Контроллер dixell wing v620 инструкция на русском

dIXEL

XW20K AND T620 – V620 – CX620

1. GENERAL WARNING

PLEASE READ BEFORE USING THIS MANUAL

This manual is part of the product and should be kept near the instrument for easy and quick

reference.

The instrument shall not be used for purposes different from those described hereunder. It

cannot be used as a safety device.

Check the application limits before proceeding.

SAFETY PRECAUTIONS

Check the supply voltage is correct before connecting the instrument.

Do not expose to water or moisture: use the controller only within the operating limits avoiding

sudden temperature changes with high atmospheric humidity to prevent

condensation

Warning: disconnect all electrical connections before any kind of maintenance.

Fit the probe where it is not accessible by the End User. The instrument must not be opened.

In case of failure or faulty operation send the instrument back to the distributor or to «Dixell

S.p.A.» (see address) with a detailed description of the fault.

Consider the maximum current which can be applied to each relay (see Technical Data).

Ensure that the wires for probes, loads and the power supply are separated and far enough from

each other, without crossing or intertwining.

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in

parallel with inductive loads could be useful.

2. General description

Model XW20K is microprocessor based controller suitable for applications on normal or medium

temperature refrigerating units. It has to be connected by means of a two-wire cable (∅ 1mm) at a

distance of up to 30 meters to the keyboard T620 or V620 or CX620.

It is provided with two relay outputs to control compressor and light. It is also provided with 3 NTC

probe inputs, one for temperature control, one to control the defrost end temperature of the evaporator

and the third to control condenser temperature or to display another temperature.

The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a

network line ModBUS-RTU compatible such as the dIXEL monitoring units of X-WEB family. It

allows to program the controller by means the HOT KEY programming keyboard.

The instrument is fully configurable through special parameters that can be easily programmed

through the keyboard.

3. Controlling loads

3.1 THE COMPRESSOR

The regulation is performed according to the temperature measured by the thermostat probe with a

positive differential from the set point: if the temperature increases and reaches set point plus

differential the compressor is started and then turned off when the temperature reaches the set point

value again.

In case of fault in the thermostat probe the start and stop of the compressor are timed through

parameters «COn» and «COF».

The relay of the second compressor is activated in parallel with the relay of the first compressor, with a

possible delay set in the AC1 parameter. Both the compressors are switched off at the same time.

3.2 FAST FREEZING

When defrost is not in progress, it can be activated by holding the «o» key pressed for about 3

seconds. The compressor operates to maintain the «ccS» set point for the time set through the «CCt»

parameter. The cycle can be terminated before the end of the set time using the same activation key

«o» for 3 seconds.

DEFROST

Defrost is performed through a simple stop of the compressor. Parameter «IdF» controls the interval

between defrost cycles, while its length is controlled by parameter «MdF».

3.3 DEFROST

Defrost is performed through a simple stop of the compressor. The parameters involved are: to control

the interval between defrost cycles (IdF), its maximum length (MdF) and two defrost modes: timed or

controlled by the evaporator’s probe (dFP and P3P). At the end of defrost dripping time is started, its

length is set in the FSt parameter. With FSt =0 the dripping time is disabled.

4. Relay 22-23 configuration- special functions

By means of the parameter oA3, it’s possible to configure the functions of the light relay (22-23), as

described in the following paragraphs:

OA3 = LIG: LIGHT RELAY (FACTORY SETTING)

By setting oA3 = Lig the relay will work as light relay, it is switched on and off by the light button on the

keyboard and is affected by status of the digital input when i1F = dor.

OA3 = CP2 2

COMPRESSOR MANAGEMENT

ND

By setting oA3 = cP2, the relay at terminals 22-23 will operate as «second compressor». It will be

activated in parallel with the relay of the first compressor, with a possible delay set in the AC1

parameter (seconds). Both the compressors are switched off at the same time.

1592026000 XW20K GB R1.0 22.02.2008.doc

Installing and Operating Instructions

formation of

OA3 = ONF: ON –OFF RELAY

By setting oA3 =onF, the relay will operate as «on-off» relay: it will be activated when the controller is

switched on and it will be switched off when the controller is in stand-by status.

OA3 = AUS: AUXILIARY RELAY

By setting oA3 = AUS, the relay 22-23 will work as auxiliary thermostat (I.E.. anti condensing heater).

Parameters involved:

ACH (cL, Ht): Kind of regulation for the auxiliary relay: Ht = heating / CL = cooling;

SAA (-50÷150) Set point for auxiliary relay

SHy (0÷25.5°C) Differential for auxiliary output.

With ACH = CL: aux relay cut in is SAA+SHy, cut out SAA.

o

With ACH = Ht: aux relay cut in is SAA-SHy, cut out SAA.

o

ArP (nP, P1, P2, P3, P4) Probe for auxiliary relay

Sdd (n, Y) Auxiliary output working during defrost

OA3 = ALR: ALARM RELAY

By setting oA3 = ALr the relay will work as alarm relay, it is switched on when an alarm happens.

Parameters involved:

tbA (n, y) Alarm relay silencing

AoP (cL; oP) Alarm relay polarity

OA3 = DB: NEUTRAL ZONE

By setting oA3 = db the controller will perform a

«neutral zone» regulation.

The heating element has to be connected to the

oA3 relay (22-23)

If the temperature increases and reaches set

point plus differential (+HY) the compressor is

started and then turned off when the

temperature reaches the set point value again.

If the temperature decreases and reaches the

set point minus differential( -HY) the oA3 output

(heater) is switched on and then turned OFF

when the temperature reaches again the set

point.

5. Keyboards

V620

To display and modify target set point; in programming mode it selects a parameter

or confirm an operation. By holding it pressed for 3s when max or min temperature

is displayed it will be erased.

To see the max. stored temperature; in programming mode it browses the

parameter codes or increases the displayed value.

By holding it pressed for 3s the fast freezing cycle is started.

To see the min stored temperature; in programming mode it browses the parameter

codes or decreases the displayed value.

By holding it pressed for 3s the defrost is started.

Switch ON and OFF the cold room light.

Switch ON and OFF the instrument.

KEY COMBINATIONS

+

To lock and unlock the keyboard.

XW20K

1592026000

T620

CX620

1/5

dIXEL

XW20K AND T620 – V620 – CX620

1. GENERAL WARNING

PLEASE READ BEFORE USING THIS MANUAL

This manual is part of the product and should be kept near the instrument for easy and quick

reference.

The instrument shall not be used for purposes different from those described hereunder. It

cannot be used as a safety device.

Check the application limits before proceeding.

SAFETY PRECAUTIONS

Check the supply voltage is correct before connecting the instrument.

Do not expose to water or moisture: use the controller only within the operating limits avoiding

sudden temperature changes with high atmospheric humidity to prevent

condensation

Warning: disconnect all electrical connections before any kind of maintenance.

Fit the probe where it is not accessible by the End User. The instrument must not be opened.

In case of failure or faulty operation send the instrument back to the distributor or to «Dixell

S.p.A.» (see address) with a detailed description of the fault.

Consider the maximum current which can be applied to each relay (see Technical Data).

Ensure that the wires for probes, loads and the power supply are separated and far enough from

each other, without crossing or intertwining.

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in

parallel with inductive loads could be useful.

2. General description

Model XW20K is microprocessor based controller suitable for applications on normal or medium

temperature refrigerating units. It has to be connected by means of a two-wire cable (∅ 1mm) at a

distance of up to 30 meters to the keyboard T620 or V620 or CX620.

It is provided with two relay outputs to control compressor and light. It is also provided with 3 NTC

probe inputs, one for temperature control, one to control the defrost end temperature of the evaporator

and the third to control condenser temperature or to display another temperature.

The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a

network line ModBUS-RTU compatible such as the dIXEL monitoring units of X-WEB family. It

allows to program the controller by means the HOT KEY programming keyboard.

The instrument is fully configurable through special parameters that can be easily programmed

through the keyboard.

3. Controlling loads

3.1 THE COMPRESSOR

The regulation is performed according to the temperature measured by the thermostat probe with a

positive differential from the set point: if the temperature increases and reaches set point plus

differential the compressor is started and then turned off when the temperature reaches the set point

value again.

In case of fault in the thermostat probe the start and stop of the compressor are timed through

parameters «COn» and «COF».

The relay of the second compressor is activated in parallel with the relay of the first compressor, with a

possible delay set in the AC1 parameter. Both the compressors are switched off at the same time.

3.2 FAST FREEZING

When defrost is not in progress, it can be activated by holding the «o» key pressed for about 3

seconds. The compressor operates to maintain the «ccS» set point for the time set through the «CCt»

parameter. The cycle can be terminated before the end of the set time using the same activation key

«o» for 3 seconds.

DEFROST

Defrost is performed through a simple stop of the compressor. Parameter «IdF» controls the interval

between defrost cycles, while its length is controlled by parameter «MdF».

3.3 DEFROST

Defrost is performed through a simple stop of the compressor. The parameters involved are: to control

the interval between defrost cycles (IdF), its maximum length (MdF) and two defrost modes: timed or

controlled by the evaporator’s probe (dFP and P3P). At the end of defrost dripping time is started, its

length is set in the FSt parameter. With FSt =0 the dripping time is disabled.

4. Relay 22-23 configuration- special functions

By means of the parameter oA3, it’s possible to configure the functions of the light relay (22-23), as

described in the following paragraphs:

OA3 = LIG: LIGHT RELAY (FACTORY SETTING)

By setting oA3 = Lig the relay will work as light relay, it is switched on and off by the light button on the

keyboard and is affected by status of the digital input when i1F = dor.

OA3 = CP2 2

COMPRESSOR MANAGEMENT

ND

By setting oA3 = cP2, the relay at terminals 22-23 will operate as «second compressor». It will be

activated in parallel with the relay of the first compressor, with a possible delay set in the AC1

parameter (seconds). Both the compressors are switched off at the same time.

1592026000 XW20K GB R1.0 22.02.2008.doc

Installing and Operating Instructions

formation of

OA3 = ONF: ON –OFF RELAY

By setting oA3 =onF, the relay will operate as «on-off» relay: it will be activated when the controller is

switched on and it will be switched off when the controller is in stand-by status.

OA3 = AUS: AUXILIARY RELAY

By setting oA3 = AUS, the relay 22-23 will work as auxiliary thermostat (I.E.. anti condensing heater).

Parameters involved:

ACH (cL, Ht): Kind of regulation for the auxiliary relay: Ht = heating / CL = cooling;

SAA (-50÷150) Set point for auxiliary relay

SHy (0÷25.5°C) Differential for auxiliary output.

With ACH = CL: aux relay cut in is SAA+SHy, cut out SAA.

o

With ACH = Ht: aux relay cut in is SAA-SHy, cut out SAA.

o

ArP (nP, P1, P2, P3, P4) Probe for auxiliary relay

Sdd (n, Y) Auxiliary output working during defrost

OA3 = ALR: ALARM RELAY

By setting oA3 = ALr the relay will work as alarm relay, it is switched on when an alarm happens.

Parameters involved:

tbA (n, y) Alarm relay silencing

AoP (cL; oP) Alarm relay polarity

OA3 = DB: NEUTRAL ZONE

By setting oA3 = db the controller will perform a

«neutral zone» regulation.

The heating element has to be connected to the

oA3 relay (22-23)

If the temperature increases and reaches set

point plus differential (+HY) the compressor is

started and then turned off when the

temperature reaches the set point value again.

If the temperature decreases and reaches the

set point minus differential( -HY) the oA3 output

(heater) is switched on and then turned OFF

when the temperature reaches again the set

point.

5. Keyboards

V620

To display and modify target set point; in programming mode it selects a parameter

or confirm an operation. By holding it pressed for 3s when max or min temperature

is displayed it will be erased.

To see the max. stored temperature; in programming mode it browses the

parameter codes or increases the displayed value.

By holding it pressed for 3s the fast freezing cycle is started.

To see the min stored temperature; in programming mode it browses the parameter

codes or decreases the displayed value.

By holding it pressed for 3s the defrost is started.

Switch ON and OFF the cold room light.

Switch ON and OFF the instrument.

KEY COMBINATIONS

+

To lock and unlock the keyboard.

XW20K

1592026000

T620

CX620

1/5

XR20C
Модель XR20C , термостат с простейшим циклом оттайки, сконструированный для применения в холодильной области при нормальной температуре. Прибор обеспечен реле выхода, для того, чтобы управлять компрессором, и входом, для датчиков РТС или NТС. Внутренний таймер организует простейший цикл оттайки.

Скачать

XR60
Модель XR60C , прибор с циклом оттайки, сконструированный для применения в холодильной области при нормальной и низкой температуре, также позволяет контролировать работу вентиляторов. Прибор обеспечен 3 реле выхода, для того, чтобы управлять компрессором, вентилятором и оттайкой, которая может быть как электрической, так и оттайкой горячим газом. Входами для 2 датчиков NТС ,один из которых нужен для контролдя температуры в объеме, другой для контроля температуры в испарителе и управления циклом оттайки и работы вентилятора.

Скачать

XR70C
Модель XR70C , прибор с циклом оттайки, сконструированный для применения в холодильной области при нормальной и низкой температуре, также позволяет контролировать работу вентиляторов. Прибор обеспечен 3 реле выхода, для того, чтобы управлять компрессором, вентилятором и оттайкой, которая может быть как электрической , так и оттайкой горячим газом. Входами для 2 датчиков NТС ,один из которых нужен для контролдя температуры в объеме, другой для контроля температуры в испарителе и управления циклом оттайки и работы вентилятора.)

Скачать

XC440(серия)
XC440C, XC440D, XC460D — серия семейства регуляторов Dixell разработан, чтобы управлять централями из нескольких компрессоров или конденсаторами с несколькими вентиляторами. Эта возможность гибко и всесторонне управлять устройствами улучшена возмлжностью выбирать номер и размер нагрузок, тип заданного действия: прямое или инверсивное, и 3 вида различной функциональной логики.

Скачать

XC650C(серия)
Серии XC650C управляют как компрессорами, так и вентиляторами в системах конденсации. Компрессора могут быть простыми, многоступенчатыми или с разными мощностями. Управление осуществляется при помощи нейтральной зоны или пропорционального регулирования и основано на давлении или температуре определяемой в зоне низкого давления (компрессоры) и в круге высокого давления (конденсаторы). Специальный алгоритм балансирует часы работы компрессоров, распределяя нагрузку равномерно. Контроллеры могут конвертировать как высокое, так и низкое давление и отображать их в виде температур.

Скачать

XC800M XC900M(серии)
Контроллеры XC807M, XC811M, XC907M, XC911M управляют как компрессорами, так и вентиляторами в системах конденсации. Компрессора могут быть простыми, многоступенчатыми или с разными мощностями. Управление осуществляется при помощи нейтральной зоны или пропорционального регулирования и основано на давлении или температуре определяемой в зоне низкого давления (компрессоры) и в круге высокого давления (конденсаторы). Специальный алгоритм балансирует часы работы компрессоров, распределяя нагрузку равномерно. Контроллеры могут конвертировать как высокое, так и низкое давление и отображать их в виде температур.

Скачать

XP110 XP111(серии)
XP110C, XP111C, (32×74мм размер), XP110D, XP111D (на ДИН-РЕЙКУ) и XP111R, (72×72мм размер), является одноступенчатым релейным регулятором для управления давлением с прямым или обратным (выбираемым) действием. Аналоговый тип входа должен быть выбран и определен при заказе, согласно технологическому параметру, которым нужно управлять.

Скачать

XR160C XR170C
Модели XR160C и XR170C , приборы с циклом оттайки, сконструированные для применения в холодильной области при нормальной и низкой температуре, также позволяют контролировать работу вентиляторов. Приборы обеспечены 3 реле выхода, для того, чтобы управлять компрессором, вентилятором и оттайкой, которая может быть как электрической, так и оттайкой горячим газом. Входами для 2 датчиков NТС ,один из которых нужен для контролдя температуры в объеме, другой для контроля температуры в испарителе и управления циклом оттайки и работы вентилятора.

Скачать

серия XT
XT120C, XT121C, XT124C, XT125C (корпус 32×74 мм.), XT120D, XT121D (крепёж на ДИН-РЕЙКУ) и XT121R, XT125R (корпус 72×72 мм.), является универсальным прибором на основе микропроцессора с выходом на реле, разработанные для широкого диапазона применения в индустриальном секторе, особенно когда требуется два ступенчатых конфигурируемых регулятора.

Скачать

XR06CX
XR06CX, в формате 32 x 74 x 60мм — это микропроцессорный контроллер, подходящий для применения в средне и низкотемпературных блоках охлаждения с вентиляцией. У него есть три релейных выхода для управления компрессором, вентилятором и оттайкой, которая может быть либо электрической, либо с реверсивным циклом (горячим газом). Прибор также снабжен 2 входами для датчиков NTC, первый — для контроля температуры, а второй должен размещаться на испарителе — для контроля температуры окончания оттайки и для управления вентилятором. Также он снабжен конфигурируемым цифровым входом. Имеется возможность легко и быстро запрограммировать контроллер с помощью ключа HOTKEY.

Скачать

XC645CX
Контроллер XC645CX разработан для управления и компрессорами, и вентиляторами конденсатора, работающими в составе агрегата. Компрессоры могут быть цифровыми спиральными (digital scroll), простыми, многоступенчатыми или разной мощности. Управление осуществляется по типу с «нейтральной зоной» или с «зоной пропорциональности» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) и нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки компрессоров, чтобы равномерно распределять рабочую нагрузку. Данный контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры. Полная информация о состоянии системы предоставляется на передней панели путем показа давления (температур) всасывания и конденсации, состояния нагрузок, возможных аварий или условий обслуживания. Каждая нагрузка имеет свой аварийный вход, который способен остановить ее при активации. Для обеспечения общей безопасности системы также имеются два входа для реле низкого и высокого давления: при их срабатывании система останавливается. Контроллер можно легко запрограммировать при подаче на него питания с помощью ключа HOT KEY. Контроллер также можно подключить к системе управления и мониторинга семейства XWEB благодаря последовательному TTL-выходу, используя стандартный протокол ModBus RTU.

Скачать

XC1008D, XC1011D, XC1015D и VGC810
Электронный контроллер для компрессорно-конденсаторных Установок. Примечание: При программировании параметров в зависимости от версии прошивки прибора, некоторые параметры могут не совпадать с указанными в инструкции. Они могут перескакивать на несколько пунктов по списку, либо вообще могут быть не указаны в таковом. Опыт работы показывает, что это ни как не сказывается на работе. Работают без сбоев в течении 5 лет непрерывной работы.

Скачать

XR03CX, XR04CX
XR03CX, в коротком формате 32х74×50 мм, — это микропроцессорный контроллер, подходящий для применения в блоках охлаждения с нормальной температурой. У него есть два релейных выхода: один – для компрессора, а другой — для выдачи аварии или как дополнительный выход. Он также снабжен входом для датчика NTC и одним цифровым входом для сигнала аварии, для включения дополнительного выхода или для запуска оттайки. Прибор полностью конфигурируется с помощью специальных параметров, которые могут быть легко запрограммированы с клавиатуры или ключом HOTKEY.

Скачать

XW60K
Модель XW60K является микропроцессорным контроллером подходящим для применения в средне- и низкотемпературных холодильных системах. При помощи двужильного кабеля (диам. 1мм) к нему на дистанции до 30м могут подключаться клавиатуры T620T или T620 или V620 или CX620. У него есть 3 релейных выхода для управления компрессором, вентилятором, освещением и оттайкой, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Он также снабжен четырьмя входами датчиков NTC или PTC, первый – для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором, третий и четвертый — для подачи сигнала аварии по температуре конденсатора или для показа температуры, отличной от температуры, по которой происходит регулирование. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к сети, совместимой с ModBUS-RTU, такой как блоки мониторинга dIXELL семейства XWEB. Также он позволяет программировать контроллер с помощью ключа программирования HOT KEY. Прибор полностью конфигурируется с помощью специальных параметров, которые могут быть легко запрограммированы с клавиатуры.

Скачать

Tb77
Модель TB77, с панелью размерами 32х74 мм, является контроллером с микропроцессором и предназначена для использования в средне- и низкотемпературных агрегатах. Она поставляется с тремя выходными реле для управления компрессором, оттайкой — которая может производиться как электронагревателями, так и горячим хладагентом — и вентиляторами воздухоохладителей. Она также комплектуется двумя входными датчиками (PTC): один для контроля температуры в камере, другой расположен в воздухоохладителе для контроля температуры прекращения оттайки. Каждый прибор полностью настраивается с помощью специальных параметров, которые могут быть легко запрограммированы с помощью кнопок.

Скачать

XR10C
Модель XR10C, с панелью размерами 32х74 мм, является одноступенчатым температурным контроллером, предназначенным для использования при охлаждении или обогреве.

Скачать

XR20CX
Модель XR20CX, формата 32×74мм – это цифровой термостат с оттайкой «off cycle», предназначенный для применения в холодильных системах с нормальной температурой. У него имеется релейный выход для управления компрессором. Он также снабжен 2 входами датчиков NTC или PTC, первый — для контроля температуры, второй, опциональный, подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Цифровой вход может работать как третий датчик температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к сети, совместимой с ModBUS-RTU, такой как блоки мониторинга DIXEL семейства XWEB. Также он позволяет программировать контроллер с помощью ключа программирования HOT KEY. Прибор полностью конфигурируется с помощью специальных параметров, которые могут быть легко запрограммированы с клавиатуры.

Скачать

XR120D-XR130D со встроенным RS со встроенным RS485
Контроллеры серии подключаются к системе мониторинга через выход RS485. Они повсеместно эксплуатируются в вентиляционных системах и устройствах охлаждения воздуха для обеспечивания максимальной производительности. Управление компрессором в данном случае выполняется по одному релейному выходу микропроцессора. Наличие двух NTC позволяет одним датчиком контролировать температурный диапазон, а другим пользоваться как элементом визуализации. Благодаря удобному программированию, контроллеры XR120D-XR130D в кратчайшие сроки настраиваются под конкретные требования системы охлаждения.

Скачать

XR160D – XR170D
Модели серии устанавливаются на DIN-рейку. Они оснащаются циклом оттайки, разработанный для эксплуатации в области холодильного оборудования. Контроллеры работают в нормально- и низкотемпературной среде, также обеспечивая управление вентиляционными системами. Электронное устройство основывается на 3х реле выхода, через которые выполняется контроль функционирования оттайки, компрессора и вентилятора. Программирование прибора осуществляется в кратчайшие сроки через клавиатуру, поэтому функции контроллера можно легко настроить под рабочие требования.

Скачать

Скачать инструкции по эксплуатации для оборудования Dixell — максимально упростить процесс знакомства с данными техническим аппаратами. В условиях современности, мануал можно скачать прямо на планшет, потому как используется популярный формат pdf-файла. Для большинства потребителей — это единственный выход ознакомиться с техникой, ведь в сложных экономических условиях вызов специалиста может влететь в копеечку. Скачать бесплатно инструкцию по эксплуатации сегодня очень просто. Большая часть специализированных сайтов и интернет-порталов готовы предоставить всем желающим данную услугу. 

  Название Инструкция Комментарий

Контроллер Dixell XH240 L-V

Контроллер Dixell XH240 L-V Контроллер Dixell XH240 L-V XH240L-V — контроллер предназначенный для поддержания температуры и влажности в среднетемпературных холодильных системах. 5 релейных выходов для управления компрессором, нагревательными элементами, вентилятором, освещением и увлажнителем. Они снабжены 1 входом NTC для контроля температуры, и входом 4-20мА для датчика влажности. Имеется один цифровой вход (контакт без напряжения), конфигурируемый параметром. Специальный выход позволяет программировать список параметров с помощью ключа «Hot Key»

Контроллер Dixell XM660K

Контроллер Dixell XM660K Контроллер Dixell XM660K XM660K — оснащен четырьмя релейными выходами, которые могут использоваться на выбор: для управления соленоидным клапаном, оттайкой (электрической либо горячим газом), для управления вентиляторами испарителя или освещением. Четыре входа датчиков: контроль температуры, контроль температуры окончания оттайки испарителя, индикация, возможное использование для систем с виртуальным датчиком или для измерения температуры воздуха на входе/выходе.

Контроллер Dixell XR60C

Контроллер Dixell XR60C Контроллер Dixell XR60C XR60C — с циклом оттайки, используется в холодильной отрасли при средней и низкой температуре, с контролем работы вентиляторов. 3 входа реле для управления компрессором, вентилятором и оттайкой (электрической / горячим газом), 2 датчика NТС.

Контроллер Dixell XC 650 C

Контроллер Dixell XC 650 C Контроллер Dixell XC 650 C XC 650C — разработан для управления и компрессорами и вентиляторами конденсатора, работающими в составе агрегата. Компрессоры могут быть простыми, многоступенчатыми или разной мощности. Управление осуществляется по типу с «нейтральной зоной» или с «зоной пропорциональности» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) и нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки компрессоров для равномерного распределения рабочей нагрузки

Dixell_XC807M-XC911M

Контроллер Dixell XC807-XC911 Контроллер Dixell XC807-XC911 XC807, XC911 — управляют как компрессорами, так и вентиляторами в системах конденсации. Передняя панель информирует о давлении на всасывании и давлении в конденсаторе, возможные аварийные сигналы и условия технического обслуживания. Контроллер оборудован двумя аварийными выключателями высокого и низкого давления системы

Dixell T66 - XW60K

Gamko Flexbar Dixell T66 — XW60K

Dixell XR 20 C

Контроллер Dixell XR 20C Dixell XR 20C XR20C — с простейшим циклом оттайки, для использования в холодильной области при нормальной температуре. Блок имеет реле выхода для управления компрессором, работает с датчиками РТС или NТС. Цикл оттайки по внутреннему таймеру

Dixell XR 70 CX

Контроллер Dixell XR 70 CX Dixell XR 70 CX XR70 CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. 4 релейных выхода для управления компрессором, вентилятором и оттайкой, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Последнее реле может использоваться для освещения, для сигнала аварии или как дополнительный выход. Он также снабжен четырьмя входами датчиков NTC или PTC, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором. Цифровой вход может работать в качестве третьего датчика температуры. Четвертый датчик, подключаемый к разъему HOT KEY, используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Выход HOT KEY позволяет подключить контроллер с помощью внешнего модуля XJ485-CX к сети, совместимой с ModBUS-RTU , такой как блоки мониторинга Dixell семейства XWEB. Разъем HOT key позволяет программировать контроллер с помощью ключа программирования HOT KEY. Прибор полностью конфигурируется с помощью специальных параметров, которые могут быть легко запрограммированы с клавиатуры

Dixell XR160C - XR170C

Контроллер Dixell XR160C — XR170C Dixell XR160C — XR170C XR160C, XR170C — цифровой контроллер для вентилируемых холодильных камер с функцией оттайки тэнами или горячими парами, управления работой вентилятора воздухоохладителя

Dixell XH360L-V

Контроллер Dixell XH360L-V Dixell XH360L-V XH360L, формата 38×185 и XH360V, формата 100×64 — это микропроцессорные контроллеры, подходящие для применения в средне — или низкотемпературных блоках охлаждения. 6 релейных выходов для управления компрессором, нагревательными элементами, оттайкой — вытяжным вентилятором, вентилятором, осушителем — светом и увлажнителем. Они снабжены 2 входами NTC: один — для контроля температуры, другой — для контроля оттайки . Также имеется вход 4 ÷ 20 мА для датчика влажности

Dixell XC440

Контроллер Dixell XC440 Dixell XC440 Контроллер XC440C разработан для управления компрессорами или вентиляторами конденсатора, работающими в составе агрегата. Компрессоры могут быть простыми, многоступенчатыми или разной мощности. Управление осуществляется по типу с «нейтральной зоной» или с «зоной пропорциональности» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) или нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки компрессоров, чтобы равномерно распределять рабочую нагрузку. Данный контроллер может конвертировать давление и показывать его на дисплее в виде температуры. Полная информация о состоянии системы предоставляется на передней панели путем показа давления (температур) всасывания и конденсации, состояния нагрузок, возможных аварий или условий обслуживания

Dixell XP 110 - 111 C - D

Контроллер Dixell XP 110-111 C-D Dixell XP 110 — 111 C — D XP110C, XP111C (32×74мм размер), XP110D, XP111D (на ДИН-РЕЙКУ) и XP111R, (72×72мм размер), является одноступенчатым релейным регулятором для управления давлением с прямым или обратным (выбираемым) действием. Аналоговый тип входа должен быть выбран и определен при заказе, согласно технологическому параметру, которым нужно управлять

Dixell XT 110-111 C-D

Контроллер Dixell XT 110-111 C-D Dixell XT 110-111 C-D XT110C, XT111C и XT110D, XT111D ( формат на DIN- рейку ) — одноступенчатые контроллеры ВКЛ / ВЫКЛ для применений с управлением по температуре, влажности и давлению с прямым или обратным действием, выбираемым пользователем. Тип аналогового входа может задаваться с помощью параметра из следующих, согласно модели : — PTC, NTC; — PTC, NTC, Pt100, Термопара J, K, S; 4 ÷ 20 мА, 0 ÷ 1 В, 0 ÷ 10 В

Dixell XR70C-D XR72C

Контроллер Dixell XR70C-D XR72C Dixell XR70C-D XR72C XR70C-D — прибор с циклом оттайки, сконструированный для применения в холодильной области при нормальной и низкой температуре, также позволяет контролировать работу вентиляторов. 3 реле выхода для управления компрессором, вентилятором и оттайкой (электрической, горячим газом), входами для 2 датчиков NТС

Dixell XT 120C – XT 125R

Контроллер Dixell XT 120C – XT 125R Dixell XT 120C – XT 125R XT120C, XT121C, XT124C, XT125C (корпус 32×74 мм), XT120D, XT121D (крепёж на ДИН-РЕЙКУ) и XT121R, XT125R (корпус 72×72 мм) является семейством универсальных приборов на основе микропроцессора с выходом на реле, особенно когда требуется два ступенчатых конфигурируемых регулятора

Dixell XW270L - XW271L

Контроллер Dixell XW270L — XW271L Dixell XW270L — XW271L XW270L — XW271L — для применения в средне- и низкотемпературных холодильных системах. 6 релейных выходов служат для управления компрессором, двумя оттайками (тэн / горячим газом), вентиляторами испарителя, освещением (вкл/выкл). Так же есть три входа для датчиков NTC, один для термостатирования и два для контроля температуры окончания оттайки

Dixell XW40L - XW40V

Контроллер Dixell XW40L — XW40V Dixell XW40L — XW40V XW40L-XW40V — для применения в средне и низкотемпературных холодильных системах. 3 релейных выхода служат для управления компрессором, двумя оттайками (тэн / горячим газом), освещением вкл/выкл. Так же есть два входа для датчиков NTC

Dixell XW 60 K

Контроллер Dixell XW 60 K Dixell XW 60 K Модель XW60K является микропроцессорным контроллером подходящим для применения в средне- и низкотемпературных холодильных системах. При помощи двужильного кабеля (1мм) к нему на дистанции до 30м могут подключаться клавиатуры T620T или T620 или V620 или CX620. У него есть 3 релейных выхода для управления компрессором, вентилятором,
освещением и оттайкой, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Он также снабжен четырьмя входами датчиков NTC или PTC, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором, третий и четвертый — для подачи сигнала аварии по температуре конденсатора или для показа температуры, отличной от температуры, по которой происходит регулирование.

Контроллер Dixell XW60LRH

Контроллер Dixell XW60LRH Контроллер Dixell XW60LRH Dixell XW60LRH — микропроцессорный контроллер для применения в среднетемпературных холодильных установок. Три релейных выхода для управления компрессором, вентилятором и освещением.

Контроллер Dixell XLR170

Контроллер Dixell XLR170 Контроллер Dixell XLR170 Модели XLR130 и XLR170, в формате 210×230мм, являются микропроцессорными контроллерами для средне- и низкотемпературных холодильных систем. Они имеют четыре (XLR130) или шесть (XLR170) релейных выходов для управления компрессором, оттайкой – которая может быть электрической или газовой (XLR170) – вентиляторами испарителя (в XLR130 надо сконфигурировать доп. реле), освещением, аварийной сигнализацией и дополнительным реле.

Контроллер Dixell XLH260

Контроллер Dixell XLH260 Контроллер Dixell XLH260 XLH 260 — контроллер для поддержания температуры и влажности в средне- и низкотемпературных холодильных системах. Прибор снабжен шестью релейными выходами для управления компрессором, нагревателем, оттайкой, вентилятором, осушителем и увлажнителем. Имеет два аналоговых входа для датчиков NTC – для термостатирования и оттайки, один вход 4-20 мА для датчика влажности. Цифровой вход – один конфигурируемый без напряжения. Контроллер может быть запрограммирован с ключа “Hot Key”.

Контроллер Dixell XLH360

Контроллер Dixell XLH360 Контроллер Dixell XLH360 (ENG)

Dixell XLR470

Контроллер Dixell XLR470 Dixell XLR470 XLR470 — цифровой контроллер для холодильных камер с двойным управлением температурой (для нормальной и низкой температуры). Идеально подходит для систем с нагревом-охлаждением, таких как стойка для водяной бани с холодильной камерой внизу. Предназначен для систем с двумя испарителями или 2 независимыми контурами. Встроенное управление оттайкой. Охлаждение или нагрев выбирается пользователем. Мгновенный обзор состояния устройства при помощи иконок на дисплее.

Dixell XW220L

Контроллер Dixell XW220L Контроллер Dixell XW220L Контроллер Dixell XW220L — для применения на холодильных установках. Контроллер снабжен двумя релейными выходами для управления компрессором и подсветкой. Два входа датчиков NTC. Два цифровых входа (свободный контакт) для дверного выключателя и настраивается по параметру. Выход TTL позволяет подключать с помощью внешнего модуля TTL / RS485 модуль ModBUS RTU для системы мониторинга

Dixell XW230L

Контроллер Dixell XW230L Dixell XW230L Контроллер Dixell XW230L для использования на средних или низкотемпературных холодильных установках. Четыре релейных выхода для управления компрессором, сигнализацией и вспомогательным выходом. Два датчика NTC (контроль температуры и дополнительный для дисплея). Два цифровых входа (свободный контакт) для дверного выключателя и настраиваемый параметром. Стандартный выход TTL позволяет пользователю подключать с помощью внешнего модуля TTL / RS485 совместимую с ModBUSRTU систему мониторинга

Контроллер Dixell XW260L

Контроллер Dixell XW260L Dixell XW260L Контроллер Dixell XW260L — для применения на средних или низкотемпературные холодильные установки. Cнабжен четырьмя релейными выходами для управления компрессором, процессом оттайки (электрической, горячий газ), вентилятором испарителя и светом. Три датчика NTC (температура объема,оттайкой и третья, опционная, для дисплея. Стандартный выход TTL позволяет пользователю подключать с помощью внешнего модуля TTL/RS485 модуль ModBUSRTU системы мониторинга

Контроллер Dixell XW263L

Контроллер Dixell XW263L Dixell XW263L Контроллер Dixell XW263L для управления средне- или низкотемпературных холодильных установок. Снабжен четырьмя релейными выходами для управления компрессором, оттайкой (электрический, горячий газ), вентилятором испарителя и светом. Два датчика NTC (объем, испаритель)

Dixell XW264L

Контроллер Dixell XW264L Dixell XW264L Контроллер Dixell XW264L являются микропроцессорными контроллерами для применения в средне- и низкотемпературных холодильных системах. У него есть 6 релейных выходов для управления компрессором, двумя оттайками (электронагреватель или горячим газом), вентиляторами испарителя, освещением или вкл/выкл. Так же есть три входа для датчиков NTC, один для термостатирования и два для контроля температуры окончания оттайки двух испарителей. Два цифровых входа (без напряжения) для контроля двери и конфигурируемый. TTL разъем позволяющий пользователю с помощью внешнего конвертора TTL/RS485 подключить контроллер к ModBUS-RTU совместимой с системой мониторинга Dixell, такой как XWEB300В/500/3000/5000 и для программирования с помощью “Hot Key”. Опционально XW-REP выход для удаленного дисплея, аналоговый выход 4÷20 мА для управления вентилятором испарителя или конденсатора и последовательный выход с RS485.

Dixell XW563L

Контроллер Dixell XW563L Dixell XW563L Контроллер Dixell XW563L является микропроцессорным контроллером, подходящим для применение на средне- или низкотемпературных холодильных установках. Снабжен четырьмя реле выходы для управления компрессором, оттайка (электричеством, горячим газом), вентиляторы испарителя и свет. Два датчика NTC (объем, испаритель). Два цифровых входа (свободный контакт) для дверного выключателя и настраивается по параметру. Выход RS485 позволяет пользователю подключать совместимый с ModBUS-RTU мониторинг система

Dixell XW570L

Контроллер Dixell XW570L Dixell XW570L Контроллер Dixell XW570L для применения на средне- или низкотемпературном холодильном оборудовании. Снабжен шестью релейными выходами для управления компрессором, оттайкой (электрическая, горячий газ), вентиляторами испарителя, лампочками, сигнализацией и вспомогательным выходом. Три датчика NTC (объем, испаритель и третий опционный для дисплея). Есть два цифровых входа (свободный контакт) для дверного выключателя и настраивается по параметру. Стандартный выход TTL позволяет пользователю подключать с помощью внешнего модуля TTL/RS485 модуль ModBUSRTU совместимая система мониторинга и запрограммировать список параметров с помощью “горячей клавиши». Выход для удаленного дисплея XW-REP, выход 4÷20 мА для управления вентиляторами испарителя или конденсатора и прямой последовательный выход RS485 доступен в качестве опции

Dixell XW30V

Контроллер Dixell XW30L-XW30V Dixell XW30V Контроллер Dixell модель XW30L, формат 38×185 мм, и модель XW30V, формат 100×64, основаны на микропроцессоре контроллеры подходят для применения на холодильных установках средней температуры. Три релейных выхода управляют компрессором, подсветкой и сигнализацией тревоги. Один датчик NTC или PTC. Есть 1 цифровой входами (свободный контакт) настраиваемый параметр

Dixell XC15CX-XC35CX

Контроллер Dixell XC15CX-XC35CX Dixell XC15CX-XC35CX Контроллер Dixell XC15CX-XC35CX являются контроллерами предназначенными для управления одно- и двухкомпрессорными агрегатами. Он может управлять простыми компрессорами, компрессорами с преобразователями частоты и компрессорами Digital. Контроллер имеет:
— 1 (ХС15СХ) или 2 (ХС35СХ) релейных выхода для управления компрессорами или вентиляторами или аварийной сигнализации;
— 1 тиристорный выход для управления скоростью вращения вентиляторов в режиме фазорезки (макс. ток 2.2 A) или соленоидным клапаном компрессора Digital;
— 1 аналоговый выход (0-10В или ШИМ) для управления ЕС-вентиляторами, преобразователями частоты или режима пропорционального повторителя;
— До 3-х цифровых входов без напряжения для мониторинга аварий;
— 2 аналоговых входа для ратиометрических датчиков давления (0-5В);
— До 4-х температурных датчиков NTC10k, NTC86k или PT1000.
XC15CX оснащён только одним реле 16 A, у ХС35СХ имеется также второе реле номиналом 5А. Все функции (исключая связанные со вторым реле) одинаковые для обоих приборов.

Dixell XC10CX-XC30CX

Контроллер Dixell XC10CX-XC30CX Dixell XC10CX-XC30CX Модель XC30CX, формат 32x74mm, представляет собой цифровой термостат для применения в конденсаторных установках. Это обеспечивает три цифровых (релейных) выхода, один для компрессора, а другой для управления вентиляторами. Два датчика NTC или ratiometric зонда, который нужно использовать на линии всасывания и конденсатора. Цифровые входы могут работать для управления безопасностью конденсаторного агрегата. Модель XC10CX отличается от XC30CX по номеру цифрового выхода. На самом деле, XC10CX имеет только один цифровой выход, который используется для управления компрессором.

Dixell XR20CX

Контроллер Dixell XR20CX Dixell XR20CX Контроллер Dixell XR20CX — цифровой термостат с оттайкой “off cycle”, предназначенный для применения в холодильных системах с нормальной температурой. Имеется релейный выход для управления компрессором. Он также снабжен 2 входами датчиков NTC или PTC, первый — для контроля температуры, второй, опциональный, подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Цифровой вход может работать как третий датчик температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к
сети, совместимой с ModBUS-RTU, такой как блоки мониторинга dIXEL семейства XWEB.

Dixell XR40CX

Контроллер Dixell XR40CX Dixell XR40CX Контроллер Dixell XR40CX — для применения в холодильных системах с нормальной и низкой температурой. Имеется два реле для управления компрессором и оттайкой (электрическая, горячим газом). Он также снабжен 3 входами датчиков NTC или PTC, первый — для контроля температуры объема, второй — испарителя, третий — опционально может быть подключен через HOT KEY для подачи сигнала тревоги температуры конденсатора или для отображения температуры. Цифровой вход может работать как четвертый температурный зонд.

Dixell XR60CX

Контроллер Dixell XR60CX Dixell XR60CX Контроллер Dixell XR60CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. Три релейных выхода для управления компрессором, вентилятором, оттайкой (электрическая, горячий газ). Он также снабжен тремя входами датчиков NTC или PTC, первый температуры объема, второй на испарителе для контроля температуры окончания оттайки и управления вентилятором, третий датчик, опциональный, подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Цифровой вход может работать как четвертый датчик температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к сети, совместимой с ModBUS-RTU, такой как блоки мониторинга dIXEL семейства XWEB.

Dixell XR70CX

Контроллер Dixell XR70CX Dixell XR70CX Контроллер Dixell XR70CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. Четыре релейных выхода для управления компрессором, вентилятором и оттайкой (электрическая, горячий газ). Последнее реле может использоваться для освещения, для сигнала аварии или как дополнительный выход. Он также снабжен четырьмя входами датчиков NTC или PTC, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором. Цифровой вход может работать в качестве третьего датчика температуры. Четвертый датчик, подключаемый к разъему HOT KEY, используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Выход HOT KEY позволяет подключить контроллер с помощью внешнего модуля XJ485-CX к сети.

Dixell XR64CX

Контроллер Dixell XR64CX Dixell XR64CX Контроллер Dixell XR64CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией и 2мя
испарителями. У него есть четыре релейных выхода для управления компрессором, вентилятором, оттайкой 1 и 2, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Он также снабжен до четырех входов датчиков NTC или PTC, первый — для контроля температуры, второй и третий, расположенные на испарителе, для контроля температуры окончания оттайки и управления вентилятором. Четвертый датчик подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к сети.

Dixell XR75CX

Контроллер Dixell XR75CX Dixell XR75CX Контроллер Dixell XR75CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. Четыре релейных выхода для управления компрессором, вентилятором, оттайкой (электрическая, горячий газ) и освещением. Он может снабжаться Часами Реального Времени, которые позволяют запрограммировать до 6 циклов оттайки ежедневно, с разделением на выходные и рабочие дни. Функция “День и Ночь” с двумя разными уставками подходит для энергосбережения. Он также снабжен четырьмя входами датчиков NTC или PT1000, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором. Один из 2 цифровых входов может работать в качестве третьего датчика температуры. Четвертый датчик используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Последовательный выход RS485 позволяет подключить контроллер к сети, совместимой с ModBUS-RTU.

Dixell XC645CX

Контроллер Dixell XC645CX Dixell XC645CX Контроллер Dixell XC645CX — для управления компрессорами и вентиляторами конденсатора, работающими в составе агрегата.
В составе агрегата один компрессор всегда – Digital (спиральный или поршневой), остальные могут быть как спиральными, так и поршневыми с регулировкой производительности или без неё. Управление компрессорами осуществляется по алгоритму с «нейтральной зоной» и основано на считывании величины давления или температуры в контурах всасывания (низкое давление — компрессоры) и нагнетания (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки нагрузок. Управление вентиляторами – пропорциональное. Контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры.

Dixell XC650CX

Контроллер Dixell XC650CX Dixell XC650CX Контроллер Dixell XC650CX — для управления компрессорами и вентиляторами конденсатора, работающими в составе агрегата.
Компрессоры могут быть спиральными, поршневыми, с регулировкой производительности, в том числе при помощи преобразователя частоты. Контроллер может управлять двумя контурами всасывания с общим контуром конденсации. Управление компрессорами осуществляется по алгоритму с «нейтральной зоной» и основано на считывании величины давления или температуры в контурах всасывания (низкое давление — компрессоры) и нагнетания (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки нагрузок. Управление вентиляторами – пропорциональное. Данный контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры.

Dixell XC660D

Контроллер Dixell XC660D Dixell XC660D Контроллер Dixell XC660D — для управления компрессорами и вентиляторами конденсатора, работающими в составе агрегата.
Компрессоры могут быть спиральными, поршневыми, с регулировкой производительности. Управление компрессорами осуществляется по алгоритму с «нейтральной зоной» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) и нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки нагрузок. Управление вентиляторами – пропорциональное. Данный контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры.

Dixell XC1000D

Контроллер Dixell XC1000D Dixell XC1000D Контроллер Dixell XC1000D — для управления систем контуров охлаждения (до 2 контуров всасывания и 2 контуров конденсации). Благодаря специальным алгоритмам эти контроллеры могут управлять и контролировать установки с CO2, которые работают по каскадному принципу с субкритическим циклом.

Dixell XC807-911M

Контроллер Dixell XC807-911M Dixell XC807-911M Контроллер Dixell серии XC800M и XC900M управляет компрессорами и вентиляторами в системах конденсации.
Компрессора могут быть простыми, многоступенчатыми или с разными мощностями. Управление осуществляется при помощи нейтральной зоны или пропорционального регулирования и основано на давлении или температуре определяемой в зоне низкого давления (компрессоры) и высокого давления (конденсаторы).

Dixell XRi77CX

Контроллер Dixell XRi77CX Dixell XRi77CX Контроллер Dixell XRi77CX — предназначен для применения на средне- или низкотемпературных вентилируемых холодильных установок. Имеет четыре релейных выхода для управления компрессором, вентилятором, оттайкой (электрическая, горячим газом). Снабжен четырьмя входами датчика NTC. Первый зонд для контроля температуры объема. Второй зонд для контроля температуры испарителя. Один из двух цифровых входов может работать как третий температурный зонд. Четвертый зонд используется для контроля температуры конденсатора (для управления сигнализацией конденсатора) или для отображения температуры.

Dixell XWi70K

Контроллер Dixell XWi70K Dixell XWi70K Контроллер Dixell XWi70K предназначен для применения на средне- и низко- температурных холодильных установках. Пять
релейных выходов для управления компрессором, оттайкой (электрическая, горячий газ), испарителем и конденсаторными вентиляторами, светом или сигнализация. Четыре датчика NTC (PTC). Он имеет как частотный выход, так и последовательный порт, который может использоваться для управления переменной скоростью компрессоров. Пара аналоговых выходов (4-20мА или 0-10В) и главный 2-проводный выход RS485

Dixell XEV11D_12D

Контроллер Dixell XEV11D-12D Dixell XEV11D_12D Контроллер Dixell XEV11D-12D — для управления импульсными (ВКЛ/ВЫКЛ) электронными расширительными вентилями. Этот модуль позволяет регулировать перегрев (SH) текучей среды, которая протекает в холодильной системе, с тем чтобы достичь оптимальной производительности и функционирования испарителя независимо от климатических условий или нагрузки. Модули XEV12D оборудованы двумя входами датчиков, один – для датчика давления с интерфейсом 4÷20мА или 0÷5В, а другой – для датчика температуры Pt1000 или NTC. Подключение в локальную сеть LAN позволяет передавать сигнал давления на другие модули XEV, чтобы использовать только один датчик давления в системах с составными шкафами. Имеется также два конфигурируемых цифровых входа, один из них должен быть сконфигурирован для получения запроса охлаждения. Другой цифровой вход может использоваться для оповещения контроллера о том, что идет оттайка. Дисплей с иконками предоставляет удобную визуализацию перегрева (SH), процент времени открытия вентиля или значений датчиков, встроенная клавиатура позволяет программировать контроллер без каких-либо других устройств. Завершая комплектацию контроллера, последовательная сеть RS485.

Dixell XEV22D

Контроллер Dixell XEV22D Dixell XEV22D Контроллер Dixell XEV22D — для управления шаговыми электронными расширительными клапанами. XEV22D позволяет регулировать перегрев (SH) хладагента в испарителе для достижения оптимальной производительности и функционирования испарителя независимо от климатических условий или нагрузки. XEV22D имеет два входа датчиков, один – для датчика давления с интерфейсом 4÷20мА или 0÷5В, а другой – для датчика температуры Pt1000 или NTC-EU / NTC-US. LAN связь позволяет передавать сигнал от одного датчика давления на несколько приборов. Имеется также два конфигурируемых цифровых входа, один – сухой контакт, второй — свободный от напряжения. С дисплея можно просмотреть значение перегрева (SH), степень открытия клапана или показания датчиков, клавиатура позволяет программировать контроллер без каких-либо других
устройств. К системам мониторинга и диспетчеризации XEV22D подключатся с помощью встроенной сетевой карты RS485.

Dixell IEV22D-IEV24D

Контроллер Dixell IEV22D-IEV24D Dixell IEV22D-IEV24D Контроллер Dixell IEV22D-IEV24D — предназначен для управления одним или двумя шаговыми двигателями электронного расширительного клапана. Доступны два различных режима регулирования: * Автономный режим: цифровые входы используются для запуска управления перегревом. Давление кипения датчик и датчик температуры всасывания должны быть соединены с контроллером; * LAN: IEV можно подключить к серии Ichill 200 EVO для того чтобы контролировать перегрев. Для обеспечения наилучшего регулирования рекомендуется подключать датчик давления всасывания непосредственно к контроллеру.
Основные характеристики: * управление одним или двумя электронными расширительными клапанами; * совместимость с несколькими моделями клапанов; * совместимость с различными типами хладагентов; * ручное управление ПИД-регулировкой или адаптивным регулированием.

Dixell_XW10L

Контроллер Dixell_XW10L Контроллер Dixell_XW10L Контроллер Dixell XW10L, формат 38×185 мм, и модель XW10V, формат 100×64, представляют собой микропроцессорные
контроллеры, подходящие для применения в области охлаждения или отопления. Снабжены 2 релейными
выходами, один из которых предназначен для регулирования, а другой — для освещения. Они также снабжены 1
входом датчика NTC или PTC для контроля температуры. Имеется 1 цифровой вход (свободный контакт), настраиваемый по параметру. Вывод позволяет пользователю запрограммировать список параметров с помощью горячей клавиши.

Dixell Wing XW10L-V

Контроллер Dixell Wing XW10L-V Контроллер Dixell Wing XW10L-V

Dixell XH260L-V

Контроллер Dixell XH260L-V Dixell XH260L-V Контроллер Dixell XH260L и XH260V применяются в холодильных установках средней или низкой температуры. Контролируют как влажность, так и температуру. Имеют 6 выходных реле для управления компрессором, нагревательными элементами, размораживанием, осушителем воздуха и увлажнителем воздуха. 2 датчика NTC: объем и испаритель. Вход 4÷20 мА для измерения влажности. Имеется один цифровой вход (свободный контакт), настраиваемый по параметру. Вывод позволяет пользователю запрограммировать список параметров с помощью “Hot Key”.

Dixell XB570L

Контроллер Dixell XB570L Dixell XB570L Контроллер Dixell серии XB созданы для быстрого охлаждения или заморозки продуктов в соответствии с международными стандартами пищевой безопасности.

Технические характеристики

Общие сведения
N-значный дисплей: ± 3 д.з. — Клавиатура: 6 кнопок
Ведомые устройства модуля
XW20K, XW40K, XW60K, XW70K
Зуммер
опционально
Соединения
винтовой клеммник < проводка 2,5 мм2 и фастонное соединение 6,3 мм
Источник питания
24, 110, 230 В перем.тока 110, 230 В перем.тока от контроллера (для моделей K)
Энергопотребление
макс. 10 ВА
Дисплей
3 цифры, красный светодиод, высота 14,2 мм
Хранение данных
в энергонезависимой памяти (EEPROM)
Рабочая температура
0÷60 °C
Температура хранения
-30÷85°C
Относительная влажность
20÷85% (без конденсации)
Диапазон измерения и регулирования
Датчик NTC: -40÷110°C, Датчик PTC: -50÷150°C
Шаг
0,1°C или 1°C
Погрешность (при температуре окружающей среды)
±0,7°C ±1 цифра
Источник питания
от контроллера

Особенности

  • Прямое подключение фазы и нейтрали нагрузки для снижения затрат на проводку
  • Прямое управление компрессорами вплоть до 1,2 л. с. (внутри реле 20 А)
  • Прямое электропитание. Не требуется внешний трансформатор
  • Удобный интерфейс благодаря использованию до 8 кнопок с прямым действием
  • Регистрация максимальной и минимальной температуры
  • Простой или плавающий контроль пониженной и повышенной влажности
  • Интеллектуальное оттаивание
  • Встроенные функции, позволяющие экономить энергию
  • Hot Key для быстрого и легкого программирования
  • Разъем для выносного дисплея
  • Последовательное подключение к системам мониторинга

  • Аналогичные товары

Вся информация на сайте о товарах и ценах носит справочный характер и не является публичной офертой. Производитель оставляет за собой право изменять характеристики товара, его внешний вид и комплектность без предварительного уведомления продавца

dIXEL

XW20K AND T620 – V620 – CX620

1. GENERAL WARNING

PLEASE READ BEFORE USING THIS MANUAL

This manual is part of the product and should be kept near the instrument for easy and quick

reference.

The instrument shall not be used for purposes different from those described hereunder. It

cannot be used as a safety device.

Check the application limits before proceeding.

SAFETY PRECAUTIONS

Check the supply voltage is correct before connecting the instrument.

Do not expose to water or moisture: use the controller only within the operating limits avoiding

sudden temperature changes with high atmospheric humidity to prevent

condensation

Warning: disconnect all electrical connections before any kind of maintenance.

Fit the probe where it is not accessible by the End User. The instrument must not be opened.

In case of failure or faulty operation send the instrument back to the distributor or to «Dixell

S.p.A.» (see address) with a detailed description of the fault.

Consider the maximum current which can be applied to each relay (see Technical Data).

Ensure that the wires for probes, loads and the power supply are separated and far enough from

each other, without crossing or intertwining.

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in

parallel with inductive loads could be useful.

2. General description

Model XW20K is microprocessor based controller suitable for applications on normal or medium

temperature refrigerating units. It has to be connected by means of a two-wire cable (∅ 1mm) at a

distance of up to 30 meters to the keyboard T620 or V620 or CX620.

It is provided with two relay outputs to control compressor and light. It is also provided with 3 NTC

probe inputs, one for temperature control, one to control the defrost end temperature of the evaporator

and the third to control condenser temperature or to display another temperature.

The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a

network line ModBUS-RTU compatible such as the dIXEL monitoring units of X-WEB family. It

allows to program the controller by means the HOT KEY programming keyboard.

The instrument is fully configurable through special parameters that can be easily programmed

through the keyboard.

3. Controlling loads

3.1 THE COMPRESSOR

The regulation is performed according to the temperature measured by the thermostat probe with a

positive differential from the set point: if the temperature increases and reaches set point plus

differential the compressor is started and then turned off when the temperature reaches the set point

value again.

In case of fault in the thermostat probe the start and stop of the compressor are timed through

parameters «COn» and «COF».

The relay of the second compressor is activated in parallel with the relay of the first compressor, with a

possible delay set in the AC1 parameter. Both the compressors are switched off at the same time.

3.2 FAST FREEZING

When defrost is not in progress, it can be activated by holding the «o» key pressed for about 3

seconds. The compressor operates to maintain the «ccS» set point for the time set through the «CCt»

parameter. The cycle can be terminated before the end of the set time using the same activation key

«o» for 3 seconds.

DEFROST

Defrost is performed through a simple stop of the compressor. Parameter «IdF» controls the interval

between defrost cycles, while its length is controlled by parameter «MdF».

3.3 DEFROST

Defrost is performed through a simple stop of the compressor. The parameters involved are: to control

the interval between defrost cycles (IdF), its maximum length (MdF) and two defrost modes: timed or

controlled by the evaporator’s probe (dFP and P3P). At the end of defrost dripping time is started, its

length is set in the FSt parameter. With FSt =0 the dripping time is disabled.

4. Relay 22-23 configuration- special functions

By means of the parameter oA3, it’s possible to configure the functions of the light relay (22-23), as

described in the following paragraphs:

OA3 = LIG: LIGHT RELAY (FACTORY SETTING)

By setting oA3 = Lig the relay will work as light relay, it is switched on and off by the light button on the

keyboard and is affected by status of the digital input when i1F = dor.

OA3 = CP2 2

COMPRESSOR MANAGEMENT

ND

By setting oA3 = cP2, the relay at terminals 22-23 will operate as «second compressor». It will be

activated in parallel with the relay of the first compressor, with a possible delay set in the AC1

parameter (seconds). Both the compressors are switched off at the same time.

1592026000 XW20K GB R1.0 22.02.2008.doc

Installing and Operating Instructions

formation of

OA3 = ONF: ON –OFF RELAY

By setting oA3 =onF, the relay will operate as «on-off» relay: it will be activated when the controller is

switched on and it will be switched off when the controller is in stand-by status.

OA3 = AUS: AUXILIARY RELAY

By setting oA3 = AUS, the relay 22-23 will work as auxiliary thermostat (I.E.. anti condensing heater).

Parameters involved:

ACH (cL, Ht): Kind of regulation for the auxiliary relay: Ht = heating / CL = cooling;

SAA (-50÷150) Set point for auxiliary relay

SHy (0÷25.5°C) Differential for auxiliary output.

With ACH = CL: aux relay cut in is SAA+SHy, cut out SAA.

o

With ACH = Ht: aux relay cut in is SAA-SHy, cut out SAA.

o

ArP (nP, P1, P2, P3, P4) Probe for auxiliary relay

Sdd (n, Y) Auxiliary output working during defrost

OA3 = ALR: ALARM RELAY

By setting oA3 = ALr the relay will work as alarm relay, it is switched on when an alarm happens.

Parameters involved:

tbA (n, y) Alarm relay silencing

AoP (cL; oP) Alarm relay polarity

OA3 = DB: NEUTRAL ZONE

By setting oA3 = db the controller will perform a

«neutral zone» regulation.

The heating element has to be connected to the

oA3 relay (22-23)

If the temperature increases and reaches set

point plus differential (+HY) the compressor is

started and then turned off when the

temperature reaches the set point value again.

If the temperature decreases and reaches the

set point minus differential( -HY) the oA3 output

(heater) is switched on and then turned OFF

when the temperature reaches again the set

point.

5. Keyboards

V620

To display and modify target set point; in programming mode it selects a parameter

or confirm an operation. By holding it pressed for 3s when max or min temperature

is displayed it will be erased.

To see the max. stored temperature; in programming mode it browses the

parameter codes or increases the displayed value.

By holding it pressed for 3s the fast freezing cycle is started.

To see the min stored temperature; in programming mode it browses the parameter

codes or decreases the displayed value.

By holding it pressed for 3s the defrost is started.

Switch ON and OFF the cold room light.

Switch ON and OFF the instrument.

KEY COMBINATIONS

+

To lock and unlock the keyboard.

XW20K

1592026000

T620

CX620

1/5

XR20C
Модель XR20C , термостат с простейшим циклом оттайки, сконструированный для применения в холодильной области при нормальной температуре. Прибор обеспечен реле выхода, для того, чтобы управлять компрессором, и входом, для датчиков РТС или NТС. Внутренний таймер организует простейший цикл оттайки.

Скачать

XR60
Модель XR60C , прибор с циклом оттайки, сконструированный для применения в холодильной области при нормальной и низкой температуре, также позволяет контролировать работу вентиляторов. Прибор обеспечен 3 реле выхода, для того, чтобы управлять компрессором, вентилятором и оттайкой, которая может быть как электрической, так и оттайкой горячим газом. Входами для 2 датчиков NТС ,один из которых нужен для контролдя температуры в объеме, другой для контроля температуры в испарителе и управления циклом оттайки и работы вентилятора.

Скачать

XR70C
Модель XR70C , прибор с циклом оттайки, сконструированный для применения в холодильной области при нормальной и низкой температуре, также позволяет контролировать работу вентиляторов. Прибор обеспечен 3 реле выхода, для того, чтобы управлять компрессором, вентилятором и оттайкой, которая может быть как электрической , так и оттайкой горячим газом. Входами для 2 датчиков NТС ,один из которых нужен для контролдя температуры в объеме, другой для контроля температуры в испарителе и управления циклом оттайки и работы вентилятора.)

Скачать

XC440(серия)
XC440C, XC440D, XC460D — серия семейства регуляторов Dixell разработан, чтобы управлять централями из нескольких компрессоров или конденсаторами с несколькими вентиляторами. Эта возможность гибко и всесторонне управлять устройствами улучшена возмлжностью выбирать номер и размер нагрузок, тип заданного действия: прямое или инверсивное, и 3 вида различной функциональной логики.

Скачать

XC650C(серия)
Серии XC650C управляют как компрессорами, так и вентиляторами в системах конденсации. Компрессора могут быть простыми, многоступенчатыми или с разными мощностями. Управление осуществляется при помощи нейтральной зоны или пропорционального регулирования и основано на давлении или температуре определяемой в зоне низкого давления (компрессоры) и в круге высокого давления (конденсаторы). Специальный алгоритм балансирует часы работы компрессоров, распределяя нагрузку равномерно. Контроллеры могут конвертировать как высокое, так и низкое давление и отображать их в виде температур.

Скачать

XC800M XC900M(серии)
Контроллеры XC807M, XC811M, XC907M, XC911M управляют как компрессорами, так и вентиляторами в системах конденсации. Компрессора могут быть простыми, многоступенчатыми или с разными мощностями. Управление осуществляется при помощи нейтральной зоны или пропорционального регулирования и основано на давлении или температуре определяемой в зоне низкого давления (компрессоры) и в круге высокого давления (конденсаторы). Специальный алгоритм балансирует часы работы компрессоров, распределяя нагрузку равномерно. Контроллеры могут конвертировать как высокое, так и низкое давление и отображать их в виде температур.

Скачать

XP110 XP111(серии)
XP110C, XP111C, (32×74мм размер), XP110D, XP111D (на ДИН-РЕЙКУ) и XP111R, (72×72мм размер), является одноступенчатым релейным регулятором для управления давлением с прямым или обратным (выбираемым) действием. Аналоговый тип входа должен быть выбран и определен при заказе, согласно технологическому параметру, которым нужно управлять.

Скачать

XR160C XR170C
Модели XR160C и XR170C , приборы с циклом оттайки, сконструированные для применения в холодильной области при нормальной и низкой температуре, также позволяют контролировать работу вентиляторов. Приборы обеспечены 3 реле выхода, для того, чтобы управлять компрессором, вентилятором и оттайкой, которая может быть как электрической, так и оттайкой горячим газом. Входами для 2 датчиков NТС ,один из которых нужен для контролдя температуры в объеме, другой для контроля температуры в испарителе и управления циклом оттайки и работы вентилятора.

Скачать

серия XT
XT120C, XT121C, XT124C, XT125C (корпус 32×74 мм.), XT120D, XT121D (крепёж на ДИН-РЕЙКУ) и XT121R, XT125R (корпус 72×72 мм.), является универсальным прибором на основе микропроцессора с выходом на реле, разработанные для широкого диапазона применения в индустриальном секторе, особенно когда требуется два ступенчатых конфигурируемых регулятора.

Скачать

XR06CX
XR06CX, в формате 32 x 74 x 60мм — это микропроцессорный контроллер, подходящий для применения в средне и низкотемпературных блоках охлаждения с вентиляцией. У него есть три релейных выхода для управления компрессором, вентилятором и оттайкой, которая может быть либо электрической, либо с реверсивным циклом (горячим газом). Прибор также снабжен 2 входами для датчиков NTC, первый — для контроля температуры, а второй должен размещаться на испарителе — для контроля температуры окончания оттайки и для управления вентилятором. Также он снабжен конфигурируемым цифровым входом. Имеется возможность легко и быстро запрограммировать контроллер с помощью ключа HOTKEY.

Скачать

XC645CX
Контроллер XC645CX разработан для управления и компрессорами, и вентиляторами конденсатора, работающими в составе агрегата. Компрессоры могут быть цифровыми спиральными (digital scroll), простыми, многоступенчатыми или разной мощности. Управление осуществляется по типу с «нейтральной зоной» или с «зоной пропорциональности» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) и нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки компрессоров, чтобы равномерно распределять рабочую нагрузку. Данный контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры. Полная информация о состоянии системы предоставляется на передней панели путем показа давления (температур) всасывания и конденсации, состояния нагрузок, возможных аварий или условий обслуживания. Каждая нагрузка имеет свой аварийный вход, который способен остановить ее при активации. Для обеспечения общей безопасности системы также имеются два входа для реле низкого и высокого давления: при их срабатывании система останавливается. Контроллер можно легко запрограммировать при подаче на него питания с помощью ключа HOT KEY. Контроллер также можно подключить к системе управления и мониторинга семейства XWEB благодаря последовательному TTL-выходу, используя стандартный протокол ModBus RTU.

Скачать

XC1008D, XC1011D, XC1015D и VGC810
Электронный контроллер для компрессорно-конденсаторных Установок. Примечание: При программировании параметров в зависимости от версии прошивки прибора, некоторые параметры могут не совпадать с указанными в инструкции. Они могут перескакивать на несколько пунктов по списку, либо вообще могут быть не указаны в таковом. Опыт работы показывает, что это ни как не сказывается на работе. Работают без сбоев в течении 5 лет непрерывной работы.

Скачать

XR03CX, XR04CX
XR03CX, в коротком формате 32х74×50 мм, — это микропроцессорный контроллер, подходящий для применения в блоках охлаждения с нормальной температурой. У него есть два релейных выхода: один – для компрессора, а другой — для выдачи аварии или как дополнительный выход. Он также снабжен входом для датчика NTC и одним цифровым входом для сигнала аварии, для включения дополнительного выхода или для запуска оттайки. Прибор полностью конфигурируется с помощью специальных параметров, которые могут быть легко запрограммированы с клавиатуры или ключом HOTKEY.

Скачать

XW60K
Модель XW60K является микропроцессорным контроллером подходящим для применения в средне- и низкотемпературных холодильных системах. При помощи двужильного кабеля (диам. 1мм) к нему на дистанции до 30м могут подключаться клавиатуры T620T или T620 или V620 или CX620. У него есть 3 релейных выхода для управления компрессором, вентилятором, освещением и оттайкой, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Он также снабжен четырьмя входами датчиков NTC или PTC, первый – для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором, третий и четвертый — для подачи сигнала аварии по температуре конденсатора или для показа температуры, отличной от температуры, по которой происходит регулирование. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к сети, совместимой с ModBUS-RTU, такой как блоки мониторинга dIXELL семейства XWEB. Также он позволяет программировать контроллер с помощью ключа программирования HOT KEY. Прибор полностью конфигурируется с помощью специальных параметров, которые могут быть легко запрограммированы с клавиатуры.

Скачать

Tb77
Модель TB77, с панелью размерами 32х74 мм, является контроллером с микропроцессором и предназначена для использования в средне- и низкотемпературных агрегатах. Она поставляется с тремя выходными реле для управления компрессором, оттайкой — которая может производиться как электронагревателями, так и горячим хладагентом — и вентиляторами воздухоохладителей. Она также комплектуется двумя входными датчиками (PTC): один для контроля температуры в камере, другой расположен в воздухоохладителе для контроля температуры прекращения оттайки. Каждый прибор полностью настраивается с помощью специальных параметров, которые могут быть легко запрограммированы с помощью кнопок.

Скачать

XR10C
Модель XR10C, с панелью размерами 32х74 мм, является одноступенчатым температурным контроллером, предназначенным для использования при охлаждении или обогреве.

Скачать

XR20CX
Модель XR20CX, формата 32×74мм – это цифровой термостат с оттайкой «off cycle», предназначенный для применения в холодильных системах с нормальной температурой. У него имеется релейный выход для управления компрессором. Он также снабжен 2 входами датчиков NTC или PTC, первый — для контроля температуры, второй, опциональный, подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Цифровой вход может работать как третий датчик температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к сети, совместимой с ModBUS-RTU, такой как блоки мониторинга DIXEL семейства XWEB. Также он позволяет программировать контроллер с помощью ключа программирования HOT KEY. Прибор полностью конфигурируется с помощью специальных параметров, которые могут быть легко запрограммированы с клавиатуры.

Скачать

XR120D-XR130D со встроенным RS со встроенным RS485
Контроллеры серии подключаются к системе мониторинга через выход RS485. Они повсеместно эксплуатируются в вентиляционных системах и устройствах охлаждения воздуха для обеспечивания максимальной производительности. Управление компрессором в данном случае выполняется по одному релейному выходу микропроцессора. Наличие двух NTC позволяет одним датчиком контролировать температурный диапазон, а другим пользоваться как элементом визуализации. Благодаря удобному программированию, контроллеры XR120D-XR130D в кратчайшие сроки настраиваются под конкретные требования системы охлаждения.

Скачать

XR160D – XR170D
Модели серии устанавливаются на DIN-рейку. Они оснащаются циклом оттайки, разработанный для эксплуатации в области холодильного оборудования. Контроллеры работают в нормально- и низкотемпературной среде, также обеспечивая управление вентиляционными системами. Электронное устройство основывается на 3х реле выхода, через которые выполняется контроль функционирования оттайки, компрессора и вентилятора. Программирование прибора осуществляется в кратчайшие сроки через клавиатуру, поэтому функции контроллера можно легко настроить под рабочие требования.

Скачать

Скачать инструкции по эксплуатации для оборудования Dixell — максимально упростить процесс знакомства с данными техническим аппаратами. В условиях современности, мануал можно скачать прямо на планшет, потому как используется популярный формат pdf-файла. Для большинства потребителей — это единственный выход ознакомиться с техникой, ведь в сложных экономических условиях вызов специалиста может влететь в копеечку. Скачать бесплатно инструкцию по эксплуатации сегодня очень просто. Большая часть специализированных сайтов и интернет-порталов готовы предоставить всем желающим данную услугу. 

  Название Инструкция Комментарий

Контроллер Dixell XH240 L-V

Контроллер Dixell XH240 L-V Контроллер Dixell XH240 L-V XH240L-V — контроллер предназначенный для поддержания температуры и влажности в среднетемпературных холодильных системах. 5 релейных выходов для управления компрессором, нагревательными элементами, вентилятором, освещением и увлажнителем. Они снабжены 1 входом NTC для контроля температуры, и входом 4-20мА для датчика влажности. Имеется один цифровой вход (контакт без напряжения), конфигурируемый параметром. Специальный выход позволяет программировать список параметров с помощью ключа «Hot Key»

Контроллер Dixell XM660K

Контроллер Dixell XM660K Контроллер Dixell XM660K XM660K — оснащен четырьмя релейными выходами, которые могут использоваться на выбор: для управления соленоидным клапаном, оттайкой (электрической либо горячим газом), для управления вентиляторами испарителя или освещением. Четыре входа датчиков: контроль температуры, контроль температуры окончания оттайки испарителя, индикация, возможное использование для систем с виртуальным датчиком или для измерения температуры воздуха на входе/выходе.

Контроллер Dixell XR60C

Контроллер Dixell XR60C Контроллер Dixell XR60C XR60C — с циклом оттайки, используется в холодильной отрасли при средней и низкой температуре, с контролем работы вентиляторов. 3 входа реле для управления компрессором, вентилятором и оттайкой (электрической / горячим газом), 2 датчика NТС.

Контроллер Dixell XC 650 C

Контроллер Dixell XC 650 C Контроллер Dixell XC 650 C XC 650C — разработан для управления и компрессорами и вентиляторами конденсатора, работающими в составе агрегата. Компрессоры могут быть простыми, многоступенчатыми или разной мощности. Управление осуществляется по типу с «нейтральной зоной» или с «зоной пропорциональности» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) и нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки компрессоров для равномерного распределения рабочей нагрузки

Dixell_XC807M-XC911M

Контроллер Dixell XC807-XC911 Контроллер Dixell XC807-XC911 XC807, XC911 — управляют как компрессорами, так и вентиляторами в системах конденсации. Передняя панель информирует о давлении на всасывании и давлении в конденсаторе, возможные аварийные сигналы и условия технического обслуживания. Контроллер оборудован двумя аварийными выключателями высокого и низкого давления системы

Dixell T66 - XW60K

Gamko Flexbar Dixell T66 — XW60K

Dixell XR 20 C

Контроллер Dixell XR 20C Dixell XR 20C XR20C — с простейшим циклом оттайки, для использования в холодильной области при нормальной температуре. Блок имеет реле выхода для управления компрессором, работает с датчиками РТС или NТС. Цикл оттайки по внутреннему таймеру

Dixell XR 70 CX

Контроллер Dixell XR 70 CX Dixell XR 70 CX XR70 CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. 4 релейных выхода для управления компрессором, вентилятором и оттайкой, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Последнее реле может использоваться для освещения, для сигнала аварии или как дополнительный выход. Он также снабжен четырьмя входами датчиков NTC или PTC, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором. Цифровой вход может работать в качестве третьего датчика температуры. Четвертый датчик, подключаемый к разъему HOT KEY, используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Выход HOT KEY позволяет подключить контроллер с помощью внешнего модуля XJ485-CX к сети, совместимой с ModBUS-RTU , такой как блоки мониторинга Dixell семейства XWEB. Разъем HOT key позволяет программировать контроллер с помощью ключа программирования HOT KEY. Прибор полностью конфигурируется с помощью специальных параметров, которые могут быть легко запрограммированы с клавиатуры

Dixell XR160C - XR170C

Контроллер Dixell XR160C — XR170C Dixell XR160C — XR170C XR160C, XR170C — цифровой контроллер для вентилируемых холодильных камер с функцией оттайки тэнами или горячими парами, управления работой вентилятора воздухоохладителя

Dixell XH360L-V

Контроллер Dixell XH360L-V Dixell XH360L-V XH360L, формата 38×185 и XH360V, формата 100×64 — это микропроцессорные контроллеры, подходящие для применения в средне — или низкотемпературных блоках охлаждения. 6 релейных выходов для управления компрессором, нагревательными элементами, оттайкой — вытяжным вентилятором, вентилятором, осушителем — светом и увлажнителем. Они снабжены 2 входами NTC: один — для контроля температуры, другой — для контроля оттайки . Также имеется вход 4 ÷ 20 мА для датчика влажности

Dixell XC440

Контроллер Dixell XC440 Dixell XC440 Контроллер XC440C разработан для управления компрессорами или вентиляторами конденсатора, работающими в составе агрегата. Компрессоры могут быть простыми, многоступенчатыми или разной мощности. Управление осуществляется по типу с «нейтральной зоной» или с «зоной пропорциональности» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) или нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки компрессоров, чтобы равномерно распределять рабочую нагрузку. Данный контроллер может конвертировать давление и показывать его на дисплее в виде температуры. Полная информация о состоянии системы предоставляется на передней панели путем показа давления (температур) всасывания и конденсации, состояния нагрузок, возможных аварий или условий обслуживания

Dixell XP 110 - 111 C - D

Контроллер Dixell XP 110-111 C-D Dixell XP 110 — 111 C — D XP110C, XP111C (32×74мм размер), XP110D, XP111D (на ДИН-РЕЙКУ) и XP111R, (72×72мм размер), является одноступенчатым релейным регулятором для управления давлением с прямым или обратным (выбираемым) действием. Аналоговый тип входа должен быть выбран и определен при заказе, согласно технологическому параметру, которым нужно управлять

Dixell XT 110-111 C-D

Контроллер Dixell XT 110-111 C-D Dixell XT 110-111 C-D XT110C, XT111C и XT110D, XT111D ( формат на DIN- рейку ) — одноступенчатые контроллеры ВКЛ / ВЫКЛ для применений с управлением по температуре, влажности и давлению с прямым или обратным действием, выбираемым пользователем. Тип аналогового входа может задаваться с помощью параметра из следующих, согласно модели : — PTC, NTC; — PTC, NTC, Pt100, Термопара J, K, S; 4 ÷ 20 мА, 0 ÷ 1 В, 0 ÷ 10 В

Dixell XR70C-D XR72C

Контроллер Dixell XR70C-D XR72C Dixell XR70C-D XR72C XR70C-D — прибор с циклом оттайки, сконструированный для применения в холодильной области при нормальной и низкой температуре, также позволяет контролировать работу вентиляторов. 3 реле выхода для управления компрессором, вентилятором и оттайкой (электрической, горячим газом), входами для 2 датчиков NТС

Dixell XT 120C – XT 125R

Контроллер Dixell XT 120C – XT 125R Dixell XT 120C – XT 125R XT120C, XT121C, XT124C, XT125C (корпус 32×74 мм), XT120D, XT121D (крепёж на ДИН-РЕЙКУ) и XT121R, XT125R (корпус 72×72 мм) является семейством универсальных приборов на основе микропроцессора с выходом на реле, особенно когда требуется два ступенчатых конфигурируемых регулятора

Dixell XW270L - XW271L

Контроллер Dixell XW270L — XW271L Dixell XW270L — XW271L XW270L — XW271L — для применения в средне- и низкотемпературных холодильных системах. 6 релейных выходов служат для управления компрессором, двумя оттайками (тэн / горячим газом), вентиляторами испарителя, освещением (вкл/выкл). Так же есть три входа для датчиков NTC, один для термостатирования и два для контроля температуры окончания оттайки

Dixell XW40L - XW40V

Контроллер Dixell XW40L — XW40V Dixell XW40L — XW40V XW40L-XW40V — для применения в средне и низкотемпературных холодильных системах. 3 релейных выхода служат для управления компрессором, двумя оттайками (тэн / горячим газом), освещением вкл/выкл. Так же есть два входа для датчиков NTC

Dixell XW 60 K

Контроллер Dixell XW 60 K Dixell XW 60 K Модель XW60K является микропроцессорным контроллером подходящим для применения в средне- и низкотемпературных холодильных системах. При помощи двужильного кабеля (1мм) к нему на дистанции до 30м могут подключаться клавиатуры T620T или T620 или V620 или CX620. У него есть 3 релейных выхода для управления компрессором, вентилятором,
освещением и оттайкой, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Он также снабжен четырьмя входами датчиков NTC или PTC, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором, третий и четвертый — для подачи сигнала аварии по температуре конденсатора или для показа температуры, отличной от температуры, по которой происходит регулирование.

Контроллер Dixell XW60LRH

Контроллер Dixell XW60LRH Контроллер Dixell XW60LRH Dixell XW60LRH — микропроцессорный контроллер для применения в среднетемпературных холодильных установок. Три релейных выхода для управления компрессором, вентилятором и освещением.

Контроллер Dixell XLR170

Контроллер Dixell XLR170 Контроллер Dixell XLR170 Модели XLR130 и XLR170, в формате 210×230мм, являются микропроцессорными контроллерами для средне- и низкотемпературных холодильных систем. Они имеют четыре (XLR130) или шесть (XLR170) релейных выходов для управления компрессором, оттайкой – которая может быть электрической или газовой (XLR170) – вентиляторами испарителя (в XLR130 надо сконфигурировать доп. реле), освещением, аварийной сигнализацией и дополнительным реле.

Контроллер Dixell XLH260

Контроллер Dixell XLH260 Контроллер Dixell XLH260 XLH 260 — контроллер для поддержания температуры и влажности в средне- и низкотемпературных холодильных системах. Прибор снабжен шестью релейными выходами для управления компрессором, нагревателем, оттайкой, вентилятором, осушителем и увлажнителем. Имеет два аналоговых входа для датчиков NTC – для термостатирования и оттайки, один вход 4-20 мА для датчика влажности. Цифровой вход – один конфигурируемый без напряжения. Контроллер может быть запрограммирован с ключа “Hot Key”.

Контроллер Dixell XLH360

Контроллер Dixell XLH360 Контроллер Dixell XLH360 (ENG)

Dixell XLR470

Контроллер Dixell XLR470 Dixell XLR470 XLR470 — цифровой контроллер для холодильных камер с двойным управлением температурой (для нормальной и низкой температуры). Идеально подходит для систем с нагревом-охлаждением, таких как стойка для водяной бани с холодильной камерой внизу. Предназначен для систем с двумя испарителями или 2 независимыми контурами. Встроенное управление оттайкой. Охлаждение или нагрев выбирается пользователем. Мгновенный обзор состояния устройства при помощи иконок на дисплее.

Dixell XW220L

Контроллер Dixell XW220L Контроллер Dixell XW220L Контроллер Dixell XW220L — для применения на холодильных установках. Контроллер снабжен двумя релейными выходами для управления компрессором и подсветкой. Два входа датчиков NTC. Два цифровых входа (свободный контакт) для дверного выключателя и настраивается по параметру. Выход TTL позволяет подключать с помощью внешнего модуля TTL / RS485 модуль ModBUS RTU для системы мониторинга

Dixell XW230L

Контроллер Dixell XW230L Dixell XW230L Контроллер Dixell XW230L для использования на средних или низкотемпературных холодильных установках. Четыре релейных выхода для управления компрессором, сигнализацией и вспомогательным выходом. Два датчика NTC (контроль температуры и дополнительный для дисплея). Два цифровых входа (свободный контакт) для дверного выключателя и настраиваемый параметром. Стандартный выход TTL позволяет пользователю подключать с помощью внешнего модуля TTL / RS485 совместимую с ModBUSRTU систему мониторинга

Контроллер Dixell XW260L

Контроллер Dixell XW260L Dixell XW260L Контроллер Dixell XW260L — для применения на средних или низкотемпературные холодильные установки. Cнабжен четырьмя релейными выходами для управления компрессором, процессом оттайки (электрической, горячий газ), вентилятором испарителя и светом. Три датчика NTC (температура объема,оттайкой и третья, опционная, для дисплея. Стандартный выход TTL позволяет пользователю подключать с помощью внешнего модуля TTL/RS485 модуль ModBUSRTU системы мониторинга

Контроллер Dixell XW263L

Контроллер Dixell XW263L Dixell XW263L Контроллер Dixell XW263L для управления средне- или низкотемпературных холодильных установок. Снабжен четырьмя релейными выходами для управления компрессором, оттайкой (электрический, горячий газ), вентилятором испарителя и светом. Два датчика NTC (объем, испаритель)

Dixell XW264L

Контроллер Dixell XW264L Dixell XW264L Контроллер Dixell XW264L являются микропроцессорными контроллерами для применения в средне- и низкотемпературных холодильных системах. У него есть 6 релейных выходов для управления компрессором, двумя оттайками (электронагреватель или горячим газом), вентиляторами испарителя, освещением или вкл/выкл. Так же есть три входа для датчиков NTC, один для термостатирования и два для контроля температуры окончания оттайки двух испарителей. Два цифровых входа (без напряжения) для контроля двери и конфигурируемый. TTL разъем позволяющий пользователю с помощью внешнего конвертора TTL/RS485 подключить контроллер к ModBUS-RTU совместимой с системой мониторинга Dixell, такой как XWEB300В/500/3000/5000 и для программирования с помощью “Hot Key”. Опционально XW-REP выход для удаленного дисплея, аналоговый выход 4÷20 мА для управления вентилятором испарителя или конденсатора и последовательный выход с RS485.

Dixell XW563L

Контроллер Dixell XW563L Dixell XW563L Контроллер Dixell XW563L является микропроцессорным контроллером, подходящим для применение на средне- или низкотемпературных холодильных установках. Снабжен четырьмя реле выходы для управления компрессором, оттайка (электричеством, горячим газом), вентиляторы испарителя и свет. Два датчика NTC (объем, испаритель). Два цифровых входа (свободный контакт) для дверного выключателя и настраивается по параметру. Выход RS485 позволяет пользователю подключать совместимый с ModBUS-RTU мониторинг система

Dixell XW570L

Контроллер Dixell XW570L Dixell XW570L Контроллер Dixell XW570L для применения на средне- или низкотемпературном холодильном оборудовании. Снабжен шестью релейными выходами для управления компрессором, оттайкой (электрическая, горячий газ), вентиляторами испарителя, лампочками, сигнализацией и вспомогательным выходом. Три датчика NTC (объем, испаритель и третий опционный для дисплея). Есть два цифровых входа (свободный контакт) для дверного выключателя и настраивается по параметру. Стандартный выход TTL позволяет пользователю подключать с помощью внешнего модуля TTL/RS485 модуль ModBUSRTU совместимая система мониторинга и запрограммировать список параметров с помощью “горячей клавиши». Выход для удаленного дисплея XW-REP, выход 4÷20 мА для управления вентиляторами испарителя или конденсатора и прямой последовательный выход RS485 доступен в качестве опции

Dixell XW30V

Контроллер Dixell XW30L-XW30V Dixell XW30V Контроллер Dixell модель XW30L, формат 38×185 мм, и модель XW30V, формат 100×64, основаны на микропроцессоре контроллеры подходят для применения на холодильных установках средней температуры. Три релейных выхода управляют компрессором, подсветкой и сигнализацией тревоги. Один датчик NTC или PTC. Есть 1 цифровой входами (свободный контакт) настраиваемый параметр

Dixell XC15CX-XC35CX

Контроллер Dixell XC15CX-XC35CX Dixell XC15CX-XC35CX Контроллер Dixell XC15CX-XC35CX являются контроллерами предназначенными для управления одно- и двухкомпрессорными агрегатами. Он может управлять простыми компрессорами, компрессорами с преобразователями частоты и компрессорами Digital. Контроллер имеет:
— 1 (ХС15СХ) или 2 (ХС35СХ) релейных выхода для управления компрессорами или вентиляторами или аварийной сигнализации;
— 1 тиристорный выход для управления скоростью вращения вентиляторов в режиме фазорезки (макс. ток 2.2 A) или соленоидным клапаном компрессора Digital;
— 1 аналоговый выход (0-10В или ШИМ) для управления ЕС-вентиляторами, преобразователями частоты или режима пропорционального повторителя;
— До 3-х цифровых входов без напряжения для мониторинга аварий;
— 2 аналоговых входа для ратиометрических датчиков давления (0-5В);
— До 4-х температурных датчиков NTC10k, NTC86k или PT1000.
XC15CX оснащён только одним реле 16 A, у ХС35СХ имеется также второе реле номиналом 5А. Все функции (исключая связанные со вторым реле) одинаковые для обоих приборов.

Dixell XC10CX-XC30CX

Контроллер Dixell XC10CX-XC30CX Dixell XC10CX-XC30CX Модель XC30CX, формат 32x74mm, представляет собой цифровой термостат для применения в конденсаторных установках. Это обеспечивает три цифровых (релейных) выхода, один для компрессора, а другой для управления вентиляторами. Два датчика NTC или ratiometric зонда, который нужно использовать на линии всасывания и конденсатора. Цифровые входы могут работать для управления безопасностью конденсаторного агрегата. Модель XC10CX отличается от XC30CX по номеру цифрового выхода. На самом деле, XC10CX имеет только один цифровой выход, который используется для управления компрессором.

Dixell XR20CX

Контроллер Dixell XR20CX Dixell XR20CX Контроллер Dixell XR20CX — цифровой термостат с оттайкой “off cycle”, предназначенный для применения в холодильных системах с нормальной температурой. Имеется релейный выход для управления компрессором. Он также снабжен 2 входами датчиков NTC или PTC, первый — для контроля температуры, второй, опциональный, подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Цифровой вход может работать как третий датчик температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к
сети, совместимой с ModBUS-RTU, такой как блоки мониторинга dIXEL семейства XWEB.

Dixell XR40CX

Контроллер Dixell XR40CX Dixell XR40CX Контроллер Dixell XR40CX — для применения в холодильных системах с нормальной и низкой температурой. Имеется два реле для управления компрессором и оттайкой (электрическая, горячим газом). Он также снабжен 3 входами датчиков NTC или PTC, первый — для контроля температуры объема, второй — испарителя, третий — опционально может быть подключен через HOT KEY для подачи сигнала тревоги температуры конденсатора или для отображения температуры. Цифровой вход может работать как четвертый температурный зонд.

Dixell XR60CX

Контроллер Dixell XR60CX Dixell XR60CX Контроллер Dixell XR60CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. Три релейных выхода для управления компрессором, вентилятором, оттайкой (электрическая, горячий газ). Он также снабжен тремя входами датчиков NTC или PTC, первый температуры объема, второй на испарителе для контроля температуры окончания оттайки и управления вентилятором, третий датчик, опциональный, подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Цифровой вход может работать как четвертый датчик температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к сети, совместимой с ModBUS-RTU, такой как блоки мониторинга dIXEL семейства XWEB.

Dixell XR70CX

Контроллер Dixell XR70CX Dixell XR70CX Контроллер Dixell XR70CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. Четыре релейных выхода для управления компрессором, вентилятором и оттайкой (электрическая, горячий газ). Последнее реле может использоваться для освещения, для сигнала аварии или как дополнительный выход. Он также снабжен четырьмя входами датчиков NTC или PTC, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором. Цифровой вход может работать в качестве третьего датчика температуры. Четвертый датчик, подключаемый к разъему HOT KEY, используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Выход HOT KEY позволяет подключить контроллер с помощью внешнего модуля XJ485-CX к сети.

Dixell XR64CX

Контроллер Dixell XR64CX Dixell XR64CX Контроллер Dixell XR64CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией и 2мя
испарителями. У него есть четыре релейных выхода для управления компрессором, вентилятором, оттайкой 1 и 2, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Он также снабжен до четырех входов датчиков NTC или PTC, первый — для контроля температуры, второй и третий, расположенные на испарителе, для контроля температуры окончания оттайки и управления вентилятором. Четвертый датчик подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к сети.

Dixell XR75CX

Контроллер Dixell XR75CX Dixell XR75CX Контроллер Dixell XR75CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. Четыре релейных выхода для управления компрессором, вентилятором, оттайкой (электрическая, горячий газ) и освещением. Он может снабжаться Часами Реального Времени, которые позволяют запрограммировать до 6 циклов оттайки ежедневно, с разделением на выходные и рабочие дни. Функция “День и Ночь” с двумя разными уставками подходит для энергосбережения. Он также снабжен четырьмя входами датчиков NTC или PT1000, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором. Один из 2 цифровых входов может работать в качестве третьего датчика температуры. Четвертый датчик используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Последовательный выход RS485 позволяет подключить контроллер к сети, совместимой с ModBUS-RTU.

Dixell XC645CX

Контроллер Dixell XC645CX Dixell XC645CX Контроллер Dixell XC645CX — для управления компрессорами и вентиляторами конденсатора, работающими в составе агрегата.
В составе агрегата один компрессор всегда – Digital (спиральный или поршневой), остальные могут быть как спиральными, так и поршневыми с регулировкой производительности или без неё. Управление компрессорами осуществляется по алгоритму с «нейтральной зоной» и основано на считывании величины давления или температуры в контурах всасывания (низкое давление — компрессоры) и нагнетания (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки нагрузок. Управление вентиляторами – пропорциональное. Контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры.

Dixell XC650CX

Контроллер Dixell XC650CX Dixell XC650CX Контроллер Dixell XC650CX — для управления компрессорами и вентиляторами конденсатора, работающими в составе агрегата.
Компрессоры могут быть спиральными, поршневыми, с регулировкой производительности, в том числе при помощи преобразователя частоты. Контроллер может управлять двумя контурами всасывания с общим контуром конденсации. Управление компрессорами осуществляется по алгоритму с «нейтральной зоной» и основано на считывании величины давления или температуры в контурах всасывания (низкое давление — компрессоры) и нагнетания (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки нагрузок. Управление вентиляторами – пропорциональное. Данный контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры.

Dixell XC660D

Контроллер Dixell XC660D Dixell XC660D Контроллер Dixell XC660D — для управления компрессорами и вентиляторами конденсатора, работающими в составе агрегата.
Компрессоры могут быть спиральными, поршневыми, с регулировкой производительности. Управление компрессорами осуществляется по алгоритму с «нейтральной зоной» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) и нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки нагрузок. Управление вентиляторами – пропорциональное. Данный контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры.

Dixell XC1000D

Контроллер Dixell XC1000D Dixell XC1000D Контроллер Dixell XC1000D — для управления систем контуров охлаждения (до 2 контуров всасывания и 2 контуров конденсации). Благодаря специальным алгоритмам эти контроллеры могут управлять и контролировать установки с CO2, которые работают по каскадному принципу с субкритическим циклом.

Dixell XC807-911M

Контроллер Dixell XC807-911M Dixell XC807-911M Контроллер Dixell серии XC800M и XC900M управляет компрессорами и вентиляторами в системах конденсации.
Компрессора могут быть простыми, многоступенчатыми или с разными мощностями. Управление осуществляется при помощи нейтральной зоны или пропорционального регулирования и основано на давлении или температуре определяемой в зоне низкого давления (компрессоры) и высокого давления (конденсаторы).

Dixell XRi77CX

Контроллер Dixell XRi77CX Dixell XRi77CX Контроллер Dixell XRi77CX — предназначен для применения на средне- или низкотемпературных вентилируемых холодильных установок. Имеет четыре релейных выхода для управления компрессором, вентилятором, оттайкой (электрическая, горячим газом). Снабжен четырьмя входами датчика NTC. Первый зонд для контроля температуры объема. Второй зонд для контроля температуры испарителя. Один из двух цифровых входов может работать как третий температурный зонд. Четвертый зонд используется для контроля температуры конденсатора (для управления сигнализацией конденсатора) или для отображения температуры.

Dixell XWi70K

Контроллер Dixell XWi70K Dixell XWi70K Контроллер Dixell XWi70K предназначен для применения на средне- и низко- температурных холодильных установках. Пять
релейных выходов для управления компрессором, оттайкой (электрическая, горячий газ), испарителем и конденсаторными вентиляторами, светом или сигнализация. Четыре датчика NTC (PTC). Он имеет как частотный выход, так и последовательный порт, который может использоваться для управления переменной скоростью компрессоров. Пара аналоговых выходов (4-20мА или 0-10В) и главный 2-проводный выход RS485

Dixell XEV11D_12D

Контроллер Dixell XEV11D-12D Dixell XEV11D_12D Контроллер Dixell XEV11D-12D — для управления импульсными (ВКЛ/ВЫКЛ) электронными расширительными вентилями. Этот модуль позволяет регулировать перегрев (SH) текучей среды, которая протекает в холодильной системе, с тем чтобы достичь оптимальной производительности и функционирования испарителя независимо от климатических условий или нагрузки. Модули XEV12D оборудованы двумя входами датчиков, один – для датчика давления с интерфейсом 4÷20мА или 0÷5В, а другой – для датчика температуры Pt1000 или NTC. Подключение в локальную сеть LAN позволяет передавать сигнал давления на другие модули XEV, чтобы использовать только один датчик давления в системах с составными шкафами. Имеется также два конфигурируемых цифровых входа, один из них должен быть сконфигурирован для получения запроса охлаждения. Другой цифровой вход может использоваться для оповещения контроллера о том, что идет оттайка. Дисплей с иконками предоставляет удобную визуализацию перегрева (SH), процент времени открытия вентиля или значений датчиков, встроенная клавиатура позволяет программировать контроллер без каких-либо других устройств. Завершая комплектацию контроллера, последовательная сеть RS485.

Dixell XEV22D

Контроллер Dixell XEV22D Dixell XEV22D Контроллер Dixell XEV22D — для управления шаговыми электронными расширительными клапанами. XEV22D позволяет регулировать перегрев (SH) хладагента в испарителе для достижения оптимальной производительности и функционирования испарителя независимо от климатических условий или нагрузки. XEV22D имеет два входа датчиков, один – для датчика давления с интерфейсом 4÷20мА или 0÷5В, а другой – для датчика температуры Pt1000 или NTC-EU / NTC-US. LAN связь позволяет передавать сигнал от одного датчика давления на несколько приборов. Имеется также два конфигурируемых цифровых входа, один – сухой контакт, второй — свободный от напряжения. С дисплея можно просмотреть значение перегрева (SH), степень открытия клапана или показания датчиков, клавиатура позволяет программировать контроллер без каких-либо других
устройств. К системам мониторинга и диспетчеризации XEV22D подключатся с помощью встроенной сетевой карты RS485.

Dixell IEV22D-IEV24D

Контроллер Dixell IEV22D-IEV24D Dixell IEV22D-IEV24D Контроллер Dixell IEV22D-IEV24D — предназначен для управления одним или двумя шаговыми двигателями электронного расширительного клапана. Доступны два различных режима регулирования: * Автономный режим: цифровые входы используются для запуска управления перегревом. Давление кипения датчик и датчик температуры всасывания должны быть соединены с контроллером; * LAN: IEV можно подключить к серии Ichill 200 EVO для того чтобы контролировать перегрев. Для обеспечения наилучшего регулирования рекомендуется подключать датчик давления всасывания непосредственно к контроллеру.
Основные характеристики: * управление одним или двумя электронными расширительными клапанами; * совместимость с несколькими моделями клапанов; * совместимость с различными типами хладагентов; * ручное управление ПИД-регулировкой или адаптивным регулированием.

Dixell_XW10L

Контроллер Dixell_XW10L Контроллер Dixell_XW10L Контроллер Dixell XW10L, формат 38×185 мм, и модель XW10V, формат 100×64, представляют собой микропроцессорные
контроллеры, подходящие для применения в области охлаждения или отопления. Снабжены 2 релейными
выходами, один из которых предназначен для регулирования, а другой — для освещения. Они также снабжены 1
входом датчика NTC или PTC для контроля температуры. Имеется 1 цифровой вход (свободный контакт), настраиваемый по параметру. Вывод позволяет пользователю запрограммировать список параметров с помощью горячей клавиши.

Dixell Wing XW10L-V

Контроллер Dixell Wing XW10L-V Контроллер Dixell Wing XW10L-V

Dixell XH260L-V

Контроллер Dixell XH260L-V Dixell XH260L-V Контроллер Dixell XH260L и XH260V применяются в холодильных установках средней или низкой температуры. Контролируют как влажность, так и температуру. Имеют 6 выходных реле для управления компрессором, нагревательными элементами, размораживанием, осушителем воздуха и увлажнителем воздуха. 2 датчика NTC: объем и испаритель. Вход 4÷20 мА для измерения влажности. Имеется один цифровой вход (свободный контакт), настраиваемый по параметру. Вывод позволяет пользователю запрограммировать список параметров с помощью “Hot Key”.

Dixell XB570L

Контроллер Dixell XB570L Dixell XB570L Контроллер Dixell серии XB созданы для быстрого охлаждения или заморозки продуктов в соответствии с международными стандартами пищевой безопасности.

dIXEL

XW20K AND T620 – V620 – CX620

1. GENERAL WARNING

PLEASE READ BEFORE USING THIS MANUAL

This manual is part of the product and should be kept near the instrument for easy and quick

reference.

The instrument shall not be used for purposes different from those described hereunder. It

cannot be used as a safety device.

Check the application limits before proceeding.

SAFETY PRECAUTIONS

Check the supply voltage is correct before connecting the instrument.

Do not expose to water or moisture: use the controller only within the operating limits avoiding

sudden temperature changes with high atmospheric humidity to prevent

condensation

Warning: disconnect all electrical connections before any kind of maintenance.

Fit the probe where it is not accessible by the End User. The instrument must not be opened.

In case of failure or faulty operation send the instrument back to the distributor or to «Dixell

S.p.A.» (see address) with a detailed description of the fault.

Consider the maximum current which can be applied to each relay (see Technical Data).

Ensure that the wires for probes, loads and the power supply are separated and far enough from

each other, without crossing or intertwining.

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in

parallel with inductive loads could be useful.

2. General description

Model XW20K is microprocessor based controller suitable for applications on normal or medium

temperature refrigerating units. It has to be connected by means of a two-wire cable (∅ 1mm) at a

distance of up to 30 meters to the keyboard T620 or V620 or CX620.

It is provided with two relay outputs to control compressor and light. It is also provided with 3 NTC

probe inputs, one for temperature control, one to control the defrost end temperature of the evaporator

and the third to control condenser temperature or to display another temperature.

The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a

network line ModBUS-RTU compatible such as the dIXEL monitoring units of X-WEB family. It

allows to program the controller by means the HOT KEY programming keyboard.

The instrument is fully configurable through special parameters that can be easily programmed

through the keyboard.

3. Controlling loads

3.1 THE COMPRESSOR

The regulation is performed according to the temperature measured by the thermostat probe with a

positive differential from the set point: if the temperature increases and reaches set point plus

differential the compressor is started and then turned off when the temperature reaches the set point

value again.

In case of fault in the thermostat probe the start and stop of the compressor are timed through

parameters «COn» and «COF».

The relay of the second compressor is activated in parallel with the relay of the first compressor, with a

possible delay set in the AC1 parameter. Both the compressors are switched off at the same time.

3.2 FAST FREEZING

When defrost is not in progress, it can be activated by holding the «o» key pressed for about 3

seconds. The compressor operates to maintain the «ccS» set point for the time set through the «CCt»

parameter. The cycle can be terminated before the end of the set time using the same activation key

«o» for 3 seconds.

DEFROST

Defrost is performed through a simple stop of the compressor. Parameter «IdF» controls the interval

between defrost cycles, while its length is controlled by parameter «MdF».

3.3 DEFROST

Defrost is performed through a simple stop of the compressor. The parameters involved are: to control

the interval between defrost cycles (IdF), its maximum length (MdF) and two defrost modes: timed or

controlled by the evaporator’s probe (dFP and P3P). At the end of defrost dripping time is started, its

length is set in the FSt parameter. With FSt =0 the dripping time is disabled.

4. Relay 22-23 configuration- special functions

By means of the parameter oA3, it’s possible to configure the functions of the light relay (22-23), as

described in the following paragraphs:

OA3 = LIG: LIGHT RELAY (FACTORY SETTING)

By setting oA3 = Lig the relay will work as light relay, it is switched on and off by the light button on the

keyboard and is affected by status of the digital input when i1F = dor.

OA3 = CP2 2

COMPRESSOR MANAGEMENT

ND

By setting oA3 = cP2, the relay at terminals 22-23 will operate as «second compressor». It will be

activated in parallel with the relay of the first compressor, with a possible delay set in the AC1

parameter (seconds). Both the compressors are switched off at the same time.

1592026000 XW20K GB R1.0 22.02.2008.doc

Installing and Operating Instructions

formation of

OA3 = ONF: ON –OFF RELAY

By setting oA3 =onF, the relay will operate as «on-off» relay: it will be activated when the controller is

switched on and it will be switched off when the controller is in stand-by status.

OA3 = AUS: AUXILIARY RELAY

By setting oA3 = AUS, the relay 22-23 will work as auxiliary thermostat (I.E.. anti condensing heater).

Parameters involved:

ACH (cL, Ht): Kind of regulation for the auxiliary relay: Ht = heating / CL = cooling;

SAA (-50÷150) Set point for auxiliary relay

SHy (0÷25.5°C) Differential for auxiliary output.

With ACH = CL: aux relay cut in is SAA+SHy, cut out SAA.

o

With ACH = Ht: aux relay cut in is SAA-SHy, cut out SAA.

o

ArP (nP, P1, P2, P3, P4) Probe for auxiliary relay

Sdd (n, Y) Auxiliary output working during defrost

OA3 = ALR: ALARM RELAY

By setting oA3 = ALr the relay will work as alarm relay, it is switched on when an alarm happens.

Parameters involved:

tbA (n, y) Alarm relay silencing

AoP (cL; oP) Alarm relay polarity

OA3 = DB: NEUTRAL ZONE

By setting oA3 = db the controller will perform a

«neutral zone» regulation.

The heating element has to be connected to the

oA3 relay (22-23)

If the temperature increases and reaches set

point plus differential (+HY) the compressor is

started and then turned off when the

temperature reaches the set point value again.

If the temperature decreases and reaches the

set point minus differential( -HY) the oA3 output

(heater) is switched on and then turned OFF

when the temperature reaches again the set

point.

5. Keyboards

V620

To display and modify target set point; in programming mode it selects a parameter

or confirm an operation. By holding it pressed for 3s when max or min temperature

is displayed it will be erased.

To see the max. stored temperature; in programming mode it browses the

parameter codes or increases the displayed value.

By holding it pressed for 3s the fast freezing cycle is started.

To see the min stored temperature; in programming mode it browses the parameter

codes or decreases the displayed value.

By holding it pressed for 3s the defrost is started.

Switch ON and OFF the cold room light.

Switch ON and OFF the instrument.

KEY COMBINATIONS

+

To lock and unlock the keyboard.

XW20K

1592026000

T620

CX620

1/5

Технические характеристики

Общие сведения
N-значный дисплей: ± 3 д.з. — Клавиатура: 6 кнопок
Ведомые устройства модуля
XW20K, XW40K, XW60K, XW70K
Зуммер
опционально
Соединения
винтовой клеммник < проводка 2,5 мм2 и фастонное соединение 6,3 мм
Источник питания
24, 110, 230 В перем.тока 110, 230 В перем.тока от контроллера (для моделей K)
Энергопотребление
макс. 10 ВА
Дисплей
3 цифры, красный светодиод, высота 14,2 мм
Хранение данных
в энергонезависимой памяти (EEPROM)
Рабочая температура
0÷60 °C
Температура хранения
-30÷85°C
Относительная влажность
20÷85% (без конденсации)
Диапазон измерения и регулирования
Датчик NTC: -40÷110°C, Датчик PTC: -50÷150°C
Шаг
0,1°C или 1°C
Погрешность (при температуре окружающей среды)
±0,7°C ±1 цифра
Источник питания
от контроллера

Особенности

  • Прямое подключение фазы и нейтрали нагрузки для снижения затрат на проводку
  • Прямое управление компрессорами вплоть до 1,2 л. с. (внутри реле 20 А)
  • Прямое электропитание. Не требуется внешний трансформатор
  • Удобный интерфейс благодаря использованию до 8 кнопок с прямым действием
  • Регистрация максимальной и минимальной температуры
  • Простой или плавающий контроль пониженной и повышенной влажности
  • Интеллектуальное оттаивание
  • Встроенные функции, позволяющие экономить энергию
  • Hot Key для быстрого и легкого программирования
  • Разъем для выносного дисплея
  • Последовательное подключение к системам мониторинга
  • Аналогичные товары

Вся информация на сайте о товарах и ценах носит справочный характер и не является публичной офертой. Производитель оставляет за собой право изменять характеристики товара, его внешний вид и комплектность без предварительного уведомления продавца

dixell V620 Installation And Operating Instructions Manual | Manualzz

3.4 CONTROL OF EVAPORATOR FANS
XW60K AND T620T - T620 – V620 – CX620
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
1
The fan control mode is selected by means of the FnC parameter:
FnC = C_n: fans will switch ON and OFF with the compressor and not run during defrost;
FnC = o_n fans will run even if the compressor is off, and not run during defrost;
After defrost, there is a timed fan delay allowing for drip time, set by means of the Fnd parameter.
FnC = C_Y fans will switch ON and OFF with the compressor and run during defrost;
FnC = o_Y fans will run continuously also during defrost.
GENERAL WARNING ............................................................................................................. 1
GENERAL DESCRIPTION ...................................................................................................... 1
CONTROLLING LOADS ......................................................................................................... 1
SPECIAL FUNCTIONS ........................................................................................................... 1
KEYBOARDS .......................................................................................................................... 1
AUTOMATIC KEYBOARD LOCK (ONLY FOR T620T) ........................................................... 2
CONTROLLER INTERFACE ................................................................................................... 2
PARAMETER LIST ................................................................................................................. 3
DIGITAL INPUT....................................................................................................................... 4
INSTALLATION AND MOUNTING .......................................................................................... 4
ELECTRICAL CONNECTIONS ............................................................................................... 5
TTL/RS485 SERIAL LINE ....................................................................................................... 5
HOW TO: USE OF THE PROGRAMMING “HOT KEY”........................................................... 5
ALARM SIGNALS ................................................................................................................... 5
TECHNICAL DATA ................................................................................................................. 5
CONNECTIONS ...................................................................................................................... 5
DEFAULT SETTING VALUES ................................................................................................ 5
An additional parameter FSt provides the setting of temperature, detected by the evaporator probe,
above which the fans are always OFF. This is used to make sure circulation of air only if his
temperature is lower than set in FSt.
3.4.1 Forced activation for fans
This function, managed by the FCt parameter, is designed to avoid short cycles of fans, that could
happen when the controller is switched on or after a defrost, when the room air warms the evaporator.
If the difference between the evaporator temperature and the room temperature is higher than the FCt
value, the controller will activate the fans. This function is disabled if FCt=0.
3.4.2 Timed activation of the fans when the compressor is off.
When FnC=C-n or C-Y (fans in parallel to the compressor), the fans will be able to carry out on and off
cycles even if the compressor is switched off. The on and off interval of time follow the Fon and FoF
parameters. When the compressor is stopped the fans will go on working for the Fon time. On the
other side, with Fon=0 the fans will stay always off when the compressor is off.
GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
4

By means of the parameter oA3, it’s possible to configure the functions of the light relay (22-23), as
described in the following paragraphs:



This manual is part of the product and should be kept near the instrument for easy and quick
reference.
The instrument shall not be used for purposes different from those described hereunder. It
cannot be used as a safety device.
Check the application limits before proceeding.
4.1 LIGHT RELAY (FACTORY SETTING, OA3 = LIG)
By setting oA3=Lig the relay will work as light relay, it is switched on and off by the light button on the
keyboard and is affected by status of the digital input when i1F=dor.
Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring the
same and unchanged functionality.
4.2 SECOND COMPRESSOR MANAGEMENT (OA3 = CP2)
1.2 Safety Precautions








2
By setting oA3=CP2, the relay at terminals 22-23 will operate as “second compressor”. It will be
activated in parallel with the relay of the first compressor, with a possible delay set in the AC1
parameter (seconds). Both the compressors are switched off at the same time.
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding
sudden temperature changes with high atmospheric humidity to prevent formation of
condensation
Warning: disconnect all electrical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.”
(see address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough from
each other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in
parallel with inductive loads could be useful.
4.3 ON –OFF RELAY (OA3 = ONF)
By setting oA3=onF, the relay will operate as “on-off” relay: it will be activated when the controller is
switched on and it will be switched off when the controller is in stand-by status.
4.4 AUXILIARY RELAY (OA3 = AUS)
By setting oA3=AUS, the relay 22-23 will work as auxiliary thermostat (ex. anti condensing heater).
Parameters involved:
ACH (cL, Ht): Kind of regulation for the auxiliary relay: Ht = heating / CL = cooling;
SAA (-50÷150) Set point for auxiliary relay
SHy (0÷25.5°C) Differential for auxiliary output.
With ACH = CL: aux relay cut in is SAA+SHy, cut out SAA.
With ACH = Ht: aux relay cut in is SAA-SHy, cut out SAA.
ArP (nP, P1, P2, P3, P4) Probe for auxiliary relay
Sdd (n, Y) Auxiliary output working during defrost
GENERAL DESCRIPTION
Model XW60K is microprocessor based controller suitable for applications on medium or low
temperature refrigerating units. It has to be connected by means of a two-wire cable ( 1mm) at a
distance of up to 10 meters to the keyboard T620T or T620 or V620 or CX620. It is provided with four
relay outputs to control compressor, defrost - which can be either electrical or hot gas - the evaporator
fans and light. It is also provided with 4 NTC or PTC probe inputs, one for temperature control, one to
control the defrost end temperature of the evaporator and the third and fourth to control condenser
temperature or to display another temperature.
The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a
network line ModBUS-RTU compatible such as the Dixell monitoring units of X-WEB family. It allows
to program the controller by means the HOT KEY programming keyboard.
The instrument is fully configurable through special parameters that can be easily programmed
through the keyboard.
3
SPECIAL FUNCTIONS
4.5 ALARM RELAY (OA3 = ALR)
By setting oA3=ALr the relay will work as alarm relay, it is switched on when an alarm happens.
Parameters involved:
tbA (n, y) Alarm relay silencing
AoP (cL; oP) Alarm relay polarity
4.6 NEUTRAL ZONE (OA3 = DB)
By setting oA3=db the controller will perform a
“neutral zone” regulation.
The heating element has to be connected to the
oA3 relay (22-23)
If the temperature increases and reaches set
point plus differential (HY) the compressor is
started and then turned off when the
temperature reaches the set point value again.
If the temperature decreases and reaches the
set point minus differential (HY) the oA3 output
(heater) is switched on and then turned OFF
when the temperature reaches again the set
point.
CONTROLLING LOADS
3.1 THE COMPRESSOR
The regulation is performed according to the temperature measured by the thermostat probe with a
positive differential from the set point: if the temperature increases and reaches set point plus
differential the compressor is started and then turned off when the temperature reaches the set point
value again.
In case of fault in the thermostat probe the start and stop of the compressor are timed through
parameters Con and CoF.
The relay of the second compressor is activated in parallel with the relay of the first compressor, with a
possible delay set in the AC1 parameter. Both the compressors are switched off at the same time.
3.2 FAST FREEZING
When defrost is not in progress, it can be activated by holding the UP key pressed for about 3 sec.
The compressor operates to maintain the CCS set point for the time set through the CCt parameter.
The cycle can be terminated before the end of the set time using the same activation key UP for 3 sec.
5
3.3 DEFROST
1592026020 XW60K GB r2.3 08.04.2015
KEYBOARDS
T620T
Two defrost modes are available through the tdF parameter: defrost through electrical heater (tdF =
EL) and hot gas defrost (tdF = in).
The defrost interval depends on the presence of the RTC (optional). If the RTC is present is controlled
by means of parameter EdF:
EdF=in: a defrost starts after elapsing the idF time (standard way for controller without RTC).
EdF=rtC: defrosts are scheduled by using a real time clock system, depending on the hours set in the
parameters Ld1..Ld6, during workdays, and in Sd1…Sd6 during holidays.
Other parameters are used to control defrost cycles: its maximum length (MdF) and two defrost
modes: timed or controlled by the evaporator’s probe (P2P).
At the end of defrost dripping time is started, its length is set in the Fdt parameter. With Fdt=0 the
dripping time is disabled.
XW60K
1/6
7
T620
CONTROLLER INTERFACE
SET THE CURRENT TIME AND DAY (ONLY WITH RTC)
V620
When the instrument is switched on, it’s necessary to program the time and day.
1.
Enter the Pr1 programming menu, by pushing the SET+ DOWN keys for 3 sec.
2.
The rtC parameter is displayed. Push the SET key to enter the real time clock menu.
3.
The Hur (hour) parameter is displayed.
4.
Push the SET and set current hour by the UP and DOWN keys, then push SET to
confirm the value.
5.
Repeat the same operations with Min (minutes), dAy (day), dYM (day of month), Mon
(month) and YAr (year) parameters.
To exit: Push both SET+UP keys or wait for 15 sec without pushing any keys.
CX620
7.1 HOW TO SEE THE MIN TEMPERATURE
1.
2.
3.
Press and release the DOWN key.
The “Lo” message will be displayed followed by the minimum temperature recorded.
By pressing the DOWN key or waiting for 5 sec the normal display will be restored.
7.2 HOW TO SEE THE MAX TEMPERATURE
To display and modify target set point; in programming mode it selects a parameter
or confirm an operation. By holding it pressed for 3 sec when max or min
temperature is displayed it will be erased.
1.
2.
3.
Press and release the UP key.
The “Hi” message will be displayed followed by the maximum temperature recorded.
By pressing the UP key or waiting for 5 sec the normal display will be restored.
(UP) To see the max stored temperature; in programming mode it browses the
parameter codes or increases the displayed value.
By holding it pressed for 3s the fast freezing cycle is started.
7.3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
(DOWN) To see the min stored temperature; in programming mode it browses the
parameter codes or decreases the displayed value.
Note: after the installation remember to RESET the temperature stored.
(DEF) By holding it pressed for 3 sec the defrost is started.
1.
2.
3.
To reset the stored temperature, when max or min temperature is displayed:
1. Press SET key until “rST” label starts blinking.
7.4 HOW TO SEE AND MODIFY THE SET POINT
Push and immediately release the SET key: the display will show the Set point value;
To change the SEt value, push the UP or DOWN arrows within 10 sec.
To memorise the new set point value push the SET key again or wait for 10 sec.
7.5 TO START A MANUAL DEFROST
(LIG) Switch ON and OFF the cold room light.
1.
7.6 TO ENTER IN PARAMETERS LIST “PR1”
(ONOFF) Switch ON and OFF the instrument.
To enter the parameter list “Pr1” (user accessible parameters) operate as follows:
1.
Enter the Programming mode by pressing the Set and DOWN key
for few seconds (
and
start blinking).
2.
The instrument will show the first parameter present in “Pr1”
+
KEY COMBINATIONS
+
To lock and unlock the keyboard.
7.7 THE HIDDEN MENU
In the hidden menu there are all the parameters of the instrument.
+
To enter the programming mode.
+
To exit the programming mode.
7.7.1 ENTERING THE HIDDEN MENU
1. Enter the Programming mode by pressing the SET+DOWN keys for 3 sec (the “°C” or “°F” LED will
start blinking).
2. Release the keys and then push again the SET+DOWN keys more than 7 sec. The “Pr2” label will
be displayed immediately, followed from the HY parameter.
NOW THE HIDDEN MENU IS DISPLAYED
5.1 USE OF LEDS
3.
4.
5.
6.
Each LED function is described in the following table.
LED
MODE
ON
FLASHING
ON
FLASHING
ON
FLASHING
ON
6
Function
The compressor is running
- Programming Phase (flashing with LED
- Anti-short cycle delay enabled
The fan is running
Programming Phase (flashing with LED
The defrost is enabled
Drip time in progress
)
NOTE1: if no parameter is present in the “Pr1” level, after the first 3 sec the “noP” message will be
displayed. Keep SET+DOWN keys pushed till the “Pr2” message will be displayed.
NOTE2: the new set value will be stored even if the procedure is exited by waiting for the time-out to
expire.
The Fast Freezing cycle is enabled
ON
ON
Energy saving enabled
ON
Light on
ON
ON
Auxiliary relay on (CX620 only)
Measurement unit (CX620 only)
7.7.2 HOW TO: MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND
VICEVERSA.
Each parameter present in the HIDDEN MENU can be moved or put into “THE FIRST LEVEL” (user
level) by pressing SET+DOWN keys. In HIDDEN MENU, if a parameter is present also in the First
Level (Pr1), the decimal point will be lit.
7.7.3 HOW TO CHANGE THE PARAMETER VALUE
1. Enter the Programming mode.
2. Select the required parameter with UP or DOWN.
3. Press the “SET” key to display its value (
and
LED starts blinking).
4. Use UP or DOWN to change its value.
5. Press SET to store the new value and move to the following parameter.
To exit: Press SET+UP or wait for 15 sec without pressing any key.
NOTE: the new programming is stored even when the procedure is exited by waiting the time-out.
AUTOMATIC KEYBOARD LOCK (ONLY FOR T620T)
To avoid accidental modifications of the controller settings, the T620T keyboard will be locked
automatically if no key will be touched for 60 seconds. The T620T will show “LoC” flashing for few
seconds when it’s locking. The light key is operating even if the keyboard is locked.
6.1 TO UNLOCK THE T620T
1.
2.
3.
Select the required parameter.
Press SET key to display its actual value
Use UP or DOWN keys to change its value.
Press SET to store the new value and move to the following parameter.
To exit: Press SET+UP or wait for 15 sec without pressing any key.
)
- ALARM signal
- In “Pr2” indicates that the parameter is also present in “Pr1”
Continuous cycle is running
ON
°C/°F
Push the DEF key for more than 2 sec and a manual defrost will start.
Touch any key.
The keys will be lighted.
Keep a key pushed for few seconds till the “on” message is displayed.
1592026020 XW60K GB r2.3 08.04.2015
XW60K
2/6
DEFROST
7.8 HOW TO LOCK THE KEYBOARD (MANUALLY)
1.
2.
+
EdF
Keep the UP and DOWN keys pressed together for more than 3 sec the UP and
DOWN keys.
The “PoF” message will be displayed and the keyboard is locked. At this point it is
only possible the viewing of the set point or the MAX o Min temperature stored and
to switch ON and OFF the light, the auxiliary output and the instrument.
tdF
dFP
TO UNLOCK THE KEYBOARD
Keep the UP and DOWN keys pressed together for more than 3 sec.
dtE
7.9 ON/OFF FUNCTION (STAND BY)
idF
By pushing the ON/OFF key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED
is switched ON.
During the OFF status, all the relays are switched OFF and the regulations are stopped; if
a monitoring system is connected, it does not record the instrument data and alarms.
When the instrument is in stand by the keyboard displays “oFF”.
MdF
dSd
N.B. During the OFF status the Light and AUX buttons are active.
dFd
7.10 TO SEE THE PROBE VALUES
1.
2.
8
dAd
Enter in “Pr1” level.
Parameters “dP1”, “dP2”, “dP3” and “dP4” display the value of probes 1, 2, 3 and 4.
Fdt
PARAMETER LIST
rtC
dPo
dAF
Real time clock menu (only for controller with RTC): to set the time, date and defrost
start time.
REGULATION
HY
LS
US
ot
P2P
oE
P3P
o3
P4P
o4
odS
AC
rtr
CCt
CCS
Con
CoF
FANS
Differential: (0.1 to 25.5°C; 1 to 45°F) intervention differential for set point. Compressor
Cut IN is Set Point + differential (HY). Compressor Cut OUT is when the temperature
reaches the set point.
Minimum set point: (-55°C to SET; -67°F to SET) sets the minimum value for the set
point.
Maximum set point: (SET to 150°C; SET to 302°F) set the maximum value for set point.
Thermostat probe calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible
offset of the thermostat probe.
Evaporator probe presence: (n; Y) n = not present, the defrost stops by time;
Y = present, the defrost stops by temperature.
Evaporator probe calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible
offset of the evaporator probe.
Third probe presence (P3): (n; Y) n = not present, the terminals 18-20 operate as digital
input; Y = present, the terminals 18-20 operate as third probe.
Third probe calibration (P3): (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible
offset of the third probe.
Fourth probe presence: (n; Y) n = Not present; Y = present.
NOTE: only for XW60LT models.
Fourth probe calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible offset
of the fourth probe.
NOTE: only for XW60LT models.
Outputs activation delay at start up: (0 to 255min) this function is enabled at the initial
start up of the instrument and inhibits any output activation for the period of time set in the
parameter.
Anti-short cycle delay: (0 to 50min) minimum interval between the compressor stop and
the following restart.
Percentage of the second and first probe for regulation: (0 to 100; 100=P1, 0=P2) it
allows to set the regulation according to the percentage of the first and second probe, as
for the following formula (rtr(P1-P2)/100 + P2).
Compressor ON time during continuous cycle: (0.0 to 24h00min, res. 10min) allows to
set the length of the continuous cycle. Compressor stays on without interruption during
CCt time. This is useful, for instance, when the room is filled with new products.
Set point for continuous cycle: (-55 to 150°C; -67 to 302°F) it sets the set point used
during the continuous cycle.
Compressor ON time with faulty probe: (0 to 255min) time during which the
compressor is active in case of faulty thermostat probe. With Con=0 compressor is
always OFF.
Compressor OFF time with faulty probe: (0 to 255min) time during which the
compressor is OFF in case of faulty thermostat probe. With CoF=0 compressor is always
active.
FnC
Fnd
FCt
FSt
Fon
FoF
FAP
rES
Lod
rEd
dLY
dtr
ACH
SAA
SHY
ArP
Sdd
Kind of regulation for auxiliary relay: (Ht; CL) Ht = heating; CL = cooling.
Set Point for auxiliary relay: (-55.0 to 150.0°C; -67 to 302°F) it defines the room
temperature set point to switch auxiliary relay.
Differential for auxiliary output: (0.1 to 25.5°C; 1 to 45°F) intervention differential for
auxiliary output set point.

ACH=CL, AUX Cut in is [SAA+SHY]; AUX Cut out is SAA.

ACH=Ht, AUX Cut in is [SAA–SHY]; AUX Cut out is SAA.
Probe selection for auxiliary: (nP; P1; P2; P3; P4) nP = no probe, the auxiliary relay is
switched only by the digital input; P1 = Probe 1 (Thermostat probe); P2 = Probe 2
(evaporator probe); P3 = Probe 3 (display probe); P4 = Probe 4.
Auxiliary relay off during defrost: (n; Y) n = the auxiliary relay operates during defrost.
Y = the auxiliary relay is switched off during defrost.
ALARMS
ALP
ALC
Temperature measurement unit: (°C; °F) °C = Celsius; °F = Fahrenheit.
WARNING: When the measurement unit is changed the SET point and the values of
the parameters HY, LS, US, ot, ALU and ALL have to be checked and modified (if
necessary).
Resolution (for °C): (in=1°C; dE=0.1°C) allows decimal point display.
Instrument display: (P1; P2, P3, P4, SET, dtr) it selects which probe is displayed by
the instrument. P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe (only
for model with this option enabled); P4 = Fourth probe, SET = set point; dtr =
percentage of visualization.
X-REP display (optional): (P1; P2, P3, P4, SET, dtr) it selects which probe is
displayed by X- REP. P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe
(only for model with this option enabled); P4 = Fourth probe, SET = set point;
dtr = percentage of visualization.
Display delay: (0 to 20min00s; res. 10s) when the temperature increases, the display
is updated of 1°C or 1°F after this time.
Percentage of the second and first probe for visualization when Lod=dtr: (0 to 99;
100=P1, 0=P2) if Lod=dtr it allows to set the visualization according to the percentage
of the first and second probe, as for the following formula (dtr(P1-P2)/100 + P2).
1592026020 XW60K GB r2.3 08.04.2015
Fans operating mode: (C-n; o-n; C-Y; o-Y) C-n = runs with the compressor, OFF during
defrost; o-n = continuous mode, OFF during defrost; C-Y = runs with the compressor, ON
during defrost; o-Y = continuous mode, ON during defrost.
Fans delay after defrost: (0 to 255min) interval between end of defrost and evaporator
fans start.
Temperature differential to avoid fan short cycles: (0 to 59°C; 0 to 90°F) (N.B.: FCt=0
means function disabled) if the difference of temperature between the evaporator and the
room probes is higher than FCt value, the fans will be switched on.
Fans stop temperature: (-55 to 50°C; -67 to 122°F) setting of temperature, detected by
evaporator probe, above which fans are always OFF.
Fan ON time: (0 to 15min) with Fnc=C_n or C_Y, (fan activated in parallel with
compressor) it sets the evaporator fan ON cycling time when the compressor is off. With
Fon=0 and FoF≠0 the fan are always off, with Fon=0 and FoF=0 the fan are always off.
Fan OFF time: (0 to 15min)
With FnC=C_n or C_Y, (fan activated in parallel with compressor) it sets the evaporator
fan off cycling time when the compressor is off.
With Fon=0 and FoF≠0 the fan are always off, with Fon=0 and FoF=0 the fan are always
off.
Probe selection for fan management: (nP; P1; P2; P3; P4) nP = no probe;
P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on Hot
Key plug.
OA3 = AUS: AUXILIARY THERMOSTAT CONFIGURATION (terms. 22-23)
DISPLAY
CF
Defrost mode (only for controller with RTC):
- rtC: Real Time Clock mode. Defrost time follows Ld1 to Ld6 parameters on
workdays and Sd1 to Sd6 on holidays.
- in: interval mode. The defrost starts when the time idf is expired.
Defrost type: (EL; in) EL = electrical heater; in = hot gas.
Probe selection for defrost termination: (nP; P1; P2; P3; P4) nP = no probe;
P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on
Hot Key plug.
Defrost termination temperature: (-55 to 50°C; -67 to 122°F) (enabled only when
EdF=Pb) sets the temperature measured by the evaporator probe, which causes the
end of defrost.
Interval between defrost cycles: (0 to 120hours) determines the interval of time
between two defrost cycles.
(Maximum) length for defrost: (0 to 255min) when P2P=n, (not evaporator probe:
timed defrost) it sets the defrost duration. When P2P=Y (defrost end based on
temperature) it sets the maximum length for defrost.
Start defrost delay: (0 to 99min) this is useful when different defrost start times are
necessary to avoid overloading the plant.
Temperature displayed during defrost: (rt; it; SEt; dEF) rt = real temperature;
it = temperature at defrost start; SEt = set point; dEF = “dEF” label.
MAX display delay after defrost: (0 to 255min) sets the maximum time between the
end of defrost and the restarting of the real room temperature display.
Drip time: (0 to 120min) time interval between reaching defrost termination temperature
and the restoring of the control’s normal operation. This time allows the evaporator to
eliminate water drops that might have formed due to defrost.
First defrost after start-up: (n; Y) n = after the idF time, Y = immediately.
Defrost delay after continuous cycle: (0.0 to 24h00min, res. 10min) time interval
between the end of the fast freezing cycle and the following defrost related to it.
ALU
ALL
AFH
ALd
dAo
XW60K
Probe selection for alarm: (nP; P1; P2; P3; P4) nP = no probe, the temperature alarms
are disabled; P1 = Probe 1 (Thermostat probe); P2 = Probe 2 (evaporator probe);
P3 = Probe 3 (display probe); P4 = Fourth probe.
Temperature alarms configuration: (Ab; rE) Ab = absolute temperature, alarm
temperature is given by the ALL or ALU values. rE = temperature alarms are referred to
the set point. Temperature alarm is enabled when the temperature exceeds the
[SET+ALU] or [SET-ALL] values.
MAXIMUM temperature alarm:

If ALC=Ab: [ALL to 150.0°C or ALL to 302°F]

If ALC=rE: [0.0 to 50.0°C or 0 to 90°F]
when this temperature is reached the alarm is enabled, after the ALd delay time.
Minimum temperature alarm:

If ALC=Ab: [-55°C to ALU; -67 to ALU]

If ALC=rE: [0.0 to 50.0°C or 0 to 90°F]
when this temperature is reached the alarm is enabled, after the ALd delay time.
Differential for temperature alarm recovery: (0.1 to 25.5°C; 1 to 45°F) intervention
differential for recovery of temperature alarm.
Temperature alarm delay: (0 to 255 min) time interval between the detection of an alarm
condition and alarm signalling.
Exclusion of temperature alarm at start-up: (0.0 to 24h00min, res. 10min) time interval
between the detection of the temperature alarm condition after instrument power on and
alarm signalling.
3/6
PbC
CONDENSER TEMPERATURE ALARM
AP2
AL2
Au2
AH2
Ad2
dA2
bLL
AC2
Probe selection for temperature alarm of condenser: (nP; P1; P2; P3; P4)
nP = no probe; P1 = thermostat probe; P2 = evaporator probe; P3 = configurable probe;
P4 = Probe on Hot Key plug.
Low temperature alarm of condenser: (-55 to 150°C; -67 to 302°F) when this
temperature is reached the LA2 alarm is signalled, possibly after the Ad2 delay.
High temperature alarm of condenser: (-55 to 150°C; -67 to 302°F) when this
temperature is reached the HA2 alarm is signalled, possibly after the Ad2 delay.
Differential for temperature condenser alarm recovery: 0.1 to 25.5°C; 1 to 45°F.
Condenser temperature alarm delay: (0 to 255 min) time interval between the detection
of the condenser alarm condition and alarm signalling.
Condenser temperature alarm exclusion at start up: 0.0 to 24h00min, res. 10min.
Compressor off with low temperature alarm of condenser: (n; Y) n = compressor
keeps on working; Y = compressor is switched off till the alarm is present, in any case
regulation restarts after AC time at minimum.
Compressor off with high temperature alarm of condenser: (n; Y) n = compressor
keeps on working; Y = compressor is switched off till the alarm is present, in any case
regulation restarts after AC time at minimum.
onF
dP1
dP2
dP3
dP4
rSE
rEL
Ptb
9
oA3
AoP
9.1 DOOR SWITCH INPUT (I1F = DOR)
It signals the door status and the corresponding relay output status through the odC parameter: no =
normal (any change); Fan = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF.
Since the door is opened, after the delay time set through parameter did, the door alarm is enabled,
the display shows the message “dA” and the regulation restarts is rtr = yES. The alarm stops as
soon as the external digital input is disabled again. With the door open, the high and low temperature
alarms are disabled.
Alarm relay silencing (with oAx =ALr): (n; Y) n = silencing disabled: alarm relay stays
on till alarm condition lasts. Y = silencing enabled: alarm relay is switched OFF by
pressing a key during an alarm.
Third relay configuration (X60LT: terminals 1-3, XW60LRT: terminals 5-6): (dEF;
FAn; ALr; LiG; AUS; onF; db; dEF2; HES) dEF = defrost; FAn = do not select it; ALr =
alarm; LiG = light; AUS = Auxiliary relay; onF = always on with instrument on; db =
neutral zone; dEF2 = do not select it; HES = night blind.
Alarm relay polarity: (CL; oP) it set if the alarm relay is open or closed when an alarm
occurs. CL = terminals closed during an alarm; oP = terminals open during an alarm.
9.2 GENERIC ALARM (I1F = EAL)
As soon as the digital input is activated the unit will wait for did time delay before signalling the “EAL”
alarm message. The outputs status doesn’t change. The alarm stops just after the digital input is deactivated.
9.3 SERIOUS ALARM MODE (I1F = BAL)
DIGITAL INPUT
i1P
i1F
did
nPS
odC
rrd
LES
HES
When the digital input is activated, the unit will wait for did delay before signalling the “CA” alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is deactivated.
First digital input polarity: (oP; CL) oP = the digital input is activated by opening the
contact; CL = the digital input is activated by closing the contact.
First digital input configuration: (EAL; bAL; PAL; dor; dEF; ES; AUS; Htr; FAn; HdF;
onF; Sbt) EAL = external alarm: “EA” message is displayed; bAL = serious alarm “CA”
message is displayed; PAL = pressure switch alarm, “CA” message is displayed; dor =
door switch function; dEF = activation of a defrost cycle; ES = energy saving; AUS =
auxiliary relay activation with oA2=AUS; Htr = type of inverting action (cooling or heating);
FAn = fan; HdF = Holiday defrost (enable only with RTC); onF = to switch the controller
off; Sbt = to activate Sabbath mode.
Digital input 1 alarm delay: (0 to 255 min) delay between the detection of the external
alarm condition and its signalling.
When i1F= PAL, it is the interval of time to calculate the number of pressure switch
activation.
Number of pressure switch activation: (0 to 15) Number of activation, during the did or
d2d interval, before signalling an alarm event (i1F, i2F=PAL).
If the nPS activation during did or d2d time is reached, switch off and on the instrument to
restart normal regulation.
Compressor status when open door: (no; FAn; CPr;F_C;) no = normal;
FAn = normal; CPr = compressor OFF, F_C = compressor OFF.
Outputs restart after door open alarm: (n; Y) n = outputs follow the odC parameter.
Y = outputs restart with a door open alarm.
Light off during Energy Saving status: n; Y.
Delta temperature during an Energy Saving cycle: (-30.0 to 30.0°C; -54 to 54°F) it
sets the increasing value of the set point [SET+HES] during the Energy Saving cycle.
9.4 PRESSURE SWITCH (I1F = PAL)
If during the interval time set by did parameter, the pressure switch has reached the number of
activation of the nPS parameter, the “CA” pressure alarm message will be displayed. The compressor
and the regulation are stopped. When the digital input is ON the compressor is always OFF. If the
nPS activation in the did time is reached, switch off and on the instrument to restart normal
regulation.
9.5 AUXILIARY OUTPUT SWITCHING (I1F =AUS)
With oA3=AUS and i1F=AUX it switches the fourth relay (22-23).
9.6 START DEFROST (I1F = DFR)
It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will
restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is
expired.
9.7 KIND OF ACTION: HEATING OR COOLING (I1F = HTR)
This function allows to invert the regulation of the controller: from cooling to heating and viceversa.
9.8 ENERGY SAVING (I1F = ES)
The Energy Saving function allows to change the set point value as the result of the SET+HES
(parameter) sum. This function is enabled until the digital input is activated.
CURRENT TIME AND WEEKLY HOLIDAYS (ONLY FOR MODELS WITH RTC)
9.9 DIGITAL INPUTS POLARITY
Hur
Min
dAY
dYM
Mon
YAr
Hd1
Current hour: 0 to 23h.
Current minute: 0 to 59min.
Current day: Sun to SAt.
Day of the month: 1 to 31.
Month: 1 to 12.
Year: 00 to 99.
First weekly holiday: (Sun to nu) set the first day of the week which follows the holiday
times.
Hd2
Second weekly holiday: (Sun to nu) set the second day of the week which follows the
holiday times.
N.B.: Hd1, Hd2 can be set also as “nu” value (Not Used).
The digital input polarity depends on the i1P parameter:
i1P=CL: the input is activated by closing the contact.
i1P=OP: the input is activated by opening the contact
10 INSTALLATION AND MOUNTING
T620 keyboard shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two screws
 3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L).
V620 keyboard shall be mounted on vertical panel, in a 72x56 mm hole, and fixed using two screws 
3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-V).
CX620 keyboard shall be mounted on vertical panel, in a 29x71 mm hole, and fixed using the special
bracket supplied.
The controller XW60K shall be mounted in a din rail
It must be connected to the keyboard by means of a two-wire cable ( 1mm). The temperature range
allowed for correct operation is 0 to 60°C. Avoid places subject to strong vibrations, corrosive gases,
excessive dirt or humidity. The same recommendations apply to probes. Let the air circulate by the
cooling holes.
ENERGY SAVING TIMES (ONLY FOR MODELS WITH RTC)
ILE
dLE
ISE
dSE
DIGITAL INPUT
The free voltage digital input is programmable in different configurations by the i1F parameter.
RELAY OA3 (22-23) CONFIGURATION
tbA
Type of probe: (PtC; ntC) it allows to set the kind of probe used by the instrument:
PtC = PTC probe;
ntC = NTC probe.
On/Off key enabling: (nU; oFF; ES) nU = disabled; oFF = enabled; ES = not set it.
Thermostat probe display.
Evaporator probe display.
Third probe display.
Fourth probe display (only for XW60LT models).
Real set point: it shows the set point used during the energy saving cycle or during the
continuous cycle.
Software release for internal use.
Parameter table code: readable only.
Energy Saving cycle start during workdays: (0 to 23h50min) during the Energy Saving
cycle the set point is increased by the value in HES so that the operation set point is
SET+HES.
Energy Saving cycle length during workdays: (0 to 24h00min) sets the duration of the
Energy Saving cycle on workdays.
Energy Saving cycle start on holidays: 0 to 23h50min.
Energy Saving cycle length on holidays: 0 to 24h00min.
TO SET DEFROST TIMES (ONLY FOR MODELS WITH RTC)
Ld1...Ld6
Sd1...Sd6
Workday defrost start: (0 to 23h50min) these parameters set the beginning of the
6 programmable defrost cycles during workdays. Ex: when Ld2=12.4 the second
defrost starts at 12.40 during workdays.
Holiday defrost start: (0 to 23h50min) these parameters set the beginning of the 6
programmable defrost cycles on holidays. Ex: when Sd2=3.4 the second defrost
starts at 3.40 on holidays.
N.B.: to disable a defrost cycle set it to “nu” (not used).
OTHER
Adr
Serial address: (1 to 247) identifies the instrument address when connected to a
ModBUS compatible monitoring system.
1592026020 XW60K GB r2.3 08.04.2015
XW60K
4/6
10.1 XW60K – 8 DIN CASE - DIMENSIONS
14.1 SILENCING BUZZER
Once the alarm signal is detected the buzzer can be silenced by pressing any key. Buzzer is mounted
in the keyboard and it is an option.
14.2 “EE” ALARM
The Dixell instruments are provided with an internal check for the data integrity. The “EE” alarm
flashes when a failure in the memory data occurs. In such cases the alarm output is enabled.
14.3 ALARM RECOVERY
Probe alarms: “P1” (probe1 faulty), “P2”, “P3” and “P4”; they automatically stop 10 sec after the probe
restarts normal operation. Check connections before replacing the probe.
Temperature alarms “HA”, “LA” “HA2” and “LA2” automatically stop as soon as the temperature
returns to normal values.
Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled.
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument.
15 Technical data
Keyboards
Housing: self extinguishing ABS
Case: T620 and T620T: facia 38x185 mm; depth 23mm
V620: facia 72x56 mm; depth 23mm
CX620: facia 75x36 mm; depth 23mm
Mounting: T620T panel mounting in a 150x31 mm panel cut-out with the 2 metal brackets supplied.
T620: panel mounting in a 150x31 mm panel cut-out with two screws.  3 x 2mm. Distance
between the holes 165mm
V620: panel mounting in a 56x72 mm panel cut-out with two screws.  3x2mm. Distance
between the holes 40mm
CX620: panel mounting in a 71x29mm panel cut-out
Protection: IP20; Frontal protection: IP65 with frontal gasket
Connections: Screw terminal block  2.5 mm2
Power supply: from XW60K power module
Display: 3 digits, red LED, 14.2 mm high
Optional output: buzzer.
11 ELECTRICAL CONNECTIONS
XW60K is provided with screw terminal blocks to connect cables with a cross section up to 2.5 mm2 for
the RS485 (optional) and the keyboard. To connect the other inputs, power supply and relays, XW60K
is provided with Faston connections (6.3mm). Heat-resistant cables have to be used. Before
connecting cables make sure the power supply complies with the instrument’s requirements. Separate
the probe cables from the power supply cables, from the outputs and the power connections. Do not
exceed the maximum current allowed on each relay, in case of heavier loads use a suitable external
relay.
NOTE: the maximum current allowed for all the loads is 20A.
11.1 PROBE CONNECTIONS
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
infiltration. It is recommended to place the thermostat probe away from air streams to correctly
measure the average room temperature. Place the defrost termination probe among the evaporator
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during
defrost, to prevent premature defrost termination.
Power module XW60K
Case: 8 DN: 140X176X148
Connections: Screw terminal block  2.5 mm2 heat-resistant wiring and 6.3mm Faston
Power supply: 230Vac or. 110Vac  10% or 24Vac
Power absorption: 10VA max
Inputs: 4 NTC or PTC probes
Digital inputs: 1 free voltage
Relay outputs: Total current on loads MAX. 20A
Compressor: relay SPST 20(8) A, 250Vac; EN60730: 100K cycles
Fan: relay SPST 8(3) A, 250Vac
Defrost: relay SPST 16(5) A, 250Vac
Light (oA3): relay SPST 16(5) A, 250Vac
Serial output: TTL standard
Communication protocol: Modbus - RTU
Data storing: on the non-volatile memory (EEPROM)
Kind of action: 1B
Pollution degree: normal
Software class: A
Operating temperature: 0 to 60°C (32 to 140°F)
Storage temperature: -25 to 60°C (-13 to 140°F)
Relative humidity: 20 to 85% (no condensing)
Measuring and regulation range:
NTC probe: -40 to 110°C (-58 to 230°F)
PTC probe: -50 to 150°C (-58 to 302°F)
Resolution: 0.1°C or 1°C or 1°F (selectable)
Accuracy (ambient temp. 25°C): ±0.5°C ±1 digit
12 TTL/RS485 SERIAL LINE
The TTL connector allows, by means of the external module TTL/RS485 (XJ485CX), to connect the
unit to a network line ModBUS-RTU compatible as the Dixell monitoring system. The same TTL
connector is used to upload and download the parameter list of the “HOT-KEY”.
13 HOW TO: USE OF THE PROGRAMMING “HOT KEY”
13.1 PROGRAM A HOT-KEY FROM AN INSTRUMENT (UPLOAD)
1.
2.
3.
4.
Program one controller with the front keypad.
When the controller is ON, insert the “HOT-KEY” and push UP button; the “uPL” message
appears followed a by a flashing “End” label.
Push SET button and the “End” will stop flashing.
Turn OFF the instrument, remove the “HOT-KEY” and then turn it ON again.
NOTE: the “Err” message appears in case of a failed programming operation. In this case push again
button if you want to restart the upload again or remove the “HOT-KEY” to abort the operation.
13.2 PROGRAM AN INSTRUMENT BY USING A HOT-KEY (DOWNLOAD)
1.
2.
3.
4.
5.
Turn OFF the instrument.
Insert a pre-programmed “HOT-KEY” into the 5-PIN receptacle and then turn the Controller
ON.
The parameter list of the “HOT-KEY” will be automatically downloaded into the Controller
memory. The “doL” message will blink followed a by a flashing “End” label.
After 10 seconds the instrument will restart working with the new parameters.
Remove the “HOT-KEY”.
16 CONNECTIONS
16.1 XW60K
NOTE: the message “Err” is displayed for failed programming. In this case turn the unit off and then on
if you want to restart the download again or remove the “HOT-KEY” to abort the operation.
14 ALARM SIGNALS
Message Cause
P1
Thermostat probe failure
P2
P3
P4
HA
LA
HA2
LA2
dA
EA
CA
CA
EE
Outputs
Alarm output ON; Compressor output according to
parameters Con and CoF.
Evaporator probe failure
Alarm output ON; Other outputs unchanged
Probe 3 probe failure
Alarm output ON; Other outputs unchanged
Probe 4 probe failure
Alarm output ON; Other outputs unchanged
Maximum temperature alarm
Alarm output ON; Other outputs unchanged
Minimum temperature alarm
Alarm output ON; Other outputs unchanged
Condenser high temperature
It depends on the AC2 parameter
Condenser low temperature
It depends on the bLL parameter
Door open
Compressor and fans restarts
External alarm
Output unchanged.
Serious external alarm (i1F=bAL) All outputs OFF.
Pressure switch alarm (i1F=PAL) All outputs OFF
Data or memory failure
Alarm output ON; Other outputs unchanged
17 Default setting values
Label
Range
Default Level
REGULATION
SEt Set point
rtC* Real time clock menu
Hy Differential
The alarm message is displayed until the alarm condition is recovery.
All the alarm messages are showed alternating with the room temperature except for the “P1” which is
flashing.
To reset the “EE” alarm and restart the normal functioning press any key, the “rSt” message is
displayed for about 3 sec.
LS Minimum set point
US Maximum set point
ot
1592026020 XW60K GB r2.3 08.04.2015
Name
XW60K
Thermostat probe calibration
LS; US
[0.1 to 25.5°C]
[1 to 45°F]
[-55.0°C to SET]
[-67°F to SET]
[SET to 150°C]
[SET to 302°F]
[-12 to 12°C]
[-21 to 21°F]
-5.0
-
--Pr1
2.0
Pr1
-50.0
Pr2
110
Pr2
0.0
Pr1
5/6
Label
Name
P2P Evaporator probe presence
oE Evaporator probe calibration
Range
n=not present; Y=pres.
[-12 to 12°C]
[-21 to 21°F]
Default Level
Y
Pr1
0.0
Pr2
n=not present; Y=pres.
n
Pr2
Label
AC2
P3P
Third probe presence (1st cond.
probe)
o3
Third probe calibration
[-12 to 12°C]
[-21 to 21°F]
0
Pr2
Fourth probe presence (2nd
P4P
cond. probe)
n=not present; Y=pres.
n
Pr2
[-12 to 12°C]
[-21 to 21°F]
0
Pr2
0 to 255 min
0
Pr2
0 to 30 min
0 to 255 sec
0 to 100 (100=P1 , 0=P2)
1
5
100
Pr1
Pr2
Pr2
0.0 to 23h50min, res. 10 min
0.0
Pr2
[-55.0 to 150.0°C]
[-67 to 302°F]
-5
Pr2
0 to 255 min
15
Pr2
0 to 255 min
30
Pr2
°C
dE
P1
0
50
Pr2
Pr1
Pr2
Pr2
Pr2
EL
Pr1
Hur*
Min*
dAY*
dYM*
Mon
YAr
Hd1*
Hd2*
P2
Pr2
ILE*
8.0
Pr1
dLE*
6
30
0
it
30
0
n
0.0
Pr1
Pr1
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
o-n
10
Pr1
Pr1
10
Pr2
2
Pr1
0
0
Pr2
Pr2
P2
Pr2
o4
Fourth probe calibration
Outputs activation delay at start
up
AC Anti-short cycle delay
Ac1 Second compressor delay
rtr P1-P2 percentage for regulation
Compressor ON time during fast
CCt
freezing
odS
CCS Set point for continuous cycle
Compressor ON time with faulty
probe
Compressor OFF time with faulty
CoF
probe
Con
tbA
oA3
AoP
i1P
i1F
did
nPS
odC
rrd
LES
HES
DISPLAY
CF
rES
rEd
dLy
dtr
Temperature measurement unit
Resolution (integer/decimal point)
Remote display
Display temperature delay
P1-P2 percentage for disply
tdF Defrost type
Probe selection for defrost
termination
dFP
dtE Defrost termination temperature
idF
MdF
dSd
dFd
dAd
Fdt
dPo
dAF
Interval between defrost cycles
(Maximum) length for 1° defrost
Start defrost delay
Displaying during defrost
MAX display delay after defrost
Draining time
First defrost after start up
Defrost delay after fast freezing
FnC Fans operating mode
Fnd Fans delay after defrost
Differential of temperature for
FCt
forced activation of fans
FSt Fans stop temperature
°C; °F
in; dE
P1; dtr
0.0 to 20min00sec, res. 10 sec
1; 100
DEFROST
EL; in
nP; P1; P2; P3; P4
[-50.0 to 150°C]
[-58 to 302°F]
1 to 120 h
0 to 255 min
0 to 99 min
rt; it; SEt; dEF; dEG
0 to 255 min
0 to 60 min
n; Y
0.0 to 23h50min, res. 10 min
FANS
C-n; C-y; O-n; O-y
0 to 255 min
[0 to 50°C]
[0 to 90°F]
[-55.0 to 50°C]
[-67 to 302°F]
0 to 15 min
0 to 15 min
Fon Fan on time with compressor off
FoF Fan off time with compressor off
Probe selection for fan
FAP
nP; P1; P2; P3; P4
management
AUXILIARY THERMOSTAT
ACH Kind of action for auxiliary relay
CL; Ht
[-55.0 to 150°C]
SAA Set Point for auxiliary relay
[-67 to 302°F]
[0.1 to 25.5°C]
SHy Differential for auxiliary relay
[1 to 45°F]
ArP Probe selection for auxiliary relay
nP; P1; P2; P3
Sdd Aux.output working during defrost
n; Y
ALARMS
Probe setting for temperature
ALP
P1; P2; P3; P4
alarm
ALC Temperature alarms configuration
rE; Ab
[-55.0 to 150.0°C]
ALU MAXIMUM temperature alarm
[-67 to 302°F]
[-55.0 to 150.0°C]
ALL minimum temperature alarm
[-67 to 302°F]
Temperature alarm and fan
[0.1 to 25.5°C]
AFH
differential
[1 to 45°F]
ALd Temperature alarm delay
0 to 255 min
Delay of temperature alarm at
dAo
0.0 to 23h50min, res. 10 min
start up
Probe for temperat. alarm of
AP2
nP; P1; P2; P3; P4
condenser
Condenser for low temperat.
[-55.0 to 150.0°C]
AL2
alarm
[-67 to 302°F]
Condenser for high temperat.
[-55.0 to 150.0°C]
AU2
alarm
[-67 to 302°F]
Differential for condenser
[0.1 to 25.5°C]
AH2
temperature alarm recovery
[1 to 45°F]
Condenser temperature alarm
Ad2
0 to 254 min , 255=nU
delay
Delay of cond. temper. alarm at
dA2
0.0 to 23h50min, res. 10 min
start up
Compressor off because of
bLL
n(0); Y(1)
condenser low temperature alarm
1592026020 XW60K GB r2.3 08.04.2015
CL
Pr2
0.0
Pr2
2.0
Pr2
nP
n
Pr2
Pr2
P1
Pr2
rE
Pr2
10.0
Pr1
10.0
Pr1
2.0
Pr2
15
Pr2
1.3
Pr2
P4
Pr2
-40
Pr2
110
Pr2
5
Pr2
15
Pr2
1.3
Pr2
n
Pr2
ISE*
dSE*
Ld1*
Ld2*
Ld3*
Ld4*
Ld5*
Ld6*
Sd1*
Sd2*
Sd3*
Sd4*
Sd5*
Sd6*
Adr
PbC
onF
dP1
dP2
dP3
dP4
rSE
rEL
Ptb
Name
Compr. off for condenser high
temperature alarm
Range
n(0); Y(1)
AUXILIARY OUTPUT
Alarm relay disabling
n=no; Y=yes
ALr = alarm; dEF = do not select it; Lig
=Light; AUS =AUX; onF=always on; Fan=
Fourth relay configuration
do not select it; db = do not select it; dF2 =
do not select it
Alarm relay polarity (oA3=ALr)
oP; CL
DIGITAL INPUT
Digital input polarity
oP=opening;CL=closing
Digital input configuration
EAL; bAL; PAL; dor; dEF; Htr; AUS
Digital input alarm delay
0 to 255 min
Number of activation of pressure
0 to 15
switch
Compress and fan status when
no; FAn; CPr; F_C
open door
Regulation restart with door open
n; Y
alarm
Light off during energy saving
n; Y
status
[-30 to 30°C]
Differential for Energy Saving
[-54 to 54°F]
RTC
Current hour
read only
Current minute
read only
Current day
read only
Day of the month
read only
Month
read only
Year
read only
First weekly holiday
Sun to SAt; nu
Second weekly holiday
Sun to SAt; nu
Energy Saving cycle start during
0.0 to 23h50min
workdays
Energy Saving cycle length during
0.0 to 24h00min
workdays
Energy Saving cycle start on
0.0 to 23h50min
holidays
Energy Saving cycle length on
0.0 to 24h00min
holidays
1st workdays defrost start
0.0 to 23h50min; nu
2nd workdays defrost start
0.0 to 23h50min; nu
3rd workdays defrost start
0.0 to 23h50min; nu
4th workdays defrost start
0.0 to 23h50min; nu
5th workdays defrost start
0.0 to 23h50min; nu
6th workdays defrost start
0.0 to 23h50min; nu
1st holiday defrost start
0.0 to 23h50min; nu
nd
2 holiday defrost start
0.0 to 23h50min; nu
rd
3 holiday defrost start
0.0 to 23h50min; nu
4th holiday defrost start
0.0 to 23h50min; nu
5th holiday defrost start
0.0 to 23h50min; nu
6th holiday defrost start
0.0 to 23h50min; nu
OTHER
Serrial address
1 to 247
Kind of probe
PtC; ntC
on/off key enabling
nu, oFF; ES
Room probe display
read only
Evaporator probe display
read only
Third probe display
read only
Fourth probe display
read only
Current set point
read only
Software release
read only
Map code
read only
Default Level
n
Pr2
Y
Pr2
Lig
Pr2
CL
Pr2
CL
dor
15
Pr1
Pr1
Pr1
15
Pr2
F-C
Pr2
Y
Pr2
Y
Pr2
0
Pr2
nu
nu
rtc
rtc
rtc
rtc
rtc
rtc
rtc
rtc
0
rtc
0
rtc
0
rtc
0
rtc
6.0
13.0
21.0
0.0
0.0
0.0
6.0
13.0
21.0
0.0
0.0
0.0
rtc
rtc
rtc
rtc
rtc
rtc
rtc
rtc
rtc
rtc
rtc
rtc
1
ntC
oFF
-
Pr1
Pr2
Pr2
Pr1
Pr1
Pr1
Pr1
Pr1
Pr2
Pr2
-
* Only for model with real time clock
XW60K
6/6
  Название Инструкция Комментарий

Контроллер Dixell XH240 L-V

Контроллер Dixell XH240 L-V Контроллер Dixell XH240 L-V XH240L-V — контроллер предназначенный для поддержания температуры и влажности в среднетемпературных холодильных системах. 5 релейных выходов для управления компрессором, нагревательными элементами, вентилятором, освещением и увлажнителем. Они снабжены 1 входом NTC для контроля температуры, и входом 4-20мА для датчика влажности. Имеется один цифровой вход (контакт без напряжения), конфигурируемый параметром. Специальный выход позволяет программировать список параметров с помощью ключа «Hot Key»

Контроллер Dixell XM660K

Контроллер Dixell XM660K Контроллер Dixell XM660K XM660K — оснащен четырьмя релейными выходами, которые могут использоваться на выбор: для управления соленоидным клапаном, оттайкой (электрической либо горячим газом), для управления вентиляторами испарителя или освещением. Четыре входа датчиков: контроль температуры, контроль температуры окончания оттайки испарителя, индикация, возможное использование для систем с виртуальным датчиком или для измерения температуры воздуха на входе/выходе.

Контроллер Dixell XR60C

Контроллер Dixell XR60C Контроллер Dixell XR60C XR60C — с циклом оттайки, используется в холодильной отрасли при средней и низкой температуре, с контролем работы вентиляторов. 3 входа реле для управления компрессором, вентилятором и оттайкой (электрической / горячим газом), 2 датчика NТС.

Контроллер Dixell XC 650 C

Контроллер Dixell XC 650 C Контроллер Dixell XC 650 C XC 650C — разработан для управления и компрессорами и вентиляторами конденсатора, работающими в составе агрегата. Компрессоры могут быть простыми, многоступенчатыми или разной мощности. Управление осуществляется по типу с «нейтральной зоной» или с «зоной пропорциональности» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) и нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки компрессоров для равномерного распределения рабочей нагрузки

Dixell_XC807M-XC911M

Контроллер Dixell XC807-XC911 Контроллер Dixell XC807-XC911 XC807, XC911 — управляют как компрессорами, так и вентиляторами в системах конденсации. Передняя панель информирует о давлении на всасывании и давлении в конденсаторе, возможные аварийные сигналы и условия технического обслуживания. Контроллер оборудован двумя аварийными выключателями высокого и низкого давления системы

Dixell T66 - XW60K

Gamko Flexbar Dixell T66 — XW60K

Dixell XR 20 C

Контроллер Dixell XR 20C Dixell XR 20C XR20C — с простейшим циклом оттайки, для использования в холодильной области при нормальной температуре. Блок имеет реле выхода для управления компрессором, работает с датчиками РТС или NТС. Цикл оттайки по внутреннему таймеру

Dixell XR 70 CX

Контроллер Dixell XR 70 CX Dixell XR 70 CX XR70 CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. 4 релейных выхода для управления компрессором, вентилятором и оттайкой, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Последнее реле может использоваться для освещения, для сигнала аварии или как дополнительный выход. Он также снабжен четырьмя входами датчиков NTC или PTC, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором. Цифровой вход может работать в качестве третьего датчика температуры. Четвертый датчик, подключаемый к разъему HOT KEY, используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Выход HOT KEY позволяет подключить контроллер с помощью внешнего модуля XJ485-CX к сети, совместимой с ModBUS-RTU , такой как блоки мониторинга Dixell семейства XWEB. Разъем HOT key позволяет программировать контроллер с помощью ключа программирования HOT KEY. Прибор полностью конфигурируется с помощью специальных параметров, которые могут быть легко запрограммированы с клавиатуры

Dixell XR160C - XR170C

Контроллер Dixell XR160C — XR170C Dixell XR160C — XR170C XR160C, XR170C — цифровой контроллер для вентилируемых холодильных камер с функцией оттайки тэнами или горячими парами, управления работой вентилятора воздухоохладителя

Dixell XH360L-V

Контроллер Dixell XH360L-V Dixell XH360L-V XH360L, формата 38×185 и XH360V, формата 100×64 — это микропроцессорные контроллеры, подходящие для применения в средне — или низкотемпературных блоках охлаждения. 6 релейных выходов для управления компрессором, нагревательными элементами, оттайкой — вытяжным вентилятором, вентилятором, осушителем — светом и увлажнителем. Они снабжены 2 входами NTC: один — для контроля температуры, другой — для контроля оттайки . Также имеется вход 4 ÷ 20 мА для датчика влажности

Dixell XC440

Контроллер Dixell XC440 Dixell XC440 Контроллер XC440C разработан для управления компрессорами или вентиляторами конденсатора, работающими в составе агрегата. Компрессоры могут быть простыми, многоступенчатыми или разной мощности. Управление осуществляется по типу с «нейтральной зоной» или с «зоной пропорциональности» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) или нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки компрессоров, чтобы равномерно распределять рабочую нагрузку. Данный контроллер может конвертировать давление и показывать его на дисплее в виде температуры. Полная информация о состоянии системы предоставляется на передней панели путем показа давления (температур) всасывания и конденсации, состояния нагрузок, возможных аварий или условий обслуживания

Dixell XP 110 - 111 C - D

Контроллер Dixell XP 110-111 C-D Dixell XP 110 — 111 C — D XP110C, XP111C (32×74мм размер), XP110D, XP111D (на ДИН-РЕЙКУ) и XP111R, (72×72мм размер), является одноступенчатым релейным регулятором для управления давлением с прямым или обратным (выбираемым) действием. Аналоговый тип входа должен быть выбран и определен при заказе, согласно технологическому параметру, которым нужно управлять

Dixell XT 110-111 C-D

Контроллер Dixell XT 110-111 C-D Dixell XT 110-111 C-D XT110C, XT111C и XT110D, XT111D ( формат на DIN- рейку ) — одноступенчатые контроллеры ВКЛ / ВЫКЛ для применений с управлением по температуре, влажности и давлению с прямым или обратным действием, выбираемым пользователем. Тип аналогового входа может задаваться с помощью параметра из следующих, согласно модели : — PTC, NTC; — PTC, NTC, Pt100, Термопара J, K, S; 4 ÷ 20 мА, 0 ÷ 1 В, 0 ÷ 10 В

Dixell XR70C-D XR72C

Контроллер Dixell XR70C-D XR72C Dixell XR70C-D XR72C XR70C-D — прибор с циклом оттайки, сконструированный для применения в холодильной области при нормальной и низкой температуре, также позволяет контролировать работу вентиляторов. 3 реле выхода для управления компрессором, вентилятором и оттайкой (электрической, горячим газом), входами для 2 датчиков NТС

Dixell XT 120C – XT 125R

Контроллер Dixell XT 120C – XT 125R Dixell XT 120C – XT 125R XT120C, XT121C, XT124C, XT125C (корпус 32×74 мм), XT120D, XT121D (крепёж на ДИН-РЕЙКУ) и XT121R, XT125R (корпус 72×72 мм) является семейством универсальных приборов на основе микропроцессора с выходом на реле, особенно когда требуется два ступенчатых конфигурируемых регулятора

Dixell XW270L - XW271L

Контроллер Dixell XW270L — XW271L Dixell XW270L — XW271L XW270L — XW271L — для применения в средне- и низкотемпературных холодильных системах. 6 релейных выходов служат для управления компрессором, двумя оттайками (тэн / горячим газом), вентиляторами испарителя, освещением (вкл/выкл). Так же есть три входа для датчиков NTC, один для термостатирования и два для контроля температуры окончания оттайки

Dixell XW40L - XW40V

Контроллер Dixell XW40L — XW40V Dixell XW40L — XW40V XW40L-XW40V — для применения в средне и низкотемпературных холодильных системах. 3 релейных выхода служат для управления компрессором, двумя оттайками (тэн / горячим газом), освещением вкл/выкл. Так же есть два входа для датчиков NTC

Dixell XW 60 K

Контроллер Dixell XW 60 K Dixell XW 60 K Модель XW60K является микропроцессорным контроллером подходящим для применения в средне- и низкотемпературных холодильных системах. При помощи двужильного кабеля (1мм) к нему на дистанции до 30м могут подключаться клавиатуры T620T или T620 или V620 или CX620. У него есть 3 релейных выхода для управления компрессором, вентилятором,
освещением и оттайкой, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Он также снабжен четырьмя входами датчиков NTC или PTC, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором, третий и четвертый — для подачи сигнала аварии по температуре конденсатора или для показа температуры, отличной от температуры, по которой происходит регулирование.

Контроллер Dixell XW60LRH

Контроллер Dixell XW60LRH Контроллер Dixell XW60LRH Dixell XW60LRH — микропроцессорный контроллер для применения в среднетемпературных холодильных установок. Три релейных выхода для управления компрессором, вентилятором и освещением.

Контроллер Dixell XLR170

Контроллер Dixell XLR170 Контроллер Dixell XLR170 Модели XLR130 и XLR170, в формате 210×230мм, являются микропроцессорными контроллерами для средне- и низкотемпературных холодильных систем. Они имеют четыре (XLR130) или шесть (XLR170) релейных выходов для управления компрессором, оттайкой – которая может быть электрической или газовой (XLR170) – вентиляторами испарителя (в XLR130 надо сконфигурировать доп. реле), освещением, аварийной сигнализацией и дополнительным реле.

Контроллер Dixell XLH260

Контроллер Dixell XLH260 Контроллер Dixell XLH260 XLH 260 — контроллер для поддержания температуры и влажности в средне- и низкотемпературных холодильных системах. Прибор снабжен шестью релейными выходами для управления компрессором, нагревателем, оттайкой, вентилятором, осушителем и увлажнителем. Имеет два аналоговых входа для датчиков NTC – для термостатирования и оттайки, один вход 4-20 мА для датчика влажности. Цифровой вход – один конфигурируемый без напряжения. Контроллер может быть запрограммирован с ключа “Hot Key”.

Контроллер Dixell XLH360

Контроллер Dixell XLH360 Контроллер Dixell XLH360 (ENG)

Dixell XLR470

Контроллер Dixell XLR470 Dixell XLR470 XLR470 — цифровой контроллер для холодильных камер с двойным управлением температурой (для нормальной и низкой температуры). Идеально подходит для систем с нагревом-охлаждением, таких как стойка для водяной бани с холодильной камерой внизу. Предназначен для систем с двумя испарителями или 2 независимыми контурами. Встроенное управление оттайкой. Охлаждение или нагрев выбирается пользователем. Мгновенный обзор состояния устройства при помощи иконок на дисплее.

Dixell XW220L

Контроллер Dixell XW220L Контроллер Dixell XW220L Контроллер Dixell XW220L — для применения на холодильных установках. Контроллер снабжен двумя релейными выходами для управления компрессором и подсветкой. Два входа датчиков NTC. Два цифровых входа (свободный контакт) для дверного выключателя и настраивается по параметру. Выход TTL позволяет подключать с помощью внешнего модуля TTL / RS485 модуль ModBUS RTU для системы мониторинга

Dixell XW230L

Контроллер Dixell XW230L Dixell XW230L Контроллер Dixell XW230L для использования на средних или низкотемпературных холодильных установках. Четыре релейных выхода для управления компрессором, сигнализацией и вспомогательным выходом. Два датчика NTC (контроль температуры и дополнительный для дисплея). Два цифровых входа (свободный контакт) для дверного выключателя и настраиваемый параметром. Стандартный выход TTL позволяет пользователю подключать с помощью внешнего модуля TTL / RS485 совместимую с ModBUSRTU систему мониторинга

Контроллер Dixell XW260L

Контроллер Dixell XW260L Dixell XW260L Контроллер Dixell XW260L — для применения на средних или низкотемпературные холодильные установки. Cнабжен четырьмя релейными выходами для управления компрессором, процессом оттайки (электрической, горячий газ), вентилятором испарителя и светом. Три датчика NTC (температура объема,оттайкой и третья, опционная, для дисплея. Стандартный выход TTL позволяет пользователю подключать с помощью внешнего модуля TTL/RS485 модуль ModBUSRTU системы мониторинга

Контроллер Dixell XW263L

Контроллер Dixell XW263L Dixell XW263L Контроллер Dixell XW263L для управления средне- или низкотемпературных холодильных установок. Снабжен четырьмя релейными выходами для управления компрессором, оттайкой (электрический, горячий газ), вентилятором испарителя и светом. Два датчика NTC (объем, испаритель)

Dixell XW264L

Контроллер Dixell XW264L Dixell XW264L Контроллер Dixell XW264L являются микропроцессорными контроллерами для применения в средне- и низкотемпературных холодильных системах. У него есть 6 релейных выходов для управления компрессором, двумя оттайками (электронагреватель или горячим газом), вентиляторами испарителя, освещением или вкл/выкл. Так же есть три входа для датчиков NTC, один для термостатирования и два для контроля температуры окончания оттайки двух испарителей. Два цифровых входа (без напряжения) для контроля двери и конфигурируемый. TTL разъем позволяющий пользователю с помощью внешнего конвертора TTL/RS485 подключить контроллер к ModBUS-RTU совместимой с системой мониторинга Dixell, такой как XWEB300В/500/3000/5000 и для программирования с помощью “Hot Key”. Опционально XW-REP выход для удаленного дисплея, аналоговый выход 4÷20 мА для управления вентилятором испарителя или конденсатора и последовательный выход с RS485.

Dixell XW563L

Контроллер Dixell XW563L Dixell XW563L Контроллер Dixell XW563L является микропроцессорным контроллером, подходящим для применение на средне- или низкотемпературных холодильных установках. Снабжен четырьмя реле выходы для управления компрессором, оттайка (электричеством, горячим газом), вентиляторы испарителя и свет. Два датчика NTC (объем, испаритель). Два цифровых входа (свободный контакт) для дверного выключателя и настраивается по параметру. Выход RS485 позволяет пользователю подключать совместимый с ModBUS-RTU мониторинг система

Dixell XW570L

Контроллер Dixell XW570L Dixell XW570L Контроллер Dixell XW570L для применения на средне- или низкотемпературном холодильном оборудовании. Снабжен шестью релейными выходами для управления компрессором, оттайкой (электрическая, горячий газ), вентиляторами испарителя, лампочками, сигнализацией и вспомогательным выходом. Три датчика NTC (объем, испаритель и третий опционный для дисплея). Есть два цифровых входа (свободный контакт) для дверного выключателя и настраивается по параметру. Стандартный выход TTL позволяет пользователю подключать с помощью внешнего модуля TTL/RS485 модуль ModBUSRTU совместимая система мониторинга и запрограммировать список параметров с помощью “горячей клавиши». Выход для удаленного дисплея XW-REP, выход 4÷20 мА для управления вентиляторами испарителя или конденсатора и прямой последовательный выход RS485 доступен в качестве опции

Dixell XW30V

Контроллер Dixell XW30L-XW30V Dixell XW30V Контроллер Dixell модель XW30L, формат 38×185 мм, и модель XW30V, формат 100×64, основаны на микропроцессоре контроллеры подходят для применения на холодильных установках средней температуры. Три релейных выхода управляют компрессором, подсветкой и сигнализацией тревоги. Один датчик NTC или PTC. Есть 1 цифровой входами (свободный контакт) настраиваемый параметр

Dixell XC15CX-XC35CX

Контроллер Dixell XC15CX-XC35CX Dixell XC15CX-XC35CX Контроллер Dixell XC15CX-XC35CX являются контроллерами предназначенными для управления одно- и двухкомпрессорными агрегатами. Он может управлять простыми компрессорами, компрессорами с преобразователями частоты и компрессорами Digital. Контроллер имеет:
— 1 (ХС15СХ) или 2 (ХС35СХ) релейных выхода для управления компрессорами или вентиляторами или аварийной сигнализации;
— 1 тиристорный выход для управления скоростью вращения вентиляторов в режиме фазорезки (макс. ток 2.2 A) или соленоидным клапаном компрессора Digital;
— 1 аналоговый выход (0-10В или ШИМ) для управления ЕС-вентиляторами, преобразователями частоты или режима пропорционального повторителя;
— До 3-х цифровых входов без напряжения для мониторинга аварий;
— 2 аналоговых входа для ратиометрических датчиков давления (0-5В);
— До 4-х температурных датчиков NTC10k, NTC86k или PT1000.
XC15CX оснащён только одним реле 16 A, у ХС35СХ имеется также второе реле номиналом 5А. Все функции (исключая связанные со вторым реле) одинаковые для обоих приборов.

Dixell XC10CX-XC30CX

Контроллер Dixell XC10CX-XC30CX Dixell XC10CX-XC30CX Модель XC30CX, формат 32x74mm, представляет собой цифровой термостат для применения в конденсаторных установках. Это обеспечивает три цифровых (релейных) выхода, один для компрессора, а другой для управления вентиляторами. Два датчика NTC или ratiometric зонда, который нужно использовать на линии всасывания и конденсатора. Цифровые входы могут работать для управления безопасностью конденсаторного агрегата. Модель XC10CX отличается от XC30CX по номеру цифрового выхода. На самом деле, XC10CX имеет только один цифровой выход, который используется для управления компрессором.

Dixell XR20CX

Контроллер Dixell XR20CX Dixell XR20CX Контроллер Dixell XR20CX — цифровой термостат с оттайкой “off cycle”, предназначенный для применения в холодильных системах с нормальной температурой. Имеется релейный выход для управления компрессором. Он также снабжен 2 входами датчиков NTC или PTC, первый — для контроля температуры, второй, опциональный, подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Цифровой вход может работать как третий датчик температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к
сети, совместимой с ModBUS-RTU, такой как блоки мониторинга dIXEL семейства XWEB.

Dixell XR40CX

Контроллер Dixell XR40CX Dixell XR40CX Контроллер Dixell XR40CX — для применения в холодильных системах с нормальной и низкой температурой. Имеется два реле для управления компрессором и оттайкой (электрическая, горячим газом). Он также снабжен 3 входами датчиков NTC или PTC, первый — для контроля температуры объема, второй — испарителя, третий — опционально может быть подключен через HOT KEY для подачи сигнала тревоги температуры конденсатора или для отображения температуры. Цифровой вход может работать как четвертый температурный зонд.

Dixell XR60CX

Контроллер Dixell XR60CX Dixell XR60CX Контроллер Dixell XR60CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. Три релейных выхода для управления компрессором, вентилятором, оттайкой (электрическая, горячий газ). Он также снабжен тремя входами датчиков NTC или PTC, первый температуры объема, второй на испарителе для контроля температуры окончания оттайки и управления вентилятором, третий датчик, опциональный, подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Цифровой вход может работать как четвертый датчик температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к сети, совместимой с ModBUS-RTU, такой как блоки мониторинга dIXEL семейства XWEB.

Dixell XR70CX

Контроллер Dixell XR70CX Dixell XR70CX Контроллер Dixell XR70CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. Четыре релейных выхода для управления компрессором, вентилятором и оттайкой (электрическая, горячий газ). Последнее реле может использоваться для освещения, для сигнала аварии или как дополнительный выход. Он также снабжен четырьмя входами датчиков NTC или PTC, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором. Цифровой вход может работать в качестве третьего датчика температуры. Четвертый датчик, подключаемый к разъему HOT KEY, используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Выход HOT KEY позволяет подключить контроллер с помощью внешнего модуля XJ485-CX к сети.

Dixell XR64CX

Контроллер Dixell XR64CX Dixell XR64CX Контроллер Dixell XR64CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией и 2мя
испарителями. У него есть четыре релейных выхода для управления компрессором, вентилятором, оттайкой 1 и 2, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Он также снабжен до четырех входов датчиков NTC или PTC, первый — для контроля температуры, второй и третий, расположенные на испарителе, для контроля температуры окончания оттайки и управления вентилятором. Четвертый датчик подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к сети.

Dixell XR75CX

Контроллер Dixell XR75CX Dixell XR75CX Контроллер Dixell XR75CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. Четыре релейных выхода для управления компрессором, вентилятором, оттайкой (электрическая, горячий газ) и освещением. Он может снабжаться Часами Реального Времени, которые позволяют запрограммировать до 6 циклов оттайки ежедневно, с разделением на выходные и рабочие дни. Функция “День и Ночь” с двумя разными уставками подходит для энергосбережения. Он также снабжен четырьмя входами датчиков NTC или PT1000, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором. Один из 2 цифровых входов может работать в качестве третьего датчика температуры. Четвертый датчик используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Последовательный выход RS485 позволяет подключить контроллер к сети, совместимой с ModBUS-RTU.

Dixell XC645CX

Контроллер Dixell XC645CX Dixell XC645CX Контроллер Dixell XC645CX — для управления компрессорами и вентиляторами конденсатора, работающими в составе агрегата.
В составе агрегата один компрессор всегда – Digital (спиральный или поршневой), остальные могут быть как спиральными, так и поршневыми с регулировкой производительности или без неё. Управление компрессорами осуществляется по алгоритму с «нейтральной зоной» и основано на считывании величины давления или температуры в контурах всасывания (низкое давление — компрессоры) и нагнетания (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки нагрузок. Управление вентиляторами – пропорциональное. Контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры.

Dixell XC650CX

Контроллер Dixell XC650CX Dixell XC650CX Контроллер Dixell XC650CX — для управления компрессорами и вентиляторами конденсатора, работающими в составе агрегата.
Компрессоры могут быть спиральными, поршневыми, с регулировкой производительности, в том числе при помощи преобразователя частоты. Контроллер может управлять двумя контурами всасывания с общим контуром конденсации. Управление компрессорами осуществляется по алгоритму с «нейтральной зоной» и основано на считывании величины давления или температуры в контурах всасывания (низкое давление — компрессоры) и нагнетания (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки нагрузок. Управление вентиляторами – пропорциональное. Данный контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры.

Dixell XC660D

Контроллер Dixell XC660D Dixell XC660D Контроллер Dixell XC660D — для управления компрессорами и вентиляторами конденсатора, работающими в составе агрегата.
Компрессоры могут быть спиральными, поршневыми, с регулировкой производительности. Управление компрессорами осуществляется по алгоритму с «нейтральной зоной» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) и нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки нагрузок. Управление вентиляторами – пропорциональное. Данный контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры.

Dixell XC1000D

Контроллер Dixell XC1000D Dixell XC1000D Контроллер Dixell XC1000D — для управления систем контуров охлаждения (до 2 контуров всасывания и 2 контуров конденсации). Благодаря специальным алгоритмам эти контроллеры могут управлять и контролировать установки с CO2, которые работают по каскадному принципу с субкритическим циклом.

Dixell XC807-911M

Контроллер Dixell XC807-911M Dixell XC807-911M Контроллер Dixell серии XC800M и XC900M управляет компрессорами и вентиляторами в системах конденсации.
Компрессора могут быть простыми, многоступенчатыми или с разными мощностями. Управление осуществляется при помощи нейтральной зоны или пропорционального регулирования и основано на давлении или температуре определяемой в зоне низкого давления (компрессоры) и высокого давления (конденсаторы).

Dixell XRi77CX

Контроллер Dixell XRi77CX Dixell XRi77CX Контроллер Dixell XRi77CX — предназначен для применения на средне- или низкотемпературных вентилируемых холодильных установок. Имеет четыре релейных выхода для управления компрессором, вентилятором, оттайкой (электрическая, горячим газом). Снабжен четырьмя входами датчика NTC. Первый зонд для контроля температуры объема. Второй зонд для контроля температуры испарителя. Один из двух цифровых входов может работать как третий температурный зонд. Четвертый зонд используется для контроля температуры конденсатора (для управления сигнализацией конденсатора) или для отображения температуры.

Dixell XWi70K

Контроллер Dixell XWi70K Dixell XWi70K Контроллер Dixell XWi70K предназначен для применения на средне- и низко- температурных холодильных установках. Пять
релейных выходов для управления компрессором, оттайкой (электрическая, горячий газ), испарителем и конденсаторными вентиляторами, светом или сигнализация. Четыре датчика NTC (PTC). Он имеет как частотный выход, так и последовательный порт, который может использоваться для управления переменной скоростью компрессоров. Пара аналоговых выходов (4-20мА или 0-10В) и главный 2-проводный выход RS485

Dixell XEV11D_12D

Контроллер Dixell XEV11D-12D Dixell XEV11D_12D Контроллер Dixell XEV11D-12D — для управления импульсными (ВКЛ/ВЫКЛ) электронными расширительными вентилями. Этот модуль позволяет регулировать перегрев (SH) текучей среды, которая протекает в холодильной системе, с тем чтобы достичь оптимальной производительности и функционирования испарителя независимо от климатических условий или нагрузки. Модули XEV12D оборудованы двумя входами датчиков, один – для датчика давления с интерфейсом 4÷20мА или 0÷5В, а другой – для датчика температуры Pt1000 или NTC. Подключение в локальную сеть LAN позволяет передавать сигнал давления на другие модули XEV, чтобы использовать только один датчик давления в системах с составными шкафами. Имеется также два конфигурируемых цифровых входа, один из них должен быть сконфигурирован для получения запроса охлаждения. Другой цифровой вход может использоваться для оповещения контроллера о том, что идет оттайка. Дисплей с иконками предоставляет удобную визуализацию перегрева (SH), процент времени открытия вентиля или значений датчиков, встроенная клавиатура позволяет программировать контроллер без каких-либо других устройств. Завершая комплектацию контроллера, последовательная сеть RS485.

Dixell XEV22D

Контроллер Dixell XEV22D Dixell XEV22D Контроллер Dixell XEV22D — для управления шаговыми электронными расширительными клапанами. XEV22D позволяет регулировать перегрев (SH) хладагента в испарителе для достижения оптимальной производительности и функционирования испарителя независимо от климатических условий или нагрузки. XEV22D имеет два входа датчиков, один – для датчика давления с интерфейсом 4÷20мА или 0÷5В, а другой – для датчика температуры Pt1000 или NTC-EU / NTC-US. LAN связь позволяет передавать сигнал от одного датчика давления на несколько приборов. Имеется также два конфигурируемых цифровых входа, один – сухой контакт, второй — свободный от напряжения. С дисплея можно просмотреть значение перегрева (SH), степень открытия клапана или показания датчиков, клавиатура позволяет программировать контроллер без каких-либо других
устройств. К системам мониторинга и диспетчеризации XEV22D подключатся с помощью встроенной сетевой карты RS485.

Dixell IEV22D-IEV24D

Контроллер Dixell IEV22D-IEV24D Dixell IEV22D-IEV24D Контроллер Dixell IEV22D-IEV24D — предназначен для управления одним или двумя шаговыми двигателями электронного расширительного клапана. Доступны два различных режима регулирования: * Автономный режим: цифровые входы используются для запуска управления перегревом. Давление кипения датчик и датчик температуры всасывания должны быть соединены с контроллером; * LAN: IEV можно подключить к серии Ichill 200 EVO для того чтобы контролировать перегрев. Для обеспечения наилучшего регулирования рекомендуется подключать датчик давления всасывания непосредственно к контроллеру.
Основные характеристики: * управление одним или двумя электронными расширительными клапанами; * совместимость с несколькими моделями клапанов; * совместимость с различными типами хладагентов; * ручное управление ПИД-регулировкой или адаптивным регулированием.

Dixell_XW10L

Контроллер Dixell_XW10L Контроллер Dixell_XW10L Контроллер Dixell XW10L, формат 38×185 мм, и модель XW10V, формат 100×64, представляют собой микропроцессорные
контроллеры, подходящие для применения в области охлаждения или отопления. Снабжены 2 релейными
выходами, один из которых предназначен для регулирования, а другой — для освещения. Они также снабжены 1
входом датчика NTC или PTC для контроля температуры. Имеется 1 цифровой вход (свободный контакт), настраиваемый по параметру. Вывод позволяет пользователю запрограммировать список параметров с помощью горячей клавиши.

Dixell Wing XW10L-V

Контроллер Dixell Wing XW10L-V Контроллер Dixell Wing XW10L-V

Dixell XH260L-V

Контроллер Dixell XH260L-V Dixell XH260L-V Контроллер Dixell XH260L и XH260V применяются в холодильных установках средней или низкой температуры. Контролируют как влажность, так и температуру. Имеют 6 выходных реле для управления компрессором, нагревательными элементами, размораживанием, осушителем воздуха и увлажнителем воздуха. 2 датчика NTC: объем и испаритель. Вход 4÷20 мА для измерения влажности. Имеется один цифровой вход (свободный контакт), настраиваемый по параметру. Вывод позволяет пользователю запрограммировать список параметров с помощью “Hot Key”.

Dixell XB570L

Контроллер Dixell XB570L Dixell XB570L Контроллер Dixell серии XB созданы для быстрого охлаждения или заморозки продуктов в соответствии с международными стандартами пищевой безопасности.
  Название Инструкция Комментарий

Контроллер Dixell XH240 L-V

Контроллер Dixell XH240 L-V Контроллер Dixell XH240 L-V XH240L-V — контроллер предназначенный для поддержания температуры и влажности в среднетемпературных холодильных системах. 5 релейных выходов для управления компрессором, нагревательными элементами, вентилятором, освещением и увлажнителем. Они снабжены 1 входом NTC для контроля температуры, и входом 4-20мА для датчика влажности. Имеется один цифровой вход (контакт без напряжения), конфигурируемый параметром. Специальный выход позволяет программировать список параметров с помощью ключа «Hot Key»

Контроллер Dixell XM660K

Контроллер Dixell XM660K Контроллер Dixell XM660K XM660K — оснащен четырьмя релейными выходами, которые могут использоваться на выбор: для управления соленоидным клапаном, оттайкой (электрической либо горячим газом), для управления вентиляторами испарителя или освещением. Четыре входа датчиков: контроль температуры, контроль температуры окончания оттайки испарителя, индикация, возможное использование для систем с виртуальным датчиком или для измерения температуры воздуха на входе/выходе.

Контроллер Dixell XR60C

Контроллер Dixell XR60C Контроллер Dixell XR60C XR60C — с циклом оттайки, используется в холодильной отрасли при средней и низкой температуре, с контролем работы вентиляторов. 3 входа реле для управления компрессором, вентилятором и оттайкой (электрической / горячим газом), 2 датчика NТС.

Контроллер Dixell XC 650 C

Контроллер Dixell XC 650 C Контроллер Dixell XC 650 C XC 650C — разработан для управления и компрессорами и вентиляторами конденсатора, работающими в составе агрегата. Компрессоры могут быть простыми, многоступенчатыми или разной мощности. Управление осуществляется по типу с «нейтральной зоной» или с «зоной пропорциональности» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) и нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки компрессоров для равномерного распределения рабочей нагрузки

Dixell_XC807M-XC911M

Контроллер Dixell XC807-XC911 Контроллер Dixell XC807-XC911 XC807, XC911 — управляют как компрессорами, так и вентиляторами в системах конденсации. Передняя панель информирует о давлении на всасывании и давлении в конденсаторе, возможные аварийные сигналы и условия технического обслуживания. Контроллер оборудован двумя аварийными выключателями высокого и низкого давления системы

Dixell T66 - XW60K

Gamko Flexbar Dixell T66 — XW60K

Dixell XR 20 C

Контроллер Dixell XR 20C Dixell XR 20C XR20C — с простейшим циклом оттайки, для использования в холодильной области при нормальной температуре. Блок имеет реле выхода для управления компрессором, работает с датчиками РТС или NТС. Цикл оттайки по внутреннему таймеру

Dixell XR 70 CX

Контроллер Dixell XR 70 CX Dixell XR 70 CX XR70 CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. 4 релейных выхода для управления компрессором, вентилятором и оттайкой, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Последнее реле может использоваться для освещения, для сигнала аварии или как дополнительный выход. Он также снабжен четырьмя входами датчиков NTC или PTC, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором. Цифровой вход может работать в качестве третьего датчика температуры. Четвертый датчик, подключаемый к разъему HOT KEY, используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Выход HOT KEY позволяет подключить контроллер с помощью внешнего модуля XJ485-CX к сети, совместимой с ModBUS-RTU , такой как блоки мониторинга Dixell семейства XWEB. Разъем HOT key позволяет программировать контроллер с помощью ключа программирования HOT KEY. Прибор полностью конфигурируется с помощью специальных параметров, которые могут быть легко запрограммированы с клавиатуры

Dixell XR160C - XR170C

Контроллер Dixell XR160C — XR170C Dixell XR160C — XR170C XR160C, XR170C — цифровой контроллер для вентилируемых холодильных камер с функцией оттайки тэнами или горячими парами, управления работой вентилятора воздухоохладителя

Dixell XH360L-V

Контроллер Dixell XH360L-V Dixell XH360L-V XH360L, формата 38×185 и XH360V, формата 100×64 — это микропроцессорные контроллеры, подходящие для применения в средне — или низкотемпературных блоках охлаждения. 6 релейных выходов для управления компрессором, нагревательными элементами, оттайкой — вытяжным вентилятором, вентилятором, осушителем — светом и увлажнителем. Они снабжены 2 входами NTC: один — для контроля температуры, другой — для контроля оттайки . Также имеется вход 4 ÷ 20 мА для датчика влажности

Dixell XC440

Контроллер Dixell XC440 Dixell XC440 Контроллер XC440C разработан для управления компрессорами или вентиляторами конденсатора, работающими в составе агрегата. Компрессоры могут быть простыми, многоступенчатыми или разной мощности. Управление осуществляется по типу с «нейтральной зоной» или с «зоной пропорциональности» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) или нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки компрессоров, чтобы равномерно распределять рабочую нагрузку. Данный контроллер может конвертировать давление и показывать его на дисплее в виде температуры. Полная информация о состоянии системы предоставляется на передней панели путем показа давления (температур) всасывания и конденсации, состояния нагрузок, возможных аварий или условий обслуживания

Dixell XP 110 - 111 C - D

Контроллер Dixell XP 110-111 C-D Dixell XP 110 — 111 C — D XP110C, XP111C (32×74мм размер), XP110D, XP111D (на ДИН-РЕЙКУ) и XP111R, (72×72мм размер), является одноступенчатым релейным регулятором для управления давлением с прямым или обратным (выбираемым) действием. Аналоговый тип входа должен быть выбран и определен при заказе, согласно технологическому параметру, которым нужно управлять

Dixell XT 110-111 C-D

Контроллер Dixell XT 110-111 C-D Dixell XT 110-111 C-D XT110C, XT111C и XT110D, XT111D ( формат на DIN- рейку ) — одноступенчатые контроллеры ВКЛ / ВЫКЛ для применений с управлением по температуре, влажности и давлению с прямым или обратным действием, выбираемым пользователем. Тип аналогового входа может задаваться с помощью параметра из следующих, согласно модели : — PTC, NTC; — PTC, NTC, Pt100, Термопара J, K, S; 4 ÷ 20 мА, 0 ÷ 1 В, 0 ÷ 10 В

Dixell XR70C-D XR72C

Контроллер Dixell XR70C-D XR72C Dixell XR70C-D XR72C XR70C-D — прибор с циклом оттайки, сконструированный для применения в холодильной области при нормальной и низкой температуре, также позволяет контролировать работу вентиляторов. 3 реле выхода для управления компрессором, вентилятором и оттайкой (электрической, горячим газом), входами для 2 датчиков NТС

Dixell XT 120C – XT 125R

Контроллер Dixell XT 120C – XT 125R Dixell XT 120C – XT 125R XT120C, XT121C, XT124C, XT125C (корпус 32×74 мм), XT120D, XT121D (крепёж на ДИН-РЕЙКУ) и XT121R, XT125R (корпус 72×72 мм) является семейством универсальных приборов на основе микропроцессора с выходом на реле, особенно когда требуется два ступенчатых конфигурируемых регулятора

Dixell XW270L - XW271L

Контроллер Dixell XW270L — XW271L Dixell XW270L — XW271L XW270L — XW271L — для применения в средне- и низкотемпературных холодильных системах. 6 релейных выходов служат для управления компрессором, двумя оттайками (тэн / горячим газом), вентиляторами испарителя, освещением (вкл/выкл). Так же есть три входа для датчиков NTC, один для термостатирования и два для контроля температуры окончания оттайки

Dixell XW40L - XW40V

Контроллер Dixell XW40L — XW40V Dixell XW40L — XW40V XW40L-XW40V — для применения в средне и низкотемпературных холодильных системах. 3 релейных выхода служат для управления компрессором, двумя оттайками (тэн / горячим газом), освещением вкл/выкл. Так же есть два входа для датчиков NTC

Dixell XW 60 K

Контроллер Dixell XW 60 K Dixell XW 60 K Модель XW60K является микропроцессорным контроллером подходящим для применения в средне- и низкотемпературных холодильных системах. При помощи двужильного кабеля (1мм) к нему на дистанции до 30м могут подключаться клавиатуры T620T или T620 или V620 или CX620. У него есть 3 релейных выхода для управления компрессором, вентилятором,
освещением и оттайкой, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Он также снабжен четырьмя входами датчиков NTC или PTC, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором, третий и четвертый — для подачи сигнала аварии по температуре конденсатора или для показа температуры, отличной от температуры, по которой происходит регулирование.

Контроллер Dixell XW60LRH

Контроллер Dixell XW60LRH Контроллер Dixell XW60LRH Dixell XW60LRH — микропроцессорный контроллер для применения в среднетемпературных холодильных установок. Три релейных выхода для управления компрессором, вентилятором и освещением.

Контроллер Dixell XLR170

Контроллер Dixell XLR170 Контроллер Dixell XLR170 Модели XLR130 и XLR170, в формате 210×230мм, являются микропроцессорными контроллерами для средне- и низкотемпературных холодильных систем. Они имеют четыре (XLR130) или шесть (XLR170) релейных выходов для управления компрессором, оттайкой – которая может быть электрической или газовой (XLR170) – вентиляторами испарителя (в XLR130 надо сконфигурировать доп. реле), освещением, аварийной сигнализацией и дополнительным реле.

Контроллер Dixell XLH260

Контроллер Dixell XLH260 Контроллер Dixell XLH260 XLH 260 — контроллер для поддержания температуры и влажности в средне- и низкотемпературных холодильных системах. Прибор снабжен шестью релейными выходами для управления компрессором, нагревателем, оттайкой, вентилятором, осушителем и увлажнителем. Имеет два аналоговых входа для датчиков NTC – для термостатирования и оттайки, один вход 4-20 мА для датчика влажности. Цифровой вход – один конфигурируемый без напряжения. Контроллер может быть запрограммирован с ключа “Hot Key”.

Контроллер Dixell XLH360

Контроллер Dixell XLH360 Контроллер Dixell XLH360 (ENG)

Dixell XLR470

Контроллер Dixell XLR470 Dixell XLR470 XLR470 — цифровой контроллер для холодильных камер с двойным управлением температурой (для нормальной и низкой температуры). Идеально подходит для систем с нагревом-охлаждением, таких как стойка для водяной бани с холодильной камерой внизу. Предназначен для систем с двумя испарителями или 2 независимыми контурами. Встроенное управление оттайкой. Охлаждение или нагрев выбирается пользователем. Мгновенный обзор состояния устройства при помощи иконок на дисплее.

Dixell XW220L

Контроллер Dixell XW220L Контроллер Dixell XW220L Контроллер Dixell XW220L — для применения на холодильных установках. Контроллер снабжен двумя релейными выходами для управления компрессором и подсветкой. Два входа датчиков NTC. Два цифровых входа (свободный контакт) для дверного выключателя и настраивается по параметру. Выход TTL позволяет подключать с помощью внешнего модуля TTL / RS485 модуль ModBUS RTU для системы мониторинга

Dixell XW230L

Контроллер Dixell XW230L Dixell XW230L Контроллер Dixell XW230L для использования на средних или низкотемпературных холодильных установках. Четыре релейных выхода для управления компрессором, сигнализацией и вспомогательным выходом. Два датчика NTC (контроль температуры и дополнительный для дисплея). Два цифровых входа (свободный контакт) для дверного выключателя и настраиваемый параметром. Стандартный выход TTL позволяет пользователю подключать с помощью внешнего модуля TTL / RS485 совместимую с ModBUSRTU систему мониторинга

Контроллер Dixell XW260L

Контроллер Dixell XW260L Dixell XW260L Контроллер Dixell XW260L — для применения на средних или низкотемпературные холодильные установки. Cнабжен четырьмя релейными выходами для управления компрессором, процессом оттайки (электрической, горячий газ), вентилятором испарителя и светом. Три датчика NTC (температура объема,оттайкой и третья, опционная, для дисплея. Стандартный выход TTL позволяет пользователю подключать с помощью внешнего модуля TTL/RS485 модуль ModBUSRTU системы мониторинга

Контроллер Dixell XW263L

Контроллер Dixell XW263L Dixell XW263L Контроллер Dixell XW263L для управления средне- или низкотемпературных холодильных установок. Снабжен четырьмя релейными выходами для управления компрессором, оттайкой (электрический, горячий газ), вентилятором испарителя и светом. Два датчика NTC (объем, испаритель)

Dixell XW264L

Контроллер Dixell XW264L Dixell XW264L Контроллер Dixell XW264L являются микропроцессорными контроллерами для применения в средне- и низкотемпературных холодильных системах. У него есть 6 релейных выходов для управления компрессором, двумя оттайками (электронагреватель или горячим газом), вентиляторами испарителя, освещением или вкл/выкл. Так же есть три входа для датчиков NTC, один для термостатирования и два для контроля температуры окончания оттайки двух испарителей. Два цифровых входа (без напряжения) для контроля двери и конфигурируемый. TTL разъем позволяющий пользователю с помощью внешнего конвертора TTL/RS485 подключить контроллер к ModBUS-RTU совместимой с системой мониторинга Dixell, такой как XWEB300В/500/3000/5000 и для программирования с помощью “Hot Key”. Опционально XW-REP выход для удаленного дисплея, аналоговый выход 4÷20 мА для управления вентилятором испарителя или конденсатора и последовательный выход с RS485.

Dixell XW563L

Контроллер Dixell XW563L Dixell XW563L Контроллер Dixell XW563L является микропроцессорным контроллером, подходящим для применение на средне- или низкотемпературных холодильных установках. Снабжен четырьмя реле выходы для управления компрессором, оттайка (электричеством, горячим газом), вентиляторы испарителя и свет. Два датчика NTC (объем, испаритель). Два цифровых входа (свободный контакт) для дверного выключателя и настраивается по параметру. Выход RS485 позволяет пользователю подключать совместимый с ModBUS-RTU мониторинг система

Dixell XW570L

Контроллер Dixell XW570L Dixell XW570L Контроллер Dixell XW570L для применения на средне- или низкотемпературном холодильном оборудовании. Снабжен шестью релейными выходами для управления компрессором, оттайкой (электрическая, горячий газ), вентиляторами испарителя, лампочками, сигнализацией и вспомогательным выходом. Три датчика NTC (объем, испаритель и третий опционный для дисплея). Есть два цифровых входа (свободный контакт) для дверного выключателя и настраивается по параметру. Стандартный выход TTL позволяет пользователю подключать с помощью внешнего модуля TTL/RS485 модуль ModBUSRTU совместимая система мониторинга и запрограммировать список параметров с помощью “горячей клавиши». Выход для удаленного дисплея XW-REP, выход 4÷20 мА для управления вентиляторами испарителя или конденсатора и прямой последовательный выход RS485 доступен в качестве опции

Dixell XW30V

Контроллер Dixell XW30L-XW30V Dixell XW30V Контроллер Dixell модель XW30L, формат 38×185 мм, и модель XW30V, формат 100×64, основаны на микропроцессоре контроллеры подходят для применения на холодильных установках средней температуры. Три релейных выхода управляют компрессором, подсветкой и сигнализацией тревоги. Один датчик NTC или PTC. Есть 1 цифровой входами (свободный контакт) настраиваемый параметр

Dixell XC15CX-XC35CX

Контроллер Dixell XC15CX-XC35CX Dixell XC15CX-XC35CX Контроллер Dixell XC15CX-XC35CX являются контроллерами предназначенными для управления одно- и двухкомпрессорными агрегатами. Он может управлять простыми компрессорами, компрессорами с преобразователями частоты и компрессорами Digital. Контроллер имеет:
— 1 (ХС15СХ) или 2 (ХС35СХ) релейных выхода для управления компрессорами или вентиляторами или аварийной сигнализации;
— 1 тиристорный выход для управления скоростью вращения вентиляторов в режиме фазорезки (макс. ток 2.2 A) или соленоидным клапаном компрессора Digital;
— 1 аналоговый выход (0-10В или ШИМ) для управления ЕС-вентиляторами, преобразователями частоты или режима пропорционального повторителя;
— До 3-х цифровых входов без напряжения для мониторинга аварий;
— 2 аналоговых входа для ратиометрических датчиков давления (0-5В);
— До 4-х температурных датчиков NTC10k, NTC86k или PT1000.
XC15CX оснащён только одним реле 16 A, у ХС35СХ имеется также второе реле номиналом 5А. Все функции (исключая связанные со вторым реле) одинаковые для обоих приборов.

Dixell XC10CX-XC30CX

Контроллер Dixell XC10CX-XC30CX Dixell XC10CX-XC30CX Модель XC30CX, формат 32x74mm, представляет собой цифровой термостат для применения в конденсаторных установках. Это обеспечивает три цифровых (релейных) выхода, один для компрессора, а другой для управления вентиляторами. Два датчика NTC или ratiometric зонда, который нужно использовать на линии всасывания и конденсатора. Цифровые входы могут работать для управления безопасностью конденсаторного агрегата. Модель XC10CX отличается от XC30CX по номеру цифрового выхода. На самом деле, XC10CX имеет только один цифровой выход, который используется для управления компрессором.

Dixell XR20CX

Контроллер Dixell XR20CX Dixell XR20CX Контроллер Dixell XR20CX — цифровой термостат с оттайкой “off cycle”, предназначенный для применения в холодильных системах с нормальной температурой. Имеется релейный выход для управления компрессором. Он также снабжен 2 входами датчиков NTC или PTC, первый — для контроля температуры, второй, опциональный, подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Цифровой вход может работать как третий датчик температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к
сети, совместимой с ModBUS-RTU, такой как блоки мониторинга dIXEL семейства XWEB.

Dixell XR40CX

Контроллер Dixell XR40CX Dixell XR40CX Контроллер Dixell XR40CX — для применения в холодильных системах с нормальной и низкой температурой. Имеется два реле для управления компрессором и оттайкой (электрическая, горячим газом). Он также снабжен 3 входами датчиков NTC или PTC, первый — для контроля температуры объема, второй — испарителя, третий — опционально может быть подключен через HOT KEY для подачи сигнала тревоги температуры конденсатора или для отображения температуры. Цифровой вход может работать как четвертый температурный зонд.

Dixell XR60CX

Контроллер Dixell XR60CX Dixell XR60CX Контроллер Dixell XR60CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. Три релейных выхода для управления компрессором, вентилятором, оттайкой (электрическая, горячий газ). Он также снабжен тремя входами датчиков NTC или PTC, первый температуры объема, второй на испарителе для контроля температуры окончания оттайки и управления вентилятором, третий датчик, опциональный, подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Цифровой вход может работать как четвертый датчик температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к сети, совместимой с ModBUS-RTU, такой как блоки мониторинга dIXEL семейства XWEB.

Dixell XR70CX

Контроллер Dixell XR70CX Dixell XR70CX Контроллер Dixell XR70CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. Четыре релейных выхода для управления компрессором, вентилятором и оттайкой (электрическая, горячий газ). Последнее реле может использоваться для освещения, для сигнала аварии или как дополнительный выход. Он также снабжен четырьмя входами датчиков NTC или PTC, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором. Цифровой вход может работать в качестве третьего датчика температуры. Четвертый датчик, подключаемый к разъему HOT KEY, используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Выход HOT KEY позволяет подключить контроллер с помощью внешнего модуля XJ485-CX к сети.

Dixell XR64CX

Контроллер Dixell XR64CX Dixell XR64CX Контроллер Dixell XR64CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией и 2мя
испарителями. У него есть четыре релейных выхода для управления компрессором, вентилятором, оттайкой 1 и 2, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Он также снабжен до четырех входов датчиков NTC или PTC, первый — для контроля температуры, второй и третий, расположенные на испарителе, для контроля температуры окончания оттайки и управления вентилятором. Четвертый датчик подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к сети.

Dixell XR75CX

Контроллер Dixell XR75CX Dixell XR75CX Контроллер Dixell XR75CX — для применения в средне- или низкотемпературных блоках охлаждения с вентиляцией. Четыре релейных выхода для управления компрессором, вентилятором, оттайкой (электрическая, горячий газ) и освещением. Он может снабжаться Часами Реального Времени, которые позволяют запрограммировать до 6 циклов оттайки ежедневно, с разделением на выходные и рабочие дни. Функция “День и Ночь” с двумя разными уставками подходит для энергосбережения. Он также снабжен четырьмя входами датчиков NTC или PT1000, первый — для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором. Один из 2 цифровых входов может работать в качестве третьего датчика температуры. Четвертый датчик используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Последовательный выход RS485 позволяет подключить контроллер к сети, совместимой с ModBUS-RTU.

Dixell XC645CX

Контроллер Dixell XC645CX Dixell XC645CX Контроллер Dixell XC645CX — для управления компрессорами и вентиляторами конденсатора, работающими в составе агрегата.
В составе агрегата один компрессор всегда – Digital (спиральный или поршневой), остальные могут быть как спиральными, так и поршневыми с регулировкой производительности или без неё. Управление компрессорами осуществляется по алгоритму с «нейтральной зоной» и основано на считывании величины давления или температуры в контурах всасывания (низкое давление — компрессоры) и нагнетания (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки нагрузок. Управление вентиляторами – пропорциональное. Контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры.

Dixell XC650CX

Контроллер Dixell XC650CX Dixell XC650CX Контроллер Dixell XC650CX — для управления компрессорами и вентиляторами конденсатора, работающими в составе агрегата.
Компрессоры могут быть спиральными, поршневыми, с регулировкой производительности, в том числе при помощи преобразователя частоты. Контроллер может управлять двумя контурами всасывания с общим контуром конденсации. Управление компрессорами осуществляется по алгоритму с «нейтральной зоной» и основано на считывании величины давления или температуры в контурах всасывания (низкое давление — компрессоры) и нагнетания (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки нагрузок. Управление вентиляторами – пропорциональное. Данный контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры.

Dixell XC660D

Контроллер Dixell XC660D Dixell XC660D Контроллер Dixell XC660D — для управления компрессорами и вентиляторами конденсатора, работающими в составе агрегата.
Компрессоры могут быть спиральными, поршневыми, с регулировкой производительности. Управление компрессорами осуществляется по алгоритму с «нейтральной зоной» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) и нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки нагрузок. Управление вентиляторами – пропорциональное. Данный контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры.

Dixell XC1000D

Контроллер Dixell XC1000D Dixell XC1000D Контроллер Dixell XC1000D — для управления систем контуров охлаждения (до 2 контуров всасывания и 2 контуров конденсации). Благодаря специальным алгоритмам эти контроллеры могут управлять и контролировать установки с CO2, которые работают по каскадному принципу с субкритическим циклом.

Dixell XC807-911M

Контроллер Dixell XC807-911M Dixell XC807-911M Контроллер Dixell серии XC800M и XC900M управляет компрессорами и вентиляторами в системах конденсации.
Компрессора могут быть простыми, многоступенчатыми или с разными мощностями. Управление осуществляется при помощи нейтральной зоны или пропорционального регулирования и основано на давлении или температуре определяемой в зоне низкого давления (компрессоры) и высокого давления (конденсаторы).

Dixell XRi77CX

Контроллер Dixell XRi77CX Dixell XRi77CX Контроллер Dixell XRi77CX — предназначен для применения на средне- или низкотемпературных вентилируемых холодильных установок. Имеет четыре релейных выхода для управления компрессором, вентилятором, оттайкой (электрическая, горячим газом). Снабжен четырьмя входами датчика NTC. Первый зонд для контроля температуры объема. Второй зонд для контроля температуры испарителя. Один из двух цифровых входов может работать как третий температурный зонд. Четвертый зонд используется для контроля температуры конденсатора (для управления сигнализацией конденсатора) или для отображения температуры.

Dixell XWi70K

Контроллер Dixell XWi70K Dixell XWi70K Контроллер Dixell XWi70K предназначен для применения на средне- и низко- температурных холодильных установках. Пять
релейных выходов для управления компрессором, оттайкой (электрическая, горячий газ), испарителем и конденсаторными вентиляторами, светом или сигнализация. Четыре датчика NTC (PTC). Он имеет как частотный выход, так и последовательный порт, который может использоваться для управления переменной скоростью компрессоров. Пара аналоговых выходов (4-20мА или 0-10В) и главный 2-проводный выход RS485

Dixell XEV11D_12D

Контроллер Dixell XEV11D-12D Dixell XEV11D_12D Контроллер Dixell XEV11D-12D — для управления импульсными (ВКЛ/ВЫКЛ) электронными расширительными вентилями. Этот модуль позволяет регулировать перегрев (SH) текучей среды, которая протекает в холодильной системе, с тем чтобы достичь оптимальной производительности и функционирования испарителя независимо от климатических условий или нагрузки. Модули XEV12D оборудованы двумя входами датчиков, один – для датчика давления с интерфейсом 4÷20мА или 0÷5В, а другой – для датчика температуры Pt1000 или NTC. Подключение в локальную сеть LAN позволяет передавать сигнал давления на другие модули XEV, чтобы использовать только один датчик давления в системах с составными шкафами. Имеется также два конфигурируемых цифровых входа, один из них должен быть сконфигурирован для получения запроса охлаждения. Другой цифровой вход может использоваться для оповещения контроллера о том, что идет оттайка. Дисплей с иконками предоставляет удобную визуализацию перегрева (SH), процент времени открытия вентиля или значений датчиков, встроенная клавиатура позволяет программировать контроллер без каких-либо других устройств. Завершая комплектацию контроллера, последовательная сеть RS485.

Dixell XEV22D

Контроллер Dixell XEV22D Dixell XEV22D Контроллер Dixell XEV22D — для управления шаговыми электронными расширительными клапанами. XEV22D позволяет регулировать перегрев (SH) хладагента в испарителе для достижения оптимальной производительности и функционирования испарителя независимо от климатических условий или нагрузки. XEV22D имеет два входа датчиков, один – для датчика давления с интерфейсом 4÷20мА или 0÷5В, а другой – для датчика температуры Pt1000 или NTC-EU / NTC-US. LAN связь позволяет передавать сигнал от одного датчика давления на несколько приборов. Имеется также два конфигурируемых цифровых входа, один – сухой контакт, второй — свободный от напряжения. С дисплея можно просмотреть значение перегрева (SH), степень открытия клапана или показания датчиков, клавиатура позволяет программировать контроллер без каких-либо других
устройств. К системам мониторинга и диспетчеризации XEV22D подключатся с помощью встроенной сетевой карты RS485.

Dixell IEV22D-IEV24D

Контроллер Dixell IEV22D-IEV24D Dixell IEV22D-IEV24D Контроллер Dixell IEV22D-IEV24D — предназначен для управления одним или двумя шаговыми двигателями электронного расширительного клапана. Доступны два различных режима регулирования: * Автономный режим: цифровые входы используются для запуска управления перегревом. Давление кипения датчик и датчик температуры всасывания должны быть соединены с контроллером; * LAN: IEV можно подключить к серии Ichill 200 EVO для того чтобы контролировать перегрев. Для обеспечения наилучшего регулирования рекомендуется подключать датчик давления всасывания непосредственно к контроллеру.
Основные характеристики: * управление одним или двумя электронными расширительными клапанами; * совместимость с несколькими моделями клапанов; * совместимость с различными типами хладагентов; * ручное управление ПИД-регулировкой или адаптивным регулированием.

Dixell_XW10L

Контроллер Dixell_XW10L Контроллер Dixell_XW10L Контроллер Dixell XW10L, формат 38×185 мм, и модель XW10V, формат 100×64, представляют собой микропроцессорные
контроллеры, подходящие для применения в области охлаждения или отопления. Снабжены 2 релейными
выходами, один из которых предназначен для регулирования, а другой — для освещения. Они также снабжены 1
входом датчика NTC или PTC для контроля температуры. Имеется 1 цифровой вход (свободный контакт), настраиваемый по параметру. Вывод позволяет пользователю запрограммировать список параметров с помощью горячей клавиши.

Dixell Wing XW10L-V

Контроллер Dixell Wing XW10L-V Контроллер Dixell Wing XW10L-V

Dixell XH260L-V

Контроллер Dixell XH260L-V Dixell XH260L-V Контроллер Dixell XH260L и XH260V применяются в холодильных установках средней или низкой температуры. Контролируют как влажность, так и температуру. Имеют 6 выходных реле для управления компрессором, нагревательными элементами, размораживанием, осушителем воздуха и увлажнителем воздуха. 2 датчика NTC: объем и испаритель. Вход 4÷20 мА для измерения влажности. Имеется один цифровой вход (свободный контакт), настраиваемый по параметру. Вывод позволяет пользователю запрограммировать список параметров с помощью “Hot Key”.

Dixell XB570L

Контроллер Dixell XB570L Dixell XB570L Контроллер Dixell серии XB созданы для быстрого охлаждения или заморозки продуктов в соответствии с международными стандартами пищевой безопасности.

Понравилась статья? Поделить с друзьями:
  • Optalgin инструкция по применению на русском
  • Yandex руководство компании
  • Omron m2 basic intellisense инструкция на русском
  • Как почистить телефон от вирусов самому бесплатно пошаговая инструкция самсунг
  • Феназепам диспергируемые в полости рта инструкция по применению