Acknowledge
button and release after one second or more. After
one second, the Shutdown lamp will begin to blink
the active fault code(s) as follows.
The Warning lamp is used to indicate the start of a
new code. The Warning lamp will remain on for 2
seconds, followed by the Shutdown lamp blinking
the fault code. This sequence occurs three times for
each code. The fourth flash of the Warning lamp in-
dicates the beginning of the second fault code.
There are distinct pauses between repetitions of the
code blink transmissions of the Shutdown lamp.
A three digit fault code is indicated by three sets of
blinks separated by a two second pause. The first
set corresponds to the hundreds position, the sec-
ond to the tens position and the third to the ones dig-
it. Example for Code No. 213:
Shutdown LED:
blink-blink-pause-blink-pause-blink-blink-blink
Warning LED:
blink (2 seconds)
The light will display the fault codes (active or inac-
tive) in succession, starting with the most recent. Up
to 32 (unacknowledged) fault codes can be stored
in control panel memory.
To return the control to the most recent fault code,
press and release the Fault Acknowledge button
(less than one second) and repeat procedure.
When the fault code is acknowledged and cor-
rected, the recorded fault will be deleted from the
LED fault log, but will remain in a data log that main-
tains a fault code history. (The InPower service tool
is required to view this data log.)
2-7
MENU DISPLAY AND SWITCHES
Figure 2-2 shows the graphical display and the
menu selection buttons.
Graphical Display: The graphical display is capa-
ble of displaying up to 9-lines of data with approxi-
mately 27 characters per line. The display is used to
view the menus of the menu-driven operating sys-
tem. Refer to the menu trees later in this section.
The display is also used to show the following sys-
tem information:
 State Line − modes of operation, such as
Stopped, Time Delay To Start, Warm Up At
Idle, etc., and paralleling operations, such as
Standby, Dead BUS Close, Synchronize, etc.
 Action Line − system actions, such as Warning,
Derate, Shutdown Cool-down and Shutdown,
and fault codes.
 Description Line − Fault code/status mes-
sages.
Menu Buttons: Six momentary buttons—three on
each side of the graphical display window—are
used to navigate through the system control menus
and to adjust generator set parameters. The button
is active when the message or symbol adjacent to
the switch is highlighted (displayed in inverse vid-
eo). The displayed message or symbol indicates
the function of the button.
In the graphical display, the “B” symbol indicates
that selecting the adjacent button causes the operat-
ing program to go to the next menu display—as
shown in the menu diagrams.
In the graphical display, the “Y” symbol indicates
that selecting the adjacent button causes the operat-
ing program to go back to the previous menu display.
In the graphical display, the “ ” symbol indicates
that selecting the adjacent button causes the operat-
ing program to go back to Main Menu A (Figure 2-4).
STATE LINE
ACTION LINE
MENU DISPLAY
AREA
GRAPHICAL
DISPLAY
MENU
BUTTONS
DESCRIPTION LINE
MENU
BUTTONS
FIGURE 2-2. GRAPHICAL DISPLAY AND MENU SELECTION BUTTONS
2-8
LANGUAGE/UNITS SELECTION MENU
During any control panel operation, you can select
one of three languages and change how units are
displayed by pressing the two lower menu buttons
(one on each side of display). When pressing these
two buttons simultaneously, the language/units
menu will appear (Figure 2-3). After making desired
selections, press the ENTER button in this menu to
change and save the selections.
Use the + buttons to select the desired option for
each field. Use the arrow () button to move to the
next field. Selected field is highlighted.
Language: Used to select desired language (de-
fault = English).
Location: This selection must be set to Local when
the graphical display is mounted on the generator
set front control panel or Remote when mounted re-
motely from the generator set.
The Local/Remote selection determines which but-
tons in the Control submenu (page 2-13) are active
(displayed).
Temp: Used to select F or C for temperature read-
ings.
Pressure Fluid: Used to select PSI, KPA, BAR or
IN for pressure readings.
Pressure Gas: Used to select INHG or MMHG for
pressure readings.
Flow Air: Used to select CFM or CMM for air flow
readings.
ENTER
LANGUAGE ENGLISH
LOCATION LOCAL
TEMP F
PRESS FLD PSI
PRESS GAS INHG
FLOW AIR CFM
+

FIGURE 2-3. LANGUAGE/UNITS MENU
2-9
MAIN MENU
Figure 2-4 shows the main menus (Menu A and
Menu B) of the system control. The two main menus
are used to divide the system submenus into major
categories, such as, Engine Data, Alternator Data,
Control, etc.
To view system data, simply press the appropriate
menu button to select the category. After pressing
the desired menu button, refer to the page number
shown in Figure 2-4 for detailed information related
to the selected category.
In the following figures, the boxed/highlighted field
indicates that the adjacent menu button is active.
Also, the submenus are shown in the order in which
they are displayed when scrolling up Y or down B.
Adjust Button
The Adjust submenu is intended for qualified site
personnel only. Note that a password may be as-
signed to allow only authorized operators to modify
this data. (Password is not required if not assigned.)
Setup Button
The Setup submenu is described in Section 3.
The “Adjust” and “Setup” submenus can be viewed,
but not modified without entering the correct pass-
words.
_\_ Button (Paralleling Applications Only)
When displayed, indicates that the feature for gen-
erator set paralleling applications is installed. This
button is used to open and close the generator set
circuit breaker (CB). The symbol indicates if the CB
is opened or closed. Opened _\_, push to close.
Closed _−_, push to open.
With the control panel 0/Manual/Auto switch in the
Auto position, the opening and closing of the CB is
controlled by the control system software. The CB
symbol will indicate an open or closed CB, but the
button will be inactive when the control is in Auto.
In the Manual position, the CB can only be closed
by using this button. When manually closed and the
CB opens, it must be closed again by using this but-
ton. To close the CB, press and hold the button until
the symbol indicates a closed CB. (CB close will oc-
cur only when setup conditions allow − dead bus or
generator synchronized with bus.)
Power Trans Button (Power Transfer
Control Applications Only)
When displayed, indicates that the Power Transfer
Control (PTC) feature is installed. Refer to page
2-17 for PTC Data submenu description. The PTC
setup submenu is described in Section 3.
2-10
ENGINE
ALTERNATOR
CONTROL
MORE>>
POWER TRAN or _\_
HISTORY/ABOUT
PAGE
2-11
PAGE
2-12
PAGE
2-13
PAGE
2-14
Page
2-9
MENU
B
GRAPHICAL
DISPLAY
MENU
BUTTONS
MENU
BUTTONS
SETUP
ADJUST
PARALLEL DATA
BACK<<
Section
3
MENU
A
PAGE
2-16
Section
3
MENU A
MENU B
FIGURE 2-4. SYSTEM CONTROL MAIN MENUS A AND B
2-11
ENGINE SUBMENUS
If you press the “ENGINE” button in Menu A, the En-
gine submenus will appear (Figure 2-5).
The first submenu displays general information that
applies to all gensets (coolant temp, oil pressure,
etc.) The data in the remaining submenu(s) will vary
according to the type and number of sensors pro-
vided with the engine.
B
COOLANT TEMP 180  F
OIL PRESSURE 75 PSI
ENGINE SPEED 1800 RPM
BATTERY 29.1 VDC
Y
MANF TEMP 75  F
MANF PRESS ABS 180 INHG
RAIL PRESS ABS 180 PSI
PUMP PRESS ABS 291 PSI
FUEL INLET TEMP 172  F
COOLANT PRESSURE 59 PSI
ENGINE
Y
BLOWBY FLOW 25 CFM
TIMING PRESS 50 PSI
AFTERCOOLER TEMP 76  F
AMBIENT PRESS 88 INHG
B
Y
FIGURE 2-5. ENGINE SUBMENUS
2-12
ALTERNATOR SUBMENUS
If you press the “ALTERNATOR” button in Menu A,
the Alternator Data submenus will appear (Figure
2-6).
Voltage L-L and L-N: Indicates voltage Line-to
Line and Line-to-Neutral. Note that the Line-to-Neu-
tral column will not be displayed for a 3 phase/3 wire
system. Accuracy 1%.
The voltage Line-to-Line (L1, L2 and L3) are mea-
sured between L1 to L2, L2 to L3 and L3 to L1, re-
spectively.
Amps: All phases. Accuracy 1%.
Frequency: Generator set output frequency.
AVR DUTY CYCLE: Displays voltage regulator
(drive) level in percentage of maximum.
kW, kVA and PF: Displays generator set kW and
kVA output (average and individual phase, and di-
rection of flow) and power factor with leading/lag-
ging indication. Accuracy 5%.
The PF reading will contain an asterisk if the power
factor is leading (for example,
*.30).
Y
kW kVA PF
L1 350 500 .80
L2 350 500 .80
L3 350 500 .80
TOT1050 1500 .80
ALTERNATOR
B
V L-L L-N AMPS
L1 480 277 1340
L2 480 277 1290
L3 480 277 1260
FREQUENCY 60.0 HZ
AVR DUTY CYCLE 10.3 %
Y
FIGURE 2-6. ALTERNATOR SUBMENUS
2-13
CONTROL SUBMENU
If you press the “CONTROL” button in Menu A, the
Control submenu will appear (Figure 2-7).
Local CONTROL Submenu Function
When the operator panel is mounted on the control
panel assembly, the Run Mode Idle/Rated button is
active (displayed). Note in Figure 2-7 that this but-
ton is not displayed in remote applications.
The shaded area in Figure 2-7 displays the se-
lected/active mode of operation, either IDLE or
RATED.
Remote CONTROL Submenu Functions
When the operator panel (Figure 2-1) is mounted
remotely of the control panel assembly, the menu
buttons in the Control submenu are used to perform
the following remote operations. (To activate these
menu buttons for remote/local use, refer to page
2-8.)
The 0/Manual/Auto switch must be in the Auto posi-
tion to activate the Remote Menu Buttons of the Con-
trol submenu.
Remote START or STOP Button: This button is
used to start and stop the generator set when the
operator panel is mounted in a remote location.
When the generator set is operating, Stop will be
displayed for this button and Start will be displayed
when not operating.
When the generator set is operating in the Remote
Start mode, removing the Remote Start command
does not shut off the engine if the load is 10 per cent,
the cooldown timer is set to zero, and the control is
configured for a single unit (not in parallel). The gen-
erator set continues to operate until it runs out of
fuel, the E−stop button is used, or the load is re-
moved.
Fault Acknowledge Button: Used to reset inactive
Warning messages, not Shutdown messages.
Local/Remote CONTROL Submenu
Function
Bargraph Test: The function of this button remains
the same and is not dependent on operator panel
location. This button sequentially lights the LEDs to
test the bar graph display.
Enable Sync: Displayed in paralleling applications
only. Intended for service personnel to turn off the
synchronizer for troubleshooting/testing purposes.
CONTROL
(Remote)
START GENSET
FAULT ACKNOWLEDGE
CONTROL
(Local)
+ RUN MODE IDLE Y
Y
Y
BARGRAPH TEST
Y
B
BARGRAPH TEST
Y
B
ENABLE SYNC
ENABLE SYNC
FIGURE 2-7. CONTROL SUBMENU
2-14
HISTORY/ABOUT SUBMENUS
If you press the “HISTORY/ABOUT” button in Menu
A, the History/About submenus will appear (Figure
2-8).
HISTORY: The control maintains a data log of the
number of engine starts and number of operating
hours for the engine and control, and the megawatt
and maximum torque hours of the generator set.
This information is stored in non-volatile memory
and will not be deleted due to loss of battery power.
ABOUT: The About submenus provide the follow-
ing generator set information.
 Genset model and wattage (kW/MW)
 Output voltage and WYE, DELTA or SINGLE
 Frequency 50 or 60 Hz
 Rating: Standby, Prime or Base
 Version level of the controller and panel operat-
ing software.
Y
STARTS 533
ENGINE HOURS 1236
CONTROL HOURS 7879
KWHRS 890
HISTORY/ABOUT
B
B
HISTORY-HRS@ %MAX TORQUE
12345@0-9 23455@50-59
12345@10-19 12345@60-69
12345@20-29 12345@70-79
12345@30-39 12345@80-89
Y
Y
B
MODEL 1750DQKB
VOLTAGE416 WYE
FREQUENCY 60
RATINGSTANDBY
CONTROLLER VERSION
RTOPDN30008.DFA
BATSAPR 23 1999
OP PANEL VERSION
RTOP1.09 AUG 17 1999
BATS1.02 MAY 6 1999
Y
B
CONTINUED TO NEXT PAGE
FIGURE 2-8. HISTORY/ABOUT SUBMENUS
2-15
HISTORY/ABOUT SUBMENUS (CONT.)
FAULT HISTORY: The control maintains a data log
of all fault conditions as they occur, and time stamps
them with the control and engine operating hours.
Up to 32 (unacknowledged) fault codes can be
stored in control panel memory. After the fault is ac-
knowledged and corrected, the recorded fault will
be deleted from the control panel memory, but will
remain in a data log that maintains a fault code his-
tory. (The InPower service tool is required to view
this data log.)
The Fault History display line: 1 of 24 indicates that
24 faults are recorded and that the most recent fault
(1) detected by the controller is displayed.
The Occurrences display line: In this example, 5 in-
dicates that this is the fifth occurrence of this fault.
(The InPower service tool is required to review the
last four faults of this code.)
The Occurrences number is incremented for each
new occurrence of the same fault. The controller
must detect that the original sensed fault is cor-
rected before it will increment the occurrence num-
ber for that fault.
For example, when a Low Oil Pressure fault is de-
tected, the controller will increment the Occurrences
number by 1. This fault will remain active until the
fault is acknowledged and the controller detects that
the fault is corrected. An active fault will prevent the
controller from incrementing the Occurrences num-
ber each time the engine is started. When the con-
troller detects that the oil pressure is normal the fault
will become inactive, allowing the occurrences num-
ber to be incremented for the next detected Low Oil
Pressure
fault.
FAULT HISTORY: 1 OF 24
CNTL HOURS 459
OCCURRENCES 5
ENGINE HOURS 334
FAULT CODE 1437
(FAULT DESCRIPTION)
HISTORY/ABOUT (CONT.)
Y +
FIGURE 2-8. HISTORY/ABOUT SUBMENUS (CONT.)
2-16
PARALLEL DATA SUBMENU
If you press the “PARALLEL DATA” button in Menu
B, the Parallel Data submenu will appear (Figure
2-9). This menu is displayed in paralleling applica-
tions only.
PARALLEL DATA STATUS LINE: The top line of
the graphical display is used to indicate the follow-
ing PARALLEL DATA status:
− STANDBY: Indicates no paralleling activity is
occurring at present.
− DEAD BUS CLOSE: Indicates first genset in
system to close to bus.
− SYNCHRONIZE: Genset is synchronizing to
bus.
− LOAD SHARE: Genset has closed to bus and
is sharing load with other gensets in system.
− LOAD GOVERN: Genset closed to bus in par-
allel with utility (mains).
BUS Voltage L-L: The BUS voltage Line-to-Line
(L1, L2 and L3) are measured between L1 to L2, L2
to L3 and L3 to L1, respectively.
BUS/GEN HZ: BUS/GEN hertz.
BUS/GEN SYNC STATUS: The bottom line of the
graphical display is used to indicate the following
BUS/GEN Sync status:
− NOT SYNCHRONIZING: Genset is in service
mode that does not allow auto sync feature.
(Selected via InPower service tool − deactivate
to allow synchronization.)
− SYNCHRONIZING: Genset is synchronizing to
bus.
− READY TO CLOSE: In manual mode, push cir-
cuit breaker close button to close breaker.
_\_ Button: Used to open and close the generator
set circuit breaker (CB). The symbol indicates if the
CB is opened or closed. Opened _\_, push to close.
Closed _−_, push to open.
With the control panel 0/Manual/Auto switch in the
Auto position, the opening and closing of the CB is
controlled by the control system software. The CB
symbol will indicate an open or closed CB, but the
button will be inactive when the control is in Auto.
In the Manual position, the CB must be closed by
this button. When manually closed and the CB
opens, it must be closed again by using this button.
To close the CB, press and hold the button until the
symbol indicates a closed CB. (CB close will occur
only when setup conditions allow − dead bus or
generator synchronized with bus.)
_\_
Y
V BUS GEN
L1480 480
L2480 480
L3480 480
HZ60.1 60.1
DEG −122 NOT SYNCHRONIZING
PARALLEL DATA
LOAD GOVERN
FIGURE 2-9. BUS DATA SUBMENU
2-17
POWER TRANSFER MAIN/SUBMENUS
If you press the “POWER TRANS” button in Menu
A, the Power Transfer main menu will appear (Fig-
ure 2-10). The Power Transfer Control (PTC) fea-
ture must be installed to display this menu.
The PTC feature enables the PCC to monitor the
utility voltage (mains) and frequency for failure and
control the opening and closing of the contacts (cir-
cuit breakers) for the utility (S1) and the genset
(S2).
If utility fails, the control will initiate the genset start-
ing sequence, open S1 and close S2 to the load.
When utility returns, the load is retransferred to the
utility (S1 closes/S2 opens) and the control initiates
the genset shutdown sequence.
The symbol displayed in the middle of the Pow-
er Transfer main menu indicates which breaker
(utility or genset) is closed/opened to the load. The
symbol presently shown indicates that the utility
breaker is closed and supplying power to the load.
The Power Transfer main menu also indicates if the
utility and the generator set are available to accept
load. When the control detects that either source is
ready to accept load, UTILITY and/or GENSET will
be displayed in inverse video.
The Power Transfer main menu has four submenu
groups. Refer to the page numbers shown in Figure
2-10 for the Power Transfer submenu descriptions.
2-18
PTC Status Line
The top line of the graphical display is used to indi-
cate the following PTC status:
− NOT ENABLED: PTC is not enabled. Control
panel switch in O (Off) position.
− MANUAL: Control panel switch is in Manual
position. All PTC actions or genset start/stop
actions are manually controlled.
− NORMAL UTIL: Load is connected to the util-
ity.
− RETRAN: Retransfer of load to utility.
− RETRAN OVRD: Immediate retransfer of load
to utility due to genset fault (e.g., warning, der-
ate, or shutdown w/cooldown fault). The re-
transfer timer is ignored as is the retransfer in-
hibit.
− EMERG TEST: Emergency Test sequence ini-
tiated through Remote Start switch with emer-
gency start sequence enabled (TB8-3 terminal
opened). Emergency test mode means that
the genset will continue to run even if a genset
warning or derate fault occurs. This test can be
performed with or without load (refer to TEST/
EXERCISE submenu in Section 3).
− TEST: Test sequence initiated through Remote
Start switch with emergency start sequence
disabled (TB8-3 terminal closed). Test mode is
non-emergency, which means that a retransfer
to utility will occur if any problems occur with
the genset while testing with load. This test can
be performed with or without load (refer to
TEST/EXERCISE submenu in Section 3).
− EXERCISE: Exercise sequence initiated
through control panel. This test can be per-
formed with or without load (refer to TEST/EX-
ERCISE submenu in Section 3). A retransfer to
utility will occur if any problems occur with the
genset during the exercise sequence.
− UTILITY FAIL: Utility has failed. (Initiates
transfer of load to genset if O/MANUAL/AUTO
switch is in AUTO.)
B UTILITY
STATUS
TRANSFER CONTROL
GENSET B
PAGE
2-19
PAGE
2-20
PAGE
2-21
MENU
A
PAGE
2-22
MENU
BUTTONS
MENU
BUTTONS
DEG −123 SYNCHRONIZING
PTC STATUS LINE
FIGURE 2-10. POWER TRANSFER MAIN MENU
2-19
UTILITY (PWR TRAN) SUBMENUS
If you press the “Utility” button in the Power Transfer
Main menu, the Utility submenus will appear (Fig-
ure 2-11).
Voltage L-L and L-N: Indicates utility voltage Line-
to Line and Line-to-Neutral. Note that the Line-to-
Neutral column will not be displayed for a 3 phase/3
wire system. Accuracy 1%.
The voltage Line-to-Line (L1, L2 and L3) are mea-
sured between L1 to L2, L2 to L3 and L3 to L1, re-
spectively.
Amps: L2 only. Accuracy 1%.
Frequency: Utility frequency.
kW, kVA and PF: Displays (L2 only) utility kW and
kVA output (average and direction of flow) and pow-
er factor with leading/lagging indication. Accuracy
5%.
The PF reading will contain an asterisk if the power
factor is leading (for example, *.30).
Y
UTILITY:
kW kVA PF
L1
L2 125 175 .96
L3
TOT
UTILITY
B
UTILITY:
V L-L L-N AMPS
L1480 277
L2 480 277 1320
L3480 277
FREQUENCY 60.0 HZ
Y
FIGURE 2-11. UTILITY SUBMENUS
2-20
STATUS (PWR TRAN) SUBMENUS
If you press the “Status” button in the Power Trans-
fer Main menu, the Status submenus will appear
(Figure 2-12).
Connected: Indicates which source(s) is con-
nected to the load.
Available: Indicates when the corresponding
sources have acceptable output voltage and fre-
quency. Both can be available simultaneously.
Volt L12: Indicates utility and generator set Line 1 to
Line 2 voltage.
HZ: Utility and generator set output frequency.
KW L2: Utility and generator set Phase B (L2) kW
output.
Transfer Inhibit: This feature is used to control
load transfer to the genset. When activated, load
transfer to the genset will not take place if the utility
fails.
Transfer inhibit is controlled by connecting a remote
contact between TB3-57 and TB3-58. Closing the
contact enables the feature and opening the con-
tact disables it. When enabled, the event is dis-
played on the graphical display.
Retransfer Inhibit: This feature is used to prevent
the PTC from automatically transferring the load
back to the utility. When activated, load transfer will
not take place unless the genset fails (Retransfer
Inhibit is ignored if the genset fails).
Retransfer inhibit is controlled by connecting a re-
mote contact between TB3-64 and TB3-65. Closing
the contact enables the feature and opening the
contact disables it. When enabled, the event is dis-
played on the graphical display.
Y
TRAN INHOFF
RETRAN INH ON
STATUS
B
UTIL GEN
CONNECTED YES NO
AVAILABLEYES NO
VOLT L12 480 0
HZ 60.0 0.0
KW L2 456 0
Y
FIGURE 2-12. STATUS SUBMENUS
2-21
TRANSFER CONTROL (PWR TRAN) SUBMENU
If you press the “TRANSFER CONTROL” button in
the Power Transfer Main menu, the Transfer Con-
trol submenu will appear (Figure 2-13).
The symbol displayed in the middle of the
TRANSFER CONTROL submenu indicates which
breaker (utility or genset) is closed/opened to the
load. The symbol presently shown indicates that the
utility breaker is closed and supplying power to the
load.
During genset operation in the manual mode, you
can manually transfer/retransfer load between the
utility and the genset. To transfer load, press the ap-
propriate CB ENABLE button (Utility or Genset).
Example (Figure 2-13)
In the example in Figure 2-13, the CB ENABLE but-
ton for “Utility” was pressed. (If the CB ENABLE
button for the “Genset” was pressed, ENABLE
GEN CB would be displayed in the second subme-
nu, allowing you to open or close the genset circuit
breaker.)
After pressing the “utility” CB ENABLE button, the
second submenu will be displayed allowing you to
either CANCEL or ENABLE the entered selection.
Pressing the CANCEL button will return the display
to the previous menu.
Pressing the ENABLE button will display the third
submenu. With this submenu displayed you can re-
turn to the second submenu without opening the
utility circuit breaker (press <<BACK) or you can
press the OPEN UTIL button.
Pressing the OPEN UTIL button will display the
fourth submenu, indicating that the utility circuit
breaker is now opened.
Note that the fourth submenu displays CLOSE
UTIL. Pressing this button will close the utility circuit
breaker and redisplay the third subme-
nu.
ENABLE UTIL CB
TRANSFER CONTROL
UTILITY GENSET
CB ENABLE CB ENABLE
<< BACK
CANCEL
UTILITY GENSET
OPEN UTIL CB ENABLE
<< BACK
UTILITY GENSET
CLOSE UTIL CB ENABLE
<< BACK
FIGURE 2-13. TRANSFER CONTROL SUBME-
NUS
2-22
GENSET (PWR TRAN) SUBMENUS
If you press the “Genset” button in the Power Trans-
fer Main menu, the Genset submenus will appear
(Figure 2-14).
Voltage L-L and L-N: Indicates voltage Line-to
Line and Line-to-Neutral. Note that the Line-to-Neu-
tral column will not be displayed for a 3 phase/3 wire
system. Accuracy 1%.
The voltage Line-to-Line (L1, L2 and L3) are mea-
sured between L1 to L2, L2 to L3 and L3 to L1, re-
spectively.
Amps: All phases. Accuracy 1%.
Frequency: Generator set output frequency.
kW, kVA and PF: Displays generator set kW and
kVA output (average and individual phase, and di-
rection of flow) and power factor with leading/lag-
ging indication. Accuracy 5%.
The PF reading will contain an asterisk if the power
factor is leading (for example,
*.30).
Y
GENSET:
kW kVA PF
L1 100 150 .97
L2 125 175 .96
L3 150 200 .95
TOT375 525 .96
GENSET
B
GENSET:
V L-L L-N AMPS
L1 480 277 1320
L2 480 277 1320
L3 480 277 1320
FREQUENCY 60.0 HZ
Y
FIGURE 2-14. GENSET SUBMENUS
3-1
3. Control Calibration and Adjustment
GENERAL
This section contains calibration and adjustment
procedures for the generator set control.
PARALLELING AND NON−PARALLELING
If the generator set was purchased for a paralling
application but will be used for a non−paralling ap-
plication, entering the checksum data into the Data-
plate Checksum dialog in InPowert is not re-
quired. However, the Adjustments Paralleling −
Paralleling Level must be set to Basic.
SOFTWARE CALIBRATIONS
If the base card has software assembly A026 F566
v1.0 on the U33 flash memory chip, you must use
the latest software calibration for the control. If you
load an earlier software calibration onto a base card
with software assembly A026 F566 v1.0, the soft-
ware calibration will fail, and the board will lock up
permanent-
ly.
FIGURE 3-1. U33 FLASH MEMORY CHIP
CAUTION If the base card has software as-
sembly A026 F566 v1.0 on the U33 flash memory
chip, you must use the latest software calibra-
tion for the control, or the board will lock up per-
manently.
MODIFYING SETUP/ADJUST SUBMENUS
The Setup and Adjust submenus allow you to cali-
brate the graphical display meters and to adjust
system parameters, customer defined faults, gen-
erator set voltage/frequency and paralleling ap-
plications.
CAUTION Improper calibration or adjustment
of the control can cause equipment malfunction
or damage. Calibration and adjustment must be
performed by technically qualified personnel
only.
The Setup submenus are intended for qualified ser-
vice personnel only. The Adjust submenu is in-
tended for qualified service and site personnel only.
For this reason, a password must be entered before
this data can be modified. The Setup and Adjust
submenus can be viewed, but not modified without
entering the correct password.
Saving Menu Changes
Changes are automatically saved when the menu is
exited.
3-2
PASSWORD Menu
To allow the site personnel to modify only the Adjust
submenu and not the Setup submenus, two pass-
words are assigned within the system software. An
Application password is used for the Setup sub-
menus and a User password is used for the Adjust
submenu.
The two passwords are assigned during the initial
installation of the generator set (via InPower) and
will vary between sites. The installer must make
sure that the passwords are available to the ap-
propriate personnel.
When the generator set is first installed, the Applica-
tion and User password are both set to GENSET to
allow initial modification of the Setup and Adjust
submenus. Assign new passwords when site instal-
lation is complete.
When viewing the Adjust menu, pressing the + or −
button will display the User Password menu.
When viewing a Setup menu, pressing the + or −
button will always display the Application Password
menu.
After entering the correct password, the system will
allow you to modify the submenus. To help prevent
unauthorized adjustment, the entered password is
valid for 10 minutes after the last button is pressed
(i.e., the password will need to be reentered after
the ten minute time−out.
Entering Password
To enter the password:
1. Display submenu to modify.
2. Press either the + or − button within the dis-
played submenu. The Password menu ap-
pears.
3. Press the + and − button to select the first char-
acter of the password (A−Z or 0−9). (Enter Ap-
plication password for Setup submenus; En-
ter User password for Adjust submenu.)
4. Press the  button to select the next character
field. Selected character field is highlighted.
5. Repeat steps 3 and 4 to enter remaining pass-
word characters.
6. Press the Enter button after entering the pass-
word. The submenu selected in step 1 will re-
appear.
7. After making desired changes to submenu, exit
submenu to save changes.
+ OR − BUTTON
ENTER
ENTER APPLICATION PASSWORD
+


XXXXXXXX
+ OR − BUTTON
ENTER
ENTER USER PASSWORD
+


XXXXXXXX
SETUP SUBMENU PASSWORD MENU ADJUST SUBMENU PASSWORD MENU
FIGURE 3-2. PASSWORD MENUS
3-3
SETUP MENUS
Figure 3-3 shows the main menus (Menu A and
Menu B) of the system control and the two Setup
menus.
The Setup procedure is intended for qualified ser-
vice personnel only. The APPLICATION password
must be entered to modify the Setup submenu
fields. Refer to PASSWORD Menu in this section to
enter password and to save menu changes.
To display the two Setup menus, press the
MORE>> button in Menu A and then the SETUP
button in Menu B.
To view system data or to adjust system parame-
ters, press the appropriate Setup menu button to
display the desired Setup submenu(s). Refer to the
page number shown in Figure 3-3 for detailed infor-
mation related to the selected submenu(s).
CAUTION Improper calibration or adjustment
of the control can cause equipment malfunction
or damage. Calibration and adjustment must be
performed by technically qualified personnel
only.
GOVERNING/VOLT REG
CUSTOMER FAULTS
CALIBRATION
Y
B
ISOLATED BUS
UTILITY
ENGINE
ALTERNATOR
CONTROL
MORE>>
POWER TRAN or _\_
HISTORY/ABOUT SETUP
ADJUST
PARALLEL DATA
BACK<<
MENU A MENU B
PAGE
3-4
PAGE
3-5
PAGE
3-6
MENU
A
MENU
B
NEXT
MENU
PAGE
3-7
PAGE
3-11
MENU
A
ABOVE
MENU
MENU
B
MENU
A
Y POWER TRANSFER SETUP
SETUP MENU 1
SETUP MENU 2
PAGE
3-12
FIGURE 3-3. SETUP SUBMENUS
3-4
GOVERNING/VOLT REG SUBMENU
If you press the “GOVERNING/VOLT REG” button
in the Setup menu, the Governing/Volt Regulator
submenu will appear (Figure 3-4).
Use the + and − buttons to increase or decrease the
values in the following fields. Use the arrow () but-
ton to move the cursor within a field or to the next
field. Exit menu to safe changes.
GOV GAIN: If the gain adjustment is set too high,
engine speed will “hunt” or oscillate. If gain is set too
low, the engine will respond too slowly to changes in
load and overspeed may result. (Gain should be re-
duced to 80% for paralleling installations.)
AVR GAIN: If the gain adjustment is set too high,
output voltage will be unstable. If gain is set too low,
the output voltage will respond sluggishly to
changes in load and overshoot may result.
3-5
GOVERNING/VOLT REG
Y
GOV GAIN 80%
AVR GAIN 100%
+


FIGURE 3-4. GOVERNING/VOLT REG SUBMENU
3-6
CUSTOMER FAULTS SUBMENUS
If you press the “CUSTOMER FAULTS” button in
the Setup menu, the Customer Faults submenus
will appear (Figure 3-5).
There are a total of four customer fault inputs.
(Faults 3 and 4 paralleling only.) The message dis-
played at the bottom of the menu can be modified
for each of these faults in addition to selecting the
following operating parameters for each fault.
 Enable − On or Off
 Active − Closed or Open
 Response − Shutdown, Cooldown, Derate or
Warning
Shutdown: Genset will immediately shut
down. Normally used for engine faults.
Cooldown: Cooldown sequence will be initi-
ated before shutdown. Should not be used for
engine faults.
Derate: Used to lower kW output of genset for
warnings such as pre-high coolant tempera-
ture, etc. Paralleling application − controller will
reduce precentage of kW load sharing on the
set. Non-paralleling application − controller will
lower percentage of kW load by operating load
shed relay contacts.
Warning: Display message, genset continues
to operate.
The Enable and the Active fields apply to the Fault 1
and 4 submenus only.
With the Active field selected, pressing the + or −
buttons will toggle the selection between CLOSED
and OPEN. Use same operation for remaining field
selections.
To enter the desired customer fault message, press
the B or Y button to display the submenu that con-
tains the customer fault message (1 through 4) to be
changed. Use the  button to scroll down through
the menu selections to the editable fault message
(bottom menu line).
Use the  button to move to each character posi-
tion within the fault message line.
With the desired character position selected, use +
or − buttons to select the appropriate character.
If these messages are changed, you should note
these changes in the Troubleshooting section of the
Operator’s manual for this generator set.
3-7
CUSTOMER FAULTS
Y
B
CUSTOMER FAULT1:
ENABLE ON
ACTIVE CLOSED
RESPONSE WARNING
***CUSTOMER FAULT1 ******************
+


CONTINUES THROUGH TWO
ADDITIONAL MENUS FOR A
TOTAL OF FOUR POSSIBLE
CUSTOMER FAULT MESSAGES
Y
B
+


CUSTOMER FAULT2:
RESPONSE WARNING
***CUSTOMER FAULT2 ******************
FIGURE 3-5. CUSTOMER FAULTS SUBMENUS
3-8
CALIBRATION SUBMENUS
If you press the “CALIBRATION” button in the Setup
menu, the Calibration submenus will appear (Fig-
ure 3-6).
Use the + and − buttons to increase or decrease the
values in the following fields. Use the arrow () but-
ton to move the cursor within a field or to the next
field. Exit menu to safe changes.
The Calibration submenus allow you to calibrate the
control with the reading from a calibrated meter.
Calibration is accomplished by using this section of
the menu software to adjust the display so that it
matches the reading taken on an accurate, recently
calibrated meter.
Calibration is normally only required when replac-
ing certain circuit cards. Refer to the Calibration
Procedure in this section which contains a list of the
cards that require control calibration.
When performing Bus Voltage Calibration from the
graphical display, the genset must be off and the Bus
live. If the genset is running, it will synchronize to the
Bus.
3-9
CALIBRATION
VOLTAGE CALIBRATION
L1 480-X.X%
L2 480-X.X%
L3 480-X.X%
+


CURRENT CALIBRATION
L1 234-X.X%
L2 123-X.X%
L3 562-X.X%
+


BUS VOLTAGE CALIBRATION
L1 480 -X.X%
L2 480 -X.X%
L3 480 -X.X%
+


Y
Y
B
Y
B
FIGURE 3-6. CALIBRATION SUBMENUS
3-10
ISOLATED BUS / UTILITY Submenus
(Paralleling Application)
The Isolated BUS submenus (Figure 3-7) and the
Utility submenus (Figure 3-8) adjust the control pa-
rameters for generator set protection, synchroniz-
ing and load sharing for both isolated bus and utility
(mains) paralleling applications. Utility (mains) par-
allel applications may require adjustment of both
the Isolated BUS and Utility submenus.
Always perform ISO BUS calibration before Utility
BUS calibration.
The sync check (permissive) function is operational
in both automatic and manual (RUN) modes. The
control will make sure that the generator set is at
proper voltage, within the defined sync check win-
dow for the defined period of time and that phase
rotation is correct. When all criteria are met, the par-
alleling breaker is closed automatically by the con-
trol (auto mode), or by operation of the breaker
close switch by the operator (manual mode).
The synchronizing function of the control is enabled
when the control has brought the generator set to
90% of rated speed and voltage, and has sensed
that bus voltage is available. The control automati-
cally adjusts the generator set speed and voltage to
match the bus frequency and voltage. The control
can force the generator set to match bus voltage
and frequency in a range of minus 40% to plus 10%
of normal bus conditions. When the paralleling
breaker has closed, the control will bring the gener-
ator set back to normal voltage and frequency.
When the generator set is paralleled to another
generator set, the control provides automatic load
sharing functions for both real (kW) and reactive
(kVAR) loads. Load sharing is proportional between
generator sets based on their standby ratings. If two
generator sets of different sizes are paralleled, they
will assume the same percentage of the system
load automatically. This can easily be verified on the
kW Load LED bar graph on the front of the control
panel.
When the utility paralleling mode is enabled and the
generator set paralleling breaker is closed, the gen-
erator set will assume load based on external ana-
log input signal. The input signal must be calibrated
from 0−5 VDC. When the signal is at 0.5 to 1 VDC,
the control will operate the generator at no load in
parallel with the utility (mains) source. At 4.5 VDC
and greater, the control will operate the generator
set at 110% of the generator set base load setting.
When the load govern signal is between 1 VDC and
4.5 VDC the control will operate the generator set at
a load level which is determined by a linear relation-
ship between the kW reference and the load govern
signal.
3-11
ISOLATED BUS SUBMENUS
If you press the “ISOLATED BUS” button in the Set-
up menu, the Isolated BUS submenus will appear
(Figure 3-7).
Use the + and − buttons to increase or decrease the
values in the following fields. Use the arrow () but-
ton to move the cursor within a field or to the next
field. Exit menu to safe changes.
SYNC TIME LIMIT: This parameter adjusts the time
delay in seconds before the Fail To Synchronize
alarm will operate.
REVERSE PWR LMT: Adjusts the reverse power
set point. For PowerCommand generator sets, a
typical set point is 10-15%.
REVERSE PWR TIME: Adjusts the reverse power
function time delay. A typical time delay which is
suitable for PowerCommand generator sets is 3
seconds.
Lower reverse power set points can result in nui-
sance reverse power shutdown faults.
PERM WIN-PHASE: Adjusts the width of the per-
missive (sync-check) acceptance window. The ad-
justment range is from five to twenty electrical de-
grees. Recommended set point is 20 degrees for
isolated bus applications, and 15 degrees for utility
(mains) paralleling applications.
PERM WIN-TIME: Adjusts the time period (in sec-
onds) for which the generator set must be synchro-
nized with the system bus, before a breaker close
signal is issued by the PowerCommand control.
Available range is 0.5 to 5 seconds. Recommended
value for PowerCommand generator sets is 0.5
seconds for isolated bus applications.
3-12
ISOLATED BUS
ISOLATED BUS:
SYNC TIME LIMIT 120 SEC
REV PWR LMT 10 %
REV PWR TIME 3 SEC
PERM WIN-PH 20 DEG
PERM WIN-TIME .5 SEC
+


Y
B
CONTINUED TO NEXT PAGE
FIGURE 3-7. ISO BUS SUBMENUS
3-13
Adjusting the control for a smaller sync-check win-
dow or longer time delay will cause synchronizing
time to be extended.
SYNC GAIN: The sync gain adjustment controls
how quickly the governor will respond to try to mini-
mize the bus/generator phase difference. Increas-
ing the gain speeds up the response. If the gain is
too high instability can result.
KW Balance and KVAR Balance changes should be
equally shared among all generator sets.
KW BALANCE: This function adjusts the kW load
sharing function of the generator set. Before adjust-
ing this value, all generator set calibrations should
be performed. If the total load on the system is not
shared proportionately, the kW Balance can be
used to adjust the generator set for more precise
load sharing. Increasing the kW Balance value will
cause the generator set to reduce the percentage of
the total kW load on that set.
KVAR BALANCE: This function adjusts the kVAR
load sharing function of the generator set. Before
adjusting this value, all generator set calibrations
should be performed. If the total load on the system
is not shared proportionately, the kVAR balance can
be used to adjust the generator set for more precise
load sharing. Increasing the kVAR balance value
will cause the generator set to reduce the percent-
age of the total kVAR load on that set.
KW GAIN: Adjusts the rate of change of kW load on
the generator set. With a constant load on the sys-
tem, if the generator set load is constantly chang-
ing, reduce the gain adjustment on the generator
set. This also allows modification of the rate of load
assumption on transient load change.
KVAR GAIN: Adjusts the rate of change of kVAR
load on the generator set. With a constant load on
the system, if the generator set load is constantly
changing, reduce the gain adjustment on the gener-
ator set. This also allows modification of the rate of
load assumption on transient load change.
3-14
ISOLATED BUS (CONT.)
ISOLATED BUS:
SYNC GAIN 1.0
KW BALANCE 0.3
KVAR BALANCE 1.2
KW GAIN 1.0
KVAR GAIN 1.0
+


Y
B
CONTINUED TO NEXT PAGE
FIGURE 3-7. ISO BUS SUBMENUS (CONT.)
3-15
1ST FAIL TIME: Time delay in seconds after a sig-
nal from the first start master is not sensed by the
PCC that a FIRST START FAIL warning is dis-
played.
RAMP UNLOAD TIME: When a load demand stop
input is sensed the load is ramped down from the
present load level on the set to the ramp unload lev-
el in the time specified in seconds.
RAMP UNLOAD LEVEL: The load demand ramp
unload function will ramp the load down from the
present level on the set to this level before opening
the set circuit breaker. Value shown is in % of genset
standby rating.
RAMP LOAD TIME: When the load demand stop
signal is removed the load is ramped from 0kW to
the load share level in the specified time after the
circuit breaker closes.
LOSS FIELD TIME: Adjusts the loss of field func-
tion time delay. A typical delay which is suitable for
PowerCommand generator sets is 2 seconds.
3-16
ISOLATED BUS (CONT.)
ISOLATED BUS:
1ST FAIL TIME 12 SEC
RAMP UNLD 20 SEC
RAMP UNLD LEVEL 10 %
RAMP LOAD TIME 3 SEC
LOSS FIELD 20 SEC
+


Y
FIGURE 3-7. ISO BUS SUBMENUS (CONT.)
3-17
UTILITY SUBMENUS
If you press the “UTILITY” button in the Setup
menu, the Utility submenus will appear (Figure 3-8).
Use the + and − buttons to increase or decrease the
values in the following fields. Use the arrow () but-
ton to move the cursor within a field or to the next
field. Exit menu to safe changes.
BASE LOAD (%): This controls the maximum kW
load level that the generator set will operate at when
paralleled with the utility (mains). The value shown
indicates the steady state load on the generator as
a percent of the generator set standby rating.
Check generator set ratings for maximum load level
at which the generator set should operate when
paralleled with the utility (mains). Extended opera-
tion at load levels in excess of the generator set rat-
ing can cause abnormal engine wear or premature
engine failure.
PF LEVEL: Adjusts the power factor that the gener-
ator set will run at when paralleled to the utility
(mains). Recommended setting is 1.0.
RAMP LOAD TIME: This is the ramp time from
present set load to level determined by the load set
analog input. This is active when the control first en-
ters the load govern mode.
RAMP UNLOAD TIME: This is the ramp time from
present set load to 0 kW. This ramp is active when
the load set analog input is less than 0.5 volts.
MODE − MULTIPLE/SINGLE: This controls wheth-
er the set is to operate as part of a multiple set or
single set (PLTE or PLTF) system. (Refer to “LOAD
DEMAND SHUTDOWN” and “SINGLE MODE EN-
ABLE” function descriptions in wiring diagram,
page 5-8.)
KW GOVERN GAIN: This controls the rate that the
generator set kW load is increased after the genera-
tor set has closed to the system bus when utility
(mains) paralleled. Decreasing this value will result
in slower loading of the generator set.
KVAR GOVERN GAIN: This controls the rate that
the generator set kVAR load is increased after the
generator set has closed to the system bus when
utility (mains) paralleled. Decreasing this value will
result in slower loading of the generator set.
3-18
UTILITY
UTILITY:
BASE LOAD 80%
PF LEVEL 1.00
RAMP LOAD 3
RAMP UNLD 20
MODE MULTIPLE
+


UTILITY:
KW GOVERN GAIN 1.00
KVAR GOVERN GAIN1.00
+


Y
B
Y
FIGURE 3-8. UTILITY SUBMENUS
3-19
POWER TRANSFER CONTROL MAIN
MENUS
If you press the “POWER TRANSFER SETUP” but-
ton in the Setup menu 2 in Figure 3-3, the two main
menus of the optional Power Transfer Control
(PTC) feature will appear (Figure 3-9).
To adjust PTC system parameters, press the ap-
propriate PTC main menu button and refer to the
page number shown in Figure 3-9 for detailed infor-
mation related to the submenu selected.
UTILITY SENSORS
GENSET SENSORS
TIMERS
Y
B
PAGE
3-13
PAGE
3-15
PAGE
3-17
NEXT
MENU
TEST/EXERCISE Y
PAGE
3-18
PTC MAIN MENU 1
PTC MAIN MENU 2
FIGURE 3-9. PTC SETUP MAIN MENUS
3-20
UTILITY SENSORS SUBMENUS
If you press the “UTILITY SENSORS” button in the
PTC Main Menu 1, the Utility Sensors submenus
will appear (Figure 3-10).
The following field descriptions show the valid field
entries and default value (shown in parenthesis) for
each field.
Use the + and − buttons to increase or decrease the
values in the following fields. Use the arrow () but-
ton to move the cursor within a field or to the next
field. Exit menu to save changes.
U PT VOLT LL: Enter the value of the utility line-to-
line voltage which yields 100% voltage at the termi-
nals of the utility (bus) PT module.
Range: 1−15000V, adjustable by standard nominal
voltage values, 100V, 10V and 1V increments (1V).
The 100% voltages for each of the four possible util-
ity (bus) PT modules are as follows, based on mod-
ule dash number:
−01 = 208 volts LL
−02 = 416 volts LL
−03 = 600 volts LL
−04 = 120 volts LL
Example 1: Nominal Utility voltage is 480V. This
means that utility (bus) PT module number −02
should be used. The voltage which will yield 100%
volts at this PT module is 416 per the above table.
Thus enter 416V.
Example 2: Nominal Utility voltage is 4160V. A pri-
mary stage transformer with a ratio of 4200/240 is
used. This means that utility (bus) PT module num-
ber −01 should be used. The voltage which will yield
the 100% volts (208V from above table) is calcu-
lated as follows:
208 x (4200/240) = 3640. Thus enter 3640V.
U NOM VOLT LL: Enter the nominal utility line-to-
line voltage. For example, 480, 4160, etc.. Range:
1−15000 V, adjustable by standard nominal voltage
values, 100V, 10V and 1V increments (1V).
U CT RATIO: Enter the CT Ratio of the Utility L2 CT.
This is the Ratio to 1 Amp. Range: 1−18000 (1A).
CAUTION This CT must be rated for 1 Amp
output (e.g. NOT 5 Amp). Be sure CT secondary
circuit has burden resistor or a shorting jumper
in place before putting power through the CT.
Example: CT Ratio = 2650:1. Thus enter 2650.
U SENSOR TYPE: Enter the line-to-line (L-N) for 3
phase line-neutral voltage sensing or line-to-line
(L-L) for 3 phase line-line voltage sensing. This ap-
plies to both the utility undervoltage and overvol-
tage sensors. Range: L−L, L−N (L−N).
U <wye> <delta>: Enter utility connection type.
Range: Delta, Wye (Wye).
U UNLOADED KW: Enter the kW on utility Line 2 at
which the utility is considered as unloaded. This is
the L2 kW level at which a closed transition soft
transfer will disconnect from the utility.
UTILITY UNDERVOLTAGE: Non-adjustable field,
always enabled.
UTILITY OVERVOLTAGE, FREQUENCY: Used to
enable or disable menu function. Choose Enabled
or Disabled (Enabled).
UV PICKUP: Enter a number between 85 and
100% of the nominal voltage (90%).
UV DROP OUT: Enter a number between 75 and
98% of the under-voltage pick-up percentage
(90%).
UV DELAY: Enter a time between 0.1 and 5.0 sec-
onds (0.5 seconds).
UV MIN PHASE: Displays the lowest line voltage of
the three utility phases.
3-21
OV PICKUP: This adjusts the over-voltage pickup
as a percentage of the over-voltage drop-out. Enter
a number between 95 and 99% (95%).
OV DROP OUT: Enter a percentage between 105
and 135% of the nominal voltage (110%).
OV DELAY: Enter a range between 0 and 120 sec-
onds (3 seconds).
OV MAX PHASE: Displays the highest line voltage
of the three utility phases.
CENTER (FREQ): Enter a frequency between 45
and 65 Hz (60 Hz).
PICK UP (FREQ): Enter a percentage between 5
and 20% of the nominal frequency (10%).
DROP OUT (FREQ): Enter a percentage between
1 and 5% of the nominal frequency (1%).
DELAY (FREQ): Enter a time between 0.1 and 15.0
seconds (5.0 seconds).
FREQUENCY: This field displays the sensed utility
line frequency.
UTILITY SENSORS
U PT VOLT LL 416
U NOM VOLT LL 480
U CT RATIO: 1 1000
U SENSOR TYPE L−L
U UNLOADED KW 50 KW
+


Y
UTILITY UV: ENABLED
% VLL
PICK UP 95 475
DROP OUT 85 465
DELAY 0.5 S
MIN PHASE 470
+


Y
B
UTILITY OV: DISABLED
% VLL
PICK UP 95 487
DROP OUT 110 490
DELAY 3.0 S
MAX PHASE485
+


Y
B
UTILITY FREQ: DISABLED
CENTER 60 HZ
PICK UP 10 %
DROP OUT 1 %
DELAY 1.0 S
FREQUENCY60.5 HZ
+


Y
B
FIGURE 3-10. UTILITY SENSORS SUBMENUS
3-22
GENSET SENSORS SUBMENUS
If you press the “GENSET SENSORS” button in the
PTC Main Menu 1, the Genset Sensors submenus
will appear (Figure 3-11).
The following field descriptions show the valid field
entries and default value (shown in parenthesis) for
each field.
Use the + and − buttons to increase or decrease the
values in the following fields. Use the arrow () but-
ton to move the cursor within a field or to the next
field. Exit menu to save changes.
G NOM VOLT LL: Non-adjustable field, displays
current setting of genset nominal voltage. (See Ad-
just submenu to adjust the output voltage 5%.)
G SENSOR TYPE: Enter the line-to-line (L-N) for 3
phase line-neutral voltage sensing or line-to-line
(L-L) for 3 phase line-line voltage sensing. This ap-
plies to both the genset undervoltage and overvol-
tage sensors. Range: L−L, L−N (L−N).
G BASE LOAD: Enter the maximum load the gen-
set will carry during a closed transition. Range:
0−100% (80%).
G RAMP LOAD: Enter the ramp time for the genset
ramp load rate during a closed transition soft load
transfer. Ramp rate is +100%kW divided by this
time setting. Range: 0−900 seconds (20 sec).
G RAMP UNLOAD: Enter the ramp time for the
genset ramp unload rate during a closed transtion
soft load retransfer. Ramp rate is −100%kW divided
by this time setting. Range: 0−900 seconds (20
sec).
G UNLOADED KW: Enter the %kW (based on
standby rating) that the genset is considered un-
loaded. This is the %kW level at which a closed tran-
sition soft retransfer will disconnect from the gen-
set. Range: 0−100% (5%).
GEN UNDERVOLTAGE: Non-adjustable field, al-
ways enabled.
GEN OVERVOLTAGE, FREQUENCY: Used to en-
able or disable menu function. Choose Enabled or
Disabled (Enabled).
UV PICKUP: Enter a number between 85 and
100% of the nominal voltage (90%).
UV DROP OUT: Enter a number between 75 and
98% of the under-voltage pick-up percentage
(90%).
UV DELAY: Enter a time between 0.1 and 5.0 sec-
onds (4 seconds).
UV MIN PHASE: Displays the lowest line voltage of
the three genset phases.
3-23
OV PICKUP: This adjusts the over-voltage pickup
as a percentage of the over-voltage drop-out. Enter
a number between 95 and 99% (95%).
OV DROP OUT: Enter a percentage between 105
and 135% of the nominal voltage (110%).
OV DELAY: Enter a range between 0 and 120 sec-
onds (3 seconds).
OV MAX PHASE: Displays the highest line voltage
of the three genset phases.
CENTER (FREQ): Enter a frequency between 45
and 65 Hz (60 Hz).
PICK UP (FREQ): Enter a percentage between 5
and 20% of the nominal frequency (10%).
DROP OUT (FREQ): Enter a percentage between
1 and 5% of the nominal frequency (1%).
DELAY (FREQ): Enter a time between 0.1 and 15.0
seconds (5.0 seconds).
FREQUENCY: Displays the sensed genset line fre-
quency.
GENSET SENSORS
G NOM VOLT LL 480
G SENSOR TYPE L−L
G BASE LOAD 80.0%
G RAMP LOAD 20 S
G RAMP UNLOAD 20 S
G UNLOADED KW 5 %
+


Y
GEN UV: ENABLED
% VLL
PICK UP 95 475
DROP OUT 85 465
DELAY 1.0 S
MIN PHASE 470
+


Y
B
GEN OV: DISABLED
% VLL
PICK UP 95 487
DROP OUT 110 490
DELAY 8.0 S
MAX PHASE485
+


Y
B
GEN FREQ: DISABLED
CENTER 59 HZ
PICK UP 12 %
DROP OUT 2 %
DELAY 5.0 S
FREQUENCY60.0 HZ
+


Y
B
FIGURE 3-11. GENSET SENSORS SUBMENUS
3-24
TIMERS SUBMENU
If you press the “TIMERS” button in the PTC Main
Menu 1, the Timers submenu will appear (Figure
3-12).
The following field descriptions show the valid field
entries and default value (shown in parenthesis) for
each field.
Use the + and − buttons to increase or decrease the
values in the following fields. Use the arrow () but-
ton to move the cursor within a field or to the next
field. Exit menu to save changes.
START DELAY: Sets time delay for genset engine
start. Prevents nuisance genset starting during brief
power interruptions.
Enter a range from 0 to 300 seconds (0 seconds).
STOP DELAY: Sets the time delay for engine cool-
down following a re-transfer. This stop delay works
in conjunction with and is activated at the same time
as the normal cooldown timer. (Will extend normal
cooldown timer if entered time is greater.)
Enter a time from 0 to 600 seconds (0 seconds).
TRANSFER: In a Normal to Emergency transfer
this function allows the genset to stabilize before
the load is applied. Enter a time from 0 to 120 sec-
onds (10 seconds).
RETRANSFER: In a Emergency to Normal transfer
this function allows the utility to stabilize before the
load is applied.
Enter a time from 0 to 1800 seconds (600 seconds).
PGM TRANSIT: Sets the time delay for Pro-
grammed Transition. A setting of 0.0 disables the
program.
Enter a time from 0 to 60 seconds (0 seconds).
MAX PARALLEL: Sets the maximum time during
closed transition that utility and genset can be paral-
leled.
Enter a time from 0 to 1800 seconds (20 seconds).
3-25
TIMERS
START DELAY60 S
STOP DELAY60 S
TRANSFER 10 S
RETRANSFER900 S
PGM TRANSIT5 S
MAX PARALLEL30 S
+


Y
FIGURE 3-12. TIMERS SUBMENU
3-26
TEST/EXERCISE SUBMENU
If you press the “TEST/EXERCISE” button in the
PTC Main Menu 2, the Test/Exercise submenu will
appear (Figure 3-13).
The following field descriptions show the valid field
entries and default value (shown in parenthesis) for
each field.
Use the + and − buttons to increase or decrease the
values in the following fields. Use the arrow () but-
ton to move the cursor within a field or to the next
field. Exit menu to save changes.
MODE: Indicates the generator set application type
for PTC option.
OT-PGM TRAN − Open transition load transfer.
CT-MOMENT − Closed transition load transfer
with momentary (<100ms) overlap.
CT-SOFT − Closed transition load transfer with
load ramping.
TEST WITH LOAD: Feature allows genset Test se-
quence, which is initiated through the Remote Start
(TEST) switch, to operate with or without load. De-
fault: OFF
EXER WITH LOAD: Feature allows genset Exer-
cise sequence, which is initiated through control
panel Exercise button to operate with or without
load. Default: OFF
3-27
TEST/EXERCISE
MODE CT-SOFT
TEST WITH LOADOFF
EXER WITH LOADOFF
+


Y
FIGURE 3-13. TIMERS SUBMENU
3-28
ADJUST SUBMENU
Figure 3-14 shows the main menus (Menu A and
Menu B) of the system control and the Adjust sub-
menu.
To display the Adjust submenu, press the MORE>>
button in Menu A and then the ADJUST button in
Menu B.
The Adjust submenus are intended for qualified
service personnel and site personnel only and may
require a USER password. If a password is re-
quired, the USER password menu will appear when
you try to modify the Adjust submenus. (Refer to
PASSWORD Menu in this section to enter pass-
word.
Changes are automatically saved when you exit
this menu.
If the generator set is operating in parallel with a
system bus, the voltage and frequency adjustments
are disabled to prevent inadvertent misadjustment
of the paralleling load sharing functions.
Use the + and − buttons to increase or decrease the
values in the following fields. Use the arrow () but-
ton to move the cursor within a field or to the next
field. Exit menu to safe changes.
START DELAY: This delay applies only to remote
starting in the Auto mode. The Start Delay adjust-
ment range is 0 to 300 seconds.
STOP DELAY: This delay applies only to remote
stopping in the Auto mode. The Stop Delay adjust-
ment range is 0 to 600 seconds.
VOLTAGE: Used to adjust the output voltage 5%.
FREQUENCY: Used to adjust the frequency 3 Hz.
VOLTAGE/SPEED DROOP: These two submenus
apply to a genset that has the paralleling option and
is configured to operate in droop mode.
ENGINE
ALTERNATOR
CONTROL
MORE>>
_\_
HISTORY/ABOUT
SETUP
ADJUST
BUS DATA
BACK<<
MENU A
MENU B
MENU
B
MENU
A
+


ADJUST:
START DELAY 5 SEC
STOP DELAY 11 SEC
VOLTAGE 208 1.2 %
FREQ 60.0 HZ -0.0 HZ
Y
B
+


ADJUST:
STANDBY
VOLTAGE DROOPOFF
BUS L1 480 V
POWER FACTOR0.80
VOLT 4.99 %
Y
B
+


ADJUST:
STANDBY
SPEED DROOPOFF
BUS FREQ60.0HZ
TOTAL KW300 KW
FREQ 60.0 0.40HZ
Y
FIGURE 3-14. ADJUST SUBMENU
3-29
CALIBRATION PROCEDURE
There are several circuit cards/modules that, when
removed and replaced, require you to recalibrate
the control panel display for genset voltage and cur-
rent and bus voltage.
Note that the type of calibration to perform varies for
each card. The letters A, B and C are used to desig-
nate which of the following three calibration proce-
dures are required for each card/module.
 Genset/Parallel board (A, B & C)
 PT/CT board (A & B)
 Bus PT (C)
 CT’s (B)
WARNING Contacting high voltage compo-
nents can cause electrocution, resulting in se-
vere personal injury or death. Calibration and
adjustment must be performed by technically
qualified personnel only. Read and observe all
WARNINGS and CAUTIONS in your generator
set manuals.
CAUTION Improper calibration or adjustment
of the PowerCommand control can cause
equipment malfunction or damage. Calibration
and adjustment must be performed by techni-
cally qualified personnel only.
Use a calibrated RMS multimeter for accurate mea-
surements.
(A) Genset Voltage Display Calibration
The PowerCommand control automatically synchro-
nizes to the system bus when bus voltage is avail-
able and the genset is running. Consequently, it is
not possible to calibrate the genset output voltage
display of the genset that is running when the bus is
energized. If it is necessary to adjust the output volt-
age display of the genset that is running, the InPower
service tool must be used to switch off the synchro-
nizer function of the control.
1. Display the Voltage Calibration submenu
(Page 3-6).
2. With the genset OFF, attach a calibrated volt-
meter to the AC output from L1 to L2. (L1 to
Neutral for single phase alternators.)
3. Start the genset and allow it to reach normal
operating speed.
4. Calibrate voltage reading for L1 so that the
reading on the display agrees with the cali-
brated voltmeter.
5. Shut the generator set OFF.
6. Repeat steps 2 through 5 for L2 and L3. (In step
2 attach meter to the AC output from L2 to L3 to
calibrate L2 and L3 to L1 to calibrate L3.)
7. Exit menu to safe changes.
(B) Genset Ammeter Display Calibration
1. Display the Current Calibration submenu
(Page 3-6).
2. With the genset OFF, attach a calibrated am-
meter to L1.
3. Start the genset and allow it to reach normal
operating speed.
4. Load the genset to maximum rated kVA at
rated voltage.
5. Calibrate the reading for L1 current so that the
reading on the display agrees with calibrated
ammeter.
6. Repeat steps 2 through 5 for L2 and L3. (In step
2, attach meter to L2 to calibrate L2 current and
L3 to calibrate L3 current.)
7. Exit menu to safe changes.
3-30
(C) Bus Voltage Calibration
The PowerCommand control automatically synchro-
nizes to the system bus when bus voltage is avail-
able and the genset is running. Consequently, it is
not possible to calibrate the genset bus voltage dis-
play of the genset that is running when the bus is en-
ergized. If it is necessary to adjust the bus voltage
display of the genset that is running, the InPower
service tool must be used to switch off the synchro-
nizer function of the control.
1. Display the Bus Voltage Calibration submenu
(Page 3-6).
2. With all gensets OFF, attach a calibrated volt-
meter to TB1-A (L1) and TB1-B (L2) of the bus
PT module (Figure 3-15).
3. Start another genset and allow it to reach nor-
mal operating speed and voltage. Connect op-
erating genset to the bus.
4. Calibrate the voltage reading for Bus Volts L1
so that the reading on the display matches the
reading on the calibrated meter.
5. Shut the generator set OFF.
6. Repeat steps 2 through 5 for Bus Volts L2 and
L3. (In step 2 attach meter to the AC output
from L2 to L3 to calibrate L2; L3 to L1 to cali-
brate L3.)
7. Exit menu to safe changes.
TB1-A (L1)
CONTROL
BOX DOOR
TB1-B (L2)
TB1-C (L3)
FIGURE 3-15. BUS PT MODULE
3-31
CONTROL BOX WIRING
The generator set control box assembly, which can
be located on either side of the genset, contains
connection points for remote control and monitor
options.
Customer monitor/control connections are at-
tached to terminal blocks TB3 and TB8 (see Figure
3-16). Optional equipment such as a remote annun-
ciator panel, sensing devices used to monitor gen-
set operation, remote start/stop switches, control
box heater, and etc. are also attached to these ter-
minal blocks. Driver signals for customer supplied
relays are also provided for several alarm and shut
down conditions. Refer to Customer Connections
diagram in Section 7.
3-32
TB8
CARD
CAGE
OPTIONAL
SHUTDOWN
ALARM RELAY K16
OPTIONAL
RUN RELAYS
K11, K12 & K13
CONTROL WIRING
ACCESS
FIGURE 3-16. CONTROL BOX ASSEMBLY INTERIOR
3-33
RUN RELAYS (K11, K12, K13)
The optional run relays are rail mounted inside the
control box (Figure 3-16). The rail mount allows you
to easily remove and replace the snap-on relays.
The generator set can be equipped with one, two or
three run relays.
The three-pole, double-throw run relays (Figure
3-17) are used to control auxiliary equipment such
as fans, pumps and motorized air dampers. The run
relays are energized when the generator set reach-
es operating speed.
The contacts are rated:
 10 amps at 28 VDC or 120 VAC, 80%PF
 6 amps at 240 VAC, 80%PF
 3 amps at 480/600 VAC, 80%PF
CUSTOMER
CONNECTIONS
TB3-7
(GND)
TB3-5
(SWITCHED B+)
NO
COIL
COM
NC
K11, K12, K13
K11
RUN RELAY
K11, K12, K13
K11, K12, K13
K12
RUN RELAY
K13
RUN RELAY
NO
NC
NO
NC
FIGURE 3-17. OPTIONAL RUN RELAYS (K11, K12, K13)
3-34
ALARM RELAY (K16)
The optional alarm relay is rail mounted inside the
control box (Figure 5-2). The rail mount allows you
to easily remove and replace the snap-on relay.
The three-pole, double-throw alarm relay (Figure
5-4) is often used to energize warning devices such
as audible alarms. Any generator set shutdown will
energize the alarm relay.
The contacts are rated:
 10 amps at 28 VDC or 120 VAC, 80%PF
 6 amps at 240 VAC, 80%PF
 3 amps at 480/600 VAC, 80%PF
CUSTOMER
CONNECTIONS
TB3-18
(GND)
TB3-17
(COM ALARM)
NO
COIL
COM
NC
K16
K16
K16
K16
SHUTDOWN ALARM
FIGURE 3-18. OPTIONAL ALARM RELAY (K16)
3-35
MAGNETIC SPEED PICKUP UNIT (MPU)
INSTALLATION
To install the MPU sensor, bar the engine until a
gear tooth on the flywheel lines up in the center of
the mounting hole. Thread the sensor in gently by
hand until it just touches the gear tooth. Back it out
one quarter turn and set the locknut.
CAUTION Do not use fan blade to bar over en-
gine. That can damage blades and cause prop-
erty damage and personal injury.
3-36
MAGNETIC
PICKUP
SENSOR
ENGINE
FLYWHEEL
RING GEAR
FIGURE 3-19. MPU SENSOR
Cummins Power Generation
1400 73rd Ave. NE
Minneapolis, MN 55432 USA
Phone 1 763 574 5000
Toll-free 1 800 888 6626
Fax 1 763 574 5298
Email [email protected]
www.cumminspower.com
Cummins
R
, the “C” logo, and “Our energy working for you.”
are trademarks of Cummins Inc.
E2010 Cummins Power Generation, Inc. All rights reserved.

Ваш город

Екатеринбург

Екатеринбург

Москва

Челябинск

Санкт-Петербург

Уфа

Тюмень

Красноярск

г. Екатеринбург, ул. Старых большевиков, д. 2

Дизельные генераторы от компании
«РУ-Техника»

  • Каталог

    • Назад
    • Каталог
    • Дизельные генераторы 10 кВт — 100 кВт

      • Назад
      • Дизельные генераторы 10 кВт — 100 кВт
      • 10 кВт

      • 12 кВт

      • 16 кВт

      • 20 кВт

      • 24 кВт

      • 30 кВт

      • 40 кВт

      • 50 кВт

      • 60 кВт

      • 75 кВт

      • 80 кВт

      • 100 кВт

    • Дизельные генераторы 120 кВт — 300 кВт

      • Назад
      • Дизельные генераторы 120 кВт — 300 кВт
      • 120 кВт

      • 140 кВт

      • 150 кВт

      • 160 кВт

      • 180 кВт

      • 200 кВт

      • 220 кВт

      • 250 кВт

      • 280 кВт

      • 300 кВт

    • Дизельные генераторы 310 кВт — 640 кВт

      • Назад
      • Дизельные генераторы 310 кВт — 640 кВт
      • 310 кВт

      • 315 кВт

      • 320 кВт

      • 350 кВт

      • 360 кВт

      • 400 кВт

      • 460 кВт

      • 500 кВт

      • 550 кВт

      • 600 кВт

      • 640 кВт

    • Дизельные генераторы 700 кВт — 1300 кВт

      • Назад
      • Дизельные генераторы 700 кВт — 1300 кВт
      • 700 кВт

      • 800 кВт

      • 900 кВт

      • 1000 кВт

      • 1100 кВт

      • 1200 кВт

      • 1300 кВт

    • Дизельные электростанции 1400 кВт — 4000 кВт

      • Назад
      • Дизельные электростанции 1400 кВт — 4000 кВт
      • 1400 кВт

      • 1500 кВт

      • 1600 кВт

      • 1800 кВт

      • 2000 кВт

      • 3000 кВт

      • 4000 кВт

    • Caterpillar (США)

    • Электростанции серии АД

    • Cummins (Великобритания)

    • FG Wilson (Великобритания)

    • AKSA (Турция)

    • SDMO (Франция)

    • Gesan (Испания)

    • Производство и продажа блок контейнеров

  • Компания

    • Назад
    • Компания
    • Новости

    • Уставные документы

  • Контакты


  • Екатеринбург

    • Назад
    • Города
    • Екатеринбург
    • Москва
    • Челябинск
    • Санкт-Петербург
    • Уфа
    • Тюмень
    • Красноярск

Контактная информация

г. Екатеринбург, ул. Старых большевиков, д. 2

Понравилась статья? Поделить с друзьями:
  • Руководство к приставке от мтс
  • Руководство по проектированию фундаментов промышленных зданий
  • Колледж полиции руководство
  • Кофемашина wmf 1500s инструкция по применению на русском
  • Таб амоксиклав инструкция по применению таблетки взрослым