Добро пожаловать на сайт Schneider Electric
Добро пожаловать на наш сайт.
MiCOM P139 Feeder Management and Bay Control, SW Version -654, Manual (global file) P139/EN M/R-53-B, P139 -315 -423/424/425 -654
Дата : 11/04/2023
Тип : Руководство пользователя
Языки : Английский
prm-latest Версия : 1.1
Обозначение документа : P139_EN_M_R-53__315_654
Дата : 11/04/2023
Тип : Руководство пользователя
Языки : Английский
prm-latest Версия : 1.1
Обозначение документа : P139_EN_M_R-53__315_654
Заголовок документа
Дата
Версия
Языки
Нужна помощь?
1 MiCOM p139 Feeder Management and Bay Control Version: -304/306/307 -405/406/407/408/409/410/411/412/413 -605/611/612 Technical Manual Volume 2 of 2 p139 /EN M/A88 Contains:V605 p139 /EN M/B33 ( ) V611 p139 /EN AD/A77 ( )V612 p139 /EN AD/A88 ( D) MiCOM p139 Feeder Management and Bay Control Version 304 405/406/407 -605 Technical Manual Volume 2 of 2 p139 /EN M/B33 ( D) ! Warning When electrical equipment is in operation, dangerous voltage will be present in certain parts of the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger personnel and equipment and cause personal injury or physical damage. Before working in the terminal strip area, the device must be isolated.
2 Where stranded conductors are used, wire end ferrules must be employed. Proper and safe operation of this device depends on appropriate shipping and handling, proper storage, installation and commissioning, and on careful operation, maintenance and servicing. For this reason only qualified personnel may work on or operate this device. Any modifications to this device must be in accordance with the manual. If any other modification is made without the express permission of AREVA T&D, it will invalidate the warranty, and may render the product unsafe. Qualified Personnel are individuals who ! are familiar with the installation, commissioning, and operation of the device and of the system to which it is being connected; !
3 Are able to perform switching operations in accordance with safety engineering standards and are authorized to energize and de-energize equipment and to isolate, ground, and label it; ! are trained in the care and use of safety apparatus in accordance with safety engineering standards; ! are trained in emergency procedures (first aid). Note The operating manual for this device gives instructions for its installation, commissioning, and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate AREVA technical sales office and request the necessary information.
4 Any agreements, commitments, and legal relationships and any obligations on the part of AREVA, including settlement of warranties, result solely from the applicable purchase contract, which is not affected by the contents of the operating manual. Appendix p139 -304-405/-406/-407-605 // / p139 /EN M/B33 AP-1 A Glossary B List of Signals C List of Bay Types D Terminal Connection Diagrams E Address Lists (Available as a PDF file only. Not included in the printed manual.) F Upgrade Documentation Appendix (continued) AP-2 p139 -304-405/-406/-407-605 // / p139 /EN M/B33 A Glossary A-1A 1 Function Groups A-1A 2 Modules A-2A 3 Symbols A-3A 4 Examples of Signal Names A-10A 5 Symbols Used A-11B List of Signals B-1B 1 Internal Signal Names B-1B 2 Telecontrol Interface per EN 60870-5-101 or IEC 870-5-101 (Companion Standard) B-6B Interoperability B-6B Network Configuration (Network-Specific Parameters) B-6B Physical Layer (Network-Specific Parameters) B-7B Link Layer (Network-Specific Parameters)
5 B-8B Application Layer B-9B Basic Application Functions B-15B 3 Communication Interface per IEC 60870-5-103 B-18B Interoperability B-18B Physical Layer B-18B Electrical Interface B-18B Optical Interface B-18B Transmission Rate B-18B Link Layer B-19B Application Layer B-19B Transmission Mode for Application Data B-19B Common Address of ASDU B-19B Selection of Standard Information Numbers in Monitor Direction B-19B System Functions in Monitor Direction B-19B Status Indications in Monitor Direction B-20B Monitoring Signals (Supervision Indications) in Monitor Direction B-21B Earth Fault Indications in Monitor Direction B-22B Fault Indications in Monitor Direction B-23B Auto-Reclosure Indications in Monitor Direction B-25B Measurands in Monitor Direction B-25B Generic Functions in Monitor Direction B-26B Selection of Standard Information Numbers in Control Direction B-27B System Functions in Control Direction B-27B General Commands in Control Direction B-27B Generic Functions in Control Direction B-28B Basic Application Functions B-29B Miscellaneous B-29 Appendix (continued)
6 p139 -304-405/-406/-407-605 // / p139 /EN M/B33 AP-3 C List of Bay Types C-1 D 1 Terminal Connection Diagrams D-1 D D D D Case 40 T Case 84 T NCIT Module Connection RTD Module for PT 100, Ni 100 or Ni 120 D-1 D-13 D-19 D-20 E Address List E-1 E 1 Parameters E-3 E Device Identification E-3 E Configuration Parameters E-14 E Function Parameters E-94 E Global E-94 E General Functions E-102 E Parameter Subsets E-182 E Control E-202 E 2 Operation E-226 E Cyclic Values E-226 E Measured Operating Data E-226 E Physical State Signals E-236 E Logic State Signals E-261 E Control and Testing E-330 E Operating Data Recording E-335 E 3 Events E-336 E Event Counters E-336 E Measured Fault Data E-339 E Fault Data Acquisition E-343 E 4 Selection Tables E-345 E Selection Table ‘Binary Outputs und LEDs’ E-345 E Selection Table ‘Binary Inputs’
7 E-355 E Selection Table K1 E-358 E Selection Table K2 E-359 E Selection Table K4 E-361 E Selection Table K5 E-362 E Selection Table K6 E-364 E Selection Table K7 E-366 E Selection Table K8 E-367 E Selection Table K9 E-368 E Selection Table K10 E-368 E Selection Table K11 E-369 E Selection Table K13 E-370 E Selection Table K15 E-370 E Selection Table K16 E-371 E Selection Table K17 E-374 E Selection Table K18 E-374 E Selection Table K19 E-375 E Selection Table K20 E-376 E Selection Table K22 E-377 E Selection Table K23 E-379 E Selection Table K24 E-379 E Selection Table K25 E-379 E Selection Table K30 E-379 Appendix (continued) AP-4 p139 -304-405/-406/-407-605 // / p139 /EN M/B33 E Selection Table K99 E-380 E Selection Table K101 E-388 E Selection Table K102 E-393 E Selection Table K103 E-409 E Selection Table K104 E-413 E Selection Table F 497 E-442 E Selection Table F 571 E-443 E Selection Table F 670 E-443 E Selection Table F 729 E-444 E Selection Table F 730 E-444 E Selection Table F 738 E-445 E Selection Table F 756 E-446 E Selection Table F 798 E-447 E 5 Possible Entries into Memory E-449 E Fault Memory E-449 E Ground
8 Fault Memory E-456 E Overload Memory E-458 E Operating Data Memory E-461 E Monitoring Signal Memory E-467 F Upgrade Documentation F-1 Appendix A — Glossary p139 -304-405/-406/-407-605 // / p139 /EN M/B33 A-1 A 1 Function Groups ARC: Auto-reclosing control ASC: Automatic synchronism check CBF: Circuit breaker failure protection CMD_1: Signale pole commands COMM1: Logic Communication Interface 1 COMM2: Logic Communication Interface 2 COMM3: Logic Communication Interface 3 COUNT: Binary counts DEV01: to DEV10: Device 01 to Device 10 DTOC: Definite-time overcurrent protection DVICE: Device FT_DA: Fault data acquisition FT_RC: Fault recording f<>: Frequency protection GF_DA: Ground fault data acquisition GF_RC: Ground fault recording GFDSS: Ground fault direction determination using steady-state values I2>: Unbalance protection IDMT: Inverse-time overcurrent protection ILOCK: Interlocking logic INP: Binary input IRIGB: IRIG-B clock synchronisation LED: LED indicators LIMIT: Limit monitoring LOC: Local control panel LOGIC.
9 Logic MAIN: Main function MCMON: Measuring-circuit monitoring MEASI: Measured data input MEASO: Measured data output MP: Motor protection MT_RC: Monitoring signal recording OL_DA: Overload data acquisition OL_RC: Overload recording OP_RC: Operating data recording OUTP: Binary and analog output P<>: Power directional protection PC: PC link PSIG: Protective signaling PSS: Parameter subset selection SCDD: Short-circuit direction determination SFMON: Self-monitoring SIG_1: Signale pole signals SOTF: Switch on to fault protection TGFD: Transient ground fault direction determination THERM: Thermal overload protection V<>: Time-voltage protection Appendix A — Glossary (continued) A-2 p139 -304-405/-406/-407-605 // / p139 /EN M/B33 A 2 Modules A: Communication module B: Bus module L: Local control module P.
10 Processor module T: Transformer module V: Power supply module X: Binary I/O module Y: Analog I/O module Appendix A — Glossary (continued) p139 -304-405/-406/-407-605 // / p139 /EN M/B33 A-3 A 3 Symbols Graphic symbols for block diagrams Binary elements according to DIN 40900 Part 12, September 1992, IEC 617-12: amended 1991 Analog information processing according to DIN 40900 Part 13, January 1981 To document the linking of analog and binary signals, additional symbols have been used, taken from several DIN documents. As a rule, direction of the signal flow is from left to right and from top to bottom.
-
MiCOM P139
Feeder Management and Bay Control
P139/EN M/Ana
Version P139 -307 -411/412/413 -614 P139 -308 -414/415/416 -630
P139 -308 -414/415/416 -615 P139 -308 -414/415/416 -616 P139 -309
-414/415/416 -631 P139 -308 -414/415/416 -617 P139 -309
-414/415/416 -632 P139 -308 -414/415/416 -618 P139 -309
-414/415/416 -633Technical Manual Content P139/EN M/Ea8 (-614) P139/EN AD/Bk9
(-630) P139/EN AD/Ab9 (-615) P139/EN AD/Ac9 (-616) P139/EN AD/Bka
(-631) P139/EN AD/Ad9 (-617) P139/EN AD/Ama (-632) P139/EN AD/Ae9
(-618) P139/EN AD/Ana (-633)Volume 2 of 2
-
MiCOM P139
Feeder Management and Bay Control
P139/EN M/Ea8 (AFSV.12.10172 D) Version P139 -307 -411/412/413
-614Technical Manual Volume 2 of 2
-
Appendix
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
AN-1A Glossary
B Signal List
C List of Bay Types
D Overview of Changes
Terminal Connection Diagrams: See Volume 1, Chapter 5
Installation and Connection. -
Appendix (continued)
AN-2 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614A Glossary A-1A1 Function Groups A-1A2 Modules A-2A3 Symbols
A-3A4 Examples of Signal Names A-10A5 Symbols used A-11B List of Signals B-1B 1 Internal Signal Names B-1B 2
Telecontrol Interface per EN 60870-5-101 orIEC 870-5-101 (Companion Standard) B-6
B 2.1 Interoperability B-6B 2.1.1 Network Configuration
(Network-Specific Parameters) B-6B 2.1.2 Physical Layer
(Network-Specific Parameters) B-7B 2.1.3 Link Layer
(Network-Specific Parameters) B-8B 2.1.4 Application Layer B-19B
2.1.5 Basic Application Functions B-15B 3 Communication Interface per IEC 60870-5-103 B-18B 3.1
Interoperability B-18B 3.1.1 Physical Layer B-18B 3.1.1.1
Electrical Interface B-18B 3.1.1.2 Optical Interface B-18B 3.1.1.3
Transmission Rate B-18B 3.1.2 Link Layer B-19B 3.1.3 Application
Layer B-19B 3.1.3.1 Transmission Mode for Application Data B-19B
3.1.3.2 Common Address of ASDU B-19B 3.1.3.3 Selection of Standard
Information Numbers in MonitorDirection B-19
B 3.1.3.3.1 System Functions in Monitor Direction B-19B
3.1.3.3.2 Status Indications in Monitor Direction B-20B 3.1.3.3.3
Monitoring Signals (Supervision Indications) in MonitorDirection B-21
B 3.1.3.3.4 Earth Fault Indications in Monitor Direction B-22B
3.1.3.3.5 Fault Indications in Monitor Direction B-23B 3.1.3.3.6
Auto-Reclosure Indications in Monitor Direction B-25B 3.1.3.3.7
Measurands in Monitor Direction B-25B 3.1.3.3.8 Generic Functions
in Monitor Direction B-26B 3.1.3.4 Selection of Standard
Information Numbers in ControlDirection B-27
B 3.1.3.4.1 System Functions in Control Direction B-27B
3.1.3.4.2 General Commands in Control Direction B-27B 3.1.3.4.3
Generic Functions in Control Direction B-28B 3.1.3.5 Basic
Application Functions B-29B 3.1.3.6 Miscellaneous B-29C List of Bay Types C-1
D Overview of Changes D-1
-
Appendix A — Glossary
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
A-1A 1 Function Groups
ARC: Auto-reclosing control ASC: Automatic synchronism check
CBF: Circuit breaker failure protection CBM: Circuit Breaker
Monitoring CMD_1: Single-pole commands COMM1: Communication
interface 1 COMM2: Communication interface 2 COMM3: Communication
interface 3 COUNT: Binary counts DEV01: to DEV10: External device
01 to External device 10 DTOC: Definite-time overcurrent protection
DVICE: Device f: Over-/underfrequency protection FT_DA: Fault data
acquisition FT_RC: Fault recording GF_DA: Ground fault data
acquisition GF_RC: Ground fault recording GFDSS: Ground fault
direction determination usingsteady-state values GOOSE: Generic Object Oriented Substation
Event GSSE: IEC Generic Substation Status Events I2>: Unbalance
protection IDMT1:, IDMT2: Inverse-time overcurrent protection IEC:
IEC 61850 Communication ILOCK: Interlocking logic INP: Binary input
IRIGB: IRIG-B interface LED: LED indicators LIMIT: Limit value
monitoring LOC: Local control panel LOGIC: Logic MAIN: Main
function MCMON: Measuring-circuit monitoring MEASI: Measured data
input MEASO: Measured data output MP: Motor protection MT_RC:
Monitoring signal recording OL_DA: Overload data acquisition OL_RC:
Overload recording OP_RC: Operating data recording OUTP: Binary
outputs P: Power directional protection PC: PC link PSIG:
Protective signaling PSS: Parameter subset selection SCDD:
Short-circuit direction determination SFMON: Self-monitoring SIG_1:
Single-pole signals SOTF: Switch on to fault protection TGFD:
Transient ground fault direction determination THERM: Thermal
overload protection V: Time-voltage protection -
Appendix A — Glossary (continued)
A-2 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614A 2 Modules
A: Communication module B: Bus module L: Local control module P:
Processor module T: Transformer module V: Power supply module X:
Binary I/O module Y: Analog I/O module -
Appendix A — Glossary (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
A-3A 3 Symbols
Graphic symbols for block diagrams Binary elements according to
DIN 40900 Part 12, September 1992, IEC 617-12: amended 1991 Analog
information processing according to DIN 40900 Part 13, January 1981
To document the linking of analog and binary signals, additional
symbols have been used, taken from several DIN documents. As a
rule, direction of the signal flow is from left to right and from
top to bottom. Other flow directions are marked by an arrow. Input
signals are listed on the left side of the signal flow, output
signals on the right side.Symbol Description
=
To obtain more space for representing a group of related
elements, contours of the elements may be joined or cascaded if the
following rules are met: There is no functional linkage between
elements whose common contour line is oriented in the signal flow
direction. Note: This rule does not necessarily apply to
configurations with two or more signal flow directions, such as for
symbols with a control block and an output block. There exists at
least one logical link between elements whose common contour line
runs perpendicularly to the signal flow direction.Components of a symbol A symbol consists of a contour or contour
combination and one or more qualifiers. -
Appendix A — Glossary (continued)
A-4 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Symbol Description
Control block A control block contains an input function common
to several symbols. It is used for the collective setting of
several trigger elements, for example.Output block An output block contains an output function common
to several symbols.MAIN: Inom Device
[ 010 003 ]
D5Z08X5B
Settable control block The 6 digits in square brackets represent
the address under which the function shown in the text is
implemented.MAIN: Inom Device
[ 010 003 ]
1.0
1.0: 1.0 A 5.0: 5.0 A
5.0
D5Z08X6B
Settable control block with function blocks The digits in the
function block show the settings that are possible for this
function. The text below the symbol assigns the corresponding unit
or meaning to each setting. -
Appendix A — Glossary (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
A-5Symbol Description
Static input Only the state of the binary input variable is
effective.Dynamic input Only the transition from value 0 to value 1 is
effective.Negation of an output The value up to the border line is negated
at the output.Negation of an input The input value is negated before the
border line.Dynamic input with negation Only the transition from value 1 to
value 0 is effective.AND element The output variable will be 1 only if all input
variables are 1.OR element The output variable will be 1 only if at least one
input variable is 1.Threshold element The output variable will be 1 only if at least
two input variables are 1. The number in the symbol may be replaced
by any other number.(m out of n) element The output variable will be 1 only if just
one input variable is 1. The number in the symbol may be replaced
by any other number if the number of inputs is increased or
decreased accordingly. -
Appendix A — Glossary (continued)
A-6 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Symbol Description
Delay element The transition from value 0 to 1 at the output
occurs after a time delay of t1 relative to the corresponding
transition at the input. The transition from value 1 to 0 at the
output occurs after a time delay of t2 relative to the
corresponding transition at the input. t1 and t2 may be replaced by
the actual delay values (in seconds or strobe ticks).Monostable flip-flop The output variable will be 1 only if the
input variable changes to 1. The output variable will remain 1 for
100 ms, independent of the duration of the input value 1
(non-retriggerable). Without a 1 in the function block the
monostable flip-flop is retriggerable. The time is 100 ms in this
example, but it may be changed to any other duration.Analog-digital converter An analog input signal is converted to
a binary signal.Subtractor The output variable is the difference between the two
input variables. A summing element is obtained by changing the
minus sign to a plus sign at the symbol input.Schmitt Trigger with binary output signal The binary output
variable will be 1 if the input signal exceeds a specific
threshold. The output variable remains 1 until the input signal
drops below the threshold again.Memory, general Storage of a binary or analog signal.
-
Appendix A — Glossary (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
A-7Symbol Description
Non-stable flip-flop When the input variable changes to 1, a
pulse sequence is generated at the output. The ! to the left of the
G indicates that the pulse sequence starts with the input variable
transition (synchronized start). If there is a ! to the right of
the G, the pulse sequence ends with the ending of the 1 signal at
the input (synchronized stop).Amplifier The output variable is 1 only if the input variable is
also 1.Band pass filter The output only transmits the 50 Hz component
of the input signals. All other frequencies (above and below 50 Hz)
are attenuated.Counter At the + input the input variable transitions from 0 to
1 are counted and stored in the function block. At the R(eset)
input a transition of the input variable from 0 to 1 resets the
counter to 0.Electromechanical drive in general, here a relay, for
example.Signal level converter with electrical isolation between input
and output. L+ = pos. voltage input L- = neg. voltage input U1 =
device identifier -
Appendix A — Glossary (continued)
A-8 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Symbol Description
Input transformer with phase and item identifiers (according to
DIN EN 60445) Phase identifiers for current inputs: for A: A1 and
A2 for B: B1 and B2 for C: C1 and C2 for N: N1 and N2 Phase
identifiers for voltage inputs via transformer 1: for A: 1U for B:
1V for C: 1W for N: 1N via transformer 2: for A: 2U for B: 2V Item
identifiers for current transformers: for A: T1 for B: T2 for C: T3
for N: T4 for voltage transformer 1: for A: T5 for B: T6 for C: T7
for N: T8 for VG-N transformer: T90 for voltage transformer 2: for
A: T15Change-over contact with item identifier
Special symbol Output relay in normally-energized arrangement
(closed-circuit operation). -
Appendix A — Glossary (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
A-9Symbol Description
PC interface with pin connections
Multiplier The output variable is the result of the
multiplication of the two input variables.Divider The output variable is the result of the division of the
two input variables.Comparator The output variable becomes 1 only if the input
variable(s) are equal to the function in the function block.Formula block The output variable becomes 1 only if the input
variable(s) satisfy the equation in the function block -
Appendix A — Glossary (continued)
A-10 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614A 4 Examples of Signal Names
All settings and signals relevant for protection are shown in
the block diagrams of Chapter 3 as follows:Signal Name Description
FT_RC: Fault recording n 305 100
Internal signal names are not coded by a data model address. In
the block diagrams they are marked with a diamond. The small figure
underneath the signal name represents a code that is irrelevant to
the user. The internal signal names used and their origins are
listed in Appendix B.DIST: VNG>> triggered [ 036 015 ]
Signal names coded by a data model address are represented by
their address (shown in square brackets). Their origin is given in
Chapters 7 and 8.MAIN: General reset [ 003 002 ]
1: Execute
A specific setting to be used later on is shown with its signal
name, address, and the setting preceded by the setting arrow. -
Appendix A — Glossary (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
A-11A 5 Symbols Used
Symbol Meaning
t Time duration
V Voltage, potential difference
V Complex voltage
I Electrical current
I Complex current
Z Complex impedance
Z Modulus of complex impedance
f Frequency
Temperature in C
Sum, result
Unit of electrical resistance
Angle
Phase angle. With subscripts: specific angle between a defined
current and a defined voltage.Time constant
T Temperature difference in K
-
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
A-12 -
Appendix B — List of signals
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
B-1B 1 Internal Signal Names
Internal signal names are not coded by an external address. In
the block diagrams they are marked with a diamond.Internal Signal Names Figure
ARC: Block/reset HSR 3-168
ARC: Block/reset TDR 3-168
ARC: Close request 3-170
ARC: HSR not permitted 3-170
ARC: HSR trip t. elapsed 3-162, 3-164, 3-165 3-166, 3-167
ARC: Starting GFDSS 3-165
ARC: TDR not permitted 3-170
ARC: TDR trip t. elapsed 3-163, 3-164, 3-165, 3-166, 3-167
ASC: AC active for DEV01 3-185
ASC: Active 3-178
ASC: Clos.rej. w. block 3-178
ASC: Close enable DEV01 AC 3-185
ASC: Close enable w. block 3-178
ASC: Gen. close request 3-179
ASC: Manual close request 3-179
ASC: Sel. meas. loop PG 3-176
ASC: Test 3-179
ASC: VMeas 3-176
CBM: Internal trip cmd. 3-267
COMM1: Communication error 3-11, 3-12, 3-13, 3-14, 3-15,
3-16COMM1: Debounced signal 3-43
COMM1: Selected protocol 3-10
DEV01: Close cmd. rejection 3-298
DEV01: Close request 3-297
DEV01: Enable BI Close 3-299
DEV01: Enable BI Open 3-299
DEV01: Enable SI Close 3-298
DEV01: Enable SI Open 3-298
DEV01: End close command 3-302
DEV01: End open command 3-302
DEV01: Latching time elaps. 3-297
DEV01: Latching time runn. 3-297
-
Appendix B — List of signals (continued)
B-2 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Internal Signal Names Figure
DEV01: Open cmd. rejection 3-298
DEV01: Open request 3-297
DEV01: Protect. close cmd. 3-300
DEV01: Protection trip cmd. 3-300
DEV01: Start runn.time mon. 3-305
DEV01: Switch. device runn. 3-302
DTOC: IN 3-122
DTOC: Pulse prolong. runn. 3-125
DTOC: Starting A 3-118
DTOC: Starting B 3-118
DTOC: Starting C 3-118
DTOC: Starting N 3-123
DTOC: t2 N 3-125
f: fMeas 3-238
f: No. periods reached 3-238
f: VMeas 3-237
FT_DA: IA-kG 3-109
FT_DA: IB-kG 3-109
FT_DA: IC-kG 3-109
FT_DA: IkG 3-109
FT_DA: Output fault locat. 3-108
FT_DA: Output meas. values 3-108
GFDSS: Direction BS 3-190, 3-196
GFDSS: Direction LS 3-190, 3-196
GFDSS: IN filtered 3-194
GFDSS: IN> triggered 3-194
GFDSS: Op. delay IN elapsed 3-194
GFDSS: Oper.delay Y(N)> elaps 3-200
GFDSS: P 3-190, 3-196
GFDSS: Q 3-190, 3-196
GFDSS: VNG 3-189
GFDSS: VNG filtered 3-190, 3-196
GFDSS: VNG> triggered 3-190
-
Appendix B — List of signals (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
B-3Internal Signal Names Figure
IDMT: IN 3-137
IDMT: Starting A 3-133
IDMT: Starting B 3-133
IDMT: Starting C 3-133
IDMT1: ARC Starting Iref,N> 3-139
IDMT1: ARC Starting Iref,P> 3-134
LOC: Remote & Local 3-8
LOC: Return time select act. 3-2
MAIN: Block start. signal 3-73
MAIN: Block tim.st. IN,neg 3-73
MAIN: Block. 1 sel.functions 3-66
MAIN: Block. 2 sel.functions 3-66
MAIN: Customized bay type 3-46
MAIN: Direct motor control 3-46
MAIN: End command 3-305
MAIN: General starting int. 3-74
MAIN: Imeas 3-110
MAIN: Inrush stabil. trigg 3-64
MAIN: Internal CB open EXT 3-268
MAIN: Protection active 3-61
MAIN: Reset LED 3-85
MAIN: Sel. meas. loop A-B 3-110
MAIN: Sel. meas. loop A-G 3-110
MAIN: Sel. meas. loop B-C 3-110
MAIN: Sel. meas. loop B-G 3-110
MAIN: Sel. meas. loop C-A 3-110
MAIN: Sel. meas. loop C-G 3-110
MAIN: Sel. meas. loop PG 3-110
MAIN: Sel. meas. loop PP 3-110
MAIN: Start. I>,kIref,P> 3-74
MAIN: Starting A int. 3-73
MAIN: Starting B int. 3-73
MAIN: Starting C int. 3-73
MAIN: Starting Ineg 3-73
MAIN: Starting N int. 3-73
-
Appendix B — List of signals (continued)
B-4 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Internal Signal Names Figure
MAIN: Time tag 3-84
MAIN: Vmeas 3-110
MEASO: Enable 3-36
MEASO: Reset meas.val.outp. 3-37
MP: Block. replica THERM 3-215
MP: IP,max r.m.s./Iref 3-210
MP: IStUp> 3-215
MP: Machine stopped 3-215
MP: St. kP*Iref>/Istup> 3-210
P: P 3-242
P: P- 3-242
P: P+ 3-242
P: Q 3-242
P: Q- 3-242
P: Q+ 3-242
SCDD: VNG 3-148a
SCDD: Block. direct. tI> 3-146
SCDD: Block. direct. tI>> 3-146
SCDD: Block. direct. tIN> 3-150
SCDD: Block. direct. tIN>> 3-150
SCDD: Block. direct. tIref,N> 3-150
SCDD: Block. direct. tIref,P> 3-146
SCDD: Determin. N enabled 3-148a
SCDD: Determin. P enabled 3-144
SCDD: Phase curr.stage bl. 3-144
SCDD: Resid. curr.stage bl. 3-148a
SOTF: ARC block. by close cm 3-152
TGFD: Direction BS 3—204
TGFD: Direction LS 3—204
TGFD: Hardware fault 3-202
TGFD: IN,p> triggered 3—204
TGFD: Reset signal 3-206
TGFD: VNG 3—203
TGFD: VNG> (f0) triggered 3—204
TGFD: VNG> triggered 3—204
-
Appendix B — List of signals (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
B-5Internal Signal Names Figure
THERM: Block. by CTA error 3-221
THERM: I 3-223
THERM: With CTA 3-221
V: Vneg 3-231
V: VNG 3-234
V: Vpos 3-231
-
Appendix B — List of signals (continued)
B-6 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614B 2 Telecontrol Interface per EN 60870-5-101 or IEC 870-5-101
(Companion Standard)This section incorporates Section 8 of EN 60870-5-101 (1996),
which includes a general definition of the telecontrol interface
for substation control systems.B 2.1 Interoperability
This application-based standard (companion standard) specifies
parameter sets and other options from which subsets are to be
selected in order to implement specific telecontrol systems.
Certain parameters such as the number of bytes (octets) in the
COMMON ADDRESS of the ASDU are mutually exclusive. This means that
only one value of the defined parameter is allowed per system.
Other parameters, such as the listed set of different process
information in the command and monitor direction, permit definition
of the total number or of subsets that are suitable for the given
application. This section combines the parameters given in the
previous sections in order to facilitate an appropriate selection
for a specific application. If a system is made up of several
system components supplied by different manufacturers, then it is
necessary for all partners to agree on the selected parameters.The boxes for the selected parameters should be checked. 1
Note: The overall definition of a system may also require
individual selection of certain parameters for specific parts of a
system such as individual selection of scaling factors for
individually addressable measured values.B 2.1.1 Network Configuration (Network-Specific Parameters)
x Point-to-point configuration x Multipoint-party line
configurationx Multiple point-to-point configuration Multipoint-star
configuration1 See National Preface of EN 60870-5-101.
-
Appendix B — List of signals (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
B-7B 2.1.2 Physical Layer 2 (Network-Specific Parameters)
Transmission Rate (Control Direction) 3
Unbalanced interface V.24/V.28
Standardized
Unbalanced interface V.24/V.28
Recommended with > 1 200 bit/s
Balanced interface X.24/X.27
100 bit/s x 2,400 bit/s 2,400 bit/s 56,000 bit/s
200 bit/s x 4,800 bit/s 4,800 bit/s 64,000 bit/s
300 bit/s x 9,600 bit/s 9,600 bit/s
x 600 bit/s 19,200 bit/s
x 1,200 bit/s 38,400 bit/s
Transmission Rate (Monitor Direction) 2
Unbalanced interface V.24/V.28
Standardized
Unbalanced interface V.24/V.28
Recommended with > 1 200 bit/s
Balanced interface X.24/X.27
100 bit/s x 2,400 bit/s 2,400 bit/s 56,000 bit/s 200 bit/s x
4,800 bit/s 4,800 bit/s 64,000 bit/s 300 bit/s x 9,600 bit/s 9,600
bit/s x 600 bit/s 19,200 bit/s x 1,200 bit/s 38 400 bit/s2 See National Preface of EN 60870-5-101. 3 The transmission
rates for control direction and monitor direction must be
identical. -
Appendix B — List of signals (continued)
B-8 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614B 2.1.3 Link Layer 4(Network-Specific Parameters)
Frame format FT 1.2, single character 1, and the fixed time-out
interval are used exclusively in this companion standard.Link Transmission Procedure Address Field of the Link x Balanced
transmission x Not present(balanced transmission only) x Unbalanced transmission x One
octet x Two octets 5 Frame Length x Structured 240 Maximum length L
(number of octets) x Unstructured4 See National Preface of EN 60870-5-101. 5 Balanced only.
-
Appendix B — List of signals (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
B-9B 2.1.4 Application Layer6
Transmission mode for application data
Mode 1 (least significant octet first), as defined in clause
4.10 of IEC 870-5-4, is used exclusively in this companion
standard.Common Address of ASDU (System-Specific Parameter)
x One octet x Two octets 1
Information Object Address (System-Specific Parameter)
x One octet x Structured x Two octets x Unstructured x Three
octetsCause of Transmission (System-Specific Parameter)
x One octet x Two octets (with originator address)
6 See National Preface of EN 60870-5-101.
-
Appendix B — List of signals (continued)
B-10 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Selection of Standard ASDUs
Process Information in Monitor Direction (Station-Specific
Parameter)x = Single-point information M_SP_NA_1
x = Single-point information with time tag M_SP_TA_1
x = Double-point information M_DP_NA_1
x = Double-point information with time tag M_DP_TA_1
x = Step position information M_ST_NA_1
x = Step position information with time tag M_ST_TA_1
x = Bit string of 32 bit M_BO_NA_1
x = Bit string of 32 bit with time tag M_BO_TA_1
x = Measured value, normalized value M_ME_NA_1
x = Measured value, normalized value with time tag M_ME_TA_1
x = Measured value, scaled value M_ME_NB_1
x = Measured value, scaled value with time tag M_ME_TB_1
= Measured value, short floating point value M_ME_NC_1
= Measured value, short floating point value with time tag
M_ME_TC_1x = Integrated totals M_IT_NA_1
x = Integrated totals with time tag M_IT_TA_1
-
Appendix B — List of signals (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
B-11x = Event of protection equipment with time tag M_EP_TA_1
x = Packed start events of protection equipment with time tag
ME_EP_TB_1x = Packed output circuit information of protection equipment
with time tag M_EP_TC_1= Packed single-point information with status change detection
M_PS_NA_1= Measured value, normalized value without quality descriptor
M_ME_ND_1 -
Appendix B — List of signals (continued)
B-12 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Process Information in Monitor Direction 7 (Station-Specific
Parameter)x = Single command C_SC_NA_1 x = Double command C_DC_NA_1 x =
Regulating step command C_IT_NA_1 = Set point command, normalized
value C_RC_NA_1 = Set point command, scaled value C_SE_NB_1 = Set
point command, short floating point value C_SE_NC_1 = Bit string of
32 bit C_BO_NA_1System Information in Monitor Direction (Station-Specific
Parameter)x = End of initialization ME_EI_NA_1
7 Incorrectly identified with control direction in IEC
870-5-101. -
Appendix B — List of signals (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
B-13System Information in Control Direction (Station-Specific
Parameter)x = Interrogation command C_IC_NA_1 x = Counter interrogation
command C_CI_NA_1 x = Read command C_RD_NA_1 x = Clock
synchronization command 8 C_CS_NA_1 x = Test command C_TS_NB_1 =
Reset process command C_RP_NC_1 = Delay acquisition command 9
C_CD_NA_18 The command procedure is formally processed, but there is no
change in the local time in the station. 9 See National Preface of
EN 60870-5-101. -
Appendix B — List of signals (continued)
B-14 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Parameter in Control Direction (Station-Specific Parameter)
x = Parameter of measured value, normalized value P_ME_NA_1
x = Parameter of measured value, scaled value P_ME_NB_1 =
Parameter of measured value, short floating point value P_ME_NC_1 =
Parameter activation P_AC_NA_1File Transfer (Station-Specific Parameter)
= File ready F_FR_NA_1 = Section ready F_SR_NA_1 = Call
directory, select file, call file, call section F_SC_NA_1 = Last
section, last segment F_LS_NA_1 = Ack file, ack section F_AF_NA_1 =
Segment F_SG_NA_1 = Directory F_DR_TA_1 -
Appendix B — List of signals (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
B-15B 2.1.5 Basic Application Functions10
Station Initialization (Station-Specific Parameter)
x Remote initialization
General Interrogation (System- or Station-Specific
Parameter)x Global
x Group 1 x Group 7 x Group 13 x Group 2 x Group 8 x Group 14 x
Group 3 x Group 9 x Group 15 x Group 4 x Group 10 x Group 16 x
Group 5 x Group 11 x Group 6 x Group 12 Addresses per group have to
be defined.Clock Synchronization (Station-Specific Parameter)
x Clock synchronization
10 See National Preface of EN 60870-5-101.
-
Appendix B — List of signals (continued)
B-16 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Command Transmission (Object-Specific Parameter)
x Direct command transmission Select and execute command Direct
set point command transmission Select and execute set point command
C_SE ACTTERM used x No additional definitionShort pulse duration
(Execution duration determined by a system parameter in the
outstation) Long pulse duration(Execution duration determined by a system parameter in the
outstation) Persistent outputTransmission of Integrated Totals (Station- or Object-Specific
Parameter)Counter request x General request counter
x Counter freeze without reset x Request counter group 1 Counter
freeze with reset x Request counter group 2 Counter reset x Request
counter group 3 Addresses per group have to be specified x Request
counter group 4 -
Appendix B — List of signals (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
B-17Parameter Loading (Object-Specific Parameter)
x Threshold value
Smoothing value Low limit for transmission of measured value
High limit for transmission of measured valueParameter Activation (Object-Specific Parameter)
Act/deact of persistent cyclic or periodic transmission of the
addressed objectFile Transfer (Station-Specific Parameter)
File transfer in monitor direction F_FR_NA_1 File transfer in
control direction F_FR_NA_1 -
Appendix B — List of signals (continued)
B-18 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614B 3 Communication Interface per IEC 60870-5-103
This section incorporates Section 8 of IEC 60870-5-103,
including definitions applicable to the P139.B 3.1 Interoperability
B 3.1.1 Physical Layer
B 3.1.1.1 Electrical Interface
x EIA RS 485
x No. of loads 32 for one device
Note: EIA RS 485 defines the loads in such a way that 32 of such
loads can be operated on one line. For detailed information see EIA
RS 485, Section 3.B 3.1.1.2 Optical Interface
x Glass fiber
x Plastic fiber
x F-SMA connector
BFOC/2.5 connector
B 3.1.1.3 Transmission Rate
x 9,600 bit/s
x 19,200 bit/s
-
Appendix B — List of signals (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
B-19B 3.1.2 Link Layer
There are no selection options for the link layer.
B 3.1.3 Application Layer
B 3.1.3.1 Transmission Mode for Application Data
Mode 1 (least significant octet first) as defined in clause 4.10
of IEC 60870-5-4 is used exclusively in this companion
standard.B 3.1.3.2 Common Address of ASDU
x One COMMON ADDRESS of ASDU (identical to the station
address)More than one COMMON ADDRESS of ASDU
B 3.1.3.3 Selection of Standard Information Numbers in Monitor
DirectionB 3.1.3.3.1 System Functions in Monitor Direction
INF Description
x End of general interrogation
x Time synchronization
x Reset FCB
x Reset CU
x Start / restart
Power on
-
Appendix B — List of signals (continued)
B-20 P139/EN M/Aa8-S // AFSV.12.10170 D ///
P139-307-411/412/413-614B 3.1.3.3.2 Status Indications in Monitor Direction Schneider
Electric Designations INF Description Address Descriptionx Auto-recloser active 015 064 ARC: Enabled
x Teleprotection active 015 008 PSIG: Enabled
x Protection active 003 030 MAIN: Device on-line
x LED reset 021 010 MAIN: Reset indicat. USER
x Blocking of monitor direction 037 075 COMM1:
Sig./meas.val.block.x Test mode 037 071 MAIN: Test mode
Local parameter setting
x Characteristic 1 036 090 PSS: PS 1 active
x Characteristic 2 036 091 PSS: PS 2 active
x Characteristic 3 036 092 PSS: PS 3 active
x Characteristic 4 036 093 PSS: PS 4 active
x Auxiliary input 1 034 000 LOGIC: Input 1 EXT
x Auxiliary input 2 034 001 LOGIC: Input 2 EXT
x Auxiliary input 3 034 002 LOGIC: Input 3 EXT
x Auxiliary input 4 034 003 LOGIC: Input 4 EXT
-
Appendix B — List of signals (continued)
P139/EN M/Aa8-S // AFSV.12.10170 D /// P139-307-411/412/413-614
B-21B 3.1.3.3.3 Monitoring Signals (Supervision Indications) in
Monitor Direction Schneider Electric Designations INF Description
Address Descriptionx Measurand supervision I 040 087 MCMON: Meas. circ. I
faultyx Measurand supervision V 038 023 MCMON: Meas. circ. V
faultyx Phase sequence supervision 038 049 MCMON: Phase sequ. V
faultyx 11 Trip circuit supervision 041 200 SFMON: Relay Kxx
faultyI>> back-up operation
x VT fuse failure 004 061 MAIN: M.c.b. trip V EXT
x Teleprotection disturbed 036 060 PSIG: Telecom. faulty
x Group warning 036 100 SFMON: Warning (relay)
x Group alarm 004 065 MAIN: Blocked/Faulty
11 The message content is formed from the OR operation of the
individual signals. -
Appendix B — List of signals (continued)
B-22 P139/EN M/Aa8-S // AFSV.12.10170 D ///
P139-307-411/412/413-614B 3.1.3.3.4 Earth Fault Indications in Monitor Direction
Schneider Electric Designations INF Description Address
Descriptionx Earth fault L1 041 054 MAIN: Ground fault A
x Earth fault L2 041 055 MAIN: Ground fault B
x Earth fault L3 041 056 MAIN: Ground fault C
x Earth fault forward, i.e. line 041 088 MAIN: Gnd. fault
forw./LSx Earth fault reverse, i.e. busbar 041 089 MAIN: Gnd. fault
backw./BS -
Appendix B — List of signals (continued)
P139/EN M/Aa8-S // AFSV.12.10170 D /// P139-307-411/412/413-614
B-23B 3.1.3.3.5 Fault Indications in Monitor Direction Schneider
Electric Designations INF Description Address Descriptionx Start /pick-up L1 040 005 MAIN: Starting A
x Start /pick-up L3 040 006 MAIN: Starting B
x Start /pick-up L3 040 007 MAIN: Starting C
x Start /pick-up N 040 008 MAIN: Starting GF
x General trip 036 071 MAIN: Gen. trip command 1
Trip L1
Trip L2
Trip L3
Trip I>> (back-up operation)
x Fault location X in ohms 004 029 FT_DA: Fault react.,
prim.x Fault forward/line 036 018 SCDD: Fault P forward
x Fault reverse/busbar 036 019 SCDD: Fault P backward
x Teleprotection signal transmitted 036 035 PSIG: Send
(signal)x Teleprotection signal received 037 029 PSIG: Receive
(signal)Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
-
Appendix B — List of signals (continued)
B-24 P139/EN M/Aa8-S // AFSV.12.10170 D ///
P139-307-411/412/413-614Schneider Electric Designations INF Description Address
Descriptionx General starting 040 000 MAIN: General starting
x Breaker failure 036 017 CBF: CB failure
Trip measuring system L1
Trip measuring system L2
Trip measuring system L3
Trip measuring system E
x Trip I> 040 042 MAIN: TripSig. tI>/tIrefP>
x Trip I>> 040 011 DTOC: Trip Signal tI>>
x Trip IN> 040 043 MAIN: TripSig. tIN>/tIrefN>
x Trip IN>> 040 028 DTOC: Trip Signal tIN>>
-
Appendix B — List of signals (continued)
P139/EN M/Aa8-S // AFSV.12.10170 D /// P139-307-411/412/413-614
B-25B 3.1.3.3.6 Auto-Reclosure Indications in Monitor Direction
Schneider Electric Designations INF Description Address
Descriptionx CB on by AR 037 007 ARC: (Re)close signal HSR
x CB on by long-time AR 037 006 ARC: (Re)close signal TDR
x AR blocked 037 008 ARC: Not ready
B 3.1.3.3.7 Measurands in Monitor Direction Schneider Electric
Designations INF Description Address Descriptionx 12 Measurand I 006 041 MAIN: Current B p.u.
x 13 Measurands I, V 006 041 005 045
MAIN: Current B p.u. MAIN: Voltage A-B p.u.
x 14 Measurands I, V, P, Q 006 041 005 045 004 051 004 053
MAIN: Current B p.u. MAIN: Voltage A-B p.u. MAIN: Active power P
p.u. MAIN: Reac. power Q p.u.x 15 Measurands IN, VEN 005 011 005 013
MAIN: Current (IP) p.u. MAIN: Volt. (VPG)/3 p.u.
x 16 Measurands IA,B,C, VA,B,C, P, Q, f 005 041 006 041 007 041
005 043 006 043 007 043 004 051 004 053 004 040MAIN: Current A p.u. MAIN: Current B p.u. MAIN: Current C p.u.
MAIN: Voltage A-G p.u. MAIN: Voltage B-G p.u. MAIN: Voltage C-G
p.u. MAIN: Active power P p.u. MAIN: Reac. power Q p.u. MAIN:
Frequency f12 only with setting C O M M 1 : T r a n s m . e n a b . c y c l
. d a t to «ASDU 3.1 p. IEC» 13 only with setting C O M M 1 : T r a
n s m . e n a b . c y c l . d a t to «ASDU 3.2 p. IEC» 14 only with
setting C O M M 1 : T r a n s m . e n a b . c y c l . d a t to
«ASDU 3.3 p. IEC» 15 only with setting C O M M 1 : T r a n s m . e
n a b . c y c l . d a t to «ASDU 3.4 p. IEC» 16 only with setting C
O M M 1 : T r a n s m . e n a b . c y c l . d a t to «ASDU 9 p.
IEC» -
Appendix B — List of signals (continued)
B-26 P139/EN M/Aa8-S // AFSV.12.10170 D ///
P139-307-411/412/413-614B 3.1.3.3.8 Generic Functions in Monitor Direction
INF Description
Read headings of all defined groups
Read values or attributes of all entries of one group
Read directory of a single entry
Read value or attribute of a single entry
General interrogation of generic data
Write entry with confirmation
Write entry with execution
Write entry abort
-
Appendix B — List of signals (continued)
P139/EN M/Aa8-S // AFSV.12.10170 D /// P139-307-411/412/413-614
B-27B 3.1.3.4 Selection of Standard Information Numbers in Control
DirectionB 3.1.3.4.1 System Functions in Control Direction
INF Description
x Initiation of general interrogation
x Time synchronization
B 3.1.3.4.2 General Commands in Control Direction Schneider
Electric Designations INF Description Address Descriptionx Auto-recloser on/off 015 060 ARC: General enable USER
x Teleprotection on/off 015 004 PSIG: General enable USER
x Protection on/off 003 030 MAIN: Device on-line
x LED reset 021 010 MAIN: Reset indicat. USER
x 17 Activate characteristic 1 003 060 PSS: Param.subs.sel.
USERx 18 Activate characteristic 2 003 060 PSS: Param.subs.sel.
USERx 19 Activate characteristic 3 003 060 PSS: Param.subs.sel.
USERx 20 Activate characteristic 4 003 060 PSS: Param.subs.sel.
USER17 Switches P S S : P a r a m . s u b s . s e l . U S E R to
«Parameter set 1» 18 Switches P S S : P a r a m . s u b s . s e l .
U S E R to «Parameter set 2» 19 Switches P S S : P a r a m . s u b
s . s e l . U S E R to «Parameter set 3» 20 Switches P S S : P a r
a m . s u b s . s e l . U S E R to «Parameter set 4» -
Appendix B — List of signals (continued)
B-28 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614B 3.1.3.4.3 Generic Functions in Control Direction
INF Description
Read headings of all defined groups
Read values or attributes of all entries of one group
Read directory of a single entry
Read value or attribute of a single entry
General interrogation of generic data
Write entry
Write entry with confirmation
Write entry with execution
Write entry abort
-
Appendix B — List of signals (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
B-29B 3.1.3.5 Basic Application Functions
x Test mode
x Blocking of monitor direction
x Disturbance data
Generic services
x Private data
B 3.1.3.6 Miscellaneous
Measured values are transmitted both with ASDU 3 and ASDU 9. As
defined in Sec. 7.2.6.8, the maximum MVAL can be either 1.2 or 2.4
times the rated value. In ASDU 3 and ASDU 9, different ratings may
not be used; in other words, there is only one choice for each
measurand.Measured value Max. MVAL = nom. value multiplied by
1,2 or 2,4
Current A x
Current B x
Current C x
Voltage A-G x
Voltage B-G x
Voltage C-G x
Enabled power P x
Reactive power Q x
Frequency f x
Voltage A-B x
-
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
B-30 -
Appendix C — List of Bay Types
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-1Key
Sorting the Bay Types The bay types are sorted by the criteria
listed below. These criteria are encoded in the first three
characters of the bay type code (example: A11.100.R01) given in
brackets after the Bay Type No. (example: 2). Sorting is first by
«Type of bay» in the order given below, then within each group by
the second and third character in ascending order.Type of bay A — Feeder bays L — Bus sectionalizer bay Q — Bus
coupler bay K — Bus coupler and sectionalizer bay M — Busbar
measurement bay E — Busbar grounding bay X — Other bay typeNumber of busbars 1 — Single busbar 2 — Double busbar 9 —
Without busbar / other configurationsEquipment 1 — Bays with switch truck or withdrawable switchgear
assembly 2 — Bays with two circuit breakers or switch disconnectors
on switch trucks or withdrawable switchgear assembly 3 — Bays with
stationary switchgear units 5 — Bays with stationary switchgear
units and three-position disconnector 9 — Other bay typesBay Type No.: This number indicates the value to be set at MAIN:
Type of bay (folder «Para/Conf») in order to configure the unit for
the selected bay type.Special Designations for External Devices: Mot.relay: Motor
relay Shunt wd. Shunt winding -
Appendix C — List of Bay Types (continued)
C-2 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Table «Assignment of Binary Inputs and Output Relays»
Column «Switchgear unit» This column begins with the designation
for the external device (switchgear unit). The function group
follows in brackets. The function group encompasses all setting
options for monitoring the switchgear unit and its signals. «Open»
and «Close(d)» indicate the signal message or control direction of
the switchgear unit.Column «Binary Input»: The «Open» or «Closed» signal should be
connected to the binary input U xxxx. The connection points of the
binary input U xxxx are shown in the terminal connection
diagrams.Column «Output relay» The «Open» or «Close» control of the
switchgear unit is effected via output relay K xxxx. The connection
points of the output relay K xxxx are shown in the terminal
connection diagrams.Table «Bay Interlock Equations for Operation without Station
Interlocking»Note! The interlock equations are stored at substation control
level, not at unit level.Symbols used in the Boolean interlock equations: /: Negation 0:
Switchgear unit «Open» I: Switchgear unit «Closed» X: Switchgear
unit in intermediate positionFctBl1: Function block 1, configuration at MAIN: Fct .asg. fc t
.b lock.1 (Folder «Para/Func/Ctrl»)FctBl2: Function block 2, configuration at MAIN: Fct .asg. fc t
.b lock.2 (Folder «Para/Func/Ctrl») -
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-3Bay Type No. 2 (A11.100.R01) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02)
Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04
K A01 K A02/ /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
-
Appendix C — List of Bay Types (continued)
C-4 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 3 (A11.100.R02) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02)
Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04
K A01 K A02K A03 K A04
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-5Bay Type No. 546 (A11.101.M03) Feeder bay with circuit breaker,
single busbar,direct motor controlAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) Mot.relay (SIG_1: Signal S012)
Shunt wd. (CMD_1: Command C011) Mot.relay (CMD_1: Command C012)Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U B06 / /
K A01 K A02K A03 K A04K A05 K A06/
K B05
K B06
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
-
Appendix C — List of Bay Types (continued)
C-6 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 4 (A11.101.R01) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q8 (DEV03)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06
K A01 K A02/ // /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-7Bay Type No. 5 (A11.101.R02) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q8 (DEV03)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06
K A01 K A02K A03 K A04/ /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
-
Appendix C — List of Bay Types (continued)
C-8 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 6 (A11.101.R03) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q8 (DEV03)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06
K A01 K A02K A03 K A04K A05 K A06
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-9Bay Type No. 523 (A11.108.R01) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q15 (DEV03)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06
K A01 K A02/ // /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & (Q15=0) & /(FctBl1=I) &
/(FctBl2=I)Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & (Q15=0) & /(FctBl1=I) &
/(FctBl2=I) -
Appendix C — List of Bay Types (continued)
C-10 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 549 (A11.109.M03) Feeder bay with circuit breaker,
single busbar,direct motor controlAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q8 (DEV02) X0 (DEV03) Q15 (DEV04) Mot.relay (SIG_1:
Signal S012) Shunt wd. (CMD_1: Command C011) Mot.relay (CMD_1:
Command C012)Open Close(d) Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U B01 U B02 U B06 / /
K A01 K A02K A03 K A04K A05 K A06/ //
K B05
K B06
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & (Q15=0) & /(FctBl1=I) &
/(FctBl2=I)Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0) & (Q15=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & (Q15=0) & /(FctBl1=I) &
/(FctBl2=I)Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0) & (Q15=0)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-11Bay Type No. 244 (A11.109.R01) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) Q15 (DEV07)
Open Close(d) Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U C01 U C02
K A01 K A02/ // // /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
-
Appendix C — List of Bay Types (continued)
C-12 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 544 (A11.109.R03) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) Q15 (DEV04)
Open Close(d) Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U B01 U B02
K A01 K A02K A03 K A04K A05 K A06/ /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & (Q15=0) & /(FctBl1=I) &
/(FctBl2=I)Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0) & (Q15=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & (Q15=0) & /(FctBl1=I) &
/(FctBl2=I)Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0) & (Q15=0)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-13Bay Type No. 567 (A11.132.R01) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) Q52 (DEV05)
Open Close(d) Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U B03 U B04
K A01 K A02/ // // /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
-
Appendix C — List of Bay Types (continued)
C-14 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 521 (A11.134.R02.1) Feeder bay with circuit
breaker, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q1 (DEV03) Q81 (DEV04) Q82 (DEV05)
Open Close(d) Open Close(d) Open Close(d) Open Close(d) Open
Close(d)U A01 U A02 U A03 U A04 U A05 U A06 U B01 U B02 U B03 U B04
K A01 K A02/ /K A05 K A06/ // /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(Q1=X) & (Q82=0) &
/(FctBl1=I) & /(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0) & (Q81=0) & (Q82=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(Q1=X) & (Q82=0) &
/(FctBl1=I) & /(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0) & (Q81=0) & (Q82=0)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-15Bay Type No. 519 (A11.135.R02.1) Feeder bay with circuit
breaker, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q1 (DEV03) Q81 (DEV04) Q82 (DEV05) Q15
(DEV06)Open Close(d) Open Close(d) Open Close(d) Open Close(d) Open
Close(d) Open Close(d)U A01 U A02 U A03 U A04 U A05 U A06 U B01 U B02 U B03 U B04 U
B05 U B06K A01 K A02/ /K A05 K A06/ // // /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(Q1=X) & (Q15=0) & (Q82=0)
& /(FctBl1=I) & /(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0) & (Q81=0) & (Q82=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(Q1=X) & (Q15=0) & (Q82=0)
& /(FctBl1=I) & /(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0) & (Q81=0) & (Q82=0)
-
Appendix C — List of Bay Types (continued)
C-16 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 7 (A11.200.R01) Feeder bay with switch
disconnector, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02)
Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04
K A01 K A02/ /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-17Bay Type No. 8 (A11.200.R02) Feeder bay with switch
disconnector, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02)
Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04
K A01 K A02K A03 K A04
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0)
-
Appendix C — List of Bay Types (continued)
C-18 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 9 (A11.201.R01) Feeder bay with switch
disconnector, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q8 (DEV03)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06
K A01 K A02/ // /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-19Bay Type No. 10 (A11.201.R02) Feeder bay with switch
disconnector, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q8 (DEV03)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06
K A01 K A02K A03 K A04/ /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
-
Appendix C — List of Bay Types (continued)
C-20 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 11 (A11.201.R03) Feeder bay with switch
disconnector, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q8 (DEV03)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06
K A01 K A02K A03 K A04K A05 K A06
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-21Bay Type No. 12 (A11.400.R01) Feeder bay with switch
disconnector / fuse unit, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) F (SIG_1: Signal S011)
Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U B05
K A01 K A02/ //
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
-
Appendix C — List of Bay Types (continued)
C-22 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 13 (A11.400.R02) Feeder bay with switch
disconnector / fuse unit, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) F (SIG_1: Signal S011)
Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U B05
K A01 K A02K A03 K A04/
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-23Bay Type No. 14 (A11.401.R01) Feeder bay with switch
disconnector / fuse unit, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) F (SIG_1: Signal S011)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U B05
K A01 K A02/ // //
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
-
Appendix C — List of Bay Types (continued)
C-24 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 15 (A11.401.R02) Feeder bay with switch
disconnector / fuse unit, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) F (SIG_1: Signal S011)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U B05
K A01 K A02K A03 K A04/ //
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-25Bay Type No. 16 (A11.401.R03) Feeder bay with switch
disconnector / fuse unit, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) F (SIG_1: Signal S011)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U B05
K A01 K A02K A03 K A04K A05 K A06/
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
-
Appendix C — List of Bay Types (continued)
C-26 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 17 (A11.900.R01) Feeder bay with other switchgear
unit, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
X0 (DEV01)
Open Close(d)
U A01 U A02
K A01 K A02
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Interlock equations not defined
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Interlock equations not defined
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-27Bay Type No. 504 (A11.901.R00) Feeder bay with other switchgear
unit, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
X0 (DEV02) Q8 (DEV03)
Open Close(d) Open Close(d)
U A03 U A04 U A05 U A06
/ // /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Interlock equations not defined
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Interlock equations not defined
-
Appendix C — List of Bay Types (continued)
C-28 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 541 (A13.104.R01) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q1 (DEV02)
Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04
K A01 K A02/ /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(FctBl1=I) & /(FctBl2=I)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(FctBl1=I) & /(FctBl2=I)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-29Bay Type No. 18 (A13.105.M03) Feeder bay with circuit breaker,
single busbar,direct motor controlAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) Mot.relay (SIG_1: Signal S012)
Shunt wd. (CMD_1: Command C011) Mot.relay (CMD_1: Command C012)Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U B06 / /
K A01 K A02K A03 K A04K A05 K A06/
K B05
K B06
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & (Q8=0) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Q8 Close(d) (Q0=0) & (Q1=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & (Q8=0) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Q8 Close(d) (Q0=0) & (Q1=0)
-
Appendix C — List of Bay Types (continued)
C-30 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 19 (A13.105.R01) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06
K A01 K A02/ // /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & (Q8=0) & /(FctBl1=I) &
/(FctBl2=I)Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & (Q8=0) & /(FctBl1=I) &
/(FctBl2=I) -
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-31Bay Type No. 20 (A13.105.R02) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06
K A01 K A02K A03 K A04/ /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & (Q8=0) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & (Q8=0) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
-
Appendix C — List of Bay Types (continued)
C-32 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 21 (A13.105.R03) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06
K A01 K A02K A03 K A04K A05 K A06
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & (Q8=0) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Q8 Close(d) (Q0=0) & (Q1=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & (Q8=0) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Q8 Close(d) (Q0=0) & (Q1=0)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-33Bay Type No. 557 (A13.106.R03) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q1 (DEV02) Q9 (DEV03)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06
K A01 K A02K A03 K A04K A05 K A06
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & /(Q9=X) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0)
Q9 Open (Q0=0)
Close(d) (Q0=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & /(Q9=X) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0)
Q9 Open (Q0=0)
Close(d) (Q0=0)
-
Appendix C — List of Bay Types (continued)
C-34 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 22 (A13.107.M04) Feeder bay with circuit breaker,
single busbar,direct motor controlAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q1 (DEV02) Q9 (DEV03) Q8 (DEV04) Mot.relay (SIG_1:
Signal S012) Shunt wd. (CMD_1: Command C011) Mot.relay (CMD_1:
Command C012)Open Close(d) Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U B01 U B02 U B06 / /
K A01 K A02K A03 K A04K A05 K A06K B01 K B02/
K B05
K B06
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & /(Q9=X) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & /(Q9=X) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-35Bay Type No. 23 (A13.107.R01) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q1 (DEV02) Q9 (DEV03) Q8 (DEV04)
Open Close(d) Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U B01 U B02
K A01 K A02/ // // /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & /(Q9=X) & /(FctBl1=I) &
/(FctBl2=I)Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & /(Q9=X) & /(FctBl1=I) &
/(FctBl2=I) -
Appendix C — List of Bay Types (continued)
C-36 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 24 (A13.107.R03) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q1 (DEV02) Q9 (DEV03) Q8 (DEV04)
Open Close(d) Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U B01 U B02
K A01 K A02K A03 K A04K A05 K A06/ /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & /(Q9=X) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0)
Q9 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & /(Q9=X) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0)
Q9 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-37Bay Type No. 25 (A13.107.R04) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q1 (DEV02) Q9 (DEV03) Q8 (DEV04)
Open Close(d) Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U B01 U B02
K A01 K A02K A03 K A04K A05 K A06K B01 K B02
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & /(Q9=X) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & /(Q9=X) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
-
Appendix C — List of Bay Types (continued)
C-38 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 508 (A13.111.R03) Feeder bay with circuit breaker,
single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) Q15 (DEV04)
Open Close(d) Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U B01 U B02
K A01 K A02K A03 K A04K A05 K A06/ /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & (Q8=0) & (Q15=0) & /(FctBl1=I)
& /(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0) & (Q15=0)
Q8 Close(d) (Q0=0) & (Q1=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & (Q8=0) & (Q15=0) & /(FctBl1=I)
& /(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0) & (Q15=0)
Q8 Close(d) (Q0=0) & (Q1=0)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-39Bay Type No. 26 (A13.200.R01) Feeder bay with switch
disconnector, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01)
Open Close(d)
U A01 U A02
K A01 K A02
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Interlock equations not defined
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Interlock equations not defined
-
Appendix C — List of Bay Types (continued)
C-40 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 27 (A13.201.M02) Feeder bay with switch
disconnector, single busbar,direct motor controlAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q8 (DEV02) Mot.relay (SIG_1: Signal S012) Shunt wd.
(CMD_1: Command C011) Mot.relay (CMD_1: Command C012)Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U B06 / /
K A01 K A02K A03 K A04/
K B05
K B06
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q0=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q0=0)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-41Bay Type No. 28 (A13.201.R01) Feeder bay with switch
disconnector, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q8 (DEV02)
Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04
K A01 K A02/ /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
-
Appendix C — List of Bay Types (continued)
C-42 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 29 (A13.201.R02) Feeder bay with switch
disconnector, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q8 (DEV02)
Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04
K A01 K A02K A03 K A04
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q0=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q0=0)
-
Appendix C — List of Bay Types (continued)
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614
C-43Bay Type No. 30 (A13.205.M03) Feeder bay with switch
disconnector, single busbar,direct motor controlAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) Mot.relay (SIG_1: Signal S012)
Shunt wd. (CMD_1: Command C011) Mot.relay (CMD_1: Command C012)Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06 U B06 / /
K A01 K A02K A03 K A04K A05 K A06/
K B05
K B06
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & (Q8=0) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Q8 Close(d) (Q0=0) & (Q1=0)
Bay Interlock Equations for Operation with Station
InterlockingSwitchgear unit Control O/C Interlock equation
Q0 Close(d) /(Q1=X) & (Q8=0) & /(FctBl1=I) &
/(FctBl2=I)Q1 Open (Q0=0)
Close(d) (Q0=0) & (Q8=0)
Q8 Close(d) (Q0=0) & (Q1=0)
-
Appendix C — List of Bay Types (continued)
C-44 P139/EN M/Aa8 // AFSV.12.10170 D ///
P139-307-411/412/413-614Bay Type No. 31 (A13.205.R01) Feeder bay with switch
disconnector, single busbarAssignment of Binary Inputs and Output Relays
Switchgear unit Binary input Output relay
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03)
Open Close(d) Open Close(d) Open Close(d)
U A01 U A02 U A03 U A04 U A05 U A06
K A01 K A02/ // /
Bay Interlock Equations for Operation without Station
InterlockingSwitchgear unit Control O/C Interlock equa
Собственники частных домов и загородных дач не понаслышке знают, что такое подтопление фундамента. Оно происходит вследствие близости к поверхности земли грунтовых вод или же из-за большого количества осадков. К счастью, проблему можно решить устройством дренажа вокруг дома. Это не потребует особых усилий и денежных вложений. Далее рассмотрим, как правильно сделать дренаж вокруг дома.
Дренаж: что это и зачем его делать
Для защиты построек от внутреннего подтопления используется дренирование. Это система осушения, предназначенная для ликвидации чрезмерного скопления воды вокруг дома или земельного участка. Особенно это важно для домов, находящихся в долине. Вода способна накапливаться вокруг объектов вследствие различных причин: это может быть таяние снега, повышение уровня грунтовой влаги, особых свойств данного типа земли. А также из-за особого расположения постройки, вследствие которого вода вокруг нее не может самостоятельно стекать.
Собственнику дома стоит задуматься о сооружении дренажной системы в следующих случаях:
- в этой местности нормальным является повышенный уровень подземных вод;
- если в подвале начала скапливаться жидкость вследствие таяния снега;
- в углах на полу помещений первого этажа начала появляться плесень;
- если фундамент постройки постоянно влажный или подмывается водой;
- местность характеризуется высоким уровнем осадков;
- почва, на которой стоит дом, по своим природным свойствам плохо впитывает влагу;
- на стенах начал появляться грибок;
- участок с домом расположен в низине.
На практике дренаж является устройством на основе труб, которые отводят попадающую в них лишнюю влагу. Специалисты советуют всегда создавать такую систему, поскольку она является эффективным методом продления срока службы любых построек.
Типы конструкций
Перед тем как сделать дренаж вокруг дома своими руками, следует определиться с желаемым вариантом. Есть несколько способов подобного обустройства. Если правильно сделать дренирование, то любой из методов будет эффективен. Но времени и финансовых средств каждый требует по-разному.
Можно обустроить такие типы систем:
- Открытый дренаж. Этот метод довольно простой, и заключается в создании вокруг дома открытых траншей (канав), куда будет стекать вода, а затем впитываться в почву. Несмотря на простоту сооружения такого водоотвода, внешне он выглядит непрезентабельно, и быстро приходит в негодность – траншеи осыпаются и ломаются.
- Закрытое дренирование. Этот способ подразумевает укладывание перфорированных труб в траншеи земли. В них попадает влага и удаляется от дома. Этот метод является наиболее действенным, но относительно сложным по части исполнения.
- Засыпной дренаж. Здесь следует выкопать канавы вокруг объекта, как и при открытом методе, а затем засыпать их измельченным кирпичом, щебнем или бутом. Траншеи закрываются дерном. Такой способ дренирования отличается долговечностью, но имеет невысокую степень пропуска влаги. Засыпной водоотвод почти невозможно обслуживать.
Виды дренирования
Разобравшись с типами дренирования, рассмотрим его популярные виды. Каждый имеет свои достоинства и недостатки. Выбирая способ обустройства, это обязательно надо учитывать.
Пристенный дренаж
Эта конструкция создается вдоль периметра фундамента. Если в доме есть подвал либо цокольный этаж, лучше сделать именно такой водоотвод. Конечно, правильнее предусмотреть его еще на стадии строительства, когда только возводится фундамент и область вокруг него не засыпана.
Если же дом уже давно возведен, пристенное дренирование также вполне реально создать, однако понадобятся масштабные земляные работы.
Особенности обустройства пристенного дренажа:
- В выкопанные области кладут трубы, они должны вести к смотровым колодцам от углов.
- Нижняя грань оборудования должна примыкать к конечному резервуару, который ведет за участок.
Кольцевой (траншейный) дренаж
Этот вид дренирования обустраивается дальше от фундамента, чем пристенный. Необходимо отступить 2-3 метра от здания, и тогда производить работы. Кольцевое дренирование применяют в основном на глинистых почвах, поскольку там его достаточно просто создать и использовать. Если в доме нет подвала или цоколя, эта система будет лучшим вариантом.
Особенности обустройства кольцевого дренажа:
- Глиняным замком разграничивают фундамент и конструкцию водоотвода.
- Такой вид дренирования следует создавать глубже, чем самая нижняя точка фундамента.
- Водоотводные изделия следует поместить на слой щебня или мелкого камня, поскольку эти материалы хорошо пропускает воду.
Производство дренажных работ своими силами
Определившись с типом и видом системы дренирования, нужно приобрести все комплектующие и начать монтажные работы. Зная технологию, с задачей может справиться даже начинающий строитель, поэтому нет смысла нанимать профессионалов, ведь несложно сделать все своими руками.
Для создания дренажной системы любого типа понадобятся трубы с перфорацией. Специалисты советуют заменить специальные изделия, если нет возможности их купить, обычными канализационными, сделав в них отверстия.
Гравий, используемый для засыпки, должен быть крупнее, чем отверстия, чтобы не попадал вовнутрь. Важно не забыть о завершающем элементе, то есть о месте, куда будет окончательно попадать вода. Это может быть общая сточная канава за пределами участка. Также можно создать собственный дренажный колодец, выводить осадки в септик или же в природный водоем, находящийся неподалеку.
Виды труб для дренажа
В продаже имеется много видов труб для дренирования, с помощью которых можно создать качественную водоотводную систему. При устройстве дренажа вокруг дома своими руками необходимо изучить характеристики таких изделий.
Выбирать можно из следующих вариантов:
- Пористые. Производятся из керамзитового стекла или пластобетона, им не требуется перфорация. Но это довольно дорогой материал. Для хорошего дренирования стоит брать трубы большого диаметра.
- Асбоцементные. Самые надежные, однако достаточно тяжелые и в них требуется сделать отверстия.
- Полимерные. Создаются из пластмассы, являются удобными и легкими, хороши в эксплуатации. В настоящее время почти всегда для дренажа берут именно такие трубы.
- Керамические. Функциональные, но хрупкие, требуют перфорации. За счет дополнительных желобков более эффективно собирают влагу.
Основные этапы монтажа
Первым делом стоит нарисовать на бумаге план участка и определиться, как именно будет проходить дренаж. Помните, что стекать вода должна в самую нижнюю точку – там и обязан быть резервуар для воды. Для определения такого участка можно воспользоваться прибором теодолитом. Исходя из плана рассчитывается необходимое количество материалов.
Поэтапная инструкция выполнения работ:
- В соответствии с проектом на бумаге стоит разметить участок на местности.
- После этого производится выкапывание траншей, размер которых должен учитывать трубу и гравий, которые будут закопаны там.
- Для рытья лучше взять штыковую лопату – она увеличит скорость работ.
- Ширина канавы должна составить примерно полметра.
- Следующим этапом будет создание уклона канавы для системы.
- При этом учитываются перепады высоты, которые отмечаются вешками.
- Чтобы дно образовало нужный уклон, используем песок.
- На основание траншеи выкладывается геотекстильный материал, который в местах стыка должен иметь хороший зап`ах.
- Далее он заполняется гравием с учетом уклона.
- В мелкой фракции делаем желоб, в который должна поместиться труба.
- Далее укладываем водоотводные изделия, соединяем их в соответствии с технологией, проверяем, чтобы остался нужный уклон.
- Проконтролировать направление можно при помощи натянутой нити.
- Стыки труб соединяются при помощи специальной ленты.
- На следующем этапе проводится установка смотровых колодцев.
- Если водоотводные изделия не имеют фильтрующего слоя, тогда стоит обернуть их геотекстилем, закрепив веревкой.
- После этого поверх засыпается гравий слоем до 18 см и сверху, с двух сторон с запа́хом закрываем систему краями нижнего геотекстиля.
- Финальным аккордом будет засыпание дренажа речным крупным песком.
Перед тем как закрыть трубы, залейте в них воду и посмотрите, насколько правильно она будет идти по системе. Пока конструкция не закопана, еще можно все исправить.
Таким образом получаем хорошую и функциональную систему. Теперь чрезмерные осадки и скопление влаги не страшны вашим постройкам. Дренаж стоит монтировать не только вокруг жилых объектов, но и по периметру хозяйственных сооружений.
Несколько советов по обустройству дренажа:
- В том случае, если система проходит под дорогой, по которой часто ездит транспорт, то на участке трассы трубы должны быть металлическими. Далее они обязаны плотно соединяться с остальной конструкцией.
- Когда траншея готова, вначале следует утрамбовать дно, а только потом начинать заполнять комплектующими.
- Засыпать водоотводные изделия гравием следует на 18-30 см.
- Геотекстиль используется для предотвращения загрязнения системы. Для этих же целей можно обернуть комплектующие фильтрующим материалом.
- При монтаже конструкции следует учесть возможность ее обслуживания. Для этого создают смотровые колодцы. Лучшим местом для них являются изгибы и стыки.
- Важно, чтобы дрены не касались и не перекрывали уже имеющиеся в земле коммуникации – провода, трубы.
- Копать траншею нужно начинать с самой высокой точки земли.
- Не стоит экономить на количестве геотекстиля, поскольку этот материал призван защищать от заиливания дренажную трубу.
- В качестве отстойника для воды проще всего прикрепить металлический сварной короб.
Смотровой колодец
Смотровой колодец необходим для обеспечения доступа к системе и проведения ремонтно-обслуживающих работ. Проще всего приобрести готовый элемент: его можно найти в строительных магазинах. Также можно сделать колодец своими силами. Для этого понадобится широкая пластиковая труба. Подходят для создания и бетонные кольца или же можно сделать цельный бетонный резервуар. В конструкции беспрепятственно должна помещаться человеческая рука для случаев ремонта или очищения. Смотровой колодец обязательно должен иметь крышку.
Сборный колодец
Это резервуар для сбора воды. Он монтируется в самой нижней точке системы. Как и смотровой, сборный элемент можно купить готовым или сделать своими руками. Сварные конструкции и изделия из железобетона являются наиболее используемыми. Колодец должен быть такой глубины, чтобы при попадании в него песка и грязи для воды все равно оставалось место. Периодически требуется прочищать сборный водонакопитель, убирая остатки грязи с дна.
Отмостка: значение и монтаж
Дополнительным элементом для защиты постройки от избыточной влаги является отмостка. Она дополняет дренаж. Отмостка являет собой укладывание по периметру фундамента водонепроницаемого материала, примыкающего прямо к постройке.
Материал следует располагать строго под углом наружу, чтобы влага могла стекать. Таким образом, попадая на отмостку вода сразу же убирается от дома. Контакт фундамента и стен с влагой будет минимальным.
В качестве материала, подходящего для отмостки, можно взять асфальт, бетон, глину, камень, тротуарную плитку. Первые два – самые популярные для отмостки и используются чаще всего. Это обусловлено тем, что они требуют меньшего труда и капиталовложений. Но и смотреться такие поверхности будут не слишком выгодно. Тротуарная плитка, камень и глина требуют большего времени и усилий, но все работы оправдает замечательный результат и привлекательный внешний вид.
Мы рассказали о том, что такое дренаж, какие существуют его типы и виды. Также дали советы относительно самостоятельной установки различных видов дренирования. Если соблюдать технологию, то процесс пройдет быстро и гладко, а полученный результат точно порадует. Современный и качественно сделанный дренаж позволит защитить жилище от негативного влияния избыточной влажности, сделает его комфортным, продлит срок эксплуатации.
Рекомендуем посмотреть видео по теме