INSTRUCTION MANUAL

NT935

1MN0102 REV. 0

operates with ISO9001 certified quality system

R. 1.6 15/03/17

ENGLISH

«Translations of the original instructions»

loading

Related Manuals for TECSYSTEM NT935

Summary of Contents for TECSYSTEM NT935

  • Page 1
    INSTRUCTION MANUAL NT935 1MN0102 REV. 0 operates with ISO9001 certified quality system R. 1.6 15/03/17 ENGLISH “Translations of the original instructions”…
  • Page 2: Table Of Contents

    INTRODUCTION First of all we wish to thank you for choosing to use a TECSYSTEM product and recommend you read this instruction manual carefully: You will understand the use of the equipment and therefore be able to take advantage of all its functions.

  • Page 3
    11) TECHNICAL SPECIFICATIONS OF THE EXTENSION — ………………………………….. CABLE FOR Pt100 ………………………………….. 12) FCD FUNCTION — ………………………………….. 13) WARRANTY CONDITIONS ………………………………….. 14) TROUBLESHOOTING — ………………………………….. 15) EQUIPMENT DISPOSAL — ………………………………….. 16) USEFUL CONTACTS ………………………………….. 17) UL SPECIFICATION AND RATINGS NT935 SERIES…
  • Page 4: Safety Requirements

    POWER SUPPLY The NT935 series control unit has UNIVERSAL power supply, i.e. it can be supplied at 24 to 240 Vac-Vdc, irrespectively of polarity in Vdc. Before use, ensure that the power cable is not damaged, knotted or pinched. Do not tamper with the power cable.

  • Page 5: Accessories

    1 RS485 terminal 3 poles pitch 3.81 (*) Code: 2PL0366 — Screws tightening torque 0.25Nm (*) only for NT935 AD version ATTENTION: always install the device using the terminals included in the pack. The use of terminals other than those included with the control unit might cause malfunctions.

  • Page 6: Technical Specifications

    NT935 BASIC NT935 AD TECHNICAL SPECIFICATIONS POWER SUPPLY 24-240 Vac-Vdc 24-240 Vac-Vdc Supply rated values 50/60HZ 50/60HZ 20-270 Vac-Vdc 20-270 Vac-Vdc Maximum and minimum supply values 50/60HZ 50/60HZ ● ● Vdc with reversible polarities INPUTS ● ● 4 inputs for RTD sensors, Pt100 type with 3 wires (max section 1.5mm²) ●…

  • Page 7
    TECHNICAL SPECIFICATIONS NT935 BASIC NT935 AD ● ● Housing NORYL 94 _V0 ● ● Absorption 7,5VA ● ● Data memory 10 years minimum ● ● Digital linearity of sensor signal ● ● Self-diagnostic circuit Protection treatment of the electronic part…
  • Page 8: Front Panel

    FAN 1 (yellow) LED T-max mode selection (red) LED FAN 2 (yellow) LED Man mode selection (yellow) LED Display mode selection key Auto mode selection (green) LED Fixing block Scan mode selection (yellow) LED UP key Fixing block DOWN key NT935 ASERIES…

  • Page 9: Display

    The first display is dedicated to temperatures The second display to the monitored channel. When switching the device ON or following a reset, the display shows the NT935 control unit model : BAS (no option) or AD, VER «00» (firmware version) and temperature range.

  • Page 10: Mounting

    Drill a 92 x 92 mm hole in the panel sheet. 1MN0007 REV. 0 Control unit Panel hole dimensions (+0.8mm tolerance) Identification label Fix the unit securely with the blocks supplied. 1MN0008 REV. 0 Control unit Fixing screw Fixing block Crosshead screwdriver #1X100mm NT935 ASERIES…

  • Page 11: Electrical Connections Nt935 Basic

    ELECTRICAL CONNECTIONS NT935 BASIC Pt100 sensors (white-red-red) Relays (FAN2-FAN1-ALARM-TRIP-FAULT) Supply 24-240Vac-dc 50/60Hz. Note: relay contact image in non-alarm condition, with the exception of the FAULT relay that opens: contacts 11-12 open (NO) contacts 11-12 closed (NC) fault condition identification. Read the Alarms and Ventilation paragraph on page 13 3 and see the opening of the fault contact.

  • Page 12
    ELECTRICAL CONNECTIONS NT935 AD Pt100 sensors (white-red-red) Relays (FAN2-FAN1-ALARM-TRIP-FAULT) Supply 24-240Vac-dc 50/60Hz. Output 4.20 mA Modbus RTU RS485 output Note: relay contact image in non-alarm condition, with the exception of the FAULT relay that opens: contacts 11-12 open (NO) contacts 11-12 closed (NC) fault condition identification. Read the Alarms and Ventilation paragraph on page 13 and see the opening of the fault contact.
  • Page 13: Power Supply

    POWER SUPPLY The NT935 control unit has UNIVERSAL power supply, i.e. it can be supplied by 24 to 240 Vac-Vdc, 50/60Hz irrespectively of polarity in Vdc (terminals 40-42). This is obtained thanks to the use of a tested power supply unit, newly designed and manufactured, that frees installers from worrying about the correct Vac and Vdc supply.

  • Page 14: Programming

    PROGRAMMING NT935 BASIC/AD STEP PRESS EFFECT PRESS NOTES Keep the PRG key pressed until the display shows PRG Select PRG SET for entering in the programming mode or PRG 1 default value PRG 1 to restore the default programmed value.

  • Page 15: Nt935

    Default NO Set YES or NO The display shows FLS (FAULT) LED flashes FAULT Set YES or NO Default YES For NT935 (BAS) version jumps to step 45 Modbus address ADR <> «datum» is displayed Default 001 Set the address…

  • Page 16: Programming Notes

    / electrical fault of the Pt100 sensors c) damage to the Pt100 inputs of the control unit. TECSYSTEM S.r.l. has designed its own special cable to transfer the measurement signals, CEI-compliant, with all the protection requirements provided for: model CT-ES…

  • Page 17: Temperature Sensor Diagnostics

    CAL message display: it appears when damage is found in the measurement circuit. The temperature values displayed might be incorrect. Return the control unit to TECSYSTEM for repairs. VOTING FUNCTION The voting function derives from the redundancy concept that consists in duplicating the components of a system to increase their reliability.

  • Page 18: Cooling Fan Control

    COOLING FAN CONTROL The NT935 control unit is fitted with two FAN controls (FAN1 and FAN2) and, if programmed correctly, can control the fans switching ON and OFF to cool the transformer. The FAN1 and FAN2 contacts can manage cooling the transformer and the room where it is installed.

  • Page 19
    The NT935 AD control unit is in communication with the network only when it is in temperature reading mode, while it is inactive when in the following modes: display, programming and relay test.
  • Page 20
    Trip thresholds and that the Fan-on thresholds must be higher than the Fan-off thresholds. If you try to set these thresholds wrongly, the NT935 monitoring unit won’t proceed with programming and data storage; therefore in the following readings you will read the data relevant to the previous programming.
  • Page 21
    In the case in which all the fans are turned off (F1, F2) the test of the relay will not take place. UNACCEPTABLE DATA Some programming is unacceptable since the NT935 AD does not provide for it; these data are discarded with no EXCEPTION CODE.
  • Page 22
    HFN (Fan test) 0=No test 1÷200h temperature 0=No FCD increment 1÷30°/sec 0=No Voting Voting 1=YES CPU Setting See Note CPU Error See Note See Note Relays Status reference 0=hot 420 mA channel channel for 4.20 1÷4= ch1÷4 5=scan NT935 ASERIES…
  • Page 23
    1°C÷200°C (*) 2’compl. Ch2 temper. 1°C ÷ 240°C 2’compl. sign As (TRP) trip set point 1°C÷200°C (*) –10°C ÷ 240°C 2’compl. sign 2’compl. Ch3 temper. –48°C÷200°C (*) 0°C ÷ 240°C 2’compl. sign 2’compl. Ch3 max temperat. 0°C÷200°C (*) NT935 SERIES…
  • Page 24
    2’compl. Ch4 max temperat. 0°C÷200°C (*) 2’compl. Ch4 temper. 1°C ÷ 240°C 2’compl. sign alarm set point 1°C÷200°C (*) 2’compl. Ch4 temper. 1°C ÷ 240°C 2’compl. sign trip set point 1°C÷200°C (*) (*) for version –40°C ÷ +200°C NT935 ASERIES…
  • Page 25
    Data HI Data LO Note 1 Note 2 (10) read/write Ch1 story Ch1 status See Note CHx Ch2 story Ch2 status See Note CHx Ch3 story Ch3 status See Note CHx Ch4 story Ch4 status See Note CHx NT935 SERIES…
  • Page 26
    BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 PT ERROR FCD Fault CPU SETTING BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 Failsafe Failsafe fault Failsafe trip alarm NT935 ASERIES…
  • Page 27
    FAIL SAFE FUNCTION The NT935 has n.o selection (contact open ) / n.c (normally closed contact) for ALARM, TRIP and FAULT relays, programming steps 30 to 35 page 15. The selection of the setting YES/NO introduces functions Fail Safe and No Fail Safe.
  • Page 28
    FCD function from activating during motor startup, or where the ΔT/sec. increase varies quickly. (*) The ΔT value shows the temperature range for each second. NOTE: you should not enable the FCD function with active VOTING. NT935 ASERIES…
  • Page 29
    Returning used electrical devices: contact TECSYSTEM or your TECSYSTEM agent for information on the correct disposal of the devices. TECSYSTEM is aware of the impact its products have on the environment and asks its customers active support in the correct and environmentally-friendly disposal of its devices.
  • Page 30
    5 relay Output: 10A 250Vac-res COS=1 OUTPUTS RELAYS OPTIONAL PORTS (AD) RS485 + 4.20mA Suitable for use on a flat surface of a type 1 enclosure if Back panel is provided with two short fixing screws tightening torque : 0.57Nm NT935 ASERIES…

File Specifications:

883/883909-nt935.pdf file (03 Sep 2023)

Accompanying Data:

TECSYSTEM NT935 Controller, Control Systems PDF Instruction Manual (Updated: Sunday 3rd of September 2023 09:31:06 AM)

Rating: 4.9 (rated by 15 users)

Compatible devices: NT935 WS, T154-4, T2612, T119 DIN, NT311 ETH, T154 Series, NT579, NT511Series.

Recommended Documentation:

Instruction Manual (Text Version):

(Ocr-Read Summary of Contents of some pages of the TECSYSTEM NT935 Document (Main Content), UPD: 03 September 2023)

  • 5, 5 NT935 SERIES Tthe following object are present inside the box : Control unit Start guide and QR code 2 blocks for panel mounting 1 supply terminal 3 poles pitch 5 Code: 2PL0367 — Screws tightening torque 0.5Nm 1 relay terminal 12 poles pitch 5 Code: 2PL0361- Screws tightening torque 0.5Nm 1 Pt100 sensor terminal 12 poles pitch 3.81 Code: 2PL0420 — Screws tightening torque 0.25Nm …

  • 9, 9 NT935 SERIES DISPLAY The first display is dedicated to temperatures The second display to the monitored channel. When switching the device ON or following a reset, the display shows the NT935 control unit model : BAS (no option) or AD, VER «00» (firmware version) and temperature range. Pressing the MODE key, the display modes can be set: SCAN: the monitoring unit displays all the activated (°C) and deactivated (NO) channels scanni…

  • 20, 20 NT935 ASERIES FUNCTION CODE The ModBus module supports the following function codes: 3 (10) : — holding register reading 16 (10) : — register multiple writing If ModBus receives a message and a CRC error is detected, no answer is given. CODE 3 (10) . Request: Slave address, code 3 (10) , St…

  • 29, TECSYSTEM NT935 29 NT935 SERIES TROUBLESHOOTING CAUSES AND SOLUTIONS The control unit does not switch on and the supply to terminals 40-42 is correct. Check that: the …

  • 3, 3 NT935 SERIES PAGE 8) RS485 MODBUS ………………………………….. 19 INTRODUCTION TO THE MODBUS INSIDE MODULE ………………………………….. — OPERATING NOTES ………………………………….. — DATA TRANSMISSION ON MODBUS NETWORK ………………………………….. — RS485 ELECTRICAL CONNECTIONS ……………�…

  • 25, 25 NT935 SERIES Address LO (10) Data HI Data LO Note 1 Note 2 R: read W:write RW: read/write 57 00 Ch1 Setting See Note CHx RW 58 00 Ch2 Setting See Note CHx RW 59 00 Ch3 Setting See Note CHx RW 60 00 Ch4 Setting See Note CHx RW 61 00 00 — R 62 00 00 — R 63 00 00 —…

  • 12, 12 NT935 ASERIES NT935 AD 1) Pt100 sensors (white-red-red) 3) Relays (FAN2-FAN1-ALARM-TRIP-FAULT) 2) Supply 24-240Vac-dc 50/60Hz. 4) Output 4.20 mA 5) Modbus RTU RS485 output SCREEN RED RED WHITE ELECTRICAL CONNECTIONS 5 …

  • 26, 26 NT935 ASERIES INFO various causes (READ) BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 — — — — — — — (*) RESET (R) has taken place COMMANDS (WRITE) BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 — — — — — (*) Reset CPU_Error (*) Reset historical data (*) Zero. BIT: RESET has taken place …

  • 6, TECSYSTEM NT935 6 NT935 ASERIES TECHNICAL SPECIFICATIONS NT935 BASIC NT935 AD POWER SUPPLY Supply rated values 24-240 Vac-Vdc 50/60HZ 24-240 Vac-Vdc 50/60HZ Maximum and minimum supply values 20-270 Vac-Vdc 50/60HZ 20-270 Vac-Vdc 50/60HZ Vdc with reversible polarities ● ● INPUTS 4 inputs for RTD sensors, Pt100 type with 3 wires (max section 1.5mm²) ● ● Connections on removable terminal …

  • 22, 22 NT935 ASERIES MODBUS MAPPING TABLE HEADER (information and commands): Address LO (10) Data HI Data LO R: read W:write RW: read/write 1 Modello – MSD (ASCII) Modello — 3° Digit (ASCII) R 2 Modello — 2° Digit (ASCII) Modello – LSD (ASCII) R 3 Space (20H) Vers. Fw – MSD(ASCII) R 4 Vers. Fw — 2° Digit (ASCII) Vers. Fw – LSD(ASCII) R 5 Channels qty (2*ASCII) R 6 Op…

  • 28, 28 NT935 ASERIES FCD FUNCTION FCD FUNCTION FCD FUNCTION The NT series equipment boasts an innovative control function combined with the dynamic status of the Pt100 sensor. Activating FCD, the control unit analyses the increase in temperature ∆T (*) recorded in a second (°C/sec). Enabling the function, the user can select the value (∆T) from a minimum of 1°C/sec to a maximum of 30°C/ sec. If the value sensed is higher than the value set by the user, the cont…

  • 2, 2 NT935 ASERIES PAGE 1) SAFETY REQUIREMENTS ………………………………………… 4 2) ACCESSORIES ………………………………….. 5 3) TECHNICAL SPECIFICATIONS ………………………………….. 6 4) FRONT PANEL ………………………………….. 8 DISPLAY ………………………………….. 9 OPERATING PROGRAM CONTROL …………………………�…

  • 24, 24 NT935 ASERIES 35 2’compl. sign 2’compl. Ch3 temper. alarm set point 1°C ÷ 240°C 1°C÷200°C (*) As (AL) R 36 2’compl. sign 2’compl. Ch3 temper. trip set point 1°C ÷ 240°C 1°C÷200°C (*) As (TRP) R 37 2’compl. sign 2’compl. Ch4 temper. –10°C ÷ 240°C –48°C÷200°C…

  • 17, 17 NT935 SERIES NOTE: the use of cables not complying with the above might cause reading anomalies. It is always important to take into account that any interference on the signal lines might cause anomalies on the Pt100 inputs (CH1- CH2-CH3-CH4…) or on the sensors themselves. TEMPERATURE SENSOR DIAGNOSTICS …

  • 21, 21 NT935 SERIES ERROR CODES (exception codes) In case of a wrong request, ModBus will answer with modified codes and codified errors according to the following: 1: — Unsupported function code 2: — Wrong data address 3: — Wrong data (for …

  • 4, TECSYSTEM NT935 4 NT935 ASERIES SAFETY REQUIREMENTS ATTENTION : Carefully read the manual before starting using the control unit. Keep the instructions for future reference. Do not open the device, touching any int…

  • TECSYSTEM NT935 User Manual

  • TECSYSTEM NT935 User Guide

  • TECSYSTEM NT935 PDF Manual

  • TECSYSTEM NT935 Owner’s Manuals

Recommended: SC-72, PR3010, MF8100 Series, MonoMixer 200 B, EG3500X

Links & Tools

Operating Impressions, Questions and Answers:

Table of Contents for TECSYSTEM NT935:

  • 17 NT935 SERIES NOTE: the use of cables not complying with the above might cause reading anomalies. It is always important to take into account that any interference on the signal lines might cause anomalies on the Pt100 inputs (CH1- CH2-CH3-CH4…) or on the sensors themselves. TEMPERATURE SENSOR DIAGNOSTICS In case of fail

  • 21 NT935 SERIES ERROR CODES (exception codes) In case of a wrong request, ModBus will answer with modified codes and codified errors according to the following: 1: — Unsupported function code 2: — Wrong data address 3: — Wrong data

  • 24 NT935 ASERIES 35 2’compl. sign 2’compl. Ch3 temper. alarm set point 1°C ÷ 240°C 1°C÷200°C (*) As (AL) R 36 2’compl. sign 2’compl. Ch3 temper. trip set point 1°C ÷ 240°C 1°C÷200°C (*) As (TRP) R 37 2’compl. sign 2’compl. Ch4 temper.

  • 29 NT935 SERIES TROUBLESHOOTING CAUSES AND SOLUTIONS The control unit does not switch on and the supply to terminals

  • 30 NT935 ASERIES FCD FUNCTION UL SPECIFICATION AND RATINGS CABLE SPECIFICATION Dimension for main circuit 18AWG, working temperature over 105°C MASS OF THE EQUIPMENT 0,45 Kg INPUT SUPPLY 24 – 240 Vac / Vdc (±10%), 50/60 Hz, 7,5VA max PROTECTION External switch or circuit breaker OUTPUTS RELAYS 5 relay Output: 10A 250Vac-res COS=1 OPTIONAL PORTS (

  • 19 NT935 SERIES RS485 MODBUS OUTPUT INTRODUCTION TO THE MODBUS INSIDE MODULE The MODBUS INSIDE expansion module is built in the monitoring unit and allows data transfer on a RS485 line with MODBUS RTU protocol, maximum 32 devices. OPERATING NOTES For the module to work correctly, it is necessary to set the RS485 network set-up parameters: address, baud rate, parity

  • 13 NT935 SERIES POWER SUPPLY The NT935 control unit has UNIVERSAL power supply, i.e. it can be supplied by 24 to 240 Vac-Vdc, 50/60Hz irrespectively of polarity in Vdc (terminals 40-42). This is obtained thanks to the use of a tested power supply unit, newly designed and manufactured, that frees installers from worrying about the correct Vac and Vdc supply. The ground must always be connected to term

  • 26 NT935 ASERIES INFO various causes (READ) BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 — — — — — — — (*) RESET (R) has taken place COMMANDS (WRITE) BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 — — — — — (*) Reset CPU_Error (*) Reset historical data (*) Zero. BIT: RESET has taken place

  • 6 NT935 ASERIES TECHNICAL SPECIFICATIONS NT935 BASIC NT935 AD POWER SUPPLY Supply rated values 24-240 Vac-Vdc 50/60HZ 24-240 Vac-Vdc 50/60HZ Maximum and minimum supply values 20-270 Vac-Vdc 50/60HZ 20-270 Vac-Vdc 50/60HZ Vdc with reversible polarities ● ● INPUTS 4 inputs for RTD sensors, Pt100 type with 3 wires (max section 1.5mm²) ● ● Connections on removable terminal strips ● ● Input channels protected again

  • 20 NT935 ASERIES FUNCTION CODE The ModBus module supports the following function codes: 3 (10) : — holding register reading 16 (10) : — register multiple writing If ModBus receives a message and a CRC error is detected, no answer is given. CODE 3 (10) . Request: Slave address, code 3 (10) , Starting address HI, Starting address LO, Number of Point HI, Number of Point LO, Crc LO, Crc HI.

  • 16 NT935 ASERIES ATTENTION : We recommend you check the unit’s programming before starting the device. The default parameters set by TECSYSTEM might not match your requirements. Programming the device is the end user’s responsibility, the settings of the alarm thresholds and the enabling of the functions described in this manual must be checked (by a specialized engineer) according

  • 7 NT935 SERIES (*)On demand, available version from -40°C to 200°C with alarm temperature management range from 0°C to 200°C TECHNICAL SPECIFICATIONS NT935 BASIC NT935 AD Housing NORYL 94 _V0 ● ● Absorption 7,5VA

  • 10 NT935 ASERIES Fix the unit securely with the blocks supplied. 1) Control unit 2) Panel hole dimensions (+0.8mm tolerance) 3) Identification label 1) Control unit 3) Fixing screw 2) Fixing block 4) Crosshead screwdriver #1X100mm MOUNTING 1 1MN0007 REV. 0 2 3 1 2

  • 28 NT935 ASERIES FCD FUNCTION FCD FUNCTION FCD FUNCTION The NT series equipment boasts an innovative control function combined with the dynamic status of the Pt100 sensor. Activating FCD, the control unit analyses the increase in temperature ∆T (*) recorded in a second (°C/sec). Enabling the function, the user can select the value (∆T) from a minimum of 1°C/sec to a maximum of 30°C/ sec. If the value sensed is higher

Questions, Opinions and Exploitation Impressions:

You can ask a question, express your opinion or share our experience of TECSYSTEM NT935 device using right now.

Понравилась статья? Поделить с друзьями:
  • Руководство по ротному хозяйству приказ 333
  • Карион таблетки инструкция по применению цена
  • Телевизор hisense 50e7hq инструкция по эксплуатации
  • Парогенератор timo для душевой кабины инструкция
  • Микон 2 практическое руководство