Micro motion 1700 руководство по эксплуатации

Configuration and Use Manual

MMI-20019028, Rev AB

March 2018

Micro Motion® Model 1700 Transmitters with Analog Outputs

Configuration and Use Manual

Safety messages

Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step.

Other information

Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.

Return policy

Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept your returned equipment if you fail to follow Micro Motion procedures.

Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion Customer Service department.

Emerson Flow customer service

Email:

Worldwide: flow.support@emerson.com

Asia-Pacific: APflow.support@emerson.com

Telephone:

North and South America

Europe and Middle East

Asia Pacific

United States

800-522-6277

U.K.

0870 240 1978

Australia

800

158 727

Canada

+1 303-527-5200

The Netherlands

+31 (0) 704 136 666

New Zealand

099

128 804

Mexico

+41 (0) 41 7686 111

France

0800 917 901

India

800

440 1468

Argentina

+54 11 4837 7000

Germany

0800 182 5347

Pakistan

888

550 2682

Brazil

+55 15 3413 8000

Italy

8008 77334

China

+86

21 2892 9000

Central & Eastern

+41 (0) 41 7686 111

Japan

+81

3 5769 6803

Russia/CIS

+7 495 981 9811

South Korea

+82

2 3438 4600

Egypt

0800 000 0015

Singapore

+65

6 777 8211

Oman

800 70101

Thailand

001

800 441 6426

Qatar

431 0044

Malaysia

800

814 008

Kuwait

663 299 01

South Africa

800 991 390

Saudi Arabia

800 844 9564

UAE

800 0444 0684

Contents

Contents

Part I

Getting started

Chapter 1

Before you begin ……………………………………………………………………………………………….

3

1.1

About this manual ………………………………………………………………………………………………………….

3

1.2

Transmitter model code ………………………………………………………………………………………………….

3

1.3

Communications tools and protocols ………………………………………………………………………………..

4

1.4

Additional documentation and resources …………………………………………………………………………..

4

Chapter 2

Quick start

………………………………………………………………………………………………………..

5

2.1

Power up the transmitter …………………………………………………………………………………………………

5

2.2

Check meter status …………………………………………………………………………………………………………

6

2.2.1 ………………………………………………………………………

Transmitter status reported by LED

6

2.3

Make ……………………………………………………………………..a startup connection to the transmitter

7

2.4

(Optional) ………………………………………………………………Adjust digital communications settings

7

2.5

Verify …………………………………………………………………………………………mass flow measurement

7

2.6

Verify ……………………………………………………………………………………………………………….the zero

8

2.6.1 ……………………………………

Terminology used with zero verification and zero calibration

9

Part II

Configuration and commissioning

Chapter 3

Introduction to configuration and commissioning …………………………………………………

13

3.1

Configuration flowchart ………………………………………………………………………………………………..

13

3.2

Default values and ranges ………………………………………………………………………………………………

15

3.3

Enable access to the off-line menu of the display ……………………………………………………………….

15

3.4

Disable write-protection on the transmitter configuration ………………………………………………….

15

3.5

Restore the factory configuration ……………………………………………………………………………………

16

Chapter 4

Configure process measurement ………………………………………………………………………..

17

4.1

Configure mass flow measurement …………………………………………………………………………………

17

4.1.1

Configure Mass Flow Measurement Unit …………………………………………………………….

17

4.1.2

Configure Flow Damping ………………………………………………………………………………….

20

4.1.3

Configure Mass Flow Cutoff ………………………………………………………………………………

21

4.2

Configure volume flow measurement for liquid applications ……………………………………………….

22

4.2.1

Configure Volume Flow Type for liquid applications ………………………………………………

23

4.2.2

Configure Volume Flow Measurement Unit for liquid applications …………………………..

23

4.2.3

Configure Volume Flow Cutoff ………………………………………………………………………….

26

4.3

Configure GSV flow measurement …………………………………………………………………………………..

27

4.3.1

Configure Volume Flow Type for gas applications …………………………………………………

28

4.3.2

Configure Standard Density of Gas …………………………………………………………………….

28

4.3.3

Configure Gas Standard Volume Flow Unit ………………………………………………………….

30

4.3.4

Configure Gas Standard Volume Flow Cutoff ……………………………………………………….

33

4.4

Configure Flow Direction ………………………………………………………………………………………………

34

4.4.1

Options for Flow Direction ……………………………………………………………………………….

35

4.5

Configure density measurement …………………………………………………………………………………….

39

4.5.1

Configure Density Measurement Unit ………………………………………………………………..

39

Configuration and Use Manual

i

Contents

4.5.2

Configure two-phase flow parameters ………………………………………………………………..

40

4.5.3

Configure Density Damping ……………………………………………………………………………..

42

4.5.4

Configure Density Cutoff ………………………………………………………………………………….

43

4.6

Configure temperature measurement ……………………………………………………………………………..

44

4.6.1

Configure Temperature Measurement Unit …………………………………………………………

44

4.6.2

Configure Temperature Damping ……………………………………………………………………..

44

4.6.3

Effect of Temperature Damping on process measurement …………………………………….

45

4.6.4

Configure Temperature Input …………………………………………………………………………..

45

4.7

Configure pressure compensation …………………………………………………………………………………..

46

4.7.1

Configure pressure compensation using ProLink III ………………………………………………

46

4.7.2

Configure pressure compensation using the Field Communicator …………………………..

47

4.7.3

Options for Pressure Measurement Unit ……………………………………………………………..

49

Chapter 5

Configure device options and preferences ……………………………………………………………

51

5.1

Configure the transmitter display ……………………………………………………………………………………

51

5.1.1

Configure the language used for the display ………………………………………………………..

51

5.1.2

Configure the process variables and diagnostic variables shown on the display ………….

51

5.1.3

Configure the number of decimal places (precision) shown on the display ………………..

53

5.1.4

Configure the refresh rate of data shown on the display …………………………………………

54

5.1.5

Enable or disable automatic scrolling through the display variables …………………………

54

5.1.6

Enable or disable the display backlight ………………………………………………………………..

55

5.1.7

Enable or disable Status LED Blinking ………………………………………………………………….

55

5.2

Enable or disable operator actions from the display ……………………………………………………………

56

5.2.1

Enable or disable Totalizer Start/Stop from the display …………………………………………..

56

5.2.2

Enable or disable Totalizer Reset from the display …………………………………………………

57

5.2.3

Enable or disable the Acknowledge All Alerts display command ………………………………

57

5.3

Configure security for the display menus ………………………………………………………………………….

58

5.4

Configure response time parameters ………………………………………………………………………………

59

5.4.1

Configure Update Rate …………………………………………………………………………………….

60

5.4.2

Configure Response Time …………………………………………………………………………………

61

5.5

Configure alert handling ………………………………………………………………………………………………..

62

5.5.1

Configure Fault Timeout ………………………………………………………………………………….

62

5.5.2

Configure Status Alert Severity ………………………………………………………………………….

63

5.6

Configure informational parameters ……………………………………………………………………………….

67

5.6.1

Configure Sensor Serial Number ………………………………………………………………………..

67

5.6.2

Configure Sensor Material ………………………………………………………………………………..

67

5.6.3

Configure Sensor Liner Material …………………………………………………………………………

68

5.6.4

Configure Sensor Flange Type …………………………………………………………………………..

68

5.6.5

Configure Descriptor ……………………………………………………………………………………….

69

5.6.6

Configure Message …………………………………………………………………………………………

69

5.6.7

Configure Date ……………………………………………………………………………………………….

69

Chapter 6

Integrate the meter with the control system …………………………………………………………

71

6.1

Configure the transmitter channels …………………………………………………………………………………

71

6.2

Configure the mA Output ………………………………………………………………………………………………

72

6.2.1

Configure mA Output Process Variable ………………………………………………………………

72

6.2.2

Configure Lower Range Value (LRV) and Upper Range Value (URV) ………………………….

74

6.2.3

Configure AO Cutoff ………………………………………………………………………………………..

75

6.2.4

Configure Added Damping ……………………………………………………………………………….

77

6.2.5

Configure mA Output Fault Action and mA Output Fault Level ……………………………….

78

6.3

Configure the Frequency Output …………………………………………………………………………………….

79

6.3.1

Configure Frequency Output Polarity …………………………………………………………………

80

ii

Micro Motion Model 1700 Transmitters with Analog Outputs

Contents

6.3.2

Configure Frequency Output Scaling Method ………………………………………………………

81

6.3.3

Configure Frequency Output Fault Action and Frequency Output Fault Level ……………

82

6.4

Configure the Discrete Output ……………………………………………………………………………………….

83

6.4.1

Configure Discrete Output Source …………………………………………………………………….

84

6.4.2

Configure Discrete Output Polarity ……………………………………………………………………

86

6.4.3

Configure Discrete Output Fault Action ………………………………………………………………

86

6.5

Configure events ………………………………………………………………………………………………………….

87

6.5.1

Configure a basic event …………………………………………………………………………………….

88

6.5.2

Configure an enhanced event ……………………………………………………………………………

88

6.6

Configure digital communications ………………………………………………………………………………….

90

6.6.1

Configure HART/Bell 202 communications …………………………………………………………

90

6.6.2

Configure HART/RS-485 communications …………………………………………………………..

95

6.6.3

Configure Modbus/RS-485 communications ……………………………………………………….

96

6.6.4

Configure Digital Communications Fault Action …………………………………………………..

98

Chapter 7

Complete the configuration ……………………………………………………………………………..

101

7.1

Test or tune the system using sensor simulation ………………………………………………………………

101

7.1.1

Sensor simulation ………………………………………………………………………………………….

102

7.2

Back up transmitter configuration …………………………………………………………………………………

103

7.3

Enable write-protection on the transmitter configuration …………………………………………………

103

Part III Operations, maintenance, and troubleshooting

Chapter 8

Transmitter operation …………………………………………………………………………………….

107

8.1

Record the process variables ………………………………………………………………………………………..

107

8.2

View process variables …………………………………………………………………………………………………

108

8.2.1

View process variables using the display ……………………………………………………………

108

8.2.2

View process variables and other data using ProLink III ………………………………………..

109

8.2.3

View process variables using the Field Communicator …………………………………………

109

8.3

View transmitter status using the status LED …………………………………………………………………..

110

8.4

View and acknowledge status alerts ………………………………………………………………………………

111

8.4.1

View and acknowledge alerts using the display ………………………………………………….

111

8.4.2

View and acknowledge alerts using ProLink III ……………………………………………………

113

8.4.3

View alerts using the Field Communicator ………………………………………………………..

114

8.5

Read totalizer and inventory values ……………………………………………………………………………….

114

8.6

Start and stop totalizers and inventories …………………………………………………………………………

114

8.6.1

Start and stop totalizers and inventories using the display ……………………………………

115

8.7

Reset totalizers …………………………………………………………………………………………………………..

116

8.7.1

Reset totalizers using the display ……………………………………………………………………..

116

8.8

Reset inventories ………………………………………………………………………………………………………..

118

Chapter 9

Measurement support …………………………………………………………………………………….

119

9.1

Options for measurement support ………………………………………………………………………………..

119

9.2

Use Smart Meter Verification (SMV) ………………………………………………………………………………

120

9.2.1

SMV requirements …………………………………………………………………………………………

120

9.2.2

SMV test preparation ……………………………………………………………………………………..

120

9.2.3

Run SMV ………………………………………………………………………………………………………

121

9.2.4

View test data ……………………………………………………………………………………………….

125

9.2.5

Schedule automatic execution of the SMV test …………………………………………………..

129

9.3

Use PVR, TBR, and TMR ………………………………………………………………………………………………..

132

9.3.1

PVR, TBR, and TMR applications ……………………………………………………………………….

133

9.4

Piecewise linearization (PWL) for calibrating gas meters ……………………………………………………

134

Configuration and Use Manual

iii

Contents

9.5

Zero the meter …………………………………………………………………………………………………………..

134

9.6

Validate the meter ………………………………………………………………………………………………………

135

9.6.1

Alternate method for calculating the meter factor for volume flow ………………………..

136

9.7

Perform a (standard) D1 and D2 density calibration ………………………………………………………….

137

9.7.1

Perform a D1 and D2 density calibration using ProLink III ……………………………………..

138

9.7.2

Perform a D1 and D2 density calibration using the Field Communicator …………………

139

9.8

Perform a D3 and D4 density calibration (T-Series sensors only) …………………………………………

140

9.8.1

Perform a D3 or D3 and D4 density calibration using ProLink III …………………………….

140

9.8.2

Perform a D3 or D3 and D4 density calibration using the Field Communicator ………..

141

9.9

Perform temperature calibration …………………………………………………………………………………..

142

9.9.1

Perform temperature calibration using the display ……………………………………………..

143

9.9.2

Perform temperature calibration using ProLink III ……………………………………………….

143

9.9.3

Perform temperature calibration using the Field Communicator …………………………..

145

Chapter 10 Troubleshooting …………………………………………………………………………………………….

147

10.1

Status LED states ………………………………………………………………………………………………………..

148

10.2

Status alerts, causes, and recommendations …………………………………………………………………..

148

10.3

Flow measurement problems ………………………………………………………………………………………

159

10.4

Density measurement problems …………………………………………………………………………………..

161

10.5

Temperature measurement problems ……………………………………………………………………………

162

10.6

Milliamp output problems ……………………………………………………………………………………………

163

10.7

Frequency Output problems …………………………………………………………………………………………

164

10.8

Using sensor simulation for troubleshooting …………………………………………………………………..

165

10.9

Check power supply wiring …………………………………………………………………………………………..

165

10.10

Check sensor-to-transmitter wiring ……………………………………………………………………………….

166

10.11

Check grounding ………………………………………………………………………………………………………..

167

10.12

Perform loop tests ………………………………………………………………………………………………………

167

10.12.1 Perform loop tests using the display …………………………………………………………………

167

10.12.2 Perform loop tests using ProLink III …………………………………………………………………..

169

10.12.3 Perform loop tests using the Field Communicator ………………………………………………

170

10.13

Check the HART communication loop ……………………………………………………………………………

171

10.14

Check HART Address and mA Output Action …………………………………………………………………..

172

10.15

Check HART burst mode ………………………………………………………………………………………………

173

10.16

Check the trimming of the mA Output …………………………………………………………………………..

173

10.17

Check Lower Range Value and Upper Range Value …………………………………………………………..

173

10.18

Check mA Output Fault Action ……………………………………………………………………………………..

173

10.19

Check for radio frequency interference (RFI) ……………………………………………………………………

174

10.20

Check Frequency Output Scaling Method ………………………………………………………………………

174

10.21

Check Frequency Output Fault Action ……………………………………………………………………………

174

10.22

Check Flow Direction ………………………………………………………………………………………………….

175

10.23

Check the cutoffs ……………………………………………………………………………………………………….

175

10.24

Check for two-phase flow (slug flow) ……………………………………………………………………………..

175

10.25

Check the drive gain ……………………………………………………………………………………………………

176

10.25.1 Collect drive gain data ……………………………………………………………………………………

177

10.26

Check the pickoff voltage …………………………………………………………………………………………….

177

10.26.1 Collect pickoff voltage data …………………………………………………………………………….

178

10.27

Check for internal electrical problems ……………………………………………………………………………

178

10.27.1 Check the sensor coils …………………………………………………………………………………….

179

10.28

Check the core processor LED ……………………………………………………………………………………….

181

10.28.1 Core processor LED states ……………………………………………………………………………….

184

10.29

Perform a 700 core processor resistance test …………………………………………………………………..

186

iv

Micro Motion Model 1700 Transmitters with Analog Outputs

Contents

Appendices and reference

Appendix A

Using the transmitter display ……………………………………………………………………………

189

A.1

Components of the transmitter interface ……………………………………………………………………….

189

A.2

Use the optical switches ………………………………………………………………………………………………

190

A.3

Access and use the display menu system ………………………………………………………………………..

191

A.3.1 Enter a floating-point value using the display ……………………………………………………..

192

A.4

Display codes for process variables ………………………………………………………………………………..

195

A.5

Codes and abbreviations used in display menus ………………………………………………………………

196

Appendix B

Using ProLink III with the transmitter …………………………………………………………………

201

B.1

Basic information about ProLink III ………………………………………………………………………………..

201

B.2

Connect with ProLink III ………………………………………………………………………………………………

202

B.2.1 Connection types supported by ProLink III …………………………………………………………

202

B.2.2 Connect with ProLink III to the service port ………………………………………………………..

203

B.2.3 Make a HART/Bell 202 connection ……………………………………………………………………

204

B.2.4 Make a HART/RS-485 connection ……………………………………………………………………..

209

B.2.5 Connect with ProLink III to the RS-485 port ………………………………………………………..

212

Appendix C

Using a Field Communicator with the transmitter ………………………………………………..

217

C.1

Basic information about the Field Communicator ……………………………………………………………

217

C.2

Connect with the Field Communicator ………………………………………………………………………….

218

Appendix D

Default values and ranges ………………………………………………………………………………..

221

D.1

Default values and ranges …………………………………………………………………………………………….

221

Appendix E

Transmitter components and installation wiring …………………………………………………

227

E.1

Installation types ………………………………………………………………………………………………………..

227

E.2

Power supply terminals and ground ………………………………………………………………………………

230

E.3

Input/output (I/O) wiring terminals ……………………………………………………………………………….

231

Appendix F

NE 53 history …………………………………………………………………………………………………

233

F.1

NE 53 history ……………………………………………………………………………………………………………..

233

Configuration and Use Manual

v

Contents

vi

Micro Motion Model 1700 Transmitters with Analog Outputs

Getting started

Part I

Getting started

Chapters covered in this part:

Before you begin

Quick start

Configuration and Use Manual

1

Getting started

2

Micro Motion Model 1700 Transmitters with Analog Outputs

Before you begin

1 Before you begin

Topics covered in this chapter:

About this manual

Transmitter model code

Communications tools and protocols

Additional documentation and resources

1.1About this manual

This manual helps you configure, commission, use, maintain, and troubleshoot

Micro Motion Model 1700 transmitters with analog outputs.

Important

This manual assumes that the following conditions apply:

The transmitter has been installed correctly and completely according to the instructions in the transmitter installation manual

The installation complies with all applicable safety requirements

The user is trained in local and corporate safety standards

1.2Transmitter model code

You can verify that this manual pertains to your transmitter by ensuring the model code on the transmitter tag matches the format.

Example:

The transmitter has a model number of the following form: 1700(R/I/E/B/C/M/P)**A******

R 4-wire remote-mount with aluminum housing

IIntegral mount

E 4-wire remote mount transmitter with 9-wire remote enhanced core processor

B4-wire remote mount transmitter with 9-wire remote core processor

C 9-wire remote-mount with integral core processor and aluminum housing

M 4-wire remote mount with stainless steel housing

P9-wire remote mount transmitter with integral core processor and stainless steel housing

A Analog outputs option board

Configuration and Use Manual

3

Before you begin

1.3Communications tools and protocols

You can use several different communications tools and protocols to interface with the transmitter, use different tools in different locations, or use different tools for different tasks.

Tool

Supported protocols

ProLink III

HART/RS-485

HART/Bell 202

Modbus/RS-485

Service port

Field Communicator

HART/Bell 202

For information about how to use the communication tools, see the appendices in this manual.

Tip

You may be able to use other communications tools, such as AMS Suite: Intelligent Device Manager, or the Smart Wireless THUMAdapter. Use of AMS or the Smart Wireless THUM Adapter is not discussed in this manual. For more information on the Smart Wireless THUM Adapter, refer to the documentation available at www.emerson.com.

1.4Additional documentation and resources

Topic

Document

Hazardous area installa-

See the approval documentation shipped with the transmitter, or

tion

download the appropriate documentation at www.emerson.com.

Product Data Sheet

Micro Motion Series 1000 and Series 2000 Transmitters with MVDTech

nology Product Data Sheet

Sensor

Sensor documentation

Transmitter installation

Micro Motion® Model 1700 and 2700 Installation Manual

All documentation resources are available at www.emerson.com or on the user documentation DVD.

4

Micro Motion Model 1700 Transmitters with Analog Outputs

Quick start

2 Quick start

Topics covered in this chapter:

Power up the transmitter

Check meter status

Make a startup connection to the transmitter

(Optional) Adjust digital communications settings

Verify mass flow measurement

Verify the zero

2.1Power up the transmitter

The transmitter must be powered up for all configuration and commissioning tasks, or for process measurement.

1.Ensure that all transmitter and sensor covers and seals are closed.

DANGER!

To prevent ignition of flammable or combustible atmospheres, ensure that all covers and seals are tightly closed. For hazardous area installations, applying power while housing covers are removed or loose can cause an explosion.

2.Turn on the electrical power at the power supply.

The transmitter will automatically perform diagnostic routines. The transmitter is self-switching and will automatically detect the supply voltage. When using DC power, a minimum of 1.5 amps of startup current is required. During this period, Alert 009 is active. The diagnostic routines should complete in approximately

30 seconds. For transmitters with a display, the status LED will turn green and begin to flash when the startup diagnostics are complete. If the status LED exhibits different behavior, an alert is active.

Postrequisites

Although the sensor is ready to receive process fluid shortly after power-up, the electronics can take up to 10 minutes to reach thermal equilibrium. Therefore, if this is the initial startup, or if power has been off long enough to allow components to reach ambient temperature, allow the electronics to warm up for approximately 10 minutes before relying on process measurements. During this warm-up period, you may observe minor measurement instability or inaccuracy.

Configuration and Use Manual

5

Quick start

2.2Check meter status

Check the meter for any error conditions that require user action or that affect measurement accuracy.

1.Wait approximately 10 seconds for the power-up sequence to complete.

Immediately after power-up, the transmitter runs through diagnostic routines and checks for error conditions. During the power-up sequence, Alert A009 is active. This alert should clear automatically when the power-up sequence is complete.

2.Check the status LED on the transmitter.

Related information

View and acknowledge status alerts

2.2.1Transmitter status reported by LED

Table 2-1: Transmitter status reported by status LED

LED state

Description

Recommendation

Solid green

No alerts are active.

Continue with configuration or process meas-

urement.

Flashing green (if ena-

Unacknowledged corrected condition (no

Continue with configuration or process meas-

bled)

alert)

urement. Acknowledge the alert if you choose.

Solid yellow

One or more low-severity alerts are active.

A low-severity alert condition does not affect

measurement accuracy or output behavior.

You can continue with configuration or proc-

ess measurement, but Micro Motion still rec-

ommends identifying and resolving the alert

condition.

Flashing yellow (if ena-

Calibration in progress, or Known Density Ver-

A low-severity alert condition does not affect

bled)

ification in progress.

measurement accuracy or output behavior.

One or more low-severity alerts are active and

You can continue with configuration or proc-

have not been acknowledged.

ess measurement, but Micro Motion still rec-

ommends identifying and resolving the alert

condition.

Solid red

One or more high-severity alerts are active.

A high-severity alert condition affects meas-

urement accuracy and output behavior. Re-

solve the alert condition before continuing.

Flashing red (if ena-

One or more high-severity alerts are active

A high-severity alert condition affects meas-

bled)

and have not been acknowledged.

urement accuracy and output behavior. Re-

solve the alert condition before continuing.

Acknowledge the alert if you choose.

If Status LED Blinking is disabled, all LEDs will show a solid color rather than flashing.

6

Micro Motion Model 1700 Transmitters with Analog Outputs

Quick start

2.3Make a startup connection to the transmitter

For all configuration tools except the display, you must have an active connection to the transmitter to configure the transmitter. Follow this procedure to make your first connection to the transmitter.

Identify the connection type to use, and follow the instructions for that connection type in the appropriate appendix. Use the default communications parameters shown in the appendix.

Communications tool

Connection type to use

Instructions

ProLink III

HART/RS-485

Appendix B

Modbus/RS-485

Service port

Field Communicator

HART/Bell 202

Appendix C

2.4(Optional) Adjust digital communications settings

Change the communications parameters to site-specific values.

Important

If you are changing communications parameters for the connection type that you are using, you will lose the connection when you write the parameters to the transmitter. Reconnect using the new parameters.

Procedure

1.To change the communications parameters using ProLink III, choose Device Tools > Configuration > Communications.

2.To change the communications parameters using the Field Communicator, choose On-Line Menu > Configure > Manual Setup > Inputs/Outputs > Communications.

2.5Verify mass flow measurement

Check to see that the mass flow rate reported by the transmitter is accurate. You can use any available method.

Read the value for Mass Flow Rate on the transmitter display.

Connect to the transmitter with ProLink III and read the value for Mass Flow Rate in the Process Variables panel.

Connect to the transmitter with the Field Communicator and read the value for Mass Flow Rate.

Configuration and Use Manual

7

Quick start

On-Line Menu > Overview > Primary Purpose Variables

Postrequisites

If the reported mass flow rate is not accurate:

Check the characterization parameters.

Review the troubleshooting suggestions for flow measurement issues.

2.6Verify the zero

Verifying the zero helps you determine if the stored zero value is appropriate to your installation, or if a field zero can improve measurement accuracy.

The zero verification procedure analyzes the Live Zero value under conditions of zero flow, and compares it to the Zero Stability range for the sensor. If the average Live Zero value is within a reasonable range, the zero value stored in the transmitter is valid. Performing a field calibration will not improve measurement accuracy.

Important

In most cases, the factory zero is more accurate than the field zero. Do not zero the meter unless one of the following is true:

The zero is required by site procedures.

The stored zero value fails the zero verification procedure.

Procedure

1.Allow the flowmeter to warm up for at least 20 minutes after applying power.

2.Run the process fluid through the sensor until the sensor temperature reaches the normal process operating temperature.

3.Stop flow through the sensor by shutting the downstream valve, and then the upstream valve if available.

4.Verify that the sensor is blocked in, that flow has stopped, and that the sensor is completely full of process fluid.

5.From ProLink III, choose Device Tools > Calibration > Zero Verification and Calibration > Verify Zero and wait until the procedure completes.

6.Observe the drive gain, temperature, and density readings. If they are stable, check the Live Zero or Field Verification Zero value. If the average value is close to 0, you should not need to zero the meter.

7.If the zero verification procedure fails:

a.Confirm that the sensor is completely blocked in, that flow has stopped, and that the sensor is completely full of process fluid.

b.Verify that the process fluid is not flashing or condensing, and that it does not contain particles that can settle out.

c.Remove or reduce sources of electromechanical noise if appropriate.

8

Micro Motion Model 1700 Transmitters with Analog Outputs

Quick start

d.Repeat the zero verification procedure.

e.If it fails again, zero the meter.

Postrequisites

Restore normal flow through the sensor by opening the valves.

Related information

Zero the meter

2.6.1Terminology used with zero verification and zero calibration

Term

Definition

Zero

In general, the offset required to synchronize the left pickoff and the right

pickoff under conditions of zero flow. Unit = microseconds.

Factory Zero

The zero value obtained at the factory, under laboratory conditions.

Field Zero

The zero value obtained by performing a zero calibration outside the fac-

tory.

Prior Zero

The zero value stored in the transmitter at the time a field zero calibration

is begun. May be the factory zero or a previous field zero.

Manual Zero

The zero value stored in the transmitter, typically obtained from a zero

calibration procedure. It may also be configured manually. Also called

“mechanical zero” or “stored zero”.

Live Zero

The real-time bidirectional mass flow rate with no flow damping or mass

flow cutoff applied. An adaptive damping value is applied only when the

mass flow rate changes dramatically over a very short interval. Unit = con-

figured mass flow measurement unit.

Zero Stability

A laboratory-derived value used to calculate the expected accuracy for a

sensor. Under laboratory conditions at zero flow, the average flow rate is

expected to fall within the range defined by the Zero Stability value (0 ±

Zero Stability). Each sensor size and model has a unique Zero Stability val-

ue. Statistically, 95% of all data points should fall within the range defined

by the Zero Stability value.

Zero Calibration

The procedure used to determine the zero value.

Zero Time

The time period over which the Zero Calibration procedure is performed.

Unit = seconds.

Field Verification Zero

A 3-minute running average of the Live Zero value, calculated by the

transmitter. Unit = configured mass flow measurement unit.

Zero Verification

A procedure used to evaluate the stored zero and determine whether or

not a field zero can improve measurement accuracy.

Configuration and Use Manual

9

Quick start

10

Micro Motion Model 1700 Transmitters with Analog Outputs

Configuration and commissioning

Part II

Configuration and commissioning

Chapters covered in this part:

Introduction to configuration and commissioning

Configure process measurement

Configure device options and preferences

Integrate the meter with the control system

Complete the configuration

Configuration and Use Manual

11

Configuration and commissioning

12

Micro Motion Model 1700 Transmitters with Analog Outputs

Introduction to configuration and commissioning

3 Introduction to configuration and commissioning

Topics covered in this chapter:

Configuration flowchart

Default values and ranges

Enable access to the off line menu of the display

Disable write protection on the transmitter configuration

Restore the factory configuration

3.1Configuration flowchart

Use the following flowchart as a general guide to the configuration and commissioning process.

Some options may not apply to your installation. Detailed information is provided in the remainder of this manual. If you are using the Weights & Measures application, additional configuration and setup are required.

Configuration and Use Manual

13

Micro Motion 1700 Operating Manual

Introduction to configuration and commissioning

Figure 3-1: Configuration flowchart

Configure process measurement

Configure mass flow measurement

Configure volume flow meaurement

Volume flow type

Define gas properties

Configure flow direction

Configure density measurement

Configure temperature measurement

Configure pressure compensation (optional)

Configure PVR, TMR,

or TBR (if available)

Configure device options and preferences

Configure display parameters

Configure fault handling parameters

Configure sensor parameters

Configure device parameters

Integrate device with control system

Configure the channel(s)

Configure the mA

output(s)

Configure the frequency output(s)

Configure the discrete output(s)

Configure events

Configure digital communications

Test and move to production

Test or tune transmitter using sensor simulation

Back up transmitter configuration

Enable write-protection on transmitter configuration

Done

14

Micro Motion Model 1700 Transmitters with Analog Outputs

Introduction to configuration and commissioning

3.2Default values and ranges

See Section D.1 to view the default values and ranges for the most commonly used parameters.

3.3Enable access to the off-line menu of the display

Display

OFF-LINE MAINT > OFF-LINE CONFG > DISPLAY

ProLink III

Device Tools > Configuration > Transmitter Display > Display Security

Field Communicator

Configure > Manual Setup > Display > Offline Variable Menu Features

Overview

By default, access to the off-line menu of the display is enabled. If it is disabled, you must enable it if you want to use the display to configure the transmitter.

Restriction

You cannot use the display to enable access to the off-line menu. You must make a connection from another tool.

3.4Disable write-protection on the transmitter configuration

Display

OFF-LINE MAINT > CONFG > LOCK

ProLink III

Device Tools > Configuration > Write-Protection

Field Communicator

Configure > Manual Setup > Info Parameters > Transmitter Info > Write Protect

Overview

If the transmitter is write-protected, the configuration is locked and you must unlock it before you can change any configuration parameters. By default, the transmitter is not write-protected.

Tip

Write-protecting the transmitter prevents accidental changes to configuration. It does not prevent normal operational use. You can always disable write-protection, perform any required configuration changes, then re-enable write-protection.

Configuration and Use Manual

15

Introduction to configuration and commissioning

3.5Restore the factory configuration

Display

Not available

ProLink III

Device Tools > Configuration Transfer > Restore Factory Configuration

Field Communicator

Service Tools > Maintenance > Reset/Restore > Restore Factory Configuration

Overview

Restoring the factory configuration returns the transmitter to a known operational configuration. This may be useful if you experience problems during configuration.

Important

You cannot restore factory configurations with a 700 core.

Tip

Restoring the factory configuration is not a common action. You may want to contact customer support to see if there is a preferred method to resolve any issues.

16

Micro Motion Model 1700 Transmitters with Analog Outputs

Configure process measurement

4 Configure process measurement

Topics covered in this chapter:

Configure mass flow measurement

Configure volume flow measurement for liquid applications

Configure GSV flow measurement

Configure Flow Direction

Configure density measurement

Configure temperature measurement

Configure pressure compensation

4.1Configure mass flow measurement

The mass flow measurement parameters control how mass flow is measured and reported.

4.1.1Configure Mass Flow Measurement Unit

Display

OFF-LINE MAINT > OFF-LINE CONFG > UNITS > MASS

ProLink III

Device Tools > Configuration > Process Measurement > Flow

Field Communicator

Configure > Manual Setup > Measurements > Flow > Mass Flow Unit

Overview

Mass Flow Measurement Unit specifies the unit of measure that will be used for the mass flow rate. The unit used for mass total and mass inventory is derived from this unit.

Any selected measurement unit, (mass, volume or gas standard volume), is automatically applied to both the mA and Frequency Outputs.

Procedure

Set Mass Flow Measurement Unit to the unit you want to use.

The default setting for Mass Flow Measurement Unit is g/sec (grams per second).

Tip

If the measurement unit you want to use is not available, you can define a special measurement unit.

Configuration and Use Manual

17

Configure process measurement

Options for Mass Flow Measurement Unit

The transmitter provides a standard set of measurement units for Mass Flow Measurement Unit, plus one user-defined special measurement unit. Different communications tools may use different labels for the units.

Label

Display

ProLink III

Field Communica-

Unit description

tor

Grams per second

G/S

g/sec

g/s

Grams per minute

G/MIN

g/min

g/min

Grams per hour

G/H

g/hr

g/h

Kilograms per second

KG/S

kg/sec

kg/s

Kilograms per minute

KG/MIN

kg/min

kg/min

Kilograms per hour

KG/H

kg/hr

kg/h

Kilograms per day

KG/D

kg/day

kg/d

Metric tons per minute

T/MIN

mTon/min

MetTon/min

Metric tons per hour

T/H

mTon/hr

MetTon/h

Metric tons per day

T/D

mTon/day

MetTon/d

Pounds per second

LB/S

lbs/sec

lb/s

Pounds per minute

LB/MIN

lbs/min

lb/min

Pounds per hour

LB/H

lbs/hr

lb/h

Pounds per day

LB/D

lbs/day

lb/d

Short tons (2000 pounds) per

ST/MIN

sTon/min

STon/min

minute

Short tons (2000 pounds) per

ST/H

sTon/hr

STon/h

hour

Short tons (2000 pounds) per

ST/D

sTon/day

STon/d

day

Long tons (2240 pounds) per

LT/H

lTon/hr

LTon/h

hour

Long tons (2240 pounds) per

LT/D

lTon/day

LTon/d

day

Special unit

SPECL

special

Spcl

18

Micro Motion Model 1700 Transmitters with Analog Outputs

Configure process measurement

Define a special measurement unit for mass flow

Display

Not available

ProLink III

Device Tools > Configuration > Process Measurement > Flow > Special Units

Field Communicator

Configure > Manual Setup > Measurements > Special Units > Mass Special Units

Overview

A special measurement unit is a user-defined unit of measure that allows you to report process data, totalizer data, and inventory data in a unit that is not available in the transmitter. A special measurement unit is calculated from an existing measurement unit using a conversion factor.

Note

Although you cannot define a special measurement unit using the display, you can use the display to select an existing special measurement unit, and to view process data using the special measurement unit.

Procedure

1.Specify Base Mass Unit.

Base Mass Unit is the existing mass unit that the special unit will be based on.

2.Specify Base Time Unit.

Base Time Unit is the existing time unit that the special unit will be based on.

3.Calculate Mass Flow Conversion Factor as follows:

a.x base units = y special units

b.Mass Flow Conversion Factor = x ÷ y

The original mass flow rate value is divided by this value.

4.Enter Mass Flow Conversion Factor.

5.Set Mass Flow Label to the name you want to use for the mass flow unit.

6.Set Mass Total Label to the name you want to use for the mass total and mass inventory unit.

The special measurement unit is stored in the transmitter. You can configure the transmitter to use the special measurement unit at any time.

Example: Defining a special measurement unit for mass flow

You want to measure mass flow in ounces per second (oz/sec).

1.Set Base Mass Unit to Pounds (lb).

2.Set Base Time Unit to Seconds (sec).

3.Calculate Mass Flow Conversion Factor:

Configuration and Use Manual

19

Configure process measurement

a.1 lb/sec = 16 oz/sec

b.Mass Flow Conversion Factor = 1 ÷ 16 = 0.0625

4.Set Mass Flow Conversion Factor to 0.0625.

5.Set Mass Flow Label to oz/sec.

6.Set Mass Total Label to oz.

4.1.2Configure Flow Damping

Display

Not available

ProLink III

Device Tools > Configuration > Process Measurement > Flow

Field Communicator

Configure > Manual Setup > Measurements > Flow > Flow Damping

Overview

Damping is used to smooth out small, rapid fluctuations in process measurement. Damping Value specifies the time period (in seconds) over which the transmitter will spread changes in the process variable. At the end of the interval, the internal value will reflect 63% of the change in the actual measured value.

Procedure

Set Flow Damping to the value you want to use.

The default value is 0.8 seconds. The range depends on the core processor type and the setting of Update Rate, as shown in the following table.

Update Rate setting

Damping range

Normal

0 to 51.2 seconds

Special

0 to 40.96 seconds

The value you enter is automatically rounded off to the nearest valid value. For example, if the damping is currently set to 0.8 seconds, any value entered up to 1.2 seconds will be rounded down to 0.8 seconds, and any value entered from 1.21 to 1.59 seconds will be rounded up to 1.6 seconds.

Update Rate setting

Valid damping values

Normal

0.0, 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, 12.8, 25.6, 51.2

Special

0.0, 0.04, 0.08, 0.16, 0.32, 0.64, 1.28, 2.56,

5.12, 10.24, 20.48, 40.96

20

Micro Motion Model 1700 Transmitters with Analog Outputs

Configure process measurement

Effect of flow damping on volume measurement

Flow damping affects volume measurement for liquid volume data. Flow damping also affects volume measurement for gas standard volume data. The transmitter calculates volume data from the damped mass flow data.

Interaction between Flow Damping and mA Output Damping

In some circumstances, both Flow Damping and mA Output Damping are applied to the reported mass flow value.

Flow Damping controls the rate of change in flow process variables. mA Output Damping controls the rate of change reported via the mA Output. If mA Output Process Variable is set to Mass Flow Rate, and both Flow Damping and mA Output Damping are set to non-zero values, flow damping is applied first, and the added damping calculation is applied to the result of the first calculation.

4.1.3Configure Mass Flow Cutoff

Display

Not available

ProLink III

Device Tools > Configuration > Process Measurement > Flow

Field Communicator

Configure > Manual Setup > Measurements > Flow > Mass Flow Cutoff

Overview

Mass Flow Cutoff specifies the lowest mass flow rate that will be reported as measured. All mass flow rates below this cutoff will be reported as 0.

Procedure

Set Mass Flow Cutoff to the value you want to use.

The default value for Mass Flow Cutoff is 0.0 g/sec or a sensor-specific value set at the factory. The recommended value is 0.5% of the nominal flow rate of the attached sensor. See the sensor specifications. Leaving Mass Flow Cutoff at 0.0 g/sec is not recommended.

Effect of Mass Flow Cutoff on volume measurement

Mass Flow Cutoff does not affect volume measurement. Volume data is calculated from the actual mass data rather than the reported value.

Volume flow has a separate Volume Flow Cutoff that is not affected by the Mass Flow Cutoff value.

Configuration and Use Manual

21

Configure process measurement

Interaction between Mass Flow Cutoff and mA Output Cutoff

Mass Flow Cutoff defines the lowest mass flow value that the transmitter will report as measured. mA Output Cutoff defines the lowest flow rate that will be reported via the mA output. If mA Output Process Variable is set to Mass Flow Rate, the mass flow rate reported via the mA Output is controlled by the higher of the two cutoff values.

Mass Flow Cutoff affects all reported values and values used in other transmitter behavior (e.g., events defined on mass flow).

mA Output Cutoff affects only mass flow values reported via the mA Output.

Example: Cutoff interaction with mA Output Cutoff lower than Mass Flow Cutoff

Configuration:

mA Output Process Variable: Mass Flow Rate

Frequency Output Process Variable: Mass Flow Rate

mA Output Cutoff: 10 g/sec

Mass Flow Cutoff: 15 g/sec

Result: If the mass flow rate drops below 15 g/sec, mass flow will be reported as 0, and 0 will be used in all internal processing.

Example: Cutoff interaction with mA Output Cutoff higher than Mass Flow Cutoff

Configuration:

mA Output Process Variable: Mass Flow Rate

Frequency Output Process Variable: Mass Flow Rate

mA Output Cutoff: 15 g/sec

Mass Flow Cutoff: 10 g/sec

Result:

If the mass flow rate drops below 15 g/sec but not below 10 g/sec:

The mA Output will report zero flow.

The Frequency Output will report the actual flow rate, and the actual flow rate will be used in all internal processing.

If the mass flow rate drops below 10 g/sec, both outputs will report zero flow, and 0 will be used in all internal processing.

4.2Configure volume flow measurement for liquid applications

The volume flow measurement parameters control how liquid volume flow is measured and reported.

22

Micro Motion Model 1700 Transmitters with Analog Outputs

Configure process measurement

Restriction

You cannot implement both liquid volume flow and gas standard volume flow at the same time. Choose one or the other.

Note

If you need to switch from gas standard volume to liquid volume, polling for base density will automatically be disabled.

4.2.1Configure Volume Flow Type for liquid applications

Display

Not available

ProLink III

Device Tools > Configuration > Process Measurement > Flow

Field Communicator

Configure > Manual Setup > Measurements > GSV > Volume Flow Type > Liquid

Overview

Volume Flow Type controls whether liquid or gas standard volume flow measurement will be used.

Restriction

Gas standard volume measurement is incompatible with some applications. Set Volume Flow Type to Liquid if you are using any of the following applications:

Production Volume Reconciliation (PVR)

Procedure

Set Volume Flow Type to Liquid.

4.2.2Configure Volume Flow Measurement Unit for liquid applications

Display

OFF-LINE MAINT > OFF-LINE CONFG > UNITS > VOL

ProLink III

Device Tools > Configuration > Process Measurement > Flow

Field Communicator

Configure > Manual Setup > Measurements > Flow > Volume Flow Unit

Overview

Volume Flow Measurement Unit specifies the unit of measurement that will be displayed for the volume flow rate. The unit used for the volume total and volume inventory is based on this unit.

Configuration and Use Manual

23

Configure process measurement

Prerequisites

Before you configure Volume Flow Measurement Unit, be sure that Volume Flow Type is set to Liquid.

Procedure

Set Volume Flow Measurement Unit to the unit you want to use.

The default setting for Volume Flow Measurement Unit is l/sec (liters per second).

Tip

If the measurement unit you want to use is not available, you can define a special measurement unit.

Options for Volume Flow Measurement Unit for liquid applications

The transmitter provides a standard set of measurement units for Volume Flow Measurement Unit, plus one user-defined measurement unit. Different communications tools may use different labels for the units.

Label

Unit description

Display

ProLink III

Field Communicator

Cubic feet per second

CUFT/S

ft3/sec

Cuft/s

Cubic feet per minute

CUF/MN

ft3/min

Cuft/min

Cubic feet per hour

CUFT/H

ft3/hr

Cuft/h

Cubic feet per day

CUFT/D

ft3/day

Cuft/d

Cubic meters per second

M3/S

m3/sec

Cum/s

Cubic meters per minute

M3/MIN

m3/min

Cum/min

Cubic meters per hour

M3/H

m3/hr

Cum/h

Cubic meters per day

M3/D

m3/day

Cum/d

U.S. gallons per second

USGPS

US gal/sec

gal/s

U.S. gallons per minute

USGPM

US gal/min

gal/min

U.S. gallons per hour

USGPH

US gal/hr

gal/h

U.S. gallons per day

USGPD

US gal/day

gal/d

Million U.S. gallons per day

MILG/D

mil US gal/day

MMgal/d

Liters per second

L/S

l/sec

L/s

Liters per minute

L/MIN

l/min

L/min

Liters per hour

L/H

l/hr

L/h

Million liters per day

MILL/D

mil l/day

ML/d

Imperial gallons per second

UKGPS

Imp gal/sec

Impgal/s

Imperial gallons per minute

UKGPM

Imp gal/min

Impgal/min

24

Micro Motion Model 1700 Transmitters with Analog Outputs

Configure process measurement

Label

Unit description

Display

ProLink III

Field Communicator

Imperial gallons per hour

UKGPH

Imp gal/hr

Impgal/h

Imperial gallons per day

UKGPD

Imp gal/day

Impgal/d

Barrels per second(1)

BBL/S

barrels/sec

bbl/s

Barrels per minute(1)

BBL/MN

barrels/min

bbl/min

Barrels per hour(1)

BBL/H

barrels/hr

bbl/h

Barrels per day(1)

BBL/D

barrels/day

bbl/d

Beer barrels per second(2)

BBBL/S

Beer barrels/sec

bbbl/s

Beer barrels per minute(2)

BBBL/MN

Beer barrels/min

bbbl/min

Beer barrels per hour(2)

BBBL/H

Beer barrels/hr

bbbl/h

Beer barrels per day(2)

BBBL/D

Beer barrels/day

bbbl/d

Special unit

SPECL

special

Spcl

(1)Unit based on oil barrels (42 U.S. gallons).

(2)Unit based on U.S. beer barrels (31 U.S. gallons).

Define a special measurement unit for volume flow

Display

Not available

ProLink III

Device Tools > Configuration > Process Measurement > Flow > Special Units

Field Communicator

Configure > Manual Setup > Measurements > Special Units > Volume Special Units

Overview

A special measurement unit is a user-defined unit of measure that allows you to report process data, totalizer data, and inventory data in a unit that is not available in the transmitter. A special measurement unit is calculated from an existing measurement unit using a conversion factor.

Note

Although you cannot define a special measurement unit using the display, you can use the display to select an existing special measurement unit, and to view process data using the special measurement unit.

Procedure

1.Specify Base Volume Unit.

Base Volume Unit is the existing volume unit that the special unit will be based on.

2.Specify Base Time Unit.

Base Time Unit is the existing time unit that the special unit will be based on.

Configuration and Use Manual

25

Configure process measurement

3.Calculate Volume Flow Conversion Factor as follows:

a.x base units = y special units

b.Volume Flow Conversion Factor = x ÷ y

4.Enter Volume Flow Conversion Factor.

The original volume flow rate value is divided by this conversion factor.

5.Set Volume Flow Label to the name you want to use for the volume flow unit.

6.Set Volume Total Label to the name you want to use for the volume total and volume inventory unit.

The special measurement unit is stored in the transmitter. You can configure the transmitter to use the special measurement unit at any time.

Example: Defining a special measurement unit for volume flow

You want to measure volume flow in pints per second (pints/sec).

1.Set Base Volume Unit to Gallons (gal).

2.Set Base Time Unit to Seconds (sec).

3.Calculate the conversion factor:

a.1 gal/sec = 8 pints/sec

b.Volume Flow Conversion Factor = 1 ÷ 8 = 0.1250

4.Set Volume Flow Conversion Factor to 0.1250.

5.Set Volume Flow Label to pints/sec.

6.Set Volume Total Label to pints.

4.2.3Configure Volume Flow Cutoff

Display

Not available

ProLink III

Device Tools > Configuration > Process Measurement > Flow

Field Communicator

Configure > Manual Setup > Measurements > Flow > Volume Flow Cutoff

Overview

Volume Flow Cutoff specifies the lowest volume flow rate that will be reported as measured. All volume flow rates below this cutoff are reported as 0.

Procedure

Set Volume Flow Cutoff to the value you want to use.

The default value for Volume Flow Cutoff is 0.0 l/sec (liters per second). The lower limit is 0.

26

Micro Motion Model 1700 Transmitters with Analog Outputs

Configure process measurement

Interaction between Volume Flow Cutoff and mAO Cutoff

Volume Flow Cutoff defines the lowest liquid volume flow value that the transmitter will report as measured. mAO Cutoff defines the lowest flow rate that will be reported via the mA Output. If mA Output Process Variable is set to Volume Flow Rate, the volume flow rate reported via the mA Output is controlled by the higher of the two cutoff values.

Volume Flow Cutoff affects both the volume flow values reported via the outputs and the volume flow values used in other transmitter behavior (e.g., events defined on the volume flow).

mAO Cutoff affects only flow values reported via the mA Output.

Example: Cutoff interaction with mAO Cutoff lower than Volume Flow Cutoff

Configuration:

mA Output Process Variable: Volume Flow Rate

Frequency Output Process Variable: Volume Flow Rate

AO Cutoff: 10 l/sec

Volume Flow Cutoff: 15 l/sec

Result: If the volume flow rate drops below 15 l/sec, volume flow will be reported as 0, and 0 will be used in all internal processing.

Example: Cutoff interaction with mAO Cutoff higher than Volume Flow Cutoff

Configuration:

mA Output Process Variable: Volume Flow Rate

Frequency Output Process Variable: Volume Flow Rate

AO Cutoff: 15 l/sec

Volume Flow Cutoff: 10 l/sec

Result:

If the volume flow rate drops below 15 l/sec but not below 10 l/sec:

The mA Output will report zero flow.

The Frequency Output will report the actual flow rate, and the actual flow rate will be used in all internal processing.

If the volume flow rate drops below 10 l/sec, both outputs will report zero flow, and 0 will be used in all internal processing.

4.3Configure GSV flow measurement

The gas standard volume (GSV) flow measurement parameters control how volume flow is measured and reported in a gas application.

Configuration and Use Manual

27

Configure process measurement

Restriction

You cannot implement both liquid volume flow and gas standard volume flow at the same time. Choose one or the other.

4.3.1Configure Volume Flow Type for gas applications

Display

Not available

ProLink III

Device Tools > Configuration > Process Measurement > Flow

Field Communicator

Configure > Manual Setup > Measurements > GSV > Volume Flow Type > Standard Gas

Volume

Overview

Volume Flow Type controls whether liquid or gas standard volume flow measurement is used.

Restriction

Gas standard volume measurement is incompatible with some applications. Set Volume Flow Type to Liquid if you are using any of the following applications:

Production Volume Reconciliation (PVR)

Procedure

Set Volume Flow Type to Gas Standard Volume.

4.3.2Configure Standard Density of Gas

Display

Not available

ProLink III

Device Tools > Configuration > Process Measurement > Flow

Field Communicator

Configure > Manual Setup > Measurements > GSV > Gas Ref Density

Overview

The Standard Density of Gas value is the gas density at standard reference conditions. Use it to convert the measured mass flow data to volume flow at reference conditions.

Prerequisites

Ensure that Density Measurement Unit is set to the measurement unit you want to use for Standard Density of Gas.

Procedure

From the Source field, choose the method to supply gas base density data and perform the required setup.

28

Micro Motion Model 1700 Transmitters with Analog Outputs

Configure process measurement

Option

Description

Fixed Value or Digital

A host writes gas base density data to the meter at appropriate intervals.

Communications

Continue to Configure fixed value or digital communications.

Poll for external value

The meter polls an external HART device for gas base density data in order

to then compute gas standard volume from the mass flow and gas base

density.

Continue to Poll for external value.

Configure fixed value or digital communications

Prerequisites

Section 4.3.2

Procedure

1.Set Standard Density of Gas to the standard reference density of the gas you are measuring.

Note

ProLink III provides a guided method that you can use to calculate your gas base density, if you do not know it.

2.Continue to Section 4.3.3.

Poll for external value

Prerequisites

Section 4.3.2

Procedure

1.

Set Polling Slot to an available slot.

2.

Set Polling Control n as one of the following options:

The n is the value you selected in the Polling Slot field.

If there is another master, and if that master is primary, then set this field to

secondary. If the other master is secondary, then set this field to primary.

Option

Description

Poll as Primary

No other HART masters will be on the network.

Poll as Secondary

Other HART masters will be on the network.

3.

Set External Device Tag n to the HART tag of the device being polled.

The n is the value you selected in the Polling Slot field.

Configuration and Use Manual

29

Configure process measurement

The device being polled (slave) cannot have special units set for density. Otherwise, the master will reject the base density and report the following alarm:

A115: No External Input or Polled Data Alert

On the slave side, setup the HART Primary Variable for Base Density. The master will reject anything other than Base Density for the HART Primary Variable and trigger an A115 alarm.

The density units on the transmitter and the polled device can be different as long as they can be classified as density units; for example, kg/m3 and g/cm3. The transmitter converts the polled units into compatible specified units.

For wiring and setup instructions for a polled device, refer to the Micro Motion Gas Density Meters (GDM) Installation manual or the Micro Motion Specific Gravity Meters (SGM) Installation manual.

4. Continue to Section 4.3.3.

4.3.3Configure Gas Standard Volume Flow Unit

Display

OFF-LINE MAINT > OFF-LINE CONFG > UNITS > GSV

ProLink III

Device Tools > Configuration > Process Measurement > Flow

Field Communicator

Configure > Manual Setup > Measurements > GSV > GSV Flow Unit

Overview

Gas Standard Volume Flow Unit specifies the unit of measure that will be displayed for the gas standard volume flow. The measurement unit used for the gas volume total and the gas volume inventory is derived from this unit.

Prerequisites

Before you configure Gas Standard Volume Flow Unit, be sure that Volume Flow Type is set to Gas Standard Volume.

For polling, the first transmitter (master) requests density from a second transmitter (slave) via HART communications. Special units for GSV are allowed on the master side, but the device being polled (slave) cannot have special units set for density, otherwise the master will reject the base density and report an A115: No External Input or Polled Data Alert.

Procedure

Set Gas Standard Volume Flow Unit to the unit you want to use.

The default setting for Gas Standard Volume Flow Unit is SCFM (Standard Cubic Feet per Minute).

Tip

If the measurement unit you want to use is not available, you can define a special measurement unit.

30

Micro Motion Model 1700 Transmitters with Analog Outputs

Configure process measurement

Options for Gas Standard Volume Flow Unit

The transmitter provides a standard set of measurement units for Gas Standard Volume Flow Unit, plus one user-defined special measurement unit. Different communications tools may use different labels for the units.

Label

Unit description

Display

ProLink III

Field Communicator

Normal cubic meters per second

NM3/S

Nm3/sec

Nm3/sec

Normal cubic meters per minute

NM3/MN

Nm3/sec

Nm3/min

Normal cubic meters per hour

NM3/H

Nm3/hr

Nm3/hr

Normal cubic meters per day

NM3/D

Nm3/day

Nm3/day

Normal liters per second

NLPS

NLPS

NLPS

Normal liters per minute

NLPM

NLPM

NLPM

Normal liters per hour

NLPH

NLPH

NLPH

Normal liters per day

NLPD

NLPD

NLPD

Standard cubic feet per second

SCFS

SCFS

SCFS

Standard cubic feet per minute

SCFM

SCFM

SCFM

Standard cubic feet per hour

SCFH

SCFH

SCFH

Standard cubic feet per day

SCFD

SCFD

SCFD

Standard cubic meters per second

SM3/S

Sm3/sec

Sm3/sec

Standard cubic meters per minute

SM3/MN

Sm3/min

Sm3/min

Standard cubic meters per hour

SM3/H

Sm3/hr

Sm3/hr

Standard cubic meters per day

SM3/D

Sm3/day

Sm3/day

Standard liters per second

SLPS

SLPS

SLPS

Standard liters per minute

SLPM

SLPM

SLPM

Standard liters per hour

SLPH

SLPH

SLPH

Standard liters per day

SLPD

SLPD

SLPD

Special measurement unit

SPECL

special

Special

Define a special measurement unit for gas standard volume flow

Display

Not available

ProLink III

Device Tools > Configuration > Process Measurement > Flow > Special Units

Field Communicator

Configure > Manual Setup > Measurements > Special Units > Special GSV Units

Configuration and Use Manual

31

Configure process measurement

Overview

A special measurement unit is a user-defined unit of measure that allows you to report process data, totalizer data, and inventory data in a unit that is not available in the transmitter. A special measurement unit is calculated from an existing measurement unit using a conversion factor.

Note

Although you cannot define a special measurement unit using the display, you can use the display to select an existing special measurement unit, and to view process data using the special measurement unit.

Procedure

1.Specify Base Gas Standard Volume Unit.

Base Gas Standard Volume Unit is the existing gas standard volume unit that the special unit will be based on.

2.Specify Base Time Unit.

Base Time Unit is the existing time unit that the special unit will be based on.

3.Calculate Gas Standard Volume Flow Conversion Factor as follows:

a.x base units = y special units

b.Gas Standard Volume Flow Conversion Factor = x ÷ y

4.Enter the Gas Standard Volume Flow Conversion Factor.

The original gas standard volume flow value is divided by this conversion factor.

5.Set Gas Standard Volume Flow Label to the name you want to use for the gas standard volume flow unit.

6.Set Gas Standard Volume Total Label to the name you want to use for the gas standard volume total and gas standard volume inventory unit.

The special measurement unit is stored in the transmitter. You can configure the transmitter to use the special measurement unit at any time.

Example: Defining a special measurement unit for gas standard volume flow

You want to measure gas standard volume flow in thousands of standard cubic feet per minute.

1.Set Base Gas Standard Volume Unit to SCF.

2.Set Base Time Unit to minutes (min).

3.Calculate the conversion factor:

a.1 thousands of standard cubic feet per minute = 1000 cubic feet per minute

b.Gas Standard Volume Flow Conversion Factor = 1 ÷ 1000 = 0.001 standard

4.Set Gas Standard Volume Flow Conversion Factor to 0.001.

5.Set Gas Standard Volume Flow Label to MSCFM.

32

Micro Motion Model 1700 Transmitters with Analog Outputs

Configure process measurement

6. Set Gas Standard Volume Total Label to MSCF.

4.3.4Configure Gas Standard Volume Flow Cutoff

Display

Not available

ProLink III

Device Tools > Configuration > Process Measurement > Flow

Field Communicator

Configure > Manual Setup > Measurements > GSV > GSV Cutoff

Overview

Gas Standard Volume Flow Cutoff specifies the lowest gas standard volume flow rate that will reported as measured. All gas standard volume flow rates below this cutoff will be reported as 0.

Procedure

Set Gas Standard Volume Flow Cutoff to the value you want to use.

The default value for Gas Standard Volume Flow Cutoff is 0.0. The lower limit is 0.0. There is no upper limit.

Interaction between Gas Standard Volume Flow Cutoff and mA Output Cutoff

Gas Standard Volume Flow Cutoff defines the lowest Gas Standard Volume flow value that the transmitter will report as measured. mA Output Cutoff defines the lowest flow rate that will be reported via the mA Output. If mA Output Process Variable is set to Gas Standard Volume Flow Rate, the volume flow rate reported via the mA Output is controlled by the higher of the two cutoff values.

Gas Standard Volume Flow Cutoff affects both the gas standard volume flow values reported via outputs and the gas standard volume flow values used in other transmitter behavior (e.g., events defined on gas standard volume flow).

mA Output Cutoff affects only flow values reported via the mA Output.

Example: Cutoff interaction with mA Output Cutoff lower than Gas Standard Volume Flow Cutoff

Configuration:

mA Output Process Variable for the primary mA Output: Gas Standard Volume Flow Rate

Frequency Output Process Variable: Gas Standard Volume Flow Rate

mA Output Cutoff for the primary mA Output: 10 SLPM (standard liters per minute)

Gas Standard Volume Flow Cutoff: 15 SLPM

Result: If the gas standard volume flow rate drops below 15 SLPM, the volume flow will be reported as 0, and 0 will be used in all internal processing.

Configuration and Use Manual

33

Configure process measurement

Example: Cutoff interaction with mA Output Cutoff higher than Gas Standard Volume Flow Cutoff

Configuration:

mA Output Process Variable for the primary mA Output: Gas Standard Volume Flow Rate

Frequency Output Process Variable: Gas Standard Volume Flow Rate

mA Output Cutoff for the primary mA Output: 15 SLPM (standard liters per minute)

Gas Standard Volume Flow Cutoff: 10 SLPM

Result:

If the gas standard volume flow rate drops below 15 SLPM but not below 10 SLPM:

The primary mA Output will report zero flow.

The Frequency Output will report the actual flow rate, and the actual flow rate will be used in all internal processing.

If the gas standard volume flow rate drops below 10 SLPM, both outputs will report zero flow, and 0 will be used in all internal processing.

4.4Configure Flow Direction

Display

Not available

ProLink III

Device Tools > Configuration > Process Measurement > Flow

Field Communicator

Configure > Manual Setup > Measurements > Flow > Flow Direction

Overview

Flow Direction controls how forward flow and reverse flow affect flow measurement and reporting.

Flow Direction is defined with respect to the flow arrow on the sensor:

Forward flow (positive flow) moves in the direction of the flow arrow on the sensor.

Reverse flow (negative flow) moves in the direction opposite to the flow arrow on the sensor.

Tip

Micro Motion sensors are bidirectional. Measurement accuracy is not affected by actual flow direction or the setting of the Flow Direction parameter.

Procedure

Set Flow Direction to the value you want to use.

The default setting is Forward.

34

Micro Motion Model 1700 Transmitters with Analog Outputs

Configure process measurement

4.4.1Options for Flow Direction

Flow Direction setting

Relationship to Flow Direction arrow

ProLink III

Field Communicator

on sensor

Forward

Forward

Appropriate when the Flow Direction ar-

row is in the same direction as the major-

ity of flow.

Reverse

Reverse

Appropriate when the Flow Direction ar-

row is in the opposite direction from the

majority of flow.

Absolute Value

Absolute Value

Flow Direction arrow is not relevant.

Bidirectional

Bi directional

Appropriate when both forward and re-

verse flow are expected, and forward

flow will dominate, but the amount of re-

verse flow will be significant.

Negate Forward

Negate/Forward Only

Appropriate when the Flow Direction ar-

row is in the opposite direction from the

majority of flow.

Negate Bidirectional

Negate/Bi-directional

Appropriate when both forward and re-

verse flow are expected, and reverse flow

will dominate, but the amount of for-

ward flow will be significant.

Effect of Flow Direction on mA Outputs

Flow Direction affects how the transmitter reports flow values via the mA Outputs. The mA Outputs are affected by Flow Direction only if mA Output Process Variable is set to a flow variable.

Flow Direction and mA Outputs

The effect of Flow Direction on the mA Outputs depends on Lower Range Value configured for the mA Output:

If Lower Range Value is set to 0, see Figure 4 1.

If Lower Range Value is set to a negative value, see Figure 4 2.

Configuration and Use Manual

35

Configure process measurement

Figure 4-1: Effect of Flow Direction on the mA Output: Lower Range Value = 0

Flow Direction = Forward

Flow Direction = Reverse, Negate Forward

Flow Direction = Absolute Value, Bidirectional,

Negate Bidirectional

20

20

20

mA output

12

mA output

12

mA output

12

4

4

4

-x

0

x

-x

0

x

-x

0

x

Reverse flow

Forward flow

Reverse flow

Forward flow

Reverse flow

Forward flow

Lower Range Value = 0

Upper Range Value = x

Figure 4-2: Effect of Flow Direction on the mA Output: Lower Range Value < 0

Flow Direction = Forward

Flow Direction = Reverse, Negate Forward

Flow Direction = Absolute Value, Bidirectional,

Negate Bidirectional

20

20

20

mA output

12

mA output

12

mA output

12

4

4

4

-x

0

x

-x

0

x

-x

0

x

Reverse flow

Forward flow

Reverse flow

Forward flow

Reverse flow

Forward flow

Lower Range Value = −x

Upper Range Value = x

Example: Flow Direction = Forward and Lower Range Value = 0

Configuration:

Flow Direction = Forward

Lower Range Value = 0 g/sec

Upper Range Value = 100 g/sec

36

Micro Motion Model 1700 Transmitters with Analog Outputs

Configure process measurement

Result:

Under conditions of zero flow, the mA Output is 4 mA.

Under conditions of forward flow, up to a flow rate of 100 g/sec, the mA Output varies between 4 mA and 20 mA in proportion to the flow rate.

Under conditions of forward flow, if the flow rate equals or exceeds 100 g/sec, the mA Output will be proportional to the flow rate up to 20.5 mA, and will be level at 20.5 mA at higher flow rates.

Example: Flow Direction = Forward and Lower Range Value < 0

Configuration:

Flow Direction = Forward

Lower Range Value = −100 g/sec

Upper Range Value = +100 g/sec

Result:

Under conditions of zero flow, the mA Output is 12 mA.

Under conditions of forward flow, for flow rates between 0 and +100 g/sec, the mA Output varies between 12 mA and 20 mA in proportion to (the absolute value of) the flow rate.

Under conditions of forward flow, if (the absolute value of) the flow rate equals or exceeds 100 g/sec, the mA Output is proportional to the flow rate up to 20.5 mA, and will be level at 20.5 mA at higher flow rates.

Under conditions of reverse flow, for flow rates between 0 and −100 g/sec, the mA Output varies between 4 mA and 12 mA in inverse proportion to the absolute value of the flow rate.

Under conditions of reverse flow, if the absolute value of the flow rate equals or exceeds 100 g/sec, the mA Output is inversely proportional to the flow rate down to 3.8 mA, and will be level at 3.8 mA at higher absolute values.

Example: Flow Direction = Reverse

Configuration:

Flow Direction = Reverse

Lower Range Value = 0 g/sec

Upper Range Value = 100 g/sec

Result:

Under conditions of zero flow, the mA Output is 4 mA.

Under conditions of reverse flow, for flow rates between 0 and +100 g/sec, the mA Output level varies between 4 mA and 20 mA in proportion to the absolute value of the flow rate.

Under conditions of reverse flow, if the absolute value of the flow rate equals or exceeds 100 g/sec, the mA Output will be proportional to the absolute value of the flow rate up to 20.5 mA, and will be level at 20.5 mA at higher absolute values.

Configuration and Use Manual

37

Configure process measurement

Effect of flow direction on Frequency Outputs

Flow direction affects how the transmitter reports flow values via the Frequency Outputs. The Frequency Outputs are affected by flow direction only if Frequency Output Process Variable is set to a flow variable.

Table 4-1: Effect of the flow direction parameter and actual flow direction on

Frequency Outputs

Actual flow direction

Flow Direction setting

Forward

Zero flow

Reverse

Forward

Hz > 0

0 Hz

0 Hz

Reverse

0 Hz

0 Hz

Hz > 0

Bidirectional

Hz > 0

0 Hz

Hz > 0

Absolute Value

Hz > 0

0 Hz

Hz > 0

Negate Forward

0 Hz

0 Hz

Hz > 0

Negate Bidirectional

Hz > 0

0 Hz

Hz > 0

Effect of flow direction on Discrete Outputs

The flow direction parameter affects the Discrete Output behavior only if Discrete Output Source is set to Flow Direction.

Table 4-2: Effect of the flow direction parameter and actual flow direction on

Discrete Outputs

Actual flow direction

Flow Direction setting

Forward

Zero flow

Reverse

Forward

OFF

OFF

ON

Reverse

OFF

OFF

ON

Bidirectional

OFF

OFF

ON

Absolute Value

OFF

OFF

ON

Negate Forward

ON

OFF

OFF

Negate Bidirectional

ON

OFF

OFF

Effect of flow direction on digital communications

Flow direction affects how flow values are reported via digital communications. The following table describes the effect of the flow direction parameter and actual flow direction on flow values reported via digital communications.

38

Micro Motion Model 1700 Transmitters with Analog Outputs

Configure process measurement

Table 4-3: Effect of the flow direction on flow values

Actual flow direction

Flow Direction setting

Forward

Zero flow

Reverse

Forward

Positive

0

Negative

Reverse

Positive

0

Negative

Bidirectional

Positive

0

Negative

Absolute Value

Positive(1)

0

Positive(1)

Negate Forward

Negative

0

Positive

Negate Bidirectional

Negative

0

Positive

(1) Refer to the digital communications status bits for an indication of whether flow is positive or negative.

Effect of flow direction on flow totals

Flow direction affects how flow totals and inventories are calculated.

Actual flow direction

Flow Direction setting

Forward

Zero flow

Reverse

Forward

Totals increase

Totals do not change

Totals do not change

Reverse

Totals do not change

Totals do not change

Totals increase

Bidirectional

Totals increase

Totals do not change

Totals decrease

Absolute Value

Totals increase

Totals do not change

Totals increase

Negate Forward

Totals do not change

Totals do not change

Totals increase

Negate Bidirectional

Totals decrease

Totals do not change

Totals increase

4.5Configure density measurement

The density measurement parameters control how density is measured and reported.

4.5.1Configure Density Measurement Unit

Display

OFF-LINE MAINT > OFF-LINE CONFG > UNITS > DENS

ProLink III

Device Tools > Configuration > Process Measurement > Density

Field Communicator

Configure > Manual Setup > Measurements > Density > Density Unit

Overview

Density Measurement Unit controls the measurement units that will be used in density calculations and reporting.

Configuration and Use Manual

39

Configure process measurement

Procedure

Set Density Measurement Unit to the option you want to use.

The default setting for Density Measurement Unit is g/cm3 (grams per cubic centimeter).

Options for Density Measurement Unit

The transmitter provides a standard set of measurement units for Density Measurement Unit. Different communications tools may use different labels.

Label

Unit description

Display

ProLink III

Field Communicator

Specific gravity(1)

SGU

SGU

SGU

Grams per cubic centimeter

G/CM3

g/cm3

g/Cucm

Grams per liter

G/L

g/l

g/L

Grams per milliliter

G/mL

g/ml

g/mL

Kilograms per liter

KG/L

kg/l

kg/L

Kilograms per cubic meter

KG/M3

kg/m3

kg/Cum

Pounds per U.S. gallon

LB/GAL

lbs/Usgal

lb/gal

Pounds per cubic foot

LB/CUF

lbs/ft3

lb/Cuft

Pounds per cubic inch

LB/CUI

lbs/in3

lb/CuIn

Degrees API

D API

degAPI

degAPI

Short ton per cubic yard

ST/CUY

sT/yd3

STon/Cuyd

(1) Non standard calculation. This value represents line density divided by the density of water at 60 °F.

4.5.2Configure two-phase flow parameters

Display

Not available

ProLink III

Device Tools > Configuration > Process Measurement > Density

Field Communicator

Configure > Manual Setup > Measurements > Density > Slug Low Limit

Configure > Manual Setup > Measurements > Density > Slug High Limit

Configure > Manual Setup > Measurements > Density > Slug Duration

Overview

The two-phase flow parameters control how the transmitter detects and reports twophase flow (gas in a liquid process or liquid in a gas process).

Note

Two-phase flow is also referred to as slug flow.

40

Micro Motion Model 1700 Transmitters with Analog Outputs

Configure process measurement

Procedure

1.Set Two-Phase Flow Low Limit to the lowest density value that is considered normal in your process.

Values below this will cause the transmitter to post Alert A105 (Two-Phase Flow).

Tip

Gas entrainment can cause your process density to drop temporarily. To reduce the occurrence of two-phase flow alerts that are not significant to your process, set Two-Phase Flow Low Limit slightly below your expected lowest process density.

You must enter Two-Phase Flow Low Limit in g/cm³, even if you configured another unit for density measurement.

The default value for Two-Phase Flow Low Limit is 0.0 g/cm³. The range is 0.0 to

10.0g/cm³.

2.Set Two-Phase Flow High Limit to the highest density value that is considered normal in your process.

Micro Motion recommends leaving Two-Phase Flow High Limit at the default value. Values above this will cause the transmitter to post Alert A105 (Two-Phase Flow).

You must enter Two-Phase Flow High Limit in g/cm³, even if you configured another unit for density measurement.

The default value for Two-Phase Flow High Limit is 5.0 g/cm³. The range is 0.0 to

10.0g/cm³.

3.Set Two-Phase Flow Timeout to the number of seconds that the transmitter will wait for a two-phase flow condition to clear before posting the alert.

The default value for Two-Phase Flow Timeout is 0.0 seconds, meaning that the alert will be posted immediately. The range is 0.0 to 60.0 seconds.

Detecting and reporting two-phase flow

Two-phase flow (gas in a liquid process or liquid in a gas process) can cause a variety of process control issues. By configuring the two-phase flow parameters appropriately for your application, you can detect process conditions that require correction.

Micro Motion recommends leaving Two-Phase Flow High Limit at the default value.

A two-phase flow condition occurs whenever the measured density goes below Two-Phase Flow Low Limit or above Two-Phase Flow High Limit. If this occurs:

A two-phase flow alert is posted to the active alert log.

All outputs that are configured to represent flow rate hold their last pre alert value for the number of seconds configured in Two-Phase Flow Timeout.

If the two-phase flow condition clears before Two-Phase Flow Timeout expires:

Outputs that represent flow rate revert to reporting actual flow.

Configuration and Use Manual

41

Configure process measurement

The two-phase flow alert is deactivated, but remains in the active alert log until it is acknowledged.

If the two-phase flow condition does not clear before Two-Phase Flow Timeout expires, the outputs that represent flow rate report a flow rate of 0.

If Two-Phase Flow Timeout is set to 0.0 seconds, the outputs that represent flow rate will report a flow rate of 0 as soon as two-phase flow is detected.

4.5.3Configure Density Damping

Display

Not available

ProLink III

Device Tools > Configuration > Process Measurement > Density

Field Communicator

Configure > Manual Setup > Measurements > Density > Density Damping

Overview

Density Damping controls the amount of damping that will be applied to the line density value.

Damping is used to smooth out small, rapid fluctuations in process measurement. Damping Value specifies the time period (in seconds) over which the transmitter will spread changes in the process variable. At the end of the interval, the internal value will reflect 63% of the change in the actual measured value.

Tip

Density damping affects all process variables that are calculated from line density.

Procedure

Set Density Damping to the value you want to use.

The default value is 1.6 seconds. The range depends on the core processor type and the setting of Update Rate, as shown in the following table:

Update Rate setting

Damping range

Normal

0 to 51.2 seconds

Special

0 to 40.96 seconds

Tips

A high damping value makes the process variable appear smoother because the reported value changes slowly.

A low damping value makes the process variable appear more erratic because the reported value changes more quickly.

42

Micro Motion Model 1700 Transmitters with Analog Outputs

Loading…

Page 1 — Model 1700 and 2700

Installation Manual 20001700, Rev CC April 2013Micro Motion® Model 1700 and 2700Installation Manual

Page 2

The transmitter’s model number is on a tag on the side of the transmitter. You can use themodel number to determine the transmitter’s output

Page 3 — Contents

• You cannot configure the combination of Channel B as discrete output and Channel C asfrequency output.9.2 mA/HART wiring9.2.1 Basic mA output wiring

Page 4

HART/analog single loop wiringFigure 9-2: ABA.820 Ω maximum loop resistanceB. HART-compatible host or controller9.2.3HART multidrop wiringTipFor opt

Page 5 — 1 Planning

HART multidrop wiringFigure 9-3: ABCDEFA. 250–600 Ω resistanceB. HART-compatible host or controllerC. HART-compatible transmittersD. Model 2700 conf

Page 6

Output voltage versus load resistanceFigure 9-5: 16141210864200 500 1000 1500 2000 2500Load resistance (Ohms)High level output voltage (Volts)Maximu

Page 7

CAUTION!Exceeding 30 VDC can damage the transmitter. Terminal current must be less than 500 mA.Recommended pull-up resistor versus supply voltageFigur

Page 8

Internally powered frequency output wiring on Channel CFigure 9-8: AA. CounterOutput voltage versus load resistanceFigure 9-9: 16141210864200 1000

Page 9 — 1.1.2 Maximum cable lengths

Externally powered frequency output wiring on Channel CFigure 9-10: ABCA. Pull-up resistorB. 3–30 VDCC. CounterCAUTION!Exceeding 30 VDC can damage t

Page 10 — Planning

9.4 Discrete output wiring9.4.1 Internally powered discrete output wiring on Channel BInternally powered discrete output wiring on Channel BFigure 9-1

Page 11 — Power requirements

9.4.2 Externally powered discrete output wiring on Channel BExternally powered discrete output wiring on Channel BFigure 9-14: ABA. 3–30 VDCB. Pull-

Page 12 — 1.6 Orientation

Recommended pull-up resistor versus supply voltageFigure 9-15: 360032002800240020001600120080005 10 15 20 25 30Supply voltage (Volts)External pull-u

Page 13 — Installation Manual 9

Output options for Model 1500 and Model 2500 transmittersTable 1-4: Letter DescriptionA Analog outputs – one mA, one frequency, one RS-485B Configur

Page 14 — 10 Micro Motion

Output voltage versus load resistanceFigure 9-17: 16141210864200 1000 2000 3000 4000 5000Load resistance (Ohms)High level output voltage (Volts)Maxi

Page 15 — D. Sensor

CAUTION!Exceeding 30 VDC can damage the transmitter. Terminal current must be less than 500 mA.Recommended pull-up resistor versus supply voltageFigur

Page 16 — (optional)

Internally powered discrete input wiringFigure 9-20: AA. Switch9.5.2 Externally powered discrete input wiringExternally powered discrete input wirin

Page 17

10 SpecificationsTopics covered in this chapter:•Electrical connections•Input/output signals•Local display•Environmental limits•Physical specification

Page 18

10.2 Input/output signalsInput/output signals – Model 1700 transmitter with analog outputsTable 10-2: Type DescriptionOutput variables • Mass flow•

Page 19 — 3.1 Mounting options

Input/output signals – Model 2700 transmitter with intrinsically safeoutputsTable 10-5: Type DescriptionOutput variables • Mass & volume flow• N

Page 20 — 16 Micro Motion

Local display (standard)Table 10-7: Type DescriptionLocal display Standard user interface with 2-line LCD panel• Two optical switches for local oper

Page 21 — D. Mounting bracket

10.4 Environmental limitsEnvironmental specificationsTable 10-9: Type ValueAmbient temperature limits –40 to +140 °F (–40 to +60 °C)Humidity limits

Page 22 — 18 Micro Motion

4-wire remote mount transmitter dimensions (painted aluminumhousing)Figure 10-1: 2 13/16(71)2 13/16(71)4 × Ø3/8(10)3 11/16(93)3 × 1/2″–14 NPTor

Page 23 — Prepare the 4-wire cable

4-wire and 9-wire remote mount transmitter dimensions (stainless steelhousing)Figure 10-3: 2 13/16(71)4 x Ø3/8(10)2 13/16(71)5 7/16(139)2 × 1/2″

Page 24 — 20 Micro Motion

• 18 to 100 VDC, 6 watts typical, 11 watts maximum• Complies with low voltage directive 2006/95/EC per EN 61010-1 (IEC 61010-1) withamendment 2, and I

Page 25

Remote core processor dimensionsFigure 10-4: 2 13/16(71)2 13/16(71)4 × Ø3/8(10)6 3/16(158)2 1/4(57)4 9/16(116)wall mount5 1/2 (140)To centerline of

Page 26

Index4-wire cablepreparation 19, 54types 21, 56user-supplied 21, 569-wire cableconnecting to sensor 37, 40, 65, 69preparation 31, 59types an

Page 27 — Installation Manual 23

frequency output 86frequency output with galvanic isolator 91hazardous area 87, 92mA output hazardous area 89MmA outputhazardous area wiring

Page 29

*20001700*20001700Rev CC2013Micro Motion Inc. USAWorldwide Headquarters7070 Winchester CircleBoulder, Colorado 80301T +1 303-527-5200T +1 800-522-6277

Page 30

1.7 Accessibility for maintenanceMount the flowmeter in a location and orientation that satisfies the following conditions:• Allows sufficient clearan

Page 32 — 28 Micro Motion

2 Mounting and sensor wiring forintegral installationsTopics covered in this chapter:•Mounting and sensor wiring•Rotate the transmitter on the sensor

Page 33 — 4.1 Mounting options

1. Loosen each of the four cap screws (4 mm) that fasten the transmitter to the base.2. Rotate the transmitter counter-clockwise so that the cap screw

Page 34 — A. Mounting bracket

Display componentsFigure 2-2: A. Transmitter housingB. Sub-bezelC. Display moduleD. Display screwsE. End-cap clampF. Cap screwG. Display cover1. Shu

Page 35 — Prepare the 9-wire cable

10. Turn the display cover clockwise until it is snug.11. Replace the end-cap clamp by reinserting and tightening the cap screw.12. Restore power to t

Page 36 — 32 Micro Motion

3 Mounting and sensor wiring for 4-wire remote installationsTopics covered in this chapter:•Mounting options•Prepare the 4-wire cable•Wire the transmi

Page 37 — Installation Manual 33

Safety messagesSafety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefullybefore procee

Page 38

Components of 4-wire remote mount transmitter (aluminumhousing)Figure 3-1: A. End capB. Cap screwsC. TransmitterD. Mounting bracketMounting and sens

Page 39 — Installation Manual 35

Components of a 4-wire remote mount transmitter (stainless steelhousing)Figure 3-2: ABDCA. End capB. Cap screwsC. TransmitterD. Mounting bracket2. A

Page 40 — 36 Micro Motion

Components of 4-wire remote mount transmitter (aluminumhousing)Figure 3-3: A. End capB. Cap screwsC. TransmitterD. Mounting bracketMounting and sens

Page 41

Components of a 4-wire remote mount transmitter (stainless steelhousing)Figure 3-4: ABDCA. End capB. Cap screwsC. TransmitterD. Mounting bracket2. A

Page 42

4-wire cable preparationFigure 3-5: Cable layoutRun conduit to sensorMetal conduitWrap the drain wires twice around the shield and cut off the exces

Page 43 — Installation Manual 39

4-wire cable shieldingFigure 3-6: Assemble the Gland1. Fold the shield or braid back over the clamping insert and 1/8 inch (3 mm) past the O-ring.2.

Page 44

• Twisted pair construction.• Applicable hazardous area requirements, if the core processor is installed in ahazardous area.• Wire gauge appropriate f

Page 45

Wiring path for transmitters with aluminum housingFigure 3-7: A. 4-wire cableB. Mating connectorMounting and sensor wiring for 4-wire remote install

Page 46

Wiring path for transmitters with stainless steel housingFigure 3-8: AVDC+VDC–RS-485ARS-485BBA. 4-wire cableB. Mating connector3.4Rotate the user in

Page 47

Display componentsFigure 3-9: A. Transmitter housingB. Sub-bezelC. Display moduleD. Display screwsE. End-cap clampF. Cap screwG. Display cover1. Shu

Page 49

10. Turn the display cover clockwise until it is snug.11. Replace the end-cap clamp by reinserting and tightening the cap screw.12. Restore power to t

Page 50

Transmitter external grounding screwFigure 3-11: Mounting and sensor wiring for 4-wire remote installationsInstallation Manual 27

Page 51

Mounting and sensor wiring for 4-wire remote installations28 Micro Motion® Model 1700 and 2700

Page 52 — 48 Micro Motion

4 Mounting and sensor wiring for 9-wire remote installationsTopics covered in this chapter:•Mounting options•Prepare the 9-wire cable•Wire the transmi

Page 53 — 5.1 Mounting options

Components of 9-wire remote mount transmitterFigure 4-1: ABCA. Mounting bracketB. Cap screwsC. Transmitter2. Attach the mounting bracket to the wall

Page 54 — 50 Micro Motion

Components of 9-wire remote mount transmitterFigure 4-2: ABCA. Mounting bracketB. Cap screwsC. Transmitter2. Attach the mounting bracket to an instr

Page 55

Preparing jacketed cableFigure 4-3: 1. Trim 4 inches (100 mm) of cable jacket.2. Remove the clear wrap and filler material.3. Remove the foil that i

Page 56 — 52 Micro Motion

Preparing shielded or armored cableFigure 4-4: 1. Without cutting the shield, strip 9 inches (225 mm) of cable jacket.2. Strip 8 ½ inches (215 mm) o

Page 57

Cable typesMicro Motion supplies three types of 9-wire cable: jacketed, shielded, and armored. Notethe following differences between the cable types:•

Page 60

Cross-section view of shielded cableFigure 4-6: AC (1)BDE (4)F (4)G (5)A. Outer jacketB. Tin-plated copper braided shieldC. Foil shield (1 total)D.

Page 61

4.3 Wire the transmitter to the sensor usingjacketed cableFor ATEX installations, the jacketed cable must be installed inside a user-supplied sealedme

Page 62 — 58 Micro Motion

Sensor and transmitter terminal designationsTable 4-5: Wire color Sensor terminal Transmitter terminal FunctionBlack No connection 0 Drain wiresBrow

Page 63

F-Series, Model D, and Model DL sensor terminalsFigure 4-9: Mounting and sensor wiring for 9-wire remote installationsInstallation Manual 39

Page 64 — 60 Micro Motion

Model 2700 transmitter terminalsFigure 4-10: ABCDEFGHIJKA. BrownB. VioletC. YellowD. OrangeE. GrayF. BlueG. WhiteH. GreenI. RedJ. Mounting screwK. G

Page 65 — Installation Manual 61

CAUTION!Improperly sealed housings can expose electronics to moisture, which can cause measurementerror or flowmeter failure. Install drip legs in con

Page 66

Cross-section of assembled cable gland with cableFigure 4-12: ABCDE FGAA. CableB. Sealing nutC. SealD. Compression nutE. Braided shieldF. Brass comp

Page 67 — Installation Manual 63

Sensor and transmitter terminal designations (continued)Table 4-6: Wire color Sensor terminal Transmitter terminal FunctionGray 8 8 Right pickoff –W

Page 68 — 64 Micro Motion

F-Series, Model D, and Model DL sensor terminalsFigure 4-14: Mounting and sensor wiring for 9-wire remote installations44 Micro Motion® Model 1700 a

Page 69

Model 2700 transmitter terminalsFigure 4-15: ABCDEFGHIJKA. BrownB. VioletC. YellowD. OrangeE. GrayF. BlueG. WhiteH. GreenI. RedJ. Mounting screwK. G

Page 70

1 PlanningTopics covered in this chapter:•Flowmeter components•Outputs option identification•Environmental limits•Hazardous area classifications•Power

Page 71 — Installation Manual 67

Display componentsFigure 4-16: A. Transmitter housingB. Sub-bezelC. Display moduleD. Display screwsE. End-cap clampF. Cap screwG. Display cover1. Sh

Page 72

10. Turn the display cover clockwise until it is snug.11. Replace the end-cap clamp by reinserting and tightening the cap screw.12. Restore power to t

Page 73

Transmitter external ground screwFigure 4-18: Mounting and sensor wiring for 9-wire remote installations48 Micro Motion® Model 1700 and 2700

Page 74

5 Mounting and sensor wiring forremote core processor with remotesensor installationsTopics covered in this chapter:•Mounting options•Mount the remote

Page 75 — Installation Manual 71

Components of 4-wire remote mount transmitter (aluminumhousing)Figure 5-1: A. End capB. Cap screwsC. TransmitterD. Mounting bracketMounting and sens

Page 76 — 72 Micro Motion

Components of a 4-wire remote mount transmitter (stainless steelhousing)Figure 5-2: ABDCA. End capB. Cap screwsC. TransmitterD. Mounting bracket2. A

Page 77 — Installation Manual 73

Components of 4-wire remote mount transmitter (aluminumhousing)Figure 5-3: A. End capB. Cap screwsC. TransmitterD. Mounting bracketMounting and sens

Page 78

Components of a 4-wire remote mount transmitter (stainless steelhousing)Figure 5-4: ABDCA. End capB. Cap screwsC. TransmitterD. Mounting bracket2. A

Page 79

a. Loosen each of the four cap screws (4 mm).b. Rotate the bracket so that the core processor is oriented as desired.c. Tighten the cap screws, torqui

Page 80

4-wire cable preparationFigure 5-6: Cable layoutRun conduit to sensorMetal conduitWrap the drain wires twice around the shield and cut off the exces

Page 81 — 6 Wiring the power supply

Integral installationFigure 1-1: TransmitterSensor• High-temperature flexible conduit – Some high-temperature meters comepreinstalled with a flexibl

Page 82 — 78 Micro Motion

4-wire cable shieldingFigure 5-7: Assemble the Gland1. Fold the shield or braid back over the clamping insert and 1/8 inch (3 mm) past the O-ring.2.

Page 83 — 7.1 Basic analog wiring

• Twisted pair construction.• Applicable hazardous area requirements, if the core processor is installed in ahazardous area.• Wire gauge appropriate f

Page 84 — 80 Micro Motion

4. Connect wires to the appropriate terminals on the mating connector.ImportantNever ground the shield, braid, or drain wire(s) at the transmitter.Tip

Page 85

Wiring path for transmitters with stainless steel housingFigure 5-10: AVDC+VDC–RS-485ARS-485BBA. 4-wire cableB. Mating connector5.5Prepare the 9-wir

Page 86 — 82 Micro Motion

Preparing jacketed cableFigure 5-11: 1. Trim 4 inches (100 mm) of cable jacket.2. Remove the clear wrap and filler material.3. Remove the foil that

Page 88 — External resistor R

Cable typesMicro Motion supplies three types of 9-wire cable: jacketed, shielded, and armored. Notethe following differences between the cable types:•

Page 89

Bend radii of armored cableTable 5-5: Jacket material Outside diameter Minimum bend radiiStatic (no load) condition Under dynamic loadPVC 0.525 inch

Page 90 — 86 Micro Motion

Cross-section view of shielded cableFigure 5-14: AC (1)BDE (4)F (4)G (5)A. Outer jacketB. Tin-plated copper braided shieldC. Foil shield (1 total)D.

Page 91 — 8.5 Hazardous area wiring

5.6 Wire the remote core processor to the sensorusing jacketed cableFor ATEX installations, the jacketed cable must be installed inside a user-supplie

Page 92

4-wire remote installation – painted aluminum housingFigure 1-3: SensorCore processorTransmitter4-wire cable4-wire remote installation – stainless s

Page 93 — Installation Manual 89

Sensor and remote core processor terminal designations(continued)Table 5-6: Wire color Sensor terminal Remote core processor terminal FunctionOrange

Page 94

ELITE, H-Series, T-Series, and some F-Series sensor terminalsFigure 5-16: DIHFEABCGA. VioletB. YellowC. OrangeD. BrownE. WhiteF. GreenG. RedH. GrayI

Page 95 — Installation Manual 91

Model DT sensor terminals (user-supplied metal junction box withterminal block)Figure 5-18: 198765432AA. Earth groundRemote core processor terminals

Page 96 — 92 Micro Motion

5.7 Wire the remote core processor to the sensorusing shielded or armored cableFor ATEX installations, shielded or armored cable must be installed wit

Page 97 — Installation Manual 93

3. Screw the nipple into the conduit opening for the 9-wire cable. Tighten it to one turnpast hand-tight.4. Slide the compression ring, compression nu

Page 98 — 94 Micro Motion

Sensor and remote core processor terminal designationsTable 5-7: Wire color Sensor terminal Remote core processor terminal FunctionBlack No connecti

Page 99 — 9 I/O wiring for Model 2700

ELITE, H-Series, T-Series, and some F-Series sensor terminalsFigure 5-22: DIHFEABCGA. VioletB. YellowC. OrangeD. BrownE. WhiteF. GreenG. RedH. GrayI

Page 100 — 9.2 mA/HART wiring

Model DT sensor terminals (user-supplied metal junction box withterminal block)Figure 5-24: 198765432AA. Earth groundRemote core processor terminals

Page 101 — HART multidrop wiring

5.8 Rotate the user interface on the transmitter(optional)The user interface on the transmitter electronics module can be rotated 90º or 180° fromthe

Page 103 — Installation Manual 99

9-wire remote installation typeFigure 1-5: TransmitterJunction boxSensor9-wire cable• Remote core processor with remote sensor – A remote core proce

Page 104 — 100 Micro Motion

Transmitter external grounding screwFigure 5-28: 3. Ground the remote core processor according to applicable local standards, usingthe remote core p

Page 105 — Installation Manual 101

6 Wiring the power supply6.1 Wire the power supplyA user-supplied switch may be installed in the power supply line. For compliance with low-voltage di

Page 107 — 9.4 Discrete output wiring

7 I/O wiring for Model 1700 andModel 2700 transmitters with analogoutputsTopics covered in this chapter:•Basic analog wiring•HART/analog single loop w

Page 108 — 104 Micro Motion

7.2 HART/analog single loop wiringNoteFor HART communications:•600 Ω maximum loop resistance•250 Ω minimum loop resistanceHART/analog single loop wiri

Page 109 — Installation Manual 105

7.3 RS-485 point-to-point wiringRS-485 point-to-point wiringFigure 7-3: ABCA. Other devicesB. Primary controllerC. Multiplexer7.4HART multidrop wiri

Page 110 — 106 Micro Motion

HART multidrop wiringFigure 7-4: ABCDEFA. 250–600 Ω resistanceB. HART-compatible host or controllerC. HART-compatible transmittersD. Model 1700 or M

Page 111 — 9.5 Discrete input wiring

8 I/O wiring for Model 1700 andModel 2700 transmitters withintrinsically safe outputsTopics covered in this chapter:•Safe area mA output wiring•Safe a

Page 112

Safe area mA output load resistance valuesFigure 8-2: 1000900800700600500400300200100012 14 16 18 20 22 24 26 28 30OPERATING REGIONSupply voltage VD

Page 113 — 10 Specifications

Safe area mA output load resistance valuesFigure 8-4: 1000900800700600500400300200100012 14 16 18 20 22 24 26 28 30OPERATING REGIONSupply voltage VD

Page 114 — 10.2 Input/output signals

Remote core processor with remote sensor installation typeFigure 1-6: Core processorTransmitter4-wire cable9-wire cableSensorJunction box1.1.2 Maxim

Page 115 — 10.3 Local display

Safe area HART multidrop wiringFigure 8-5: ABCDEFA. 250–600 Ω resistanceB. HART-compatible host or controllerC. HART-compatible transmittersD. Model

Page 116 — 112 Micro Motion

Safe area frequency output/discrete output load resistance valuesFigure 8-7: 1000090008000700060005000400030002000100005 7 9 11 13 15 17 19 21 23OPE

Page 118 — Specifications

8.5.1 Hazardous area mA output wiringHazardous area mA output wiringFigure 8-8: ABCDEHazardous area Safe areaA. VinB. VoutC. GroundD. RloadE. Rbarri

Page 119 — Installation Manual 115

Safe area mA output load resistance valuesFigure 8-9: 1000900800700600500400300200100012 14 16 18 20 22 24 26 28 30OPERATING REGIONSupply voltage VD

Page 120 — 116 Micro Motion

8.5.2 Hazardous area frequency/discrete output wiring usinggalvanic isolatorHazardous area frequency/discrete output wiring using galvanicisolatorFigu

Page 121 — Installation Manual 117

8.5.3 Hazardous area frequency/discrete output wiring usingbarrier with external load resistanceHazardous area frequency/discrete output wiring using

Page 122 — 118 Micro Motion

Safe area frequency output/discrete output load resistance valuesFigure 8-12: 1000090008000700060005000400030002000100005 7 9 11 13 15 17 19 21 23OP

Page 123

I/O wiring for Model 1700 and Model 2700 transmitters with intrinsically safe outputs94 Micro Motion® Model 1700 and 2700

Page 124 — *20001700*

9 I/O wiring for Model 2700transmitters with configurable input/outputsTopics covered in this chapter:•Channel configuration•mA/HART wiring•Frequency

(Ocr-Read Summary of Contents of some pages of the Emerson Micro Motion 1700 Document (Main Content), UPD: 05 July 2023)

  • 38, • The device being polled (slave) cannot have special units set for density. Otherwise, the master will reject the base density and report the following alarm: A115: No External Input or Polled Data Alert • On the slave side, setup the HART Primary Variable for Base Density. The master will reject anything other than Base Density for the HART Primary Variable and trigger an A115 alarm. • The density units on the transmitter and the polled …

  • 157, Alert num- ber Alert title Possible cause Recommended actions A002 RAM Error (Core Pro- cessor) The core processor has experienced a memory error. • Cycle power to the meter. • Replace the core processor. • Contact customer support. A003 No Sensor Response The transmitter is not receiving one or more basic electrical signals from the sensor. This alert often occurs in conjunc- tion with Alert 102. • Check the drive gain…

  • 183, Emerson Micro Motion 1700 10.22 Check Flow Direction If Flow Direction is set inappropriately for your process, the transmitter may report flow data that is not appropriate for your requirements. The Flow Direction parameter interacts with actual flow direction to affect flow values, flow totals and inventories, and output behavior. For the simplest operation, actual process flow should match the flow arrow that is on the side of the sensor case. Procedure 1. Verify the actual direction of process flow through the …

  • 93, Emerson Micro Motion 1700 Important If you assign Flow Switch to the Discrete Output, you should also configure Flow Switch Variable, Flow Switch Setpoint, and Hysteresis. Related information Configure an enhanced event Fault indication with the Discrete Output Configure Flow Switch parameters Display OFF-LINE MAINT > OFF-LINE CONFG > IO > CH B > SET DO > CONFIG FL SW ProLink III Device Tools > Configuration > I/O > Outputs > Disc…

  • 81, • If you have configured Display Variable 1 to track mA Output Process Variable, be aware that changing the configuration of mA Output Process Variable will change the contents of Display Variable 1. Procedure Set mA Output Process Variable as desired. The default setting is Mass Flow Rate. Postrequisites If you changed the setting of mA Output Process Variable, verify the settings of Lower Range Value (LRV) and Upper Range Value (URV). Options …

  • 91, Emerson Micro Motion 1700 Options for Frequency Output Fault Action Options for Frequency Output Fault Action Table 6-5: Label Frequency Output behavior Upscale Goes to configured Upscale value: • Range: 10 Hz to 15000 Hz • Default: 15000 Hz Downscale 0 Hz Internal Zero 0 Hz None (default) Tracks data for the assigned process variable; no fault action CAUTION! If you set mA Output Fault Action or Frequency Output Fault Action to None, be sure to set Digital Communications Fault Action to …

  • 63, Option Description Enabled The display automatically scrolls through each display variable as specified by Scroll Rate. The operator can move to the next display variable at any time using Scroll. Disabled (de- fault) The display shows Display Variable 1 and does not scroll automatically. The operator can move to the next display variable at any time using Scroll. 2. If you enabled Auto Scroll, set …

  • 19, Part II Configuration and commissioning Chapters covered in this part: • Introduction to configuration and commissioning • Configure process measurement • Configure device options and preferences • Integrate the meter with the control system • Complete the configuration Configuration and commissioning Configuration and Use Manual 11

  • 92, Emerson Micro Motion 1700 6.4.1 Configure Discrete Output Source Display OFF-LINE MAINT > OFF-LINE CONFG > IO > CH B > SET DO > DO SRC ProLink III Device Tools > Configuration > I/O > Outputs > Discrete Output Field Communicator Configure > Manual Setup > Inputs/Outputs > Discrete Output > DO Assignment Overview Discrete Output Source controls which device condition or process condition is reported via the Discrete Output. Procedure Set Discrete Output Source to the…

  • 69, Effects of Update Rate = Special Incompatible features and functions Special mode is not compatible with the following features and functions: • Enhanced events. Use basic events instead. • All calibration procedures. • Zero verification. • Restoring the factory zero or the prior zero. If required, you can switch to Normal mode, perform the desired procedures, and then return to Special mode. Proce…

  • 240, Transmitter components and installation wiring 232 Micro Motion Model 1700 Transmitters with Analog Outputs

  • 243, September 2006, version 5.x Modification type Change Expansion • Discrete Output assignable as a flow switch • Discrete Output fault indication configurability • Discrete Input support for multiple action assignments • Added support for querying the display LED status via Mod- bus • Additional HART and Modbus commands • Process comparator expanded to five configurable events • Factory configuration restore function • Factory zero restore function • Alarm history expanded �…

  • 48, Procedure Set Density Measurement Unit to the option you want to use. The default setting for Density Measurement Unit is g/cm3 (grams per cubic centimeter). Options for Density Measurement Unit The transmitter provides a standard set of measurement units for Density Measurement Unit. Different communications tools may use different labels. Unit description Label Display ProLink III Field Communicator Specific gravity (1) SGU SGU SGU Grams per cubic…

  • 231, Transmitter default values and ranges (continued)Table D-1: Type Parameter Default Range Comments Special units Base mass unit g Base mass time sec Mass flow conversion factor 1 Base volume unit L Base volume time sec Volume flow conversion factor 1 Variable map- ping Primary variable Mass flow Secondary variable Volume flow Tertiary variable Mass flow Quaternary variable Volume flow mA Output 1 Primary variable Mass flow LRV –200.00…

  • 115, 8 Transmitter operation Topics covered in this chapter: • Record the process variables • View process variables • View transmitter status using the status LED • View and acknowledge status alerts • Read totalizer and inventory values • Start and stop totalizers and inventories • Reset totalizers • Reset inventories 8.1 Record the process variables Micro Motion suggests that you make a reco…

  • 216, Connection over multidrop networkFigure B-4: B A C D A. Signal converter B. 250–600 Ω resistance C. Devices on the network D. Master device 5. Start ProLink III. 6. Choose Connect to Physical Device. 7. Set Protocol to HART Bell 202. Tip HART/Bell 202 connections use standard connection parameters. You do not need to configure them here. 8. If you are using a USB signal converter, enable Toggle R…

Table of Contents for Emerson Micro Motion 1700:

  • 4.5 Configure density measurement ……………………………………………………………………………………. 45 4.5.1 Configure Density Measurement Unit …………………………………………………………………46 4.5.2 Configure slug flow parameters …………………………………………………………………………47 4.5.3 Configure Density Damping ………………………………………

  • View test result data using ProLink II 1. Choose Tools > Meter Verification > Run Meter Verification and click View Previous Test Results and Print Report. The chart shows test results for all tests stored in the ProLink II database. 2. (Optional) Click Next to view and print a test report. 3. (Optional) Click Export Data to CSV File to save the data to a file on your PC. View test result data using ProLink III 1. Choose Device Tools > Diagnostics > Meter Verification and click Previous T

  • 5.4.1 Configure Update Rate Display Not available ProLink II ProLink > Configuration > Device > Update Rate ProLink III Device Tools > Configuration > Process Measurement > Response > Update Rate Field Communicator Configure > Manual Setup > Measurements > Update Rate Overview Update Rate controls the rate at which process data is polled and process variables are calculated. Update Rate = Special produ

  • Connection over local loopFigure C-3: A C D E R1 R3 R2 B A. PC B. Signal converter C. Any combination of resistors R1, R2, and R3 as necessary to meet HART communication resistance requirements D. DCS or PLC E. Transmitter, with wiring compartment and power supply compartment opened Note This figure shows a serial port connection. USB connections are also supported. 4. To connect over a HART multidrop network: a. Attach the leads from the signal converter to any point on the network. b. Add resistance as necessary. Important HART/Bel

  • Overview Digital Communications Fault Action specifies the values that will be reported via digital communications if the transmitter encounters an internal fault condition. Procedure Set Digital Communications Fault Action as desired. The default setting is None. Options for Digital Communications Fault Action Options for Digital Communications Fault ActionTable 6-15: Label Description ProLink II ProLink III Field Communicator Upscale Upscale Upscale �

  • • Current flowmeter identification data • Current flow and density configuration parameters • Current zero values • Current process values for mass flow rate, volume flow rate, density, temperature, and external pressure • Customer and test descriptions (if entered by the user) If you use ProLink II or ProLink III to run a test, a test result chart and a test report are displayed at the completion of the test. On-screen directions are provided to manipulate the test data or export the data to a CSV file for offline analysis. View

  • Effect of Flow Direction on frequency outputs Flow Direction affects how the transmitter reports flow values via the frequency outputs. The frequency outputs are affected by Flow Direction only if Frequency Output Process Variable is set to a flow variable. Effect of the Flow Direction parameter and actual flow direction on frequency outputs Table 4-6: Flow Direction setting Actual flow direction Forward Zero flow Reverse Forward

  • f. Test the gray terminal against all other terminals except the blue one. g. Test the orange terminal against all other terminals except the yellow and violet ones. h. Test the yellow terminal against all other terminals except the orange and violet ones. i. Test the violet terminal against all other terminals except the yellow and orange ones. There should be infinite resistance for each pair. If there is any resistance at all, there is a short between terminals. Postrequisites To return to normal operati

  • Postrequisites For each channel that you configured, perform or verify the corresponding input or output configuration. When the configuration of a channel is changed, the channel’s behavior will be controlled by the configuration that is stored for the selected input or output type, and the stored configuration may not be appropriate for your process. After verifying channel an

  • Using the display to view and acknowledge the status alarmsFigure 8-2: SEE ALARM Yes Scroll and Select simultaneously for 4 seconds ACK ALL Yes EXIT Select No Alarm code Scroll ACK Yes Select No Active/ unacknowledged alarms? NoYes Select NO ALARM EXIT Scroll Scroll Select Scroll ScrollSelect Is ACK ALL enabled? Yes No Transmitter operation 124 Micro Motion ® Model 1700 Transmitters with Analog Outputs

  • Configuration menu (continued)Figure B-13: ProLink > Configuration Device • Model • Manufacturer • Hardware Rev • Distributor • Software Rev • ET O • CP Software Rev • CP ETO • Option Board • Firmware Checksum • CP Firmware Checksum • Tag • Date • Descriptor • Message • Sensor type • Transmitter Serial • Floating PT Ordering • Add Comm Resp Delay • Restore Factory Configuration • Digital Comm Fault Set

  • Q quaternary variable (QV) 105 R radio frequency interference (RFI) troubleshooting 194 Rate Factor 91 reference density, See standard density refresh rate display 62 Response Time 70 S safety messages ii scaling frequency outputs 90 mA outputs 83 Scroll Rate 63 secondary variable (SV) 105 security access to display menus 67 sensor coils troubleshooting 201 Sensor Flange Type 79 Sens

Questions, Opinions and Exploitation Impressions:

You can ask a question, express your opinion or share our experience of Emerson Micro Motion 1700 device using right now.

Понравилась статья? Поделить с друзьями:
  • Белова нейрореабилитация руководство для врачей купить
  • Типовая должностная инструкция начальника участка в строительстве
  • Asus crosshair v formula z инструкция на русском скачать
  • Инструкция ac rapid rac 09 су т6
  • Liver life инструкция по применению на русском языке