Digital Controller
EN
INSTRUCTION MANUAL
Thank you for purchasing the OMRON E5EC Digital Controller.
This manual describes the functions, performance, and
application methods needed for optimum use of the product.
Please observe the following items when using the product.
‡ This product is designed for use by qualified personnel with a
knowledge of electrical systems.
‡ Before using the product, thoroughly read and understand this
manual to ensure correct use.
‡ Keep this manual in a safe location so that it is available for
reference whenever required.
OMRON Corporation
©All Rights Reserved
Refer to the E5
C Digital Controllers User’s Manual (Cat. No. H174)
□
for detailed application procedures.
Key to Warning Symbols
Indicates a potentially hazardous situation which, if
not avoided, is likely to result in minor or moderate
injury or property damage. Read this manual
CAUTION
carefully before using the product.
1654642-3F
EC1
Wiring
Dimensions
Dimensions (mm)
Solderless terminal size
(64)
M3
4
60
In the pack:
48
1
44
‡ 0DLQ XQLW
‡ ,QVWUXFWLRQ PDQXDO
‡ Watertight packing (Y92S-P9):
‡ Two adapters (Y92F-51):
‡ Terminal cover
(Provided only for models with E5EC-
‡ )URQWSDQHO 6HWXS Tool port cover (Y92S-P7):
Sold Separately
‡ Terminal cover: (Model: E53-COV24)
‡ 86%6HULDO &RQYHUVLRQ &DEOH (&,)4
‡ &RQYHUVLRQ &DEOH (&,)4(
e
f
c
d
* Do not remove the terminal block. Doing so may result in failure or malfunction.
* Setup Tool ports are provided on the top and front of the Digital Controller. Use these ports to connect a personal
computer to the Digital Controller when using the Setup Tool. 7KH (&,)4 86%6HULDO &RQYHUVLRQ &DEOH LV
required to connect to the top-panel port. 7KH (&,)4( 86%6HULDO &RQYHUVLRQ &DEOH LV UHTXLUHG WR FRQQHFW WR
the front-panel port. (Do not use the product with the USB-Serial Conversion Cable left permanently connected.)
Refer to the instruction manual provided with the USB-Serial Conversion Cable for details on connection methods.
* If the front-panel port cover is lost or damaged, order it separately. The Waterproof Packing should be periodically
replaced because it may deteriorate, shrink, or harden depending on the operating environment.
Names of Parts on Front Panel
‡ ƒ& ƒ) WHPSHUDWXUH XQLW
The temperature unit is displayed when
the displayed value is a temperature.
Either C or F is displayed according to the
set value of the temperature unit.
‡ 6KLIW NH\ 3) NH\
The default PF Setting parameter is for
shifting the digit. This is a function key.
When it is pressed, the function set for the
PF Setting parameter will operate.
‡ )URQWSDQHO 6HWXS Tool port
This port is used to connect the Controller
to a computer to use the Setup Tool.
‡ /HYHO NH\
Use this key to change levels:
Operation Menu
Input Type
Input type
Input
Setting
Setting range
°C
°F
0
-200 to 850
-300 to 1500
Platinum
Pt100
1
-199.9 to 500.0
-199.9 to 900.0
resistance
thermometer
2
0.0 to 100.0
0.0 to 210.0
3
-199.9 to 500.0
-199.9 to 900.0
JPt100
4
0.0 to 100.0
0.0 to 210.0
K
5
-200 to 1300
-300 to 2300
Thermocouple
6
-20.0 to 500.0
0.0 to 900.0
J
7
-100 to 850
-100 to 1500
8
0.0 to 750.0
-20.0 to 400.0
T
9
-200 to 400
-300 to 700
10
-199.9 to 400.0
-199.9 to 700.0
E
11
-200 to 600
-300 to 1100
L
12
-100 to 850
-100 to 1500
U
13
-300 to 700
-200 to 400
14
-199.9 to 400.0
-199.9 to 700.0
N
15
-200 to 1300
-300 to 2300
R
16
0 to 1700
0 to 3000
S
17
0 to 1700
0 to 3000
B
18
300 to 3200
100 to 1800
19
W
0 to 2300
0 to 3200
20
0 to 1300
0 to 2300
PL
10 to 70°C
21
0 to 90
0 to 190
Infrared
60 to 120°C
22
0 to 120
0 to 240
Thermosensor
115 to 165°C
23
0 to 165
0 to 320
ES1B
24
140 to 260°C
0 to 260
0 to 500
4 to 20mA
25
Current input
Use the following ranges for scaling: -1999
0 to 20mA
26
to 9999, -199.9 to 999.9, -19.99 to 99.99,
1 to 5V
27
-1.999 to 9.999
Voltage input
0 to 5V
28
0 to 10V
29
*The default is»5″.
*s. e rr will be displayed when a platinum resistance thermometer is mistakenly connected
while input type is not set for it. To clear the s. e rr display, correct the wiring and cycle the
power supply.
Alarms
Alarm output function
Setting
Alarm type
Positive alarm value (X) Negative alarm value (X)
0
No alarm function
Output off
Vary with
*1
1
Deviation upper/lower limit
«L», «H» values
SP
X
X
ON
ON
2
Deviation upper limit
OFF
OFF
SP
SP
X
ON
ON
3
Deviation lower limit
OFF
OFF
SP
SP
L H
Vary with
ON
*1
4
Deviation upper/lower range
«L», «H» values
OFF
SP
L H
Deviation upper/lower limit
Vary with
ON
*1
5
«L», «H» values
standby sequence ON
OFF
SP
X
X
Deviation upper limit
ON
ON
6
standby sequence ON
OFF
OFF
SP
SP
Deviation lower limit
X
ON
ON
7
standby sequence ON
OFF
OFF
SP
SP
X
Absolute value upper limit
ON
ON
8
OFF
OFF
0
X
X
ON
ON
9
Absolute value lower limit
OFF
OFF
0
Absolute value upper limit
X
ON
ON
10
standby sequence ON
OFF
OFF
0
Absolute value lower limit
X
ON
11
ON
standby sequence ON
OFF
OFF
0
12
LBA (only for alarm 1)
13
PV Change Rate Alarm
X
14
SP absolute value upper limit
ON
ON
OFF
OFF
0
X
ON
15
SP absolute value lower limit
ON
OFF
OFF
0
X
ON
ON
16
MV absolute value upper limit
OFF
OFF
0
X
ON
17
MV absolute value lower limit
ON
OFF
OFF
0
X
ON
ON
18
RSP absolute value upper limit
OFF
OFF
0
X
ON
19
RSP absolute value lower limit
ON
OFF
OFF
0
*1: Upper and lower limits can be set for parameters 1, 4 and 5 to provide for
different types of alarm. These are indicated by the letter «L» and «H».
‡ The default alarm type is «2»
Conformance to EN/IEC Standards
This is a class A product.
In residential areas it may cause radio interference, in which case the user
may be required to take adequate measures to reduce interference.
Warning Symbols
CAUTION
Minor injury due to electric shock may occasionally occur.
Do not touch the terminals while power is being supplied.
Electric shock, fire, or malfunction may occasionally occur. Do not allow metal objects, conductors,
cuttings from installation work, or moisture to enter the Digital Controller, the Setup Tool ports, or
between the pins on the connectors on the Setup Tool cable.
Do not use the product where subject to flammable or explosive gas. Otherwise, minor injury from
explosion may occasionally occur.
Never disassemble, modify, or repair the product or touch any of the internal parts. Minor electric
shock, fire, or malfunction may occasionally occur.
CAUTION — Risk of Fire and Electric Shock
a) This is the product UL listed as Open Type Process Control Equipment. It must be mounted in an enclosure
that does not allow fire to escape externally.
b) More than one disconnect switch may be required to de-energize the equipment before servicing.
c) Signal inputs are SELV, limited energy.
d) Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits.
If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur.
Always consider the application conditions and use the output relays within their rated load and
electrical life expectancy. The life expectancy of output relays varies considerably with the output load
and switching conditions.
Loose screws may occasionally result in fire. Tighten the terminal screws to the specified torque of 0.43
WR 1‡P
Set the parameters of the product so that they are suitable for the system being controlled. If they are
not suitable, unexpected operation may occasionally result in property damage or accidents.
A malfunction in the Digital Controller may occasionally make control operations impossible or prevent
alarm outputs, resulting in property damage. To maintain safety in the event of malfunction of the Digital
Controller, take appropriate safety measures, such as installing a monitoring device on a separate line.
Suitability for Use
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which
apply to the combination of the Product in the Buyer’s application or use of the Product.
At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and
limitations of use which apply to the Product. This information by itself is not sufficient for a complete
determination of the suitability of the Product in combination with the end product, machine, system, or
other application or use. Buyer shall be solely responsible for determining appropriateness of the particular
product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in
all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED
)25 7+( ,17(1′(‘ 86( :,7+,1 7+( 29(5$// (48,30(17 25 6<67(0
Installation
Individual mounting (mm)
c
d
Waterproofing is
impossible with
e
5 .):
side-by-side installation.
f
When waterproofing is
required, fit watertight
packing on the
backside of front panel.
+ 0.6
45
0
Operation indicators
‡ 1R GLVSOD\
‡ 68% Auxiliary output 1 indicator
Process value or set data type
‡ 68% Auxiliary output 2 indicator
‡ 1R GLVSOD\
‡ 68% Auxiliary output 3 indicator
Set point, set data read-out value or changed
input value
‡ 68% Auxiliary output 4 indicator
‡ 287 &RQWURO RXWSXW LQGLFDWRU
‡ No. 3 display
For a current output, lit except for a
MV, Soak Time Remain, and Multi-SP.
0% output.
‡ 287 &RQWURO RXWSXW LQGLFDWRU
‡ 8S DQG ‘RZQ NH\V
Each press of U key increments or advances
‡ 563 5HPRWH 6P indicator
the values displayed on the No.2 display.
Lit when the assigned function is ON.
Each press of D key decrements or returns the
‡ TUNE:
values displayed on the No.2 display.
Flashing during self-tuning.
Lit during auto-tuning.
‡ 0RGH NH\
Press this key to change the contents of the display.
Press this button for 1 s or longer for reverse scroll.
‡ 3UHVV WKH O key and the M key
together for at least 3 seconds to switch to protect level.
Operation stopped.
Initial Setting Level
(Control/alarm are both stopped.)
in-t
alh3
Alarm 3
3
Input Type *
*6
Hysteresis
5
0.2
M
M
Scaling Upper Limit
alt4
Alarm 3 Type:
in-h
(only when setting
*6
Specified
*6
2
100
analog input)
models only
M
M
Scaling Lower Limit
in-l
alh4
Alarm 3
*6
*6
(only when setting
Hysteresis
0
0.2
analog input)
M
M
Decimal Point
o1st
dp
Control Output 1
(only when setting
*6
*6
Signal
4-20
0
analog input)
M
M
o2st
d-u
c
Temperature
°C=
Control Output 2
*6
*6
Unit
4-20
Signal
f
c
°F=
M
M
trst
sl-h
Transfer Output
*6
SP Upper Limit
4-20
Signal
1300
M
M
tr-t
sl-l
Transfer Output
*6
SP Lower Limit
Type
off
-200
M
M
tr-h
cntl
3,’‡212))
Transfer Output
onof
*6
In ON/OFF control =
100.0
Upper Limit
onof
pid
In 2-PID control =
M
M
tr-l
s-hc
Standard or Heating/Cooling
Transfer Output
stnd
*6
Standard control =
Lower Limit
0.0
stnd
h-c
Heating and cooling control =
M
M
ev-1
st
ST (Self-tuning)
Event Input
*6
on
*6
ST ON =
Assignment 1
msp0
on
off
ST OFF =
M
M
ev-2
ptrn
Event Input
*6
Program Pattern
Assignment 2
stop
off
M
M
ev-3
cp
Control Period (Heating)
Event Input
*6
*6
(Unit: Seconds)
Assignment 3
none
20
*Voltage output (for driving SSR): 2
M
M
ev-4
c-cp
Control Period (Cooling)
Event Input
*6
*6
(Unit: Seconds)
Assignment 4
none
20
*Voltage output (for driving SSR): 2
X
M
M
ev-5
Direct/Reverse Operation
orev
Event Input
*6
or-r
In Reverse operation (Heating) =
Assignment 5
none
or-r
or-d
In Direct operation (Cooling) =
M
M
ev-6
alt1
*3
Event Input
*6
Alarm 1 Type:
*6
Assignment 6
none
Specified models only
*4
2
M
M
clfl
Closed/
alh1
X
*6
*6
Floating
Alarm 1 Hysteresis
flot
0.2
M
M
X
calb
alt2
*3
Motor
0
Alarm 2 Type:
*6
*6
Calibration
*4
off
Specified models only
2
M
M
M
0
mot
X
alh2
Travel Time
*6
Alarm 2 Hysteresis
*6
30
0
0.2
X
M
M
Extraction of
sqr
0
alt3
Alarm 3 Type:
Square Root Enable
*3
*6
*6
Specified
(Only when analog
off
2
models only
*4
input is set)
M
M
amov
Move to Advanced
*6
Function Setting
0
Level
X
M
0
X
Initial setting level enables users to specify their preferred operating conditions
(input type, alarm type, control method, etc.)
0
X
0
Conformance to Safety Standard
X
0
Reinforced insulation is provided between input power
X
supply, relay outputs, and between other terminals.
0
Do not allow temporary overvoltages on the primary circuit to exceed
X
the following values.
Check the power supply voltage to the Digital Controller.
0
Short-term overvoltage: 1,200 V + (Power supply voltage)
Long-term overvoltage: 250 V + (Power supply voltage)
Always externally connect the recommended fuse that is specified
in the Instruction Manual before you use the Digital Controller.
Analog Input
‡ If you input an analog voltage or current, set the Input Type
parameter to the correct input type.
‡ Do not use the Digital Controller to measure a circuit with
Measurement Category II, III, or IV.
‡ Do not use the Digital Controller to measure an energized circuit to
which a voltage that exceeds 30 Vms or 60 VDC is applied.
The protection provided by the Digital Controller may be impaired if the
Digital Controller is used in a manner that is not specified by the
manufacturer.
Be sure to observe the following precautions to prevent operation failure, malfunction, or adverse affects on the
performance and functions of the product. Not doing so may occasionally result in unexpected events. Use the
product within specifications.
(1) The product is designed for indoor use only. Do not use the product outdoors. Do not use or store the product in
any of the following locations.
‡ 3ODFHV GLUHFWO\ VXEMHFW WR KHDW UDGLDWHG IURP KHDWLQJ HTXLSPHQW
‡ 3ODFHV VXEMHFW WR VSODVKLQJ OLTXLG RU RLO DWPRVSKHUH
‡ 3ODFHV VXEMHFW WR GLUHFW VXQOLJKW
‡ 3ODFHV VXEMHFW WR GXVW RU FRUURVLYH JDV LQ SDUWLFXODr, sulfide gas and ammonia gas).
‡ 3ODFHV VXEMHFW WR LQWHQVH WHPSHUDWXUH FKDQJH
‡ 3ODFHV VXEMHFW WR LFLQJ DQG FRQGHQVDWLRQ
‡ 3ODFHV VXEMHFW WR YLEUDWLRQ DQG ODUJH VKRFNV
(2) Use/store within the rated temperature and humidity ranges. Provide forced-cooling if required.
(3) To allow heat to escape, do not block the area around the product.
Do not block the ventilation holes on the product.
(4) Be sure to wire properly with correct polarity of terminals.
(5) Use the specified size of crimped terminals (M3, width 5.8 mm or less) for wiring. To connect bare wires to the
terminal block, use copper braided or solid wires with a gage of AWG24 to AWG18 (equal to a cross-
sectional area of 0.205 to 0.8231 mm
type, or two crimped terminals can be inserted into a single terminal.
(6) Do not wire the terminals which are not used.
(7) Allow as much space as possible between the controller and devices that generate a powerful high-frequency
or surge. Separate the high-voltage or large-current power lines from other lines, and avoid parallel or common
wiring with the power lines when you are wiring to the terminals.
(8) Use this product within the rated load and power supply.
(9) Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or relay
contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur.
(10) Make sure that the Digital Controller has 30 minutes or more to warm up after turning ON the power before
starting actual control operations to ensure the correct temperature display.
(11) When executing self-tuning, turn the load and the unit ON simultaneously, or turn the load ON before you turn
the controller ON.
(12) A switch or circuit breaker should be provided close to this unit. The switch or circuit breaker should be within
easy reach of the operator, and must be marked as a disconnecting means for this unit.
(13) Wipe off any dirt from the Digital Controller with a soft dry cloth. Never use thinners, benzine, alcohol, or any
cleaners that contain these or other organic solvents. Deformation or discoloration may occur.
(14) Design system (control panel, etc) considering the 2 second of delay that the controller’s output to be set after
power ON.
(15) The output will turn OFF when you move to the Initial Setting Level. Take this into consideration when
performing control.
(16) The number of non-volatile memory write operations is limited. Therefore, use RAM write mode when frequently
overwriting data during communications or other operations.
(17) When disassembling the Digital Controller for disposal, use suitable tools.
(18) Do not connect cables to both the front-panel Setup Tool port and the top-panel Setup Tool port at the same
time. The Digital Controller may be damaged or may malfunction.
(19) Do not exceed the communications distance that is given in the specifications and use the specified
communications cable. Refer to the E5
communications distance and cable specifications.
(20) Do not turn the power supply to the Digital Controller ON or OFF while the USB-Serial Conversion Cable is
connected. The Digital Controller may malfunction.
(21) The maximum terminal temperature is 75°C.
Connections
Side-by-side mounting (mm)
Control output 1
Relay output
(48 x number of units–2.5) + 1 0
250 VAC, 5A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 40 mA
21 mA if there are two
control outputs
Current output
0 to 20 mA DC
4 to 20 mA DC
/RDG
*2 Control Outputs
One relay
‡ ,QVHUW WKH PDLQ XQLW WKURXJK WKH PRXQWLQJ KROH LQ WKH SDQHO
output
(1-8 mm thickness). Insert the mounting brackets (supplied)
3
into the fixing slots located on the top and bottom of the rear
case.
4
‡ Tighten the two mounting screws on the top and bottom of
5
the adapter to keep them balanced, and finally tighten them
6
to a torque of between 0.29 and 0.39 N·m.
‡ :KHQ PRUH WKDQ RQH PDFKLQH LV LQVWDOOHG PDNH VXUH WKDW WKH
ambient temperature does not exceed the specified limit.
‡ 6TOP: Control stop indicator
Lit when «Run/Stop» is stopped during operation.
During control stop, functions other than control output
are valid.
‡ CMW: Communications writing enable/ disable indicator
Lit when communications writing is «enabled» and is
out when it is «disabled».
‡
3URWHFWLRQ LQGLFDWRU
Lit when Setting Change Protect is ON (disables the
*3 Auxiliary Outputs
Up and Down Keys).
Auxiliary outputs 1 and 2
‡ 0$18 0DQXDO RXWSXW LQGLFDWRU
Lit when the Auto/Manual Mode is set to Manual
Mode.
10
11
12
* When complying with EMC standards, the line connecting the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
Check the wiring before turning ON the power supply.
*5
POWER ON
Operation Level
*3
Process Value/Set Point
25
*4
s.err is displayed when
*6
connected sensor is
0
different from input type.
M
Hold O down
Auto/Manual Switch
a-m
PID control only.
*6
*6
for at least
3 seconds
M
(No.1 display flashes,
m-sp
Multi-SP
*6
*6
then the control stops.)
Set Point Selection
0
M
Hold O down
rsp
for at least
*6
*6
Remote SP Monitor
0.0
1 second
M
sp-m
Set Point During
*6
*6
SP Ramp
0
M
Heater Current 1
ct1
*6
Value Monitor
*6
0.0
7
(Unit: A) *
M
Heater Current 2
ct2
*6
*6
Value Monitor
0.0
(Unit: A) *
7
M
Leakage Current 1
lcr1
*6
*6
Value Monitor
0.0
7
(Unit: A) *
M
Leakage Current 2
lcr2
*6
*6
Value Monitor
0.0
7
(Unit: A) *
M
prst
*6
*6
Program Start
rset
M
sktr
*6
*6
Soak Time Remain
0
M
RUN/STOP
r-s
run
*6
*6
When control start =
run
stop
When control stop =
M
al-1
*6
4
*6
Alarm Value 1 *
0
M
al1h
A
larm Value
*6
*4
Upper Limit 1
0
M
Operation level should normally be used during operations.
Hold O and M keys
Hold O and M keys
down for at least 1 second
down for at least 3 seconds
Protect Level
Move to Protect Level
pmov
Displayed only when a
password is set. Restricts
0
moving to Protect Level.
M
Operation / Adjustment Protect
Restricts displaying and
oapt
modifying menu items in
Operation, Adjustment, and
0
Manual Control Levels.
M
Initial Setting /
Communication Protect
icpt
Restricts movement to the
Initial Setting, Communications
1
Setting, and Advanced Function
M
Setting Levels.
wtpt
Setting Change Protect
Restricts changes to settings
off
by operating the front panel keys.
M
pfpt
PF Key Protect
Restricts PF key operation.
off
M
Restricts which settings can be displayed or changed, and restricts
change by key operation.
*3: Refer to the adjoining tables for details of input types and alarm types.
*4: Applicable only to models with alarm functions.
*5: Operation is stopped when moved to the initial setting level.
(control/alarm are both stopped.)
*6: The grayed-out setting items may not be displayed according to the models
and setting.
*7: Applicable only to models with heater burnout functions.
The four numeric digits of the product code are displayed in the No. 2
*8:
display. The setting cannot be changed and there is nothing that you need
to set.
Other functions
Refer to the E5□C Digital Controllers User’s Manual (Cat. No. H174)
for information on the Advanced Function Setting Level,
Monitor/Setting Item Level, Manual Control Level, and other functions.
Refer to the E5□C Digital Controllers Communications Manual
(Cat. No. H175) for information on communications.
Precautions for Safe Use
2
). (The stripping length is 6 to 8 mm.). Up to two wires of same size and
C Digital Controllers User’s Manual (Cat. No. H174) for the
□
(The applicability of the electric terminals varies with the type of machine.)
Auxiliary output 1, 2, 3, 4
*5 Options
Control output 2
004
Relay output
Relay output
250 VAC, 5 A
two outputs 250 VAC, 3 A
Communications
(resistive load)
(resistive load)
and two event inputs
four outputs 250 VAC, 2 A
Voltage output
(resistive load)
B(+)
(for driving SSR)
RS-485
12 VDC, 21 mA
Current output
A()
0 to 20 mA DC
4 to 20 mA DC
/RDG
PD[
EV1
E5EC
PD[
EV2
2. Control outputs
5. Options
RX
4;
One voltage output
*1 Input Power Supply
(for driving SSR)
100 to 240 VAC
24 VAC/DC
OUT1
3
OUT1
+
R
4
1
1
4
2
2
5
(no polarity)
6
CX
44
45
One linear
Two voltage outputs
Voltage output (for driving
current output
(for driving SSRs)
SSR)/relay output
OUT1
OUT1
OUT1
3
3
3
+
+
+
C
4
4
4
4
4
5
5
OUT2
5
OUT2
+
4
R
6
6
6
RR/PR
CC
CQ
Two relay
Two linear
Linear current/voltage
outputs
current outputs
output (for driving SSR)
OUT1
OUT1
3
OUT1
3
3
+
+
R
C
C
—
4
4
4
5
OUT2
5
OUT2
5
OUT2
+
+
R
C
Q
—
6
6
6
*4 Sensor Temperature/Analog Input
Auxiliary outputs 1 to 4
Potentiometer
TC
Pt
I
V
7
7
A
input
+
22
22
22
22
Auxiliary output 4
8
8
B
mA
O
Auxiliary output 3
23
23
23
23
9
9
B
W
V
24
24
24
24
Auxiliary output 2
+
10
+
C
Auxiliary output 2
11
The E5EC is set for a K thermocouple (input type of 5) by
Auxiliary output 1
Auxiliary output 1
default. If a different sensor is used, an input error (s.err) will
12
occur. Check the setting of the Input Type parameter.
Adjustment Level
l.adj
Adjustment Level
*8
Displayed only once when
entering Adjustment Level.
M
AT Execute/Cancel
at
*6
100%AT Execute
at-2
off
al1l
(The No.3 display
40%AT Execute
at-1
Alarm Value
has been omitted.)
M
0
*
4
Lower Limit 1
cmwt
M
Communications Writing
*6
off
al-2
4
Alarm Value 2 *
M
0
Press O
spmd
M
*6
SP Mode
(less than
lsp
al2h
Alarm Value
1 second)
M
0
*
4
Upper Limit 2
ct1
Heater Current 1
M
*6
Value Monitor
0.0
al2l
(Unit: A) *
7
Alarm Value
M
0
*
4
Lower Limit 2
hb1
Heater Burnout
M
*6
Detection 1
0.0
al-3
(Unit: A) *
7
Alarm Value 3 *
4
M
0
Heater Current 2
ct2
M
Value Monitor
*6
0.0
al3h
7
(Unit: A) *
Alarm Value
4
M
0
Upper Limit 3
*
Heater Burnout
hb2
M
*6
Detection 2
0.0
al3l
(Unit: A) *
7
Alarm Value
M
*4
0
Lower Limit 3
Leakage Current 1
lcr1
M
*6
Value Monitor
al-4
0.0
7
4
(Unit: A) *
Alarm Value 4 *
M
0
hs1
HS Alarm 1
M
*6
(Unit: A) *
7
5 0.0
al4h
Alarm Value
4
M
Upper Limit 4
*
0
Leakage Current 2
lcr2
M
*6
Value Monitor
0.0
al4l
7
(Unit: A) *
Alarm Value
M
4
Lower Limit 4
*
0
hs2
HS Alarm 2
M
*6
7
(Unit: A) *
50.0
o
MV Monitor
M
(Heating)
0.0
sp-0
SP 0
M
*6
0
c-o
MV Monitor
M
(Cooling)
0.0
sp-1
SP 1
M
M
*6
0
v-m
Valve Opening
M
Monitor
0.0
sp-2
SP 2
M
*6
0
M
sp-3
SP 3
*6
0
M
Error Display (troubleshooting)
When an error has occurred, the No.1 display shows the error code. Take
necessary measure according to the error code, referring the table below.
No.1 display
Meaning
s.err
Input error
(S. Err)
chgp
*2
Changed
Parameters Only
off
M
e333
Parameter Mask
(E333)
A/D converter error
pmsk
Enable
*2
Displayed only
on
when a parameter
mask is set.
M
prlp
e111
Memory error
Password to
(E111)
Move to Protect
0
Level
M
If the input value exceeds the display limit (-1999 to 9999), though it is within the control
range, [[[[ will be displayed under -1999 and ]]]] above 9999. Under these conditions,
control output and alarm output will operate normally. Refer to the E5□C Digital Controllers
User’s Manual (Cat. No. H174) for the controllable ranges.
*2: Error shown only for «Process value / Set point». Not shown for other status.
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands
Phone 31-2356-81-300
FAX 31-2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg, IL 60173-5302 U.S.A
Phone 1-847-843-7900
FAX 1-847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark, Singapore 119967
Phone 65-6835-3011
FAX 65-6835-2711
OMRON Corporation
Shiokoji Horikawa, Shimogyo-ku, Kyoto 600-8530 JAPAN
Specifications
Power supply voltage
100 to 240 VAC, 50/60 Hz or
24 VAC, 50/60 Hz / 24VDC
Operating voltage range
85 to 110% of the rated voltage
Power consumption
Option 000:
6.6 VA max. (100 to 240 VAC)
4.1 VA max. (24 VAC)/2.3 W max. (24 VDC)
All other specifications:
8.3 VA max. (100 to 240 VAC)
5.5 VA max. (24 VAC)/3.2 W max. (24 VDC)
Indication accuracy
Thermocouple:
(Ambient temperature: 23°C) (±0.3 % of indication value or ±1°C,
whichever is greater) ±1 digit max.
Platinum resistance thermometer:
(±0.2 % of indication value or ±0.8°C,
whichever is greater) ±1 digit max.
Analog input: ±0.2 % FS ±1 digit max.
Event input
Output current: approx. 7 mA per contact.
Contact input
21 N
PD[ 2)) N
PLQ
No-contact input
ON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.
Remote SP input
4 to 20 mA DC or 0 to 20 mA DC
0 to 5 V DC or 1 to 5 V DC or 0 to 10 V DC
Potentiometer input
%HWZHHQ
DQG N IRU PD[LPXP RSHQ SRVLWLRQ
Control output 1
Relay output: SPST-NO,
250 VAC, 5 A (resistive load)
Electrical life of relay: 100,000 operations
Voltage output (for driving SSR):
12 VDC ±20%, 40 mA for one control output,
21 mA if there are two control outputs
Current output: 4 to 20 mA DC, 0 to 20 mA DC
/RDG
PD[
Control output 2
Relay output: SPST-NO,
250 VAC, 5 A (resistive load)
Electrical life of relay: 100,000 operations
Voltage output (for driving SSR): 12 VDC, 21 mA
Current output: 4 to 20 mA DC or 0 to 20 mA DC
ZLWK ORDG RI Ÿ PD[
Control method
ON/OFF or 2-PID control
Auxiliary outputs
Relay outputs: 250 VAC, two outputs: 3 A
(resistive load), four outputs: 2 A (resistive load)
Electrical life of relay: 100,000 operations
Transfer output
4 to 20 mA ‘& ZLWK ORDG RI
PD[
WR 9’& ZLWK ORDG RI N
PLQ
Ambient temperature
–10 to 55°C
(Avoid freezing or condensation)
Ambient humidity
25% to 85%
Storage temperature
–25 to 65°C
(Avoid freezing or condensation)
Altitude
Max. 2,000 m
Recommended fuse
T2A, 250 VAC, time-lag, low-breaking capacity
Weight
Approx. 210 g (Digital Controller only)
Degree of protection
Front panel: IP66
Rear case: IP20, Terminal section: IP00
Installation environment
Installation category II, pollution
degree 2 (as per IEC61010-1)
Memory protection
Non-volatile memory
(Number of write operations: 1,000,000)
Temporary overvoltage
Short term: 1200 V+ (power supply voltage)
Long term: 250 V+ (power supply voltage)
Do not connect anything to the terminals that are shaded gray.
005
008
010
009
Four event inputs
Communications, two event
Communications, two event
Four event inputs
inputs, and one CT
inputs, and two CTs
and one CT
B(+)
B(+)
13
13
13
13
13
RS-485
RS-485
14
14
14
14
14
EV3
EV3
A()
A()
15
15
15
15
15
EV4
EV4
16
16
16
16
16
17
17
17
17
17
EV1
EV1
EV1
EV1
18
18
18
18
18
EV2
EV2
EV2
EV2
19
19
19
19
19
CT1
CT1
CT1
20
20
20
20
20
COM
CT2
21
21
21
21
21
011
012
Six event inputs, one CT,
Communications, four event inputs,
transfer output, and remote SP
one CT, transfer output, and remote SP
13
B(+)
13
RS-485
14
EV3
14
A( )
15
EV4
15
28
16
28
16
29
17
EV5
EV1
29
17
30
EV5
EV1
18
EV6
EV2
30
18
EV6
+
31
19
EV2
+
+
31
19
Transfer
V
CT1
32
20
+
Transfer
V
CT1
output
I
32
20
output
I
33
21
33
21
+
34
+
+
34
Remote
V
35
+
V
mA
Remote
SP
35
mA
36
SP
36
014
013
Communications, four event inputs,
Six event inputs, transfer output,
transfer output, and remote SP
and remote SP
B(+)
13
13
RS-485
14
14
A( )
EV3
15
15
EV4
28
28
16
16
29
29
17
17
EV5
EV1
EV5
EV1
19
30
18
30
18
EV6
EV6
EV2
EV2
20
+
31
+
31
19
19
Transfer
V
+
+
Transfer
V
21
32
output
20
32
20
I
output
I
33
33
21
21
+
34
+
34
+
Remote
V
+
V
35
Remote
35
mA
mA
SP
SP
36
36
Only the value set to the «ins: Temperature Input Shift» parameter is applied to the entire temperature input range. When the
process value is 200 °C, the process value is treated as 201.2 °C after input shift if the input shift value is set to 1.2 °C.
The process value is treated as 198.8 °C after input shift if the input shift value is set to –1.2 °C.
sp-4
hys
SP 4
Hysteresis
*6
*6
(Heating)
0
1.0
M
M
sp-5
chys
SP 5
Hysteresis
*6
*6
(Cooling)
0
1.0
M
M
sp-6
soak
SP 6
*6
*6
Soak Time
1
0
M
M
sp-7
wt-b
SP 7
*6
*6
Wait Band
0
off
M
M
ins
mv-s
PV
*6
*6
MV at Stop
0.0
Input Shift
0.0
M
M
inrt
mv-e
PV input
*6
*6
MV at PV Error
1.000
Slope Coefficient
0.0
M
M
sprt
rss
Remote SP
*6
*6
SP Ramp Set Value
0 .0
Input Shift
off
M
M
rsrt
sprl
Remote SP input
SP Ramp Set Value
*6
*6
(SP Ramp Fall Value)
1.000
Slope Coefficient
same
M
M
p
ol-h
MV Upper Limit
*6
Proportional
*6
8.0
Band
100.0
M
M
i
ol-l
Integral Time
*6
*6
MV Lower Limit
(Unit: Seconds)
233
0.0
M
M
d
orl
Derivative Time
MV Change
*6
*6
Rate Limit
40
(Unit: Seconds)
0.0
M
M
c-p
db
Position
*6
Proportional
*6
Proportional
8.0
2.0
Band (Cooling)
Dead Band
M
M
Integral Time
c-i
oc-h
Open/Close
*6
(Cooling)
*6
Hysteresis
233
0.8
(Unit: Seconds)
M
M
Derivative Time
c-d
sqrp
Extraction of Square
*6
*6
(Cooling)
Root Low-cut Point
40
0.0
(Unit: Seconds)
M
M
c-db
plcm
Communications
Dead Band
*6
*6
Monitor
0.0
1234
M
M
of-r
Manual Reset Value
*6
Clears the offset
Adjustment level is for entering
50.0
during P or PD control.
set values and shift values for
M
control.
Status at error
Action
Control
Alarm
output
Check the setting of the Input Type parameter,
Operates
OFF
as above the
check the input wiring, and check for broken or
shorts in the temperature sensor.
upper limit.
After the correction of A/D converter error, turn the
power OFF then back ON again. If the display
remains the same, the controller must be repaired.
OFF
OFF
If the display is restored to normal, then a
probable cause can be external noise affecting the
control system. Check for external noise.
Turn the power OFF then back ON again. If the
display remains the same, the controller must be
repaired. If the display is restored to normal, then
OFF
OFF
a probable cause can be external noise affecting
the control system. Check for external noise.
Digital Controller
EN
INSTRUCTION MANUAL
Thank you for purchasing the OMRON E5EC Digital Controller.
This manual describes the functions, performance, and
application methods needed for optimum use of the product.
Please observe the following items when using the product.
‡ This product is designed for use by qualified personnel with a
knowledge of electrical systems.
‡ Before using the product, thoroughly read and understand this
manual to ensure correct use.
‡ Keep this manual in a safe location so that it is available for
reference whenever required.
OMRON Corporation
©All Rights Reserved
Refer to the E5
C Digital Controllers User’s Manual (Cat. No. H174)
□
for detailed application procedures.
Key to Warning Symbols
Indicates a potentially hazardous situation which, if
not avoided, is likely to result in minor or moderate
injury or property damage. Read this manual
CAUTION
carefully before using the product.
1654642-3F
EC1
Wiring
Dimensions
Dimensions (mm)
Solderless terminal size
(64)
M3
4
60
In the pack:
48
1
44
‡ 0DLQ XQLW
‡ ,QVWUXFWLRQ PDQXDO
‡ Watertight packing (Y92S-P9):
‡ Two adapters (Y92F-51):
‡ Terminal cover
(Provided only for models with E5EC-
‡ )URQWSDQHO 6HWXS Tool port cover (Y92S-P7):
Sold Separately
‡ Terminal cover: (Model: E53-COV24)
‡ 86%6HULDO &RQYHUVLRQ &DEOH (&,)4
‡ &RQYHUVLRQ &DEOH (&,)4(
e
f
c
d
* Do not remove the terminal block. Doing so may result in failure or malfunction.
* Setup Tool ports are provided on the top and front of the Digital Controller. Use these ports to connect a personal
computer to the Digital Controller when using the Setup Tool. 7KH (&,)4 86%6HULDO &RQYHUVLRQ &DEOH LV
required to connect to the top-panel port. 7KH (&,)4( 86%6HULDO &RQYHUVLRQ &DEOH LV UHTXLUHG WR FRQQHFW WR
the front-panel port. (Do not use the product with the USB-Serial Conversion Cable left permanently connected.)
Refer to the instruction manual provided with the USB-Serial Conversion Cable for details on connection methods.
* If the front-panel port cover is lost or damaged, order it separately. The Waterproof Packing should be periodically
replaced because it may deteriorate, shrink, or harden depending on the operating environment.
Names of Parts on Front Panel
‡ ƒ& ƒ) WHPSHUDWXUH XQLW
The temperature unit is displayed when
the displayed value is a temperature.
Either C or F is displayed according to the
set value of the temperature unit.
‡ 6KLIW NH 3) NH
The default PF Setting parameter is for
shifting the digit. This is a function key.
When it is pressed, the function set for the
PF Setting parameter will operate.
‡ )URQWSDQHO 6HWXS Tool port
This port is used to connect the Controller
to a computer to use the Setup Tool.
‡ /HYHO NH
Use this key to change levels:
Operation Menu
Input Type
Input type
Input
Setting
Setting range
°C
°F
0
-200 to 850
-300 to 1500
Platinum
Pt100
1
-199.9 to 500.0
-199.9 to 900.0
resistance
thermometer
2
0.0 to 100.0
0.0 to 210.0
3
-199.9 to 500.0
-199.9 to 900.0
JPt100
4
0.0 to 100.0
0.0 to 210.0
K
5
-200 to 1300
-300 to 2300
Thermocouple
6
-20.0 to 500.0
0.0 to 900.0
J
7
-100 to 850
-100 to 1500
8
0.0 to 750.0
-20.0 to 400.0
T
9
-200 to 400
-300 to 700
10
-199.9 to 400.0
-199.9 to 700.0
E
11
-200 to 600
-300 to 1100
L
12
-100 to 850
-100 to 1500
U
13
-300 to 700
-200 to 400
14
-199.9 to 400.0
-199.9 to 700.0
N
15
-200 to 1300
-300 to 2300
R
16
0 to 1700
0 to 3000
S
17
0 to 1700
0 to 3000
B
18
300 to 3200
100 to 1800
19
W
0 to 2300
0 to 3200
20
0 to 1300
0 to 2300
PL
10 to 70°C
21
0 to 90
0 to 190
Infrared
60 to 120°C
22
0 to 120
0 to 240
Thermosensor
115 to 165°C
23
0 to 165
0 to 320
ES1B
24
140 to 260°C
0 to 260
0 to 500
4 to 20mA
25
Current input
Use the following ranges for scaling: -1999
0 to 20mA
26
to 9999, -199.9 to 999.9, -19.99 to 99.99,
1 to 5V
27
-1.999 to 9.999
Voltage input
0 to 5V
28
0 to 10V
29
*The default is»5″.
*s. e rr will be displayed when a platinum resistance thermometer is mistakenly connected
while input type is not set for it. To clear the s. e rr display, correct the wiring and cycle the
power supply.
Alarms
Alarm output function
Setting
Alarm type
Positive alarm value (X) Negative alarm value (X)
0
No alarm function
Output off
Vary with
*1
1
Deviation upper/lower limit
«L», «H» values
SP
X
X
ON
ON
2
Deviation upper limit
OFF
OFF
SP
SP
X
ON
ON
3
Deviation lower limit
OFF
OFF
SP
SP
L H
Vary with
ON
*1
4
Deviation upper/lower range
«L», «H» values
OFF
SP
L H
Deviation upper/lower limit
Vary with
ON
*1
5
«L», «H» values
standby sequence ON
OFF
SP
X
X
Deviation upper limit
ON
ON
6
standby sequence ON
OFF
OFF
SP
SP
Deviation lower limit
X
ON
ON
7
standby sequence ON
OFF
OFF
SP
SP
X
Absolute value upper limit
ON
ON
8
OFF
OFF
0
X
X
ON
ON
9
Absolute value lower limit
OFF
OFF
0
Absolute value upper limit
X
ON
ON
10
standby sequence ON
OFF
OFF
0
Absolute value lower limit
X
ON
11
ON
standby sequence ON
OFF
OFF
0
12
LBA (only for alarm 1)
13
PV Change Rate Alarm
X
14
SP absolute value upper limit
ON
ON
OFF
OFF
0
X
ON
15
SP absolute value lower limit
ON
OFF
OFF
0
X
ON
ON
16
MV absolute value upper limit
OFF
OFF
0
X
ON
17
MV absolute value lower limit
ON
OFF
OFF
0
X
ON
ON
18
RSP absolute value upper limit
OFF
OFF
0
X
ON
19
RSP absolute value lower limit
ON
OFF
OFF
0
*1: Upper and lower limits can be set for parameters 1, 4 and 5 to provide for
different types of alarm. These are indicated by the letter «L» and «H».
‡ The default alarm type is «2»
Conformance to EN/IEC Standards
This is a class A product.
In residential areas it may cause radio interference, in which case the user
may be required to take adequate measures to reduce interference.
Warning Symbols
CAUTION
Minor injury due to electric shock may occasionally occur.
Do not touch the terminals while power is being supplied.
Electric shock, fire, or malfunction may occasionally occur. Do not allow metal objects, conductors,
cuttings from installation work, or moisture to enter the Digital Controller, the Setup Tool ports, or
between the pins on the connectors on the Setup Tool cable.
Do not use the product where subject to flammable or explosive gas. Otherwise, minor injury from
explosion may occasionally occur.
Never disassemble, modify, or repair the product or touch any of the internal parts. Minor electric
shock, fire, or malfunction may occasionally occur.
CAUTION — Risk of Fire and Electric Shock
a) This is the product UL listed as Open Type Process Control Equipment. It must be mounted in an enclosure
that does not allow fire to escape externally.
b) More than one disconnect switch may be required to de-energize the equipment before servicing.
c) Signal inputs are SELV, limited energy.
d) Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits.
If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur.
Always consider the application conditions and use the output relays within their rated load and
electrical life expectancy. The life expectancy of output relays varies considerably with the output load
and switching conditions.
Loose screws may occasionally result in fire. Tighten the terminal screws to the specified torque of 0.43
WR 1‡P
Set the parameters of the product so that they are suitable for the system being controlled. If they are
not suitable, unexpected operation may occasionally result in property damage or accidents.
A malfunction in the Digital Controller may occasionally make control operations impossible or prevent
alarm outputs, resulting in property damage. To maintain safety in the event of malfunction of the Digital
Controller, take appropriate safety measures, such as installing a monitoring device on a separate line.
Suitability for Use
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which
apply to the combination of the Product in the Buyer’s application or use of the Product.
At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and
limitations of use which apply to the Product. This information by itself is not sufficient for a complete
determination of the suitability of the Product in combination with the end product, machine, system, or
other application or use. Buyer shall be solely responsible for determining appropriateness of the particular
product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in
all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED
)25 7+( ,17(1′(‘ 86( :,7+,1 7+( 29(5$// (48,30(17 25 6<67(0
Installation
Individual mounting (mm)
c
d
Waterproofing is
impossible with
e
5 .):
side-by-side installation.
f
When waterproofing is
required, fit watertight
packing on the
backside of front panel.
+ 0.6
45
0
Operation indicators
‡ 1R GLVSOD
‡ 68% Auxiliary output 1 indicator
Process value or set data type
‡ 68% Auxiliary output 2 indicator
‡ 1R GLVSOD
‡ 68% Auxiliary output 3 indicator
Set point, set data read-out value or changed
input value
‡ 68% Auxiliary output 4 indicator
‡ 287 &RQWURO RXWSXW LQGLFDWRU
‡ No. 3 display
For a current output, lit except for a
MV, Soak Time Remain, and Multi-SP.
0% output.
‡ 287 &RQWURO RXWSXW LQGLFDWRU
‡ 8S DQG ‘RZQ NHV
Each press of U key increments or advances
‡ 563 5HPRWH 6P indicator
the values displayed on the No.2 display.
Lit when the assigned function is ON.
Each press of D key decrements or returns the
‡ TUNE:
values displayed on the No.2 display.
Flashing during self-tuning.
Lit during auto-tuning.
‡ 0RGH NH
Press this key to change the contents of the display.
Press this button for 1 s or longer for reverse scroll.
‡ 3UHVV WKH O key and the M key
together for at least 3 seconds to switch to protect level.
Operation stopped.
Initial Setting Level
(Control/alarm are both stopped.)
in-t
alh3
Alarm 3
3
Input Type *
*6
Hysteresis
5
0.2
M
M
Scaling Upper Limit
alt4
Alarm 3 Type:
in-h
(only when setting
*6
Specified
*6
2
100
analog input)
models only
M
M
Scaling Lower Limit
in-l
alh4
Alarm 3
*6
*6
(only when setting
Hysteresis
0
0.2
analog input)
M
M
Decimal Point
o1st
dp
Control Output 1
(only when setting
*6
*6
Signal
4-20
0
analog input)
M
M
o2st
d-u
c
Temperature
°C=
Control Output 2
*6
*6
Unit
4-20
Signal
f
c
°F=
M
M
trst
sl-h
Transfer Output
*6
SP Upper Limit
4-20
Signal
1300
M
M
tr-t
sl-l
Transfer Output
*6
SP Lower Limit
Type
off
-200
M
M
tr-h
cntl
3,’‡212))
Transfer Output
onof
*6
In ON/OFF control =
100.0
Upper Limit
onof
pid
In 2-PID control =
M
M
tr-l
s-hc
Standard or Heating/Cooling
Transfer Output
stnd
*6
Standard control =
Lower Limit
0.0
stnd
h-c
Heating and cooling control =
M
M
ev-1
st
ST (Self-tuning)
Event Input
*6
on
*6
ST ON =
Assignment 1
msp0
on
off
ST OFF =
M
M
ev-2
ptrn
Event Input
*6
Program Pattern
Assignment 2
stop
off
M
M
ev-3
cp
Control Period (Heating)
Event Input
*6
*6
(Unit: Seconds)
Assignment 3
none
20
*Voltage output (for driving SSR): 2
M
M
ev-4
c-cp
Control Period (Cooling)
Event Input
*6
*6
(Unit: Seconds)
Assignment 4
none
20
*Voltage output (for driving SSR): 2
X
M
M
ev-5
Direct/Reverse Operation
orev
Event Input
*6
or-r
In Reverse operation (Heating) =
Assignment 5
none
or-r
or-d
In Direct operation (Cooling) =
M
M
ev-6
alt1
*3
Event Input
*6
Alarm 1 Type:
*6
Assignment 6
none
Specified models only
*4
2
M
M
clfl
Closed/
alh1
X
*6
*6
Floating
Alarm 1 Hysteresis
flot
0.2
M
M
X
calb
alt2
*3
Motor
0
Alarm 2 Type:
*6
*6
Calibration
*4
off
Specified models only
2
M
M
M
0
mot
X
alh2
Travel Time
*6
Alarm 2 Hysteresis
*6
30
0
0.2
X
M
M
Extraction of
sqr
0
alt3
Alarm 3 Type:
Square Root Enable
*3
*6
*6
Specified
(Only when analog
off
2
models only
*4
input is set)
M
M
amov
Move to Advanced
*6
Function Setting
0
Level
X
M
0
X
Initial setting level enables users to specify their preferred operating conditions
(input type, alarm type, control method, etc.)
0
X
0
Conformance to Safety Standard
X
0
Reinforced insulation is provided between input power
X
supply, relay outputs, and between other terminals.
0
Do not allow temporary overvoltages on the primary circuit to exceed
X
the following values.
Check the power supply voltage to the Digital Controller.
0
Short-term overvoltage: 1,200 V + (Power supply voltage)
Long-term overvoltage: 250 V + (Power supply voltage)
Always externally connect the recommended fuse that is specified
in the Instruction Manual before you use the Digital Controller.
Analog Input
‡ If you input an analog voltage or current, set the Input Type
parameter to the correct input type.
‡ Do not use the Digital Controller to measure a circuit with
Measurement Category II, III, or IV.
‡ Do not use the Digital Controller to measure an energized circuit to
which a voltage that exceeds 30 Vms or 60 VDC is applied.
The protection provided by the Digital Controller may be impaired if the
Digital Controller is used in a manner that is not specified by the
manufacturer.
Be sure to observe the following precautions to prevent operation failure, malfunction, or adverse affects on the
performance and functions of the product. Not doing so may occasionally result in unexpected events. Use the
product within specifications.
(1) The product is designed for indoor use only. Do not use the product outdoors. Do not use or store the product in
any of the following locations.
‡ 3ODFHV GLUHFWO VXEMHFW WR KHDW UDGLDWHG IURP KHDWLQJ HTXLSPHQW
‡ 3ODFHV VXEMHFW WR VSODVKLQJ OLTXLG RU RLO DWPRVSKHUH
‡ 3ODFHV VXEMHFW WR GLUHFW VXQOLJKW
‡ 3ODFHV VXEMHFW WR GXVW RU FRUURVLYH JDV LQ SDUWLFXODr, sulfide gas and ammonia gas).
‡ 3ODFHV VXEMHFW WR LQWHQVH WHPSHUDWXUH FKDQJH
‡ 3ODFHV VXEMHFW WR LFLQJ DQG FRQGHQVDWLRQ
‡ 3ODFHV VXEMHFW WR YLEUDWLRQ DQG ODUJH VKRFNV
(2) Use/store within the rated temperature and humidity ranges. Provide forced-cooling if required.
(3) To allow heat to escape, do not block the area around the product.
Do not block the ventilation holes on the product.
(4) Be sure to wire properly with correct polarity of terminals.
(5) Use the specified size of crimped terminals (M3, width 5.8 mm or less) for wiring. To connect bare wires to the
terminal block, use copper braided or solid wires with a gage of AWG24 to AWG18 (equal to a cross-
sectional area of 0.205 to 0.8231 mm
type, or two crimped terminals can be inserted into a single terminal.
(6) Do not wire the terminals which are not used.
(7) Allow as much space as possible between the controller and devices that generate a powerful high-frequency
or surge. Separate the high-voltage or large-current power lines from other lines, and avoid parallel or common
wiring with the power lines when you are wiring to the terminals.
(8) Use this product within the rated load and power supply.
(9) Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or relay
contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur.
(10) Make sure that the Digital Controller has 30 minutes or more to warm up after turning ON the power before
starting actual control operations to ensure the correct temperature display.
(11) When executing self-tuning, turn the load and the unit ON simultaneously, or turn the load ON before you turn
the controller ON.
(12) A switch or circuit breaker should be provided close to this unit. The switch or circuit breaker should be within
easy reach of the operator, and must be marked as a disconnecting means for this unit.
(13) Wipe off any dirt from the Digital Controller with a soft dry cloth. Never use thinners, benzine, alcohol, or any
cleaners that contain these or other organic solvents. Deformation or discoloration may occur.
(14) Design system (control panel, etc) considering the 2 second of delay that the controller’s output to be set after
power ON.
(15) The output will turn OFF when you move to the Initial Setting Level. Take this into consideration when
performing control.
(16) The number of non-volatile memory write operations is limited. Therefore, use RAM write mode when frequently
overwriting data during communications or other operations.
(17) When disassembling the Digital Controller for disposal, use suitable tools.
(18) Do not connect cables to both the front-panel Setup Tool port and the top-panel Setup Tool port at the same
time. The Digital Controller may be damaged or may malfunction.
(19) Do not exceed the communications distance that is given in the specifications and use the specified
communications cable. Refer to the E5
communications distance and cable specifications.
(20) Do not turn the power supply to the Digital Controller ON or OFF while the USB-Serial Conversion Cable is
connected. The Digital Controller may malfunction.
(21) The maximum terminal temperature is 75°C.
Connections
Side-by-side mounting (mm)
Control output 1
Relay output
(48 x number of units–2.5) + 1 0
250 VAC, 5A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 40 mA
21 mA if there are two
control outputs
Current output
0 to 20 mA DC
4 to 20 mA DC
/RDG
*2 Control Outputs
One relay
‡ ,QVHUW WKH PDLQ XQLW WKURXJK WKH PRXQWLQJ KROH LQ WKH SDQHO
output
(1-8 mm thickness). Insert the mounting brackets (supplied)
3
into the fixing slots located on the top and bottom of the rear
case.
4
‡ Tighten the two mounting screws on the top and bottom of
5
the adapter to keep them balanced, and finally tighten them
6
to a torque of between 0.29 and 0.39 N·m.
‡ :KHQ PRUH WKDQ RQH PDFKLQH LV LQVWDOOHG PDNH VXUH WKDW WKH
ambient temperature does not exceed the specified limit.
‡ 6TOP: Control stop indicator
Lit when «Run/Stop» is stopped during operation.
During control stop, functions other than control output
are valid.
‡ CMW: Communications writing enable/ disable indicator
Lit when communications writing is «enabled» and is
out when it is «disabled».
‡
3URWHFWLRQ LQGLFDWRU
Lit when Setting Change Protect is ON (disables the
*3 Auxiliary Outputs
Up and Down Keys).
Auxiliary outputs 1 and 2
‡ 0$18 0DQXDO RXWSXW LQGLFDWRU
Lit when the Auto/Manual Mode is set to Manual
Mode.
10
11
12
* When complying with EMC standards, the line connecting the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
Check the wiring before turning ON the power supply.
*5
POWER ON
Operation Level
*3
Process Value/Set Point
25
*4
s.err is displayed when
*6
connected sensor is
0
different from input type.
M
Hold O down
Auto/Manual Switch
a-m
PID control only.
*6
*6
for at least
3 seconds
M
(No.1 display flashes,
m-sp
Multi-SP
*6
*6
then the control stops.)
Set Point Selection
0
M
Hold O down
rsp
for at least
*6
*6
Remote SP Monitor
0.0
1 second
M
sp-m
Set Point During
*6
*6
SP Ramp
0
M
Heater Current 1
ct1
*6
Value Monitor
*6
0.0
7
(Unit: A) *
M
Heater Current 2
ct2
*6
*6
Value Monitor
0.0
(Unit: A) *
7
M
Leakage Current 1
lcr1
*6
*6
Value Monitor
0.0
7
(Unit: A) *
M
Leakage Current 2
lcr2
*6
*6
Value Monitor
0.0
7
(Unit: A) *
M
prst
*6
*6
Program Start
rset
M
sktr
*6
*6
Soak Time Remain
0
M
RUN/STOP
r-s
run
*6
*6
When control start =
run
stop
When control stop =
M
al-1
*6
4
*6
Alarm Value 1 *
0
M
al1h
A
larm Value
*6
*4
Upper Limit 1
0
M
Operation level should normally be used during operations.
Hold O and M keys
Hold O and M keys
down for at least 1 second
down for at least 3 seconds
Protect Level
Move to Protect Level
pmov
Displayed only when a
password is set. Restricts
0
moving to Protect Level.
M
Operation / Adjustment Protect
Restricts displaying and
oapt
modifying menu items in
Operation, Adjustment, and
0
Manual Control Levels.
M
Initial Setting /
Communication Protect
icpt
Restricts movement to the
Initial Setting, Communications
1
Setting, and Advanced Function
M
Setting Levels.
wtpt
Setting Change Protect
Restricts changes to settings
off
by operating the front panel keys.
M
pfpt
PF Key Protect
Restricts PF key operation.
off
M
Restricts which settings can be displayed or changed, and restricts
change by key operation.
*3: Refer to the adjoining tables for details of input types and alarm types.
*4: Applicable only to models with alarm functions.
*5: Operation is stopped when moved to the initial setting level.
(control/alarm are both stopped.)
*6: The grayed-out setting items may not be displayed according to the models
and setting.
*7: Applicable only to models with heater burnout functions.
The four numeric digits of the product code are displayed in the No. 2
*8:
display. The setting cannot be changed and there is nothing that you need
to set.
Other functions
Refer to the E5□C Digital Controllers User’s Manual (Cat. No. H174)
for information on the Advanced Function Setting Level,
Monitor/Setting Item Level, Manual Control Level, and other functions.
Refer to the E5□C Digital Controllers Communications Manual
(Cat. No. H175) for information on communications.
Precautions for Safe Use
2
). (The stripping length is 6 to 8 mm.). Up to two wires of same size and
C Digital Controllers User’s Manual (Cat. No. H174) for the
□
(The applicability of the electric terminals varies with the type of machine.)
Auxiliary output 1, 2, 3, 4
*5 Options
Control output 2
004
Relay output
Relay output
250 VAC, 5 A
two outputs 250 VAC, 3 A
Communications
(resistive load)
(resistive load)
and two event inputs
four outputs 250 VAC, 2 A
Voltage output
(resistive load)
B(+)
(for driving SSR)
RS-485
12 VDC, 21 mA
Current output
A()
0 to 20 mA DC
4 to 20 mA DC
/RDG
PD[
EV1
E5EC
PD[
EV2
2. Control outputs
5. Options
RX
4;
One voltage output
*1 Input Power Supply
(for driving SSR)
100 to 240 VAC
24 VAC/DC
OUT1
3
OUT1
+
R
4
1
1
4
2
2
5
(no polarity)
6
CX
44
45
One linear
Two voltage outputs
Voltage output (for driving
current output
(for driving SSRs)
SSR)/relay output
OUT1
OUT1
OUT1
3
3
3
+
+
+
C
4
4
4
4
4
5
5
OUT2
5
OUT2
+
4
R
6
6
6
RR/PR
CC
CQ
Two relay
Two linear
Linear current/voltage
outputs
current outputs
output (for driving SSR)
OUT1
OUT1
3
OUT1
3
3
+
+
R
C
C
—
4
4
4
5
OUT2
5
OUT2
5
OUT2
+
+
R
C
Q
—
6
6
6
*4 Sensor Temperature/Analog Input
Auxiliary outputs 1 to 4
Potentiometer
TC
Pt
I
V
7
7
A
input
+
22
22
22
22
Auxiliary output 4
8
8
B
mA
O
Auxiliary output 3
23
23
23
23
9
9
B
W
V
24
24
24
24
Auxiliary output 2
+
10
+
C
Auxiliary output 2
11
The E5EC is set for a K thermocouple (input type of 5) by
Auxiliary output 1
Auxiliary output 1
default. If a different sensor is used, an input error (s.err) will
12
occur. Check the setting of the Input Type parameter.
Adjustment Level
l.adj
Adjustment Level
*8
Displayed only once when
entering Adjustment Level.
M
AT Execute/Cancel
at
*6
100%AT Execute
at-2
off
al1l
(The No.3 display
40%AT Execute
at-1
Alarm Value
has been omitted.)
M
0
*
4
Lower Limit 1
cmwt
M
Communications Writing
*6
off
al-2
4
Alarm Value 2 *
M
0
Press O
spmd
M
*6
SP Mode
(less than
lsp
al2h
Alarm Value
1 second)
M
0
*
4
Upper Limit 2
ct1
Heater Current 1
M
*6
Value Monitor
0.0
al2l
(Unit: A) *
7
Alarm Value
M
0
*
4
Lower Limit 2
hb1
Heater Burnout
M
*6
Detection 1
0.0
al-3
(Unit: A) *
7
Alarm Value 3 *
4
M
0
Heater Current 2
ct2
M
Value Monitor
*6
0.0
al3h
7
(Unit: A) *
Alarm Value
4
M
0
Upper Limit 3
*
Heater Burnout
hb2
M
*6
Detection 2
0.0
al3l
(Unit: A) *
7
Alarm Value
M
*4
0
Lower Limit 3
Leakage Current 1
lcr1
M
*6
Value Monitor
al-4
0.0
7
4
(Unit: A) *
Alarm Value 4 *
M
0
hs1
HS Alarm 1
M
*6
(Unit: A) *
7
5 0.0
al4h
Alarm Value
4
M
Upper Limit 4
*
0
Leakage Current 2
lcr2
M
*6
Value Monitor
0.0
al4l
7
(Unit: A) *
Alarm Value
M
4
Lower Limit 4
*
0
hs2
HS Alarm 2
M
*6
7
(Unit: A) *
50.0
o
MV Monitor
M
(Heating)
0.0
sp-0
SP 0
M
*6
0
c-o
MV Monitor
M
(Cooling)
0.0
sp-1
SP 1
M
M
*6
0
v-m
Valve Opening
M
Monitor
0.0
sp-2
SP 2
M
*6
0
M
sp-3
SP 3
*6
0
M
Error Display (troubleshooting)
When an error has occurred, the No.1 display shows the error code. Take
necessary measure according to the error code, referring the table below.
No.1 display
Meaning
s.err
Input error
(S. Err)
chgp
*2
Changed
Parameters Only
off
M
e333
Parameter Mask
(E333)
A/D converter error
pmsk
Enable
*2
Displayed only
on
when a parameter
mask is set.
M
prlp
e111
Memory error
Password to
(E111)
Move to Protect
0
Level
M
If the input value exceeds the display limit (-1999 to 9999), though it is within the control
range, [[[[ will be displayed under -1999 and ]]]] above 9999. Under these conditions,
control output and alarm output will operate normally. Refer to the E5□C Digital Controllers
User’s Manual (Cat. No. H174) for the controllable ranges.
*2: Error shown only for «Process value / Set point». Not shown for other status.
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands
Phone 31-2356-81-300
FAX 31-2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg, IL 60173-5302 U.S.A
Phone 1-847-843-7900
FAX 1-847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark, Singapore 119967
Phone 65-6835-3011
FAX 65-6835-2711
OMRON Corporation
Shiokoji Horikawa, Shimogyo-ku, Kyoto 600-8530 JAPAN
Specifications
Power supply voltage
100 to 240 VAC, 50/60 Hz or
24 VAC, 50/60 Hz / 24VDC
Operating voltage range
85 to 110% of the rated voltage
Power consumption
Option 000:
6.6 VA max. (100 to 240 VAC)
4.1 VA max. (24 VAC)/2.3 W max. (24 VDC)
All other specifications:
8.3 VA max. (100 to 240 VAC)
5.5 VA max. (24 VAC)/3.2 W max. (24 VDC)
Indication accuracy
Thermocouple:
(Ambient temperature: 23°C) (±0.3 % of indication value or ±1°C,
whichever is greater) ±1 digit max.
Platinum resistance thermometer:
(±0.2 % of indication value or ±0.8°C,
whichever is greater) ±1 digit max.
Analog input: ±0.2 % FS ±1 digit max.
Event input
Output current: approx. 7 mA per contact.
Contact input
21 N
PD[ 2)) N
PLQ
No-contact input
ON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.
Remote SP input
4 to 20 mA DC or 0 to 20 mA DC
0 to 5 V DC or 1 to 5 V DC or 0 to 10 V DC
Potentiometer input
%HWZHHQ
DQG N IRU PD[LPXP RSHQ SRVLWLRQ
Control output 1
Relay output: SPST-NO,
250 VAC, 5 A (resistive load)
Electrical life of relay: 100,000 operations
Voltage output (for driving SSR):
12 VDC ±20%, 40 mA for one control output,
21 mA if there are two control outputs
Current output: 4 to 20 mA DC, 0 to 20 mA DC
/RDG
PD[
Control output 2
Relay output: SPST-NO,
250 VAC, 5 A (resistive load)
Electrical life of relay: 100,000 operations
Voltage output (for driving SSR): 12 VDC, 21 mA
Current output: 4 to 20 mA DC or 0 to 20 mA DC
ZLWK ORDG RI Ÿ PD[
Control method
ON/OFF or 2-PID control
Auxiliary outputs
Relay outputs: 250 VAC, two outputs: 3 A
(resistive load), four outputs: 2 A (resistive load)
Electrical life of relay: 100,000 operations
Transfer output
4 to 20 mA ‘& ZLWK ORDG RI
PD[
WR 9’& ZLWK ORDG RI N
PLQ
Ambient temperature
–10 to 55°C
(Avoid freezing or condensation)
Ambient humidity
25% to 85%
Storage temperature
–25 to 65°C
(Avoid freezing or condensation)
Altitude
Max. 2,000 m
Recommended fuse
T2A, 250 VAC, time-lag, low-breaking capacity
Weight
Approx. 210 g (Digital Controller only)
Degree of protection
Front panel: IP66
Rear case: IP20, Terminal section: IP00
Installation environment
Installation category II, pollution
degree 2 (as per IEC61010-1)
Memory protection
Non-volatile memory
(Number of write operations: 1,000,000)
Temporary overvoltage
Short term: 1200 V+ (power supply voltage)
Long term: 250 V+ (power supply voltage)
Do not connect anything to the terminals that are shaded gray.
005
008
010
009
Four event inputs
Communications, two event
Communications, two event
Four event inputs
inputs, and one CT
inputs, and two CTs
and one CT
B(+)
B(+)
13
13
13
13
13
RS-485
RS-485
14
14
14
14
14
EV3
EV3
A()
A()
15
15
15
15
15
EV4
EV4
16
16
16
16
16
17
17
17
17
17
EV1
EV1
EV1
EV1
18
18
18
18
18
EV2
EV2
EV2
EV2
19
19
19
19
19
CT1
CT1
CT1
20
20
20
20
20
COM
CT2
21
21
21
21
21
011
012
Six event inputs, one CT,
Communications, four event inputs,
transfer output, and remote SP
one CT, transfer output, and remote SP
13
B(+)
13
RS-485
14
EV3
14
A( )
15
EV4
15
28
16
28
16
29
17
EV5
EV1
29
17
30
EV5
EV1
18
EV6
EV2
30
18
EV6
+
31
19
EV2
+
+
31
19
Transfer
V
CT1
32
20
+
Transfer
V
CT1
output
I
32
20
output
I
33
21
33
21
+
34
+
+
34
Remote
V
35
+
V
mA
Remote
SP
35
mA
36
SP
36
014
013
Communications, four event inputs,
Six event inputs, transfer output,
transfer output, and remote SP
and remote SP
B(+)
13
13
RS-485
14
14
A( )
EV3
15
15
EV4
28
28
16
16
29
29
17
17
EV5
EV1
EV5
EV1
19
30
18
30
18
EV6
EV6
EV2
EV2
20
+
31
+
31
19
19
Transfer
V
+
+
Transfer
V
21
32
output
20
32
20
I
output
I
33
33
21
21
+
34
+
34
+
Remote
V
+
V
35
Remote
35
mA
mA
SP
SP
36
36
Only the value set to the «ins: Temperature Input Shift» parameter is applied to the entire temperature input range. When the
process value is 200 °C, the process value is treated as 201.2 °C after input shift if the input shift value is set to 1.2 °C.
The process value is treated as 198.8 °C after input shift if the input shift value is set to –1.2 °C.
sp-4
hys
SP 4
Hysteresis
*6
*6
(Heating)
0
1.0
M
M
sp-5
chys
SP 5
Hysteresis
*6
*6
(Cooling)
0
1.0
M
M
sp-6
soak
SP 6
*6
*6
Soak Time
1
0
M
M
sp-7
wt-b
SP 7
*6
*6
Wait Band
0
off
M
M
ins
mv-s
PV
*6
*6
MV at Stop
0.0
Input Shift
0.0
M
M
inrt
mv-e
PV input
*6
*6
MV at PV Error
1.000
Slope Coefficient
0.0
M
M
sprt
rss
Remote SP
*6
*6
SP Ramp Set Value
0 .0
Input Shift
off
M
M
rsrt
sprl
Remote SP input
SP Ramp Set Value
*6
*6
(SP Ramp Fall Value)
1.000
Slope Coefficient
same
M
M
p
ol-h
MV Upper Limit
*6
Proportional
*6
8.0
Band
100.0
M
M
i
ol-l
Integral Time
*6
*6
MV Lower Limit
(Unit: Seconds)
233
0.0
M
M
d
orl
Derivative Time
MV Change
*6
*6
Rate Limit
40
(Unit: Seconds)
0.0
M
M
c-p
db
Position
*6
Proportional
*6
Proportional
8.0
2.0
Band (Cooling)
Dead Band
M
M
Integral Time
c-i
oc-h
Open/Close
*6
(Cooling)
*6
Hysteresis
233
0.8
(Unit: Seconds)
M
M
Derivative Time
c-d
sqrp
Extraction of Square
*6
*6
(Cooling)
Root Low-cut Point
40
0.0
(Unit: Seconds)
M
M
c-db
plcm
Communications
Dead Band
*6
*6
Monitor
0.0
1234
M
M
of-r
Manual Reset Value
*6
Clears the offset
Adjustment level is for entering
50.0
during P or PD control.
set values and shift values for
M
control.
Status at error
Action
Control
Alarm
output
Check the setting of the Input Type parameter,
Operates
OFF
as above the
check the input wiring, and check for broken or
shorts in the temperature sensor.
upper limit.
After the correction of A/D converter error, turn the
power OFF then back ON again. If the display
remains the same, the controller must be repaired.
OFF
OFF
If the display is restored to normal, then a
probable cause can be external noise affecting the
control system. Check for external noise.
Turn the power OFF then back ON again. If the
display remains the same, the controller must be
repaired. If the display is restored to normal, then
OFF
OFF
a probable cause can be external noise affecting
the control system. Check for external noise.
Содержание
- Как правильно настроить терморегулятор Omron E5CC для работы с муфельной печью
- Как правильно подключить терморегулятор Omron E5CC к муфельной печи
- Почему стоит установить терморегулятор Omron E5CC на муфельную печь
- Регуляторы температуры OMRON E5CC
- Особенности
- Характеристики
- Преимущества
- Информация для заказа терморегуляторов OMRON E5CC
- E5_C-T
- Компактные и интеллектуальные регуляторы c режимами разгона/выдержки
- E5_C/E5_C-T Digital Temperature Controller Спецификация
- Характеристики и информация для заказа
- Фильтры для продуктов
- Общие характеристики
- Size (1)
- Functions (3)
- Number of control loops (1)
- Temperature range (1)
- Temperature input type (14)
- Linear analog input type (5)
- Features (1)
- Number of event inputs (1)
- Number of alarm outputs (1)
- Supply voltage AC (2)
- Supply voltage DC (1)
- Control output (2)
- Communication port(s) (1)
- Terminal (1)
- Как мы можем помочь вам?
- Свяжитесь со мной E5_C-T
- Предложение для E5_C-T
- Особенности
- Temperature profiles
- Управление процессами в соответствии с вашими потребностями
- LCD display
- ЖК-дисплей «JUMBO» для лучшей видимости
- Easy Set-up
- Быстрый ввод машин в эксплуатацию
- Precise control
- Положитесь на наш запатентованный 2-ПИД
- Useful functions
- Аварийные сигналы
- Входы событий
- Коммуникационные функции
- Выход передачи данных
Как правильно настроить терморегулятор Omron E5CC для работы с муфельной печью
Терморегулятор Omron E5CC относится к новому поколению устройств контроля температуры. Установка этого оборудования гарантирует точность регулировки и поддержание работы обжиговых и лабораторных печей.
Регулятор Omron способен работать даже в условиях повышенной влажности
Японские терморегуляторы не зря считаются самыми высокоточными в мире. Достаточно посмотреть на перечень их достоинств:
- Жидкокристаллический дисплей. Монитор этой модели отличается увеличенными размерами, наличием подсветки и повышенной контрастностью изображения. Благодаря этому информация будет видна с большого расстояния и под разными углами.
- Производительность работы. Главные характеристики регуляторов – это скорость и точность измерения. Иногда от колебания температуры всего в несколько градусов может зависеть конечный результат исследований. Алгоритм работы регулятора Omron E5CC позволяет поддерживать выставленные параметры в пределах 0,5°С.
- Легкость управления. Автоматическая настройка намного уменьшит затраты времени, а также максимально упростит регулирование температуры во время работы.
- Компактность. Данный прибор можно устанавливать на любые муфельные электропечи SNOL.
Цитата: Во время устранения загрязнений после работы печи, регулятор также можно очищать. Для этого используются неагрессивные моющие средства
Как правильно подключить терморегулятор Omron E5CC к муфельной печи
Изучив инструкцию на русском про терморегулятор Omron E5CC, можно сделать вывод, что это устройство не сложное в эксплуатации. Для любых этапов работы – подключения, настройки или пользования достаточно сделать всего несколько простых шагов. Все операции проводятся путем нажатия клавиш с интуитивно понятными значениями.
Оптимальная температура окружающей среды во время работы прибора – не выше 45 градусов Цельсия
Для регулятора Omron E5CC инструкция на русском языке предусматривает возможность установки на разное оборудование – промышленное, бытовое и лабораторное. В их число входят, в том числе, муфельные печи и сушильные шкафы. При первичном подключении руководством по эксплуатации предусмотрены такие меры:
- Убедиться, что упаковка и сам прибор не носят следы повреждений.
- Осмотреть вентиляционные отверстия вокруг места для монтажа терморегулятора – они должны оставаться свободными для отвода тепла.
- Не стоит сильно затягивать клеммные зажимы.
- Необходимо правильно подсоединить входы питания.
- В месте установки обеспечить отсутствие жидкостей и посторонних предметов.
Если терморегулятор будет подвергаться постоянному нагреву, нужно позаботиться о дополнительном охлаждении или вентиляции
Опишем процесс монтажа на панель электропечи и особенности настройки Omron E5CC:
- Вставить устройство в специальное отверстие.
- Для обеспечения водонепроницаемости использовать прокладку.
- Предварительно закрепить регулятор, надев переходник от клеммного блока.
- Поочередно затянуть два крепежных винта.
Для подключения терморегулятора к компьютеру используется стандартный кабель USB
После включения питания на дисплее автоматически отображается эксплуатационный уровень. Чтобы изменить параметры, нужно перейти на одну из таких систем настроек:
- Первоначальной подготовки.
- Регулирования.
- Расширенной функциональности.
- Передачи информационных данных.
При выставлении настроек не забудьте выбрать единицы измерения температуры — ºC или °F
Какие функции еще входят в инструкцию по программированию Omron E5CC, наглядно можно посмотреть в представленном видео:
Почему стоит установить терморегулятор Omron E5CC на муфельную печь
Как видим, терморегулятор Omron E5CC способен контролировать множественные рабочие функции лабораторных печей. Его отличительными особенностями являются:
- 2Пид-регулирование.
- Наличие аналоговых входов.
- Небольшие габариты.
- Возможность использования интерфейса RS-485.
- Датчики сигналов о неисправностях.
- Работа с термопарами разных типов.
- Простая инструкция по настройке и управлению.
- Контрастный ЖК-дисплей с крупноразмерными цифрами, видными издалека.
Любые лабораторные исследования или работа с образцами предусматривают точное соблюдение температурных параметров. Использование терморегуляторов Omron E5CC дает возможность обеспечить необходимые условия для проведения опытов.
Производитель обеспечивает техническую поддержку для устройств любого типа. Сотрудники более 200 сервисных центров по всему миру помогут быстро устранить неисправности и произвести замену нужных деталей.
Еще один бонус – гарантия единой цены на устройства во всех странах
По всем вопросам эксплуатации и приобретения терморегуляторов обращайтесь в компанию «Лабор».
Источник
Регуляторы температуры OMRON E5CC
Терморегуляторы Omron E5CC — это новый стандарт в области регулирования температуры!
Регулятор температуры нового поколения Omron E5CC устанавливает новый мировой стандарт в отношении точности регулирования и простоты использования. Лучшие характеристики регулирования, простота настройки и отличная видимость показаний на ЖК-дисплее в исполнении IP66 с цифрами белого цвета— все это в компактном корпусе глубиной всего 60 мм.
Особенности
- Быстрое и точное регулирование: длительность измерительного цикла всего 50 мс
- Простая настройка без источника питания с помощью интуитивно понятной программы CX-Thermo
- Четкие, хорошо различимые цифры белого цвета на ЖК дисплее отлично видны с большого расстояния и под любым углом
- Высота символов на экране 15.2 мм
- Функции сигнализации аварийных состояний и диагностики обеспечивают безопасную работу
- Благодаря практичным функциям таймера и логических операций не требуется использовать ПЛК
- Увеличенное количество входов и выходов: 3 дополнительных выхода, 4 входа событий, сигнальный выход и дистанционное задание уставок
- Доступны дополнительные модели с различными функциональными возможностями.
Характеристики
Характеристики входов
- Термопара: K, J, T, E, L, U, N, R, S, B, W или PL II
- Платиновый термометр сопротивления: Pt100 или JPt100
- Инфракрасный датчик температуры: 10-70 С, 60-120 С, 115-165 С, 140-260 С
- Аналоговый вход: токовый вход 4-20 мА или 0-20 мА; вход напряжения 1-5 В, 0-5 В или 0-10 В
Характеристики управляющих выходов
- Релейный выход: 1НО, 250 VAC, 3 A (резистивная нагрузка), электрический ресурс 100000. Минимально допустимая нагрузка: 5 В, 10 мА.
- Выход напряжения: 12 VDC (+/- 20%), PNP, максимальный ток нагрузки 21 мА, со схемой защиты от КЗ
- Токовый выход: 4-20 мА=, 0-20 мА=, нагрузка: максимально 500 Ом, разрешение 10000
Преимущества
LCD display
Новый дизайн дисплея — превосходная видимость значений
Большой дисплей с отображением текущего значения белым цветом (15.2 мм в модели E5CC и 18 мм для модели E5EC) позволяет считывать данные на большом расстоянии, при плохой видимости и под разным углом обзора
Easy Set-up
Простота настройки и легкость эксплуатации
Настройка контроллеров упрощена за счет применения алгоритмов автонастройки и нового интуитивно понятного программного обеспечения CX-Thermo. Это позволяет быстро устанавливать параметры и изменять настройки устройства, а также существенно упрощает обслуживание. На передней панели контроллера расположена клавиша переключения регистра, позволяющая быстро настраивать установленные значения, а также выполнить как Auto-Tuning (автонастройка), так и RUN/STOP (пуск/останов).
Precise control
Высокая точность терморегуляции
Период измерения в новых терморегуляторах составляет всего 50 мсек., что минимум в 5 раз меньше, чем у аналогичных моделей. Благодаря высокой точности контролирования термопроцесса модели E5CC и E5EC могут применяться в тех областях, где точность регулирование температуры является особо критичной.
Useful functions
Расширенная функциональность благодаря увеличенному кол-ву входов и выходов по событиям
Модель E5EC оснащенная 4-мя вспомогательными выходами и 6-ю входами событий. Помимо этого модели E5CC и E5EC поддерживают дополнительные входы/ выходы, включая сигнальные выходы и удаленные входы для внешних устройств. С увеличенным количеством входов/выходов и дополнительных функций терморегулятор может контролировать сложные термопроцессы, тем самым внося свой вклад в эффективность работы всей системы.
Печи, оборудованные регулирующим клапаном, с обратной связью с потенциометром в отрасли производства керамики
Информация для заказа терморегуляторов OMRON E5CC
© 2001—2021, ООО Промэнерго Автоматика. Все права защищены.
Источник
E5_C-T
Компактные и интеллектуальные регуляторы c режимами разгона/выдержки
Регуляторы температуры с режимами разгона и выдержки E5_C-T расширяют семейство E5_C для выполнения сложных задач в различных отраслях промышленности. Регуляторы поддерживают до 6 входов событий и до 4 вспомогательных выходов, а также имеют компактный корпус с монтажной глубиной 60 мм, что делает данную серию самой мощной и универсальной среди всех регуляторов температуры Omron.
- Простая настройка до 8 программ (32 сегмента на программу), при помощи программного обеспечения CX-Thermo.
- Трехуровневый дисплей позволяет одновременно отображать состояние каждого процесса.
- Функция «Segement Jump» позволяет пользователям легко перемещаться к необходимому сегменту, что сокращает время программирования и повышает производительность.
E5_C/E5_C-T Digital Temperature Controller Спецификация
Характеристики и информация для заказа
Фильтры для продуктов
Общие характеристики
Size (1)
Functions (3)
- HB/HS alarm for 3-phase heaters ()
- ON/OFF control ()
- PID control ()
Number of control loops (1)
Temperature range (1)
Temperature input type (14)
- B ()
- C (WRe5-26) ()
- E ()
- J ()
- JPt100 ()
- K ()
- L ()
- N ()
- P (PLII) ()
- Pt100 ()
- R ()
- S ()
- T ()
- U ()
Linear analog input type (5)
- 0 to 10 V ()
- 0 to 20 mA ()
- 0 to 5 V ()
- 1 to 5 V ()
- 4 to 20 mA ()
Features (1)
- SV programmer (8 programs of 32 segments) ()
Number of event inputs (1)
Number of alarm outputs (1)
Supply voltage AC (2)
Supply voltage DC (1)
Control output (2)
Communication port(s) (1)
Terminal (1)
Продукт | Size | Functions | Number of control loops | Temperature range | Temperature input type | Linear analog input type | Features | Number of event inputs | Number of alarm outputs | Supply voltage AC | Supply voltage DC | Control output | Communication port(s) | Terminal | Описание |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1/16 DIN (48 x 48 mm) | ON/OFF control, PID control | 1 | -200-2300 °C | B, C (WRe5-26), E, J, JPt100, K, L, N, P (PLII), Pt100, R, S, T, U | 0 to 10 V, 0 to 20 mA, 0 to 5 V, 1 to 5 V, 4 to 20 mA | SV programmer (8 programs of 32 segments) | 0 | 3 | 100-240 V | Voltage pulse | Screw | Контроллер температуры цифровой серии E5CC, выход напряжения для управления ТТР, три вспомогательных выхода, напряжение питания 100..240 VAC, универсальный вход | |||
1/16 DIN (48 x 48 mm) | HB/HS alarm for 3-phase heaters, ON/OFF control, PID control | 1 | -200-2300 °C | B, C (WRe5-26), E, J, JPt100, K, L, N, P (PLII), Pt100, R, S, T, U | 0 to 10 V, 0 to 20 mA, 0 to 5 V, 1 to 5 V, 4 to 20 mA | SV programmer (8 programs of 32 segments) | 0 | 3 | 100-240 V | Voltage pulse | Serial RS-485 | Screw | Контроллер температуры цифровой серии E5CC, выход напряжения для управления ТТР, три вспомогательных выхода, напряжение питания 100..240 VAC, универсальный вход, две сигнализации HB и HS (для трехфазных нагревателей), RS-485 | ||
1/16 DIN (48 x 48 mm) | HB/HS alarm for 3-phase heaters, ON/OFF control, PID control | 1 | -200-2300 °C | B, C (WRe5-26), E, J, JPt100, K, L, N, P (PLII), Pt100, R, S, T, U | 0 to 10 V, 0 to 20 mA, 0 to 5 V, 1 to 5 V, 4 to 20 mA | SV programmer (8 programs of 32 segments) | 0 | 3 | 20.4-26.4 V | 20.4-26.4 V | Voltage pulse | Serial RS-485 | Screw | Контроллер температуры цифровой серии E5CC, выход напряжения для управления ТТР, три вспомогательных выхода, напряжение питания 24 V AC/DC, универсальный вход, две сигнализации HB и HS (для трехфазных нагревателей), RS-485 | |
1/16 DIN (48 x 48 mm) | ON/OFF control, PID control | 1 | -200-2300 °C | B, C (WRe5-26), E, J, JPt100, K, L, N, P (PLII), Pt100, R, S, T, U | 0 to 10 V, 0 to 20 mA, 0 to 5 V, 1 to 5 V, 4 to 20 mA | SV programmer (8 programs of 32 segments) | 0 | 3 | 100-240 V | Relay | Screw | Контроллер температуры цифровой серии E5CC, релейный выход, три вспомогательных выхода, напряжение питания 100..240 VAC, универсальный вход | |||
1/16 DIN (48 x 48 mm) | ON/OFF control, PID control | 1 | -200-2300 °C | B, C (WRe5-26), E, J, JPt100, K, L, N, P (PLII), Pt100, R, S, T, U | 0 to 10 V, 0 to 20 mA, 0 to 5 V, 1 to 5 V, 4 to 20 mA | SV programmer (8 programs of 32 segments) | 0 | 3 | 20.4-26.4 V | 20.4-26.4 V | Relay | Screw | Контроллер температуры цифровой серии E5CC, релейный выход, три вспомогательных выхода, напряжение питания 24 V AC/DC, универсальный вход |
Как мы можем помочь вам?
Если вы хотите задать вопрос или узнать информацию о ценах, свяжитесь с нами или отправьте запрос.
Свяжитесь со мной E5_C-T
Спасибо за Ваш запрос. Мы свяжемся с Вами в ближайшее время.
Возникли технические проблемы. Ваша форма не была отправлена. Примите наши извинения и повторите попытку позже. Детали: [details]
Предложение для E5_C-T
С помощью этой формы вы можете запросить коммерческое предложение на выбранный вами продукт. Пожалуйста, заполните все поля отмеченные звездочкой. Ваши персональные данные будут обработаны с соблюдением конфиденциальности.
Благодарим за интерес к нашей продукции. Мы вышлем интересующую Вас информацию в ближайшее время.
Возникли технические проблемы. Ваша форма не была отправлена. Примите наши извинения и повторите попытку позже. Детали: [details]
Особенности
Temperature profiles
Управление процессами в соответствии с вашими потребностями
Четкое и плавное регулирование позволяет моментально отрабатывать возмущающие воздействия, не причиняя сильно стресса процессу и сохраняя оборудование. В терморегуляторе предусмотрена возможность плавного выполнения линейного возрастания и выдержки без необходимости ручной регулировки параметров. Даже в случае изменяющихся характеристик процесса, эффективная автонастройка позволяет быстро достигнуть стабильной работы, автоматически опережая настройки ПИД.
Настройка температурных профилей упрощена благодаря программному обеспечению CX-Thermo, совместимому со всей платформой E5_C. Данный инструмент помогает визуализировать и отслеживать процесс в виде диаграмм или системных журналов на внешнем устройстве с операционной системой Windows.
LCD display
ЖК-дисплей «JUMBO» для лучшей видимости
Вывод относительных значений PV/SV на крупнейший в своем классе дисплей на глобальном рынке* с непревзойденной видимостью и контрастностью. Даже в сложных условиях наружного освещения E5_C может читаться с большого расстояния. Благодаря современному эргономичному дизайну (награда IF за дизайн) E5_C можно органично встроить в любую панель управления. Дополнительную информацию о выполняемой программе и операционном сегменте можно посмотреть в кратком обзоре.
Easy Set-up
Быстрый ввод машин в эксплуатацию
Контроллеры серии E5_C легко подключаются, настраиваются за несколько шагов с использованием 5 передних кнопок. Программное обеспечение CX-Thermo и помощник навигации позволяют очень быстро задавать параметры, легко настраивать устройство и без затруднений его обслуживать.
Precise control
Положитесь на наш запатентованный 2-ПИД
На протяжении многих лет наша цель заключалась в том, чтобы обеспечить наивысшую эффективность в управлении температурой. Помимо запатентованного алгоритма 2-ПИД-регулирования, встроенного практически в каждый контроллер Omron, аналогичную программу можно найти в семействе программного устройства “T”. В сочетании с уникальным быстродействием в 50 мс и разрешению в 0,1 °C, E5_C-T является лучшим средством для экономии времени с точки зрения быстрой реакции на возмущения и поддержания высокой точности для регулировки температуры. Конструкция машин непрерывно изменяется с учетом требований к высокой скорости работы, поэтому наши контроллеры уже адаптированы к современным тенденциям.
Useful functions
Аварийные сигналы
-Стандартные аварийные сигналы
- Можно задать аварийный сигнал для случаев, когда отклонение, параметр процесса, заданное значение или регулируемое значение достигает указанного значения.
- Также можно задать аварийные сигналы для скорости изменения PV и перегорания контура.
- При необходимости, можно добиться более лучшего функционирования аварийного сигнала, установив резервную последовательность, гистерезис аварийного сигнала, дополнительное закрытие/открытие в аварийном сигнале, защелкивание аварийного сигнала, задержку включения аварийного сигнала и задержку выключения аварийного сигнала.
-Аварийные сигналы HB и HS
- В моделях, оборудованных дополнительными аварийными сигналами HB и HS, вы можете обнаружить аварийные сигналы перегорания и короткого замыкания нагревательного элемента, основанные на входах CT.
-Встроенный аварийный сигнал
- Вы можете задать встроенный аварийный сигнал при включении стандартного аварийного сигнала, аварийного сигнала HB или аварийного сигнала HS.
Входы событий
В моделях, поддерживающих входы событий, можно использовать внешний контакт или входы транзисторов для выполнения любой из следующих функцийконтроля:
- Изменение программ (количество изменяемых программ, макс. 8), переключение между состоянием запуска и сброса, переключение между автоматическим и ручным режимом работы, изменение работы в прямом/обратном направлении, переключение между программой SP и фиксированной SP, выполнение/отмена 100% AT, выполнение/отмена 40% AT, выполнение/отмена 100% AT для всех настроек ПИД, выполнение/отмена 40% AT для всех настроек ПИД, изменение настроек разрешение/запрет, запись модулей связи разрешение/запрет, отмена защелкивания аварийного сигнала, удержание/отмена удержания, повышение и ожидание разрешение/запрет.
Коммуникационные функции
- В любых моделях E5_C-T, поддерживающих коммуникации, можно использовать CompoWay/F, Modbus-RTU *1, не требующие программирования, и компонентные коммуникации. Дополнительно поддерживаются протоколы TCP Profibus, Profinet и Modbus.
*1 Modbus является зарегистрированным торговым знаком Schneider Electric.
Выход передачи данных
- В любой модели с выходом передачи данных можно задать установить заданное выходное значение, значение процесса, регулируемое значение или другие значения, например, выход передачи данных от 4 до 20 мА или от 1 до 5 В.
-Модели программы: Программы: макс. 8 моделей, Сегменты: макс. 32 на каждую программу
- Первоначальное заданное значение программы: Сегмент 0, заданное значение, текущее значение (PV) или фиксированная SP
- Время начала программы: Можно задать резервный режим (задержку).
- Также возможно повторение и компоновка программ.
-Управление программой
- Запуск (программа начала работу)/Сброс (программа прекратила работу)
- Выдержка сегмента
- Ожидание перехода к следующему сегменту
- Переход к сегментам ключевой программой
-Выходы состояния программы
- Сигналы времени
- Сигнализация о состоянии работы
- Сигнализация об окончании программы
- Выходы этапов (одноимпульсный выход в начале каждого сегмента)
-Регулировка констант ПИД
- Вы можете с легкостью задавать оптимальные константы ПИД для текущей настройки ПИД или для всех настроек ПИД, задействуя AT (автонастройку) с помощью метода ограниченного цикла.
- Вы также можете задать RT (настройку запаздывания), чтобы установить приоритет стабильности управления.
Источник
Предписание
В этом руководстве описаны функции, рабочие параметры и области применения для оптимального использования продукта. Пожалуйста, соблюдайте следующие правила при использовании этого продукта:
• Этот продукт предназначен для использования только квалифицированным персоналом, знакомым с электрическими системами.
• Внимательно прочтите и усвойте содержание данного руководства перед использованием оборудования, чтобы обеспечить правильную работу оборудования.
Типы подключаемых датчиков и входов
Примечание:
- Значение по умолчанию: 5.
- S.ERR отображается, если при подключении платинового термометра сопротивления
соответствующим образом не будет настроен тип входа. Для снятия отображения S.ERR необходимо правильно выполнить подсоединения при этом выключить и снова включить
питание.
Программирование и настройка прибора
Список возможных ошибок
В случае возникновения ошибки на дисплее № 1 отображается код ошибки.
Примите необходимые меры в соответствии с кодом ошибки, руководствуясь таблицей ниже.
Примечание:
Если входной сигнал находится в пределах диапазона регулирования, но выходит за диапазон отображения значений на дисплее (-1999…9999), на дисплее отобразится [[[[, если значение меньше -1999, и ]]]], если значение больше 9999. При такой индикации выходы управления и сигнализации аварий работают в своем обычном режиме.
*2: Ошибка отображается только в режиме «Значение процесса / Уставка».
В других режимах ошибка не отображаются.
Схема подключения прибора
Внимание!
Выход напряжения (выход управления срабатыванием твердотельного реле) не изолирован гальванически от внутренних цепей. При использовании заземленной термопары не подключайте к земле какие-либо управляющие выходные клеммы. Если клеммы выхода управления подключен к земле, измеренные значения температуры будут неправильными из-за тока утечки.
Скачать полную документацию.
RU
Digital Temperature Controller (Simple Type) (48 × 96 mm)
48 × 96 mm. Large White PV Display That’s Easier to Read. Easy to Use, from Model Selection to Setup and Operation. A Complete Range of I/O Capacities, Functions, and Performance. Handles More Applications.
- Features
- Lineup
- Specifications
- Dimensions
- Catalog / Manual / CAD / Software
last update: October 2, 2017
Model Number Legend
Models with Screw Terminals
E5EC-800 48 × 96 mm
Control output 1 | Control output 2 |
Auxiliary output |
Commu- nications |
Heater burnout |
Event inputs |
Power supply voltage |
Model |
---|---|---|---|---|---|---|---|
Relay output | — | Two | — | — | — | 100 to 240 VAC |
E5EC-RX2ASM-800 |
Voltage output | — | E5EC-QX2ASM-800 | |||||
Linear current output | — | E5EC-CX2ASM-800 | |||||
Relay output | Relay output | E5EC-RR2ASM-800 | |||||
Voltage output | Relay output | E5EC-QR2ASM-800 | |||||
Linear current output | Relay output | E5EC-CR2ASM-800 | |||||
Relay output | — | 24 VAC/ VDC |
E5EC-RX2DSM-800 | ||||
Voltage output | — | E5EC-QX2DSM-800 | |||||
Linear current output | — | E5EC-CX2DSM-800 | |||||
Relay output | Relay output | E5EC-RR2DSM-800 | |||||
Voltage output | Relay output | E5EC-QR2DSM-800 | |||||
Linear current output | Relay output | E5EC-CR2DSM-800 | |||||
Relay output | Relay output | RS-485 | One | Two | 100 to 240 VAC |
E5EC-RR2ASM-808 | |
Voltage output | Relay output | E5EC-QR2ASM-808 | |||||
Relay output | Relay output | 24 VAC/ VDC |
E5EC-RR2DSM-808 | ||||
Voltage output | Relay output | E5EC-QR2DSM-808 | |||||
Relay output | Relay output | — | Four | 100 to 240 VAC |
E5EC-RR2ASM-810 | ||
Voltage output | Relay output | E5EC-QR2ASM-810 | |||||
Relay output | Relay output | 24 VAC/ VDC |
E5EC-RR2DSM-810 | ||||
Voltage output | Relay output | E5EC-QR2DSM-810 | |||||
Linear current output | Relay output | RS-485 | — | Two | 100 to 240 VAC |
E5EC-CR2ASM-804 | |
Linear current output | Relay output | 24 VAC/ VDC |
E5EC-CR2DSM-804 | ||||
Relay output (Open) * | Relay output (Close) * |
— | — | — | — | 100 to 240 VAC |
E5EC-PR0ASM-800 |
Relay output (Open) * | Relay output (Close) * |
Two | E5EC-PR2ASM-800 | ||||
Relay output (Open) * | Relay output (Close) * |
RS-485 | Two | E5EC-PR2ASM-804 |
* Position proportional control model.
Note: Draw-out-type models of the E5EC-800 are available. Ask your OMRON representative for details.
Heating and Cooling Control
Using Heating and Cooling Control
(1) Control Output Assignment
If there is no control output 2, an auxiliary output is used as the cooling control output.
If there is a control output 2, the two control outputs are used for heating and cooling.
(It does not matter which output is used for heating and which output is used for cooling.)
(2) Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.
Optional Products (Order Separately)
Terminal Covers
Waterproof Packing
Note: This Waterproof Packing is provided with the Digital Temperature Controller.
Waterproof Cover
Front Port Cover
Note: This Front Port Cover is provided with the Digital Temperature Controller.
Mounting Adapter
Model |
---|
Y92F-51 (Two Adapters are included.) |
Note: This Mounting Adapter is provided with the Digital Temperature Controller.
Current Transformers (CTs)
Hole diameter | Model |
---|---|
5.8 mm | E54-CT1 |
5.8 mm | E54-CT1L * |
12.0 mm | E54-CT3 |
12.0 mm | E54-CT3L * |
* Lead wires are included with these CTs. If UL certification is required, use these CTs.
last update: October 2, 2017
Терморегуляторы Omron E5CC и E5EC — многофункциональные регуляторы температуры Омрон!
Техническая документация Omron E5CC, E5EC (PDF, 74 страницы, 23.6 Мб)
Новейшие регуляторы температуры Omron E5CC и E5EC задают новые стандарты качества регулирования и удобства эксплуатации. Обладая великолепными характеристиками, новые терморегуляторы Омрон имеют великолепные характеристики, они удобны и понятны в настройках и имеют безупречный внешний вид. Отличный сверх четкий жидкокристаллический дисплей символы на котором читаются под большим углом обзора с большого расстояния. Время дискретизации составляет всего 50 мс. Для настройки контроллера температуры вы можете использовать так же ПО CX-Thermo. Пользователь имеет возможность настраивать термоконтроллер без источника питания. Регулятор температуры Omron E5EC и E5CC обладают набором важных функций, среди которых функции ПИД нагрева и охлаждения, функция таймера, а так же функция линейного роста до заданного уровня. Значительно расширены возможности ручного ввода и усовершенствован режим сигнализации. В регуляторе температуры предусмотрен выход для передачи данных, вход по событию и вспомогательный выход, а так же присутствуют функции удаленного ввода уровней. Благодаря специальным алгоритмам автоподстройки значительно упрощена процедура настройки терморегуляторов. Благодаря этим новшествам пользователь сможет значительно быстрее задать параметры и значительно сократить время настройки. Вы можете использовать кнопку переключения регистра, которая находится на передней панели с помощью которой вы быстро настроите установленные значения. Так же вы можете связать с этой кнопкой такие функции как Автонастройка (Auto- Tuning) и Пуск/Стоп (RUN/STOP).
E5CC (48 x 48 mm) Screw terminals
Control Output | Option no | Option description | Alarm outputs | Order code | |
---|---|---|---|---|---|
100 to 240 VAC | 24 VAC/DC | ||||
Out1: Relay Out2: non |
000 | No option | 3 | E5CC-RX3A5M-000 | E5CC-RX3D5M-000 |
001 | HB/HS alarm for 1-phase heaters, 2 EV inputs | 3 | E5CC-RX3A5M-001 | E5CC-RX3D5M-001 | |
003 | HB/HS alarm for 3-phase heaters, RS485 | 3 | E5CC-RX3A5M-003 | E5CC-RX3D5M-003 | |
006 | 2 EV inputs, transfer output | 3 | E5CC-RX3A5M-006 | E5CC-RX3D5M-006 | |
007 | 2 EV inputs, remote SP | 3 | E5CC-RX3A5M-007 | E5CC-RX3D5M-007 | |
Out1: Voltage (pulse) Out2: non |
000 | No option | 3 | E5CC-QX3A5M-000 | E5CC-QX3D5M-000 |
001 | HB/HS alarm for 1-phase heaters, 2 EV inputs | 3 | E5CC-QX3A5M-001 | E5CC-QX3D5M-001 | |
003 | HB/HS alarm for 3-phase heaters, RS485 | 3 | E5CC-QX3A5M-003 | E5CC-QX3D5M-003 | |
006 | 2 EV inputs, transfer output | 3 | E5CC-QX3A5M-006 | E5CC-QX3D5M-006 | |
007 | 2 EV inputs, remote SP | 3 | E5CC-QX3A5M-007 | E5CC-QX3D5M-007 | |
Out1: Linear current Out2: non |
000 | No option | 3 | E5CC-CX3A5M-000 | E5CC-CX3D5M-000 |
004 | RS485, 2 EV inputs | 3 | E5CC-CX3A5M-004 | E5CC-CX3D5M-004 | |
006 | 2 EV inputs, transfer output | 3 | E5CC-CX3A5M-006 | E5CC-CX3D5M-006 | |
007 | 2 EV inputs, remote SP | 3 | E5CC-CX3A5M-007 | E5CC-CX3D5M-007 |
E5CC (48 x 48 mm) Push-in plus terminals
Control Output | Option no | Option description | Alarm outputs | Order code | |
---|---|---|---|---|---|
100 to 240 VAC | 24 VAC/DC | ||||
Out1: Relay Out2: non |
0 | No option | 2 | E5CC-RX2ABM-000 | E5CC-RX2DBM-000 |
1 | HB/HS alarm for 1-phase heaters, 2 EV inputs | 2 | E5CC-RX2ABM-001 | E5CC-RX2DBM-001 | |
2 | HB/HS alarm for 1-phase heaters, RS485 | 2 | E5CC-RX2ABM-002 | E5CC-RX2DBM-002 | |
4 | RS485, 2 EV inputs | 2 | E5CC-RX2ABM-004 | E5CC-RX2DBM-004 | |
6 | 2 EV inputs, Tranfer output | 2 | E5CC-RX2ABM-006 | E5CC-RX2DBM-006 | |
Out1: Voltage (pulse) Out2: non |
0 | No option | 2 | E5CC-QX2ABM-000 | E5CC-QX2DBM-000 |
1 | HB/HS alarm for 1-phase heaters, 2 EV inputs | 2 | E5CC-QX2ABM-001 | E5CC-QX2DBM-001 | |
2 | HB/HS alarm for 1-phase heaters, RS485 | 2 | E5CC-QX2ABM-002 | E5CC-QX2DBM-002 | |
4 | RS485, 2 EV inputs | 2 | E5CC-QX2ABM-004 | E5CC-QX2DBM-004 | |
6 | 2 EV inputs, Tranfer output | 2 | E5CC-QX2ABM-006 | E5CC-QX2DBM-006 |
E5EC (48 x 96 mm)/E5AC (96 x 96 mm) Screw terminals
Control Output | Option no | Option description | Alarm outputs | Order code | |
---|---|---|---|---|---|
100 to 240 VAC | 24 VAC/DC | ||||
Out1: Relay Out2: non |
000 | No option | 4 | E5_C-RX4A5M-000 | E5_C-RX4D5M-000 |
009 | HB/HS alarm for 3-phase heaters, RS485, 2 EV inputs | 4 | E5_C-RX4A5M-009 | E5_C-RX4D5M-009 | |
010 | HB/HS alarm for 1-phase heaters, 4 EV inputs | 4 | E5_C-RX4A5M-010 | E5_C-RX4D5M-010 | |
011 | HB/HS alarm for 1-phase heaters, 6 EV inputs, remote SP, transfer output | 4 | E5_C-RX4A5M-011 | E5_C-RX4D5M-011 | |
Out1: Voltage (pulse) Out2: non |
000 | No option | 4 | E5_C-QX4A5M-000 | E5_C-QX4D5M-000 |
009 | HB/HS alarm for 3-phase heaters, RS485, 2 EV inputs | 4 | E5_C-QX4A5M-009 | E5_C-QX4D5M-009 | |
010 | HB/HS alarm for 1-phase heaters, 4 EV inputs | 4 | E5_C-QX4A5M-010 | E5_C-QX4D5M-010 | |
011 | HB/HS alarm for 1-phase heaters, 6 EV inputs, remote SP, transfer output | 4 | E5_C-QX4A5M-011 | E5_C-QX4D5M-011 | |
Out1: Linear current Out2: non |
000 | No option | 4 | E5_C-CX4A5M-000 | E5_C-CX4D5M-000 |
004 | 2 EV inputs, RS485 | 4 | E5_C-CX4A5M-004 | E5_C-CX4D5M-004 | |
014 | RS485, 4 EV inputs, remote SP, transfer output | 4 | E5_C-CX4A5M-014 | E5_C-CX4D5M-014 | |
Out1: Relay Out2: Relay Positional proportional control model |
000 | No option | 4 | E5_C-PR4A5M-000 | E5_C-PR4D5M-000 |
004 | 2 EV inputs, RS485 | 4 | E5_C-PR4A5M-004 | E5_C-PR4D5M-004 | |
014 | RS485, 4 EV inputs, remote SP, transfer output | 4 | E5_C-PR4A5M-014 | E5_C-PR4D5M-014 |
E5EC (48x96mm) Push-in plus terminals
Control Output | Option no | Option description | Alarm outputs | Order code | |
---|---|---|---|---|---|
100 to 240 VAC | 24 VAC/DC | ||||
Out1: Relay Out2: non |
0 | No option | 4 | E5EC-RX4ABM-000 | E5EC-RX4DBM-000 |
8 | HB/HS alarm for 1-phase heaters, RS485, 2 EV inputs | 4 | E5EC-RX4ABM-008 | E5EC-RX4DBM-008 | |
10 | HB/HS alarm for 1-phase heaters, 4 EV inputs | 4 | E5EC-RX4ABM-010 | E5EC-RX4DBM-010 | |
11 | HB/HS alarm for 1-phase heaters, 6 EV inputs, remote SP, transfer output | 4 | E5EC-RX4ABM-011 | E5EC-RX4DBM-011 | |
Out1: Voltage (pulse) Out2: non |
0 | No option | 4 | E5EC-QX4ABM-000 | E5EC-QX4DBM-000 |
8 | HB/HS alarm for 1-phase heaters, RS485, 2 EV inputs | 4 | E5EC-QX4ABM-008 | E5EC-QX4DBM-008 | |
10 | HB/HS alarm for 1-phase heaters, 4 EV inputs | 4 | E5EC-QX4ABM-010 | E5EC-QX4DBM-010 | |
11 | HB/HS alarm for 1-phase heaters, 6 EV inputs, remote SP, transfer output | 4 | E5EC-QX4ABM-011 | E5EC-QX4DBM-011 |
E5CC/E5EC/E5AC
Item | E5CC | E5EC | E5AC |
---|---|---|---|
Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC |
||
Operating voltage range | 85% to 110% of rated supply voltage | ||
Power consumption | 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC |
8.3 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC |
9.0 VA max. at 100 to 240 VAC, and 5.6 VA max. at 24 VAC or 3.4 W max. at 24 VDC |
Sensor input |
|
||
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) |
||
Control method | ON/OFF control or 2-PID control (with auto-tuning) | ||
Indication accuracy | Thermocouple input: (±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max. Platinum resistance thermometer input: (±0.2% of indicated value or ±0.8°C, whichever is greater) ±1 digit max. Analog input: ±0.2% FS ±1 digit max. CT input: ±5% FS ±1 digit max. |
Thermocouple input: (±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max. Platinum resistance thermometer input: (±0.2% of indicated value or ±0.8°C, whichever is greater) ±1 digit max. Analog input: ±0.2% FS ±1 digit max. CT input: ±5% FS ±1 digit max. Potentiometer input: ±5% FS ±1 digit max. |
|
Auto-Tuning | Yes, 40%/100% MV output limit selection. When using Heat/Cool: Automatic cool gain adjustment | ||
Self-Tuning | Yes | ||
Control outputs | Relay output | SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
Voltage output (for driving SSR) | Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit | Output voltage: 12 VDC ±20% (PNP), max. load current: 40 mA, with short-circuit protection circuit (The maximum load current is 21 mA for models with two control outputs.) |
|
Linear current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | ||
Auxiliary outputs | Number of outputs | 2,3 | 4 |
Output specifications | N.O. relay outputs, 250 VAC, Models with 3 outputs: 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
N.O. relay outputs, 250 VAC, Models with 4 outputs: 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
|
Event inputs | Number of inputs | 2 or 4 or 6 max (depends on the model) | |
External contact input specifications | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | ||
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | |||
Current flow: approx. 7 mA per contact | |||
Setting method | Digital setting using front panel keys or via Remote Software CX-Thermo V4.5 | ||
Indication method | 11-segment digital display and individual indicators | ||
Multi SP | Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or serial communications. | ||
Other functions | Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection (including SSR failure detection), 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, extraction of square root, MV change rate limit, logic operations, PV/SV status display, simple program, automatic cooling coefficient adjustment | ||
Ambient operating temperature | -10 to 55°C (with no condensation or icing) | ||
Ambient operating humidity | 25% to 85% | ||
Storage temperature | -25 to 65°C (with no condensation or icing) | ||
Degree of protection | Front panel: IP66, Rear case: IP20, Terminals: IP00 | ||
Sampling period | 50 ms | ||
Size in mm (HxWxD) | 48x48x64 | 48x96x64 | 96x96x64 |