1
GRID
Krishnakumar Venkataraman
Simon Richards
12/03/2011
MiCOM P120 to P127 Range
Overcurrent Relays
Presentation title — 01/01/2010 — P 2
PlatformPlatformSelectorSelector
2
Presentation title — 01/01/2010 — P 3
Selection Tips: MiCOM P12xy or P14x Feeder
YIndependent derived E/F and measured transformer Y-n Standby E/F in one device
YProgrammable curvesYDistance to fault requiredYA/R requires check synch, or sequence co-ordination
YBasic autoreclose with modest I/O countsYEthernet protocols IEC 61850 or DNP3 OE requiredYFull graphical programmable logic
YLogic functionality satisfied with 8 boolean equationsY> 250 event records or 5 disturbance traces
YI/O count no greater than 8o + 7i (12i for P127)YWith function keysY> 4 programmable LEDs
YSmall case size 20TE or 30TEYWithdrawable devicesYSimple overcurrent and earth fault applications
MiCOM AlstomP14x Preferable
P12xy Series Preferable
Presentation title — 01/01/2010 — P 4
OverviewOverview
3
— — P 5
Non-Directional RelaysMiCOM P120, P121, P122 & P123
P120: Earth fault or Single phase O/C
P121: Basic 3 phase + Earth O/C
P122: 3 phase + Earth O/C
P123: 3 phase + Earth O/C + Autoreclose
Presentation title — 01/01/2010 — P 6
P125: Directional / Non Directional Single PhaseAnd Earth Fault Protection
MiCOM P125, P126 & P127Directional Relays
P125: Single phase Overcurrent / earth fault & directional earth fault protection
4
Presentation title — 01/01/2010 — P 7
P126: Three phase Overcurrent & directional/non directional earth fault protection
P127: Directional / non directional three-phase Overcurrent & directional /non directional earth fault protection
MiCOM P125, P126 & P127Directional Relays
Presentation title — 01/01/2010 — P 8
P120-P127 Range: Protection Features
5
Presentation title — 01/01/2010 — P 9
P120-P127 Range: Control, Logic and Events
Presentation title — 01/01/2010 — P 10
NonNon—DirectionalDirectionalApplicationsApplications
6
— — P 11
97 7811.6
158168
99
Panel cut-out Flush mountingfixing details
All dimensionsin mm.
4 holes / 4.4 (M4 screw)O
25.1 226
151.2 max.Alarme C
P121MiCOM
IA = 214.50 A
103
177
Trip
Auxiliarysupply
Equip. fail
AUX. 1
AUX. 3
AUX. 2
AUX. 4
24.6 52
4 holes / 3.4O
MiCOM P120 – P123 Range Housing(20TE)
— — P 12
51
52 RL1 TripProgrammableLogic inputs
Phase orearth CT
P120
RS 485
Busbar
50
51N 50N
L 1
RL 2RL 3RL 4
Supervisionsystem
Uaux
L 2
ProgrammableLogic outputs
86
RL0 Watchdog
MiCOM P120: Single Line Diagram
7
— — P 13
51
52 RL1 TripProgrammableLogic inputs
Earth CT
P121
RS 485
Busbar
50
51N 50N
L 1
RL 2RL 3RL 4
Supervisionsystem
Uaux
Phase CTs 3
L 2
ProgrammableLogic outputs
86
RL0 Watchdog
MiCOM P121: Single Line Diagram
— — P 14
52 RL1 Trip
RL0
ProgrammableLogic inputs
Earth CT
P122
RS 485
Busbar
L 1
L 3
RL 2RL 3RL 4
Supervisionsystem
Uaux
Phase CTs 3
L 2
RS 232 Front panel PC
RL 5RL 6
ProgrammableLogic outputs
Watchdog
51 50
51N 50N
46
37 49
50BF 86
MiCOM P122: Single Line Diagram
8
— — P 15
MiCOM P123 : Single Line Diagram
51
52 RL1 Trip
RL0
ProgrammableLogic inputs
ProgrammableLogic outputs
Earth CT
P123
RS 485
Busbar
50
51N 50N
L 1
L 3
RL 2RL 3RL 4
Supervision systemUaux
Phase CTs 3
L 2
46 RS 232
Front panel PC
RL 5RL 6
L 4L 5
RL 7RL 8
37 49
79
50BF 86
Watchdog
Presentation title — 01/01/2010 — P 16
DirectionalDirectionalApplicationsApplications
9
Presentation title — 01/01/2010 — P 17
MICOM Case with MIDOS terminals
P125 CASE:− 4U height (177 mm)− 272 mm depth− 20 TE width (102.8mm)
P126 & P127 CASE:− 4U height (177 mm)− 272 mm depth− 30 TE width (154.2mm)
MiCOM P125 P126 & P127Housing
Presentation title — 01/01/2010 — P 18
Busbar
52
ResidualVT
SupervisionSystem
Uaux
Logic inputs
Setting/ControlSoftware
67N
Trip
59N
86
32N
P125L1L2L3L4
Logic outputs
Watch Dog
RL 4RL 5RL 6
RL 1RL 2RL 3
RS 232
RS 485
MiCOM P125
Earth CT
10
Presentation title — 01/01/2010 — P 19
52
ResidualVT
SupervisionSystem
UauxSetting/ControlSoftware
67N
Trip 59N
8632N
P126
Earth CT
Logic outputs
Watch Dog
RL 4RL 5RL 6
RL 1RL 2RL 3
RS 232
RS 485
Phase CTs 50
51
Logic inputs
L1L2L3L4
49
L5L6L7
RL 8RL 7
46
37
50BF
TCS
79
46BC
50N51N
Busbar
SOTF
MiCOM P126
Presentation title — 01/01/2010 — P 20
Setting/ControlSoftware
Busbar
Uaux
Trip
Earth CT
Phase CTs
SupervisionSystem
67N
59N
8632N
P127
Logic outputs
Watch Dog
RL 4RL 5RL 6
RL 1RL 2RL 3
RS 232
RS 485
5051
Logic inputs
L1L2L3L4
49 L5L6L7
RL 8RL 7
46
37
50BF
TCS
79 46BC
50N51N67
SOTF
52
MiCOM P127
11
— — P 21
Five additional opto-inputs− In addition to existing seven opto-inputs, five digital inputs are
now available (Input 8, 9, A, B, C)− 12 opto-inputs in total
− Benefits :• Increase number hardwired digital information• No need to use extra I/O box
P127 Hardware Option
— — P 22
− In addition to existing RS485 port for digital control system communication, a 2nd RS485 port is now available to perform remote maintenance in Modbus:
• Settings modification• Records upload (25 fault, 250 events & 5 disturbance)• Measurements upload• Remote command via MiCOM S1
− Benefits :• Speed up post fault analysis • Minimize power system outage• Separate network fault analysis from real time process• Multi drop connection to centralize maintenance record in a single
PC
P127 Option:Additional 2nd RS485 for remote maintenance
Digital Control System
Maintenance PC
IEC103 or Modbus or
DNP3Modbus
only
RS485 n°1RS485 n°2
12
— — P 23
− To ensure an accurate time stamping of P127 records, IRIG-B time synchronization from via GPS clock is now supported :
• Demodulated signal• Modulated signal (via BNC adapter)
− Both option in a single hardware variant with software selection
− Benefits :• Compensate internal clock drift• 1ms of time stamping accuracy • Full compatibility with any GPS clock• Minimize protection relays variants (2 in 1 solution)• Automatic switch to RS485 if GPS signal lost
P127 Option:IRIG-B Synchronisation
Presentation title — 01/01/2010 — P 24
ProtectionProtectionFunctionsFunctions
13
— — P 25
I>>> tI>>>
tI>>I>>
tI>I>
Ith
I<
Current
Tim
e
Thresholds
Presentation title — 01/01/2010 — P 26
Protection and Control FunctionsEarth CT Ordering Options
Three current threshold ranges selected by ordering code:− From 0.100 to 40 Ien [ A version ]− From 0.010 to 8 Ien [ B version ]− From 0.002 to 1 Ien [ C version ]
Earth Fault Overcurrent
14
— — P 27
Ie>>> tIe>>>
tIe>>Ie>>
Ie>
Current
Tim
e
Thresholds
— — P 28
STI : Short Time InverseSI* : Short InverseVI* : Very InverseEI* : Extremely InverseLTI : Long Time InverseRI : Electromechanical
* IEC Curves
Ope
ratin
g Ti
me
(sec
onds
)
Setting Current Multiple1 10 100
0.001
0.01
0.1
1
10
100
1000
10000
100000
20
IEC and RI Curves
15
— — P 29
STI : Short Time Inverse (CO2)MI* : Moderately InverseI : Inverse (CO8)VI* : Very InverseEI* : Extremely Inverse
* IEEE/ANSI Curves
Ope
ratin
g Ti
me
(sec
onds
)
Setting Current Multiple1 10 100
0.01
0.1
1
10
100
1000
10000
20
IEEE/ANSI Curves
— — P 30
T = 45900/ [(I/Is)5,6 — 1]
Ope
ratin
g tim
e (s
econ
ds)
Current (multiples of Is)1 10 100
0.001
0.01
0.1
1
10
100
1000
10000
100000
201,6
TMS = 1
RC Rectifier Curve
16
— — P 31
T =a I + b
Type of curve
1
2
3
a b
-0.0897
-0.0897
-0.0897
4.0897
4.5897
5.0897
Rated current = 1AEarth current range = 0.01 Ien to 8 IenCore balanced CT = 20/1
Curve 1
Curve 2Curve 3
LABORELEC Curve
Presentation title — 01/01/2010 — P 32
I> t
I>> t
I>>> t
I> t
I>> t
I>>> t
Application OptionsInterlocking of Curve and DT Threshold(s)
t
II>>I>
t_I>
I> >> >>> Interlock NO
t
II>>I>
t_I>>
I> >> >>> Interlock YES
t_I>>>
I>>>
1st threshold suspended by 2nd and 3rd
threshold pickup
17
Presentation title — 01/01/2010 — P 33
Benefits:No requirement to use
alternate setting groupsMay eliminate need for earth fault
stabilising resistorSecurity /dependability on energisation
Potential applications:Motor feedersHV transformer earth fault protectionAir conditioningResistive heating
Energisation period characteristic
Normal load characteristic
Energisationcurrent profile
Current
Time
Cold Load Pick-Up
Presentation title — 01/01/2010 — P 34
Thermal Replica Overload Protection [49]
18
Presentation title — 01/01/2010 — P 35
Circuit Breaker Failure [50BF]
Three independent high speed undercurrent threshold I<
Definite time tBF
Possibility to suspend blocking outputs (logic selectivity)
IA<
Trip ordertBF
&&
IB<
IC<
CB Fail(50BF)
IA<
Trip ordertBF
&&
RESET tBFTIMER
IB<
IC<
Presentation title — 01/01/2010 — P 36
Circuit Breaker Monitoring
Cumulated I or I2 per phase− Adjustable alarm threshold− Display of Σ I or Σ I2
Total of CB open number− Adjustable alarm threshold
Operating time − Adjustable alarm thresholds for opening and closing
times
19
— — P 37
(RL1) Trip
P12x/y
Busbar
52
CB trip circuitfailure
+ Uaux
— Uaux
CB coil
52a
52bRS 485 Supervision system
RS 232 Front panel PC
Trip Circ
Trip Circuit Supervision
— — P 38
Boolean logic equations− Opto-input status to be directly used in
Boolean logic equation to perform basic automation scheme
− Boolean logic equation interaction− Possibility to inhibit alarm signal of Boolean
logic result− Settings:
• Affect selected input in each equation• Use Equ.X in Equ.Y• Define if equation alarm should be
inhibited or not in Configuration/Alarms
Logic Equations
20
Presentation title — 01/01/2010 — P 39
Directional RelayDirectional RelayExtra FunctionsExtra Functions
Presentation title — 01/01/2010 — P 40
Three directional / non directional three phase overcurrent thresholds
Directional phase elements internally polarised by quadraturewith the relevant phase to phase voltage
Synchronous polarisation for the collapse of the phase to phase voltage
Directional / non directional three phase Overcurrent
MiCOM P127Protection and Control Functions
21
Presentation title — 01/01/2010 — P 41
MiCOM P127Protection and Control Functions
Trip conditions:− Iphase thresholds
exceeded in module− Iphase current vector
in the tripping zone
Directional three phase Overcurrent Forward and reverse zone
Presentation title — 01/01/2010 — P 42
MiCOM P125 P126 & P127Protection and Control Functions
Trip conditions:− Ie and Ue thresholds
exceeded in module− Ie current vector in
the tripping areaIen=1A:
− Ie [mA] + Ue [V] > 18Ien=5A:
− Ie [mA] + 5 x Ue [V] > 90
Directional Earth Fault Overcurrent Forward and reverse zone
22
Presentation title — 01/01/2010 — P 43
MiCOM P125 P126 & P127Protection and Control functions
Operation mode selectable:− Pe: residual active power− IeCosφ: active earth fault current component
Two thresholds (Pe>; Pe>>) or (IeCos>; IeCos>>
First threshold with:− Definite trip delay time− or Inverse trip delay time
• IEC, ANSI/IEEE, RI and RECT curves available• Definite reset time available on IEC and RI curves• Definite or Inverse time on IEEE/ANSI curves
Wattmetric & IeCosϕ Earth Fault Protection
Presentation title — 01/01/2010 — P 44
Definite trip delay time for second and third thresholds
Setting characteristic angle ϕc for the thresholds− Pe= Ue x Ie x Cos (ϕ – ϕc)− Internal Automatic setting adaptation for 1/5A Ien− IeCos(ϕ – ϕc )− ϕ = Ue^Ie− Accuracy range of Pe and IeCos measurement: 85°< ϕ <+
85°
IeSinϕ available by adding 90° to the characteristic angle ϕc
MiCOM P125 P126 & P127Protection and Control functions
Wattmetric & IeCosϕ Earth Fault Protection
23
Presentation title — 01/01/2010 — P 45
E/F IcosϕUe = Residual voltageUe’ = Polarisation voltage after RCA settingIecosϕ’ = Active component referred to Ue’Iesinϕ’ = Reactive component referred to Ue’
Ue
Ue’
RCAIe
Iesinϕ’Iecosϕ’
Trip zone
Trip zone
UeUe’
RCA
IeIesin
ϕ’
Iecosϕ’
Trip zo
ne
Trip zo
ne
Earth Wattmetric/IeCosϕ Protection
MiCOM P125 P126 & P127Protection and Control Functions
Presentation title — 01/01/2010 — P 46
MiCOM P127Three Phase Overvoltage [59]
Two overvoltage thresholds− Each threshold independently configurable for AND/OR operating mode− Definite trip time
»U»A / AB»>..>> »>=1
»TRIP DELAY
»U»B/BC»>..>>
»U»C/CA»>..>>
»&
command
UA / AB>..>> >=1
TRIP DELAY
UB/BC>..>>
UC/CA>..>>
&AND/OR
Trip
Alarm
24
Presentation title — 01/01/2010 — P 47
MiCOM P127Three Phase Undervoltage [27]
Two undervoltage thresholds− Each threshold independently configurable for AND/OR operating mode− Definite trip time
UA / AB<..<< ³ 1
UB/BC<..<<
UC/CA<..<<
&
command
Alarm
UA / AB<..<< ≥ 1
TRIP DELAY
UB/BC<..<<
U C/CA<..<<
&AND/OR
Trip
Presentation title — 01/01/2010 — P 48
MiCOM Px20 Supplied by Alstom:Advantages
• Continuity of Expertise: The Centre of Excellence in Stafford, UK, remains a core asset, supplemented by satellite expert teams.
• Benefit from local support, right through to the flagship APPS training courses, with all of the know-how in Alstom.
• On-call assistance from our Contact Centre in Stafford, UK – a unique Alstom Grid facility.
• The entire value chain that customers previously experienced in AREVA T&D Automation – with a technically strong, respected local face to the customer. All from Alstom Grid.
• We offer the full scheme solution: Auxiliary/Trip/Hinged Armature relays – right up to MiCOM Px40 – a full solution from Alstom.
• Loose products to complete PACiS schemes – with local commissioning, and application support.
25
GRID
END
Каталог
-
-
Устройство релейной защиты Sepam
-
Устройства микропроцессорной защиты MiCOM
-
Микропроцессорные терминалы РЗА серии ТОР
-
Микропроцессорные терминалы РЗА серии БМРЗ
-
Микропроцессорные терминалы РЗА серии БЭМП
-
Микропроцессорные терминалы РЗА серии Сириус
-
Регуляторы напряжения
-
Реле микропроцессорное защиты серии МР
-
-
-
Реле защиты трансформатора
-
Микроэлектронные и микропроцессорные реле
-
Реле тока
-
Реле напряжения
-
Реле времени
-
Реле промежуточное
-
Реле указательное
-
Реле автоматики, контроля и сигнализации
-
Реле управления
-
Реле мощности
-
Реле защиты электродвигателей
-
Блоки реле и комплекты защит
-
Прочие реле
-
Реле защиты генератора
-
-
-
Силовые масляные трансформаторы
-
Сухие трансформаторы
-
Измерительные трансформаторы тока
-
Измерительные трансформаторы напряжения
-
-
-
Устройства дуговой защиты ДУГА
-
Устройства дуговой защиты ОВОД
-
Устройства дуговой защиты ФВИП
-
Устройства дговой защиты БДЗ
-
Устройства дуговой защиты Орион
-
Устройства дуговой защиты ПД
-
Устройства дуговой защиты РДЗ
-
Устройство дуговой защиты БССДЗ
-
-
-
Низковольтные комплектные устройства
-
Комплектные распределительные устройства КРУ
-
Камеры сборные одностороннего обслуживания КСО
-
Вакуумные и элегазовые выключатели
-
Выкатные элементы для КРУ
-
Коммутационные аппараты
-
Комплектные распределительные устройства наружной установки КРУН
-
Ограничители перенапряжений нелинейные ОПН
-
-
-
Запасные части к трансформаторам
-
Запасные части для ячеек КРУ, КМ, КМВ
-
Запасные части к масляным выключателям и разьеденителям
-
Оперативная блокировка
-
-
-
Автоматические выключатели
-
Звукосигнальная аппаратура
-
Клеммные зажимы
-
Коммутационная аппаратура
-
Контакторы
-
Переключатели, выключатели, кнопки
-
Пускатели электромагнитные
-
Светосигнальная арматура
-
-
-
Преобразователи измерительне
-
Стрелочные приборы
-
Счетчики электроэнергии
-
Цифровые приборы
-
-
-
Legrand
-
CHINT Electric
-
Меандр | Все продукты
-
Новатек-Электро
-
Schneider Electric
-
-
-
Апаратура высокочастотной связи
-
Двигатели, генераторы, сельсины
-
Исполнительные механизмы МЭО, МЭОФ
-
Кабель и провод
-
Резисторы, предохранители, радиодетали
-
Шкафы
-
Услуги
-
-
Монтаж и обслуживание трансформаторов
-
Доставка и внедрение оборудования на объект
-
Подбор и изготовление оборудования
-
-
-
Ретрофит (модернизация) ячеек КРУ, КСО
-
-
-
Гарантийное обслужование
-
Пуско-наладочные работы
-
Шеф-монтаж
-
-
-
Обучение после внедрения оборудования
-
Технологическая поддержка
-
Адрес
428024, Россия, г. Чебоксары, Мясокомбинатский проезд, д. 14
MiCOM P127 | Многофункциональная направленная защита линии
Возможны дополнительные опции
MiCOM P127 | Многофункциональная направленная защита линии
Возможны дополнительные опции
- Как купить
- Оплата
- Доставка
Чтобы приобрести понравившийся товар, необходимо его заказать. Есть несколько сценариев того, как это можно сделать.
- Выбрать понравившийся товар и нажать кнопку «Заказать». При оформлении заказа заполнить форму. Вписать информацию в поля: ФИО, телефон и e-mail. Затем вам перезвонит менеджер, чтобы подтвердить ваше согласие на совершение покупки.
- Выбрать понравившийся товар и нажать кнопку «В корзину». Затем перейти в корзину и нажать «Оформить заказ». Далее заполнить форму с контактными данными и отправить заявку. С вами свяжется менеджер для дальнейшего обсуждения.
- Перейти в карточку товара и нажать «Купить в один клик». После нажатия нужно заполнить форму и отправить заявку. С вами свяжется менеджер для дальнейшего обсуждения.
Мы работаем с юридическими лицами.
- Безналичный расчет.
Можем доставить ваш заказ собственными ресурсами. Либо через варианты доставки:
- Мы осуществляем доставку грузов по всей России и ближнему зарубежью. По желанию Заказчика доставка груза может быть осуществлена, как автомобильным, так и железнодорожным транспортом. Экспедирование по г.Чебоксары осуществляем бесплатно. Как показывает статистика, наиболее высоким спросом среди наших клиентов являются следующие транспортно-экспедиционные компании: «Деловые Линии», «ПЭК», «ЖелДорЭкспедиция», «КИТ», «Энергия»
- Курьерская доставка. Курьерская доставка работает с 9:00 до 18:00. Когда товар поступит на склад, курьерская служба свяжется для уточнения деталей. Специалист предложит выбрать удобное время доставки и уточнит адрес.
- Самовывоз со склада. Для получения заказа обратитесь к сотруднику в зоне выдачи и назовите номер.
Вам может понравиться
Устройства микропроцессорной защиты MiCOM
P12y/EN CM/C22
Page 14/24
4.3.4
Line CT primary
Line CT Sec
E/Gnd CT primary
E/Gnd CT Sec
Line VT primary
Line VT Sec
E/Gnd VT primary
E/Gnd VT Sec
I>
I>
tI>
tI> (if DT)
Curve (if IDMT)
TMS value (if IDMT)
K value (if RI)
U>
U>
tU>
Ie>
Ie>
tIe>
tIe> (if DT)
Curve (if IDMT)
TMS value (if IDMT)1
Ue>>>>
tUe>>>>
TRIP tI>
TRIP tU>
TRIP tIe>
TRIP Ue>>>>
CONFIGURATION
General Options
2Vpp+Vr
Transfo. Ratio
1 A
1 A
1 A
1 A
0.100 kV
100.0 V
0.100 kV
100.0 V
Protection Menu G1
Yes
1 In
DT or IDMT or RI
10 s
IEC VI or IEEE VI
1
1
Yes
20V
10 s
Yes
1 In
DT or IDMT or RI
20 s
IEC VI or IEEE VI
K value (if RI)=1
10 V
10 s
Automation Menu
YES
YES
YES
YES
Commissioning and Maintenance
MiCOM P125/P126 & P127