    SJ100 Series Inverter Instruction Manual • Single-phase Input 200V Class • Three-phase Input 200V Class • Three-phase Input 400V Class Manual Number: NB585XF December 2003 After reading this manual, keep it handy for future reference. Hitachi Industrial Equipment Systems Co., Ltd.
  • Page 2: Hazardous High Voltage

    Safety Messages For the best results with the SJ100 Series inverter, carefully read this manual and all of the warning labels attached to the inverter before installing and operating it, and follow the instructions exactly. Keep this manual handy for quick reference.

  • Page 3: General Precautions — Read These First

    Equipment Systems Co., Ltd. CAUTION: Be sure to connect a motor thermal disconnect switch or overload device to the SJ100 series controller to assure that the inverter will shut down in the event of an overload or an overheated motor.

  • Page 4
    Cable support Cable CAUTION: A double-pole disconnection device must be fitted to the incoming main power supply close to the inverter. Additionally, a protection device meeting IEC947-1/ IEC947-3 must be fitted at this point (protection device data shown in “Determining Wire and Fuse Sizes”…
  • Page 5: Index To Warnings And Cautions In This Manual

    Index to Warnings and Cautions in This Manual Installation — Cautions for Mounting Procedures CAUTION: The inverter is shipped with a plastic cover over the top vent grill. REMOVE this cover after the installation is complete. Operation with this cover in place will not allow proper cooling, and damage to the inverter may result.

  • Page 6
    Otherwise, there is the possibility of damage to the inverter and the danger of fire. CAUTION: Be sure not to connect an AC power supply to the output terminals. Otherwise, there is the possibility of damage to the inverter and the danger of injury and/or fire.
  • Page 7
    CAUTION: Remarks for using ground fault interrupter breakers in the main power supply: Adjustable frequency inverters with CE-filters (RFI- filter) and shielded (screened) motor cables have a higher leakage current toward Earth GND. Especially at the moment of switching ON this can cause an inadvertent trip of ground fault interrupters.
  • Page 8
    (be sure to design the machine so that safety for personnel is secure even if it restarts.) Otherwise, it may cause injury to personnel. WARNING: If the power supply is cut OFF for a short period of time, the inverter may restart operation after the power supply recovers if the Run command is active.
  • Page 9
    viii WARNING: Be sure not to touch the inside of the energized inverter or to put any conductive object into it. Otherwise, there is a danger of electric shock and/or fire. WARNING: If power is turned ON when the Run command is already active, the motor will automatically start and injury may result.
  • Page 10: General Warnings And Cautions

    Warnings and Cautions for Troubleshooting and Maintenance WARNING: Wait at least five (5) minutes after turning OFF the input power supply before performing maintenance or an inspection. Other- wise, there is the danger of electric shock. WARNING: Make sure that only qualified personnel will perform maintenance, inspection, and part replacement.

  • Page 11
    (Mgo) on the power supply side, so that the circuit does not allow automatic restarting after the power supply recovers. If the optional remote operator is used and the retry function has been selected, this will also cause automatic restarting when a Run command is active.
  • Page 12
    MUST install an input-side AC reactor of 3% (at a voltage drop at rated current) with respect to the supply voltage on the power supply side. Also, where the effects of an indirect lightning strike are possible, install a lightning conductor.
  • Page 13: Ul® Cautions, Warnings, And Instructions

    CAUTION: When the EEPROM error E08 occurs, be sure to confirm the setting values again. CAUTION: When using normally closed active state settings (C_11 to C_16) for exter- nally commanded Forward or Reverse terminals [FW] or [RV], the inverter may start automatically when the external system is powered OFF or disconnected from the inverter! So, do not use normally closed active state settings for Forward or Reverse terminals [FW] or [RV] unless your system design protects against unintended motor…

  • Page 14
    The connector must be fixed using the crimping tool specified by the connector manufacturer. Wiring Size Inverter Model Range (AWG) Terminal (ring lug) xiii SJ100 Inverter Torque ft-lbs (N-m) Cable support Cable…
  • Page 15: Motor Overload Protection

    200V 0.75 400V Motor Overload Protection Hitachi SJ100 inverters provide solid state motor overload protection, which depends on the proper setting of the following parameters: • B_12 “electronic overload protection” • B212 “electronic overload protection, 2nd motor” Set the rated current [Amperes] of the motor(s) with the above parameters. The setting range is 0.5 * rated current to 1.2 * rated current.

  • Page 16: Table Of Contents

    UL® Cautions, Warnings, and Instructions Table of Contents Revisions Contact Information Chapter 1: Getting Started Introduction SJ100 Inverter Specifications Introduction to Variable-Frequency Drives Frequently Asked Questions Chapter 2: Inverter Mounting and Installation Orientation to Inverter Features Basic System Description Step-by-Step Basic Installation…

  • Page 17
    Warranty Appendix A: Glossary and Bibliography Glossary Bibliography Appendix B: Drive Parameter Settings Tables Introduction Parameter Settings for Keypad Entry Appendix C: CE–EMC Installation Guidelines CE–EMC Installation Guidelines Hitachi EMC Recommendations Index 4–2 4–4 4–5 4–8 4–24 4–32 4–33 4–35 4–39…
  • Page 18: Revisions

    Revision D Minor corrections throughout Revision E Minor corrections throughout Revision F Minor corrections throughout Revision History Table Date of Issue August 1999 xvii SJ100 Inverter Operation Manual No. April 1999 NB585X May 1999 NB585XA NB585XB May 2002 NB585XC Nov. 2002…

  • Page 19: Contact Information

    NOTE: To receive technical support for the Hitachi inverter you purchased, contact the Hitachi inverter dealer from whom you purchased the unit, or the sales office or factory contact listed above. Please be prepared to provide the following inverter nameplate information: 1.

  • Page 20
    Getting Started In This Chapter… — Introduction — SJ100 Inverter — Introduction to Variable-Frequency Drives — Frequently Asked Questions Specifications… page…
  • Page 21: Introduction

    • Motor constants are programmable, or may be set via auto-tuning • PID control adjusts motor speed automatically to maintain a process variable value The design in Hitachi inverters overcomes many of the traditional trade-offs between speed, torque and efficiency. The performance characteristics are: •…

  • Page 22
    1–3 SJ100 Inverter A full line of accessories from Hitachi is available to complete your motor application. These include: • Digital remote operator keypad • Braking resistors (shown at right) • Radio noise filters • CE compliance filters • DIN rail mounting adapter (35mm rail size)
  • Page 23
    Introduction Inverter Specifications Label The Hitachi SJ100 inverters have product labels located on the right side of the housing, as pictured below. Be sure to verify that the specifications on the labels match your power source, motor, and application safety requirements.
  • Page 24: Sj100 Inverter Specifications

    SJ100 Inverter Specifications Model-specific tables for 200V and 400V class inverters The following tables are specific to SJ100 inverters for the 200V and 400V class model groups. Note that “General Specifications” on page 1–9 groups. Footnotes for all specifications tables follow the table below.

  • Page 25
    Note 5: When SLV is selected, please set the carrier frequency higher than 2.1 kHz. Note 6: At the rated voltage when using a Hitachi standard 3-phase, 4-pole motor (when selecting sensorless vector control—SLV). Note 7: The braking torque via capacitive feedback is the average deceleration torque at the shortest deceleration (stopping from 50/60 Hz as indicated).
  • Page 26
    SJ100 Inverter Specifications, continued… Item SJ100 inverters, CE version 200V models UL version Applicable motor size *2 Rated capacity 230V (kVA) *12 240V Rated input voltage Rated input 1-phase current (A) 3-phase Rated output voltage *3 Rated output current (A)
  • Page 27
    1–8 SJ100 Inverter Specifications Item SJ100 inverters, CE version 400V models UL version Applicable motor size *2 Rated capacity (460V) kVA Rated input voltage Rated input current (A) Rated output voltage *3 Rated output current (A) Efficiency at 100% rated output (%)
  • Page 28: General Specifications

    50/60 Hz torque, short time with resistor stop *7 DC braking Weight General Specifications The following table applies to all SJ100 inverters. Item Protective housing *1 Control method Output frequency range *4 Frequency accuracy Frequency setting resolution Volt./Freq. characteristic *5…

  • Page 29
    1–10 SJ100 Inverter Specifications Item Input Freq. Operator panel Up and Down keys / Value settings signal setting Potentiometer External signal FWD/ Operator panel Run/Stop (Forward/Reverse run change by command) External signal Forward run/stop, Reverse run/stop Intelligent input terminal Output…
  • Page 30
    10VDC nominal, 10 mA maximum Alarm relay contacts 250 VAC, 2.5A (R load) max., 0.2A (I load, P.F.=0.4) max. 100 VAC, 10mA min. 30 VDC, 3.0A (R load) max., 0.7A (I load, P.F.=0.4) max. 5 VDC, 100mA min. SJ100 Inverter 4–6. Ratings 1–11…
  • Page 31: Derating Curves

    Use the following derating curves to help determine the optimal carrier frequency setting for your inverter, and to find the output current derating. Be sure to use the proper curve for your particular SJ100 inverter model number. Legend: SJ100–002NFE/NFU…

  • Page 32
    Derating curves, continued… SJ100–007NFE/NFU 100% % of rated output current SJ100–0015NFE/NFU 100% % of rated output current SJ100–022NFE/NFU 100% % of rated output current SJ100 Inverter Carrier frequency Carrier frequency Carrier frequency 1–13…
  • Page 33
    1–14 SJ100 Inverter Specifications Derating curves, continued… SJ100–037LF/LFU % of rated output current SJ100–055LFU % of rated output current SJ100–075LFU % of rated output current 100% Carrier frequency 100% Carrier frequency 100% Carrier frequency…
  • Page 34
    Derating curves, continued… SJ100–004HFE/HFU 100% % of rated output current SJ100–007HFE/HFU 100% % of rated output current SJ100–015HFE/HFU 100% % of rated output current SJ100 Inverter Carrier frequency Carrier frequency Carrier frequency 1–15…
  • Page 35
    1–16 SJ100 Inverter Specifications Derating curves, continued… SJ100–022HFE/HFU % of rated output current SJ100–040HFE/HFU % of rated output current SJ100–055HFE/HFU % of rated output current 100% Carrier frequency 100% Carrier frequency 100% Carrier frequency…
  • Page 36
    1–17 SJ100 Inverter Derating curves, continued… SJ100–075HFE/HFU 100% % of rated output current Carrier frequency…
  • Page 37: Introduction To Variable-Frequency Drives

    Introduction to Variable-Frequency Drives The Purpose of Motor Speed Control for Industry Hitachi inverters provide speed control for 3-phase AC induction motors. You connect AC power to the inverter, and connect the inverter to the motor. Many applications benefit from a motor with variable speed, in several ways: •…

  • Page 38
    From this it mathematically calculates two vector currents. One vector is related to motor flux current, and the other to motor torque current. The ability to separately control these two vectors is what allows the SJ100 to deliver extraordinary low-speed performance and speed control accuracy.
  • Page 39
    The Hitachi inverter is a rugged and reliable device. The intention is for the inverter to assume the role of controlling power to the motor during all normal operations. There- fore, this manual instructs you not to switch off power to the inverter while the motor is running (unless it is an emergency stop).
  • Page 40
    (see page 5–2 “Dynamic Braking” on page 5–5 continuously overhaul the motor for extended periods of time, the SJ100 may not be suitable (contact your Hitachi distributor). The inverter parameters include acceleration and deceleration, which you can set to match the needs of the application.
  • Page 41
    FWD and REV commands determine the direction before the motion starts. NOTE: The SJ100 can move loads in both directions. However, it is not designed for use in servo-type applications that use a bipolar velocity signal that determines direction. Set speed…
  • Page 42: Frequently Asked Questions

    Amplifier is a term almost exclusively used to describe drives for servo or stepper motors. Although the SJ100 inverter is a variable speed drive, can I use it in a fixed-speed application? Yes, sometimes an inverter can be used simply as a “soft-start”…

  • Page 43
    The greater the number of poles, the slower the top motor speed will be, but it will have higher torque at the base speed. Will I be able to add dynamic (resistive) braking to my Hitachi SJ100 drive after the initial installation? Yes.
  • Page 44
    Other applications may not need noise suppression, unless you notice electrical interference with the operation of other devices. The SJ100 features a PID loop feature. PID loops are usually associated with chemical processes, heating, or process industries in general. How could the PID…
  • Page 45
    Inverter Mounting and Installation In This Chapter… — Orientation to Inverter Features — Basic System Description — Step-by-Step Basic — Powerup Test — Using the Front Panel Keypad Installation… page…
  • Page 46: Orientation To Inverter Features

    Orientation to Inverter Features Unpacking and Inspection Please take a few moments to unpack your new SJ100 inverter and perform these steps: 1. Look for any damage that may have occurred during shipping. 2. Verify the contents of the box include: a.

  • Page 47
    Then adhere the remaining trip code label to the area beside the connectors. Be careful not to cover the screw access on models like the one shown. 2–3 SJ100 Inverter Controls for mode and parameter changes…
  • Page 48
    2–4 Orientation to Inverter Features 3. Third-level access — First, ensure no power source of any kind is connected to the inverter. If power has been connected, wait five minutes after powerdown and verify the Power LED is OFF to proceed. Then locate the recessed retention screw on the left side main front panel (it is along the left hinge area on some models, or behind…
  • Page 49: Basic System Description

    Input-side This is useful in suppressing harmonics induced on the AC Reactor power supply lines and for improving the power factor. WARNING: Some applications must use an input- side AC reactor to prevent inverter damage. See Warning on next page.

  • Page 50: Step-By-Step Basic Installation

    MUST install an input-side AC reactor of 3% (at a voltage drop at rated current) with respect to the supply voltage on the power supply side. Also, where the effects of an indirect lightning strike are possible, install a lightning conductor.

  • Page 51
    2–7 SJ100 Inverter Choosing a Mounting Location Step 1: Study the following caution messages associated with mounting the inverter. This is the time when mistakes are most likely to occur that will result in expensive rework, equipment damage, or personal injury.
  • Page 52
    Remember to remove the top cover (unless the installation is to have a NEMA rating)! 2. Keep any other heat-producing equipment as far away from the inverter as possible. 10 cm (3.94”) minimum 12 cm (4.72”) SJ100 minimum 10 cm (3.94”) minimum Air flow Top cover…
  • Page 53
    107 (4.21) -005NFE NOTE: Some inverter housings require two mounting screws, while others require four. Be sure to use lock washers or other means to ensure screws do not loosen due to vibration. SJ100 Inverter 67(2.64) 5(0.20) 4(0.16) 80(3.15) 2–9…
  • Page 54
    2–10 Step-by-Step Basic Installation Dimensional drawings, continued… External Dimensions MODEL SJ 100 -004HFE -004HFU -007NFE -007NFU -011NFE MODEL SJ 100 -007HFE(No fan) -007HFU(No fan) -015HFE -015HFU -022HFE -022HFU 5(0.20) Ground Terminal 98(3.86) 5(0.20) 5(0.20) 110(4.33) 4(0.16) Ground Terminal 98(3.86) 5(0.20) 110(4.33) 4(0.16)
  • Page 55
    Dimensional drawings, continued… SJ100 -015NFE -015NFU SJ100 -022NFE -022NFU -030HFE -037LFU -040HFE -040HFU Ground Terminal 140(5.51) 128(5.04) 5(0.20) 5(0.20) 140(5.51) 128(5.04) 5(0.20) 5(0.20) 2–11 SJ100 Inverter Ground Terminal…
  • Page 56
    2–12 Step-by-Step Basic Installation Dimensional drawings, continued… SJ100 -055LFU -055HFE -055HFU -075LFU -075HFE -075HFU 182 (7.17) 160 (6.30) 7 (0.28) NOTE: Model SJ100-075LFU has (2) fans. All other models in this housing have (1) fan. 7 (0.28) Ground Terminal…
  • Page 57
    HIGH VOLTAGE: Wiring work shall be carried out only by qualified personnel. Oth- erwise, there is a danger of electric shock and/or fire. HIGH VOLTAGE: Implement wiring after checking that the power supply is OFF. Otherwise, you may incur electric shock and/or fire.
  • Page 58: Basic System Description

    The “Signal Lines” column applies to any wire connecting to the two green 8-position connectors just inside the front panel half-door. Motor Output (kW/HP) Inverter Model SJ100-002NFE/NFU SJ100-004NFE/NFU 0.55 SJ100-005NFE 0.75 SJ100-007NFE/NFU…

  • Page 59
    Terminal Dimensions and Torque Specs The terminal screw dimensions for all SJ100 inverters are listed in table below. This information is useful in sizing spade lug or ring lug connectors for wire terminations. CAUTION: Fasten the screws with the specified fastening torque in the table below.
  • Page 60
    2–16 Step-by-Step Basic Installation Please use the terminal arrangement below corresponding to your inverter model. –002NFE/NFU, –004NFE/NFU, –005NFE –007 to 022NFE/NFU, –037LFU, 004 to 040HFE/HFU –055LFU, –075LFU, 055HFE/HFU, 075HFE/HFU NOTE: An inverter powered by a portable power generator may receive a distorted power waveform, overheating the generator.
  • Page 61
    Ground fault interrupters in the power input wiring of an inverter are not an absolute protection against electric shock. CAUTION: Be sure to install a fuse in each phase of the main power supply to the inverter. Otherwise, there is the danger of fire.
  • Page 62
    2–18 Step-by-Step Basic Installation Wire the Inverter Output to Motor Step 7: The process of motor selection is beyond the scope of this manual. However, it must be an AC induction motor with three phases. It should also come with a chassis ground lug.
  • Page 63: Powerup Test

    • The inverter is connected to a power source and motor. • No additional wiring of inverter connectors or terminals has been done. • The power supply is reliable, and the motor is a known working unit, and the motor nameplate ratings match the inverter ratings.

  • Page 64
    Please study the following instructions and messages before proceeding with the powerup test. 1. The power supply must have fusing suitable for the load. Check the fuse size chart presented in Step 5, if necessary. 2. Be sure you have access to a disconnect switch for the drive input power if necessary.
  • Page 65: Using The Front Panel Keypad

    • Potentiometer — Allows an operator to directly set the motor speed when the potenti- ometer is enabled for output frequency control. • Potentiometer Enable LED — ON when the potentiometer is enabled for value entry. SJ100 Inverter Power LED POWER…

  • Page 66
    2–22 Using the Front Panel Keypad • Parameter Display — A 4-digit, 7-segment display for parameters and function codes. • Display Units, Hertz/Amperes — One of these LEDs will be ON to indicate the units associated with the parameter display. •…
  • Page 67: Powerup Test

    Keypad Navigational Map The SJ100 Series inverter drives have many programmable functions and parameters. Chapter 3 will cover these in detail, but you need to access just a few items to perform the powerup test. The menu structure makes use of function codes and parameter codes to allow programming and monitoring with only a 4-digit display and a few keys and LEDs.

  • Page 68: Using The Front Panel Keypad

    2–24 Using the Front Panel Keypad Selecting Functions and Editing Parameters In order to run the motor for the powerup test, this section will show how to: • select the inverter’s maximum output frequency to the motor • select the keypad potentiometer as the source of motor speed command •…

  • Page 69
    Run Enable LED above the RUN switch on the keypad will turn ON. This is normal, and does not mean the motor is trying to run. It means that the RUN key is now enabled. DO NOT press the RUN key at this time—finish out the programming exercise first. SJ100 Inverter Display Func./Parameter…
  • Page 70
    2–26 Using the Front Panel Keypad Configure the Inverter for the Number of Motor Poles- The number of magnetic poles of a motor is determined by the motor’s internal winding arrangement. The specifi- cations label on the motor usually indicates its number of poles. For proper operation, verify the parameter setting matches the motor poles.
  • Page 71: Running The Motor

    7. Slowly increase the potentiometer setting in clockwise fashion. The motor should start turning when the indicator is in the 9:00 position and beyond. 8. Press the STOP key to stop the motor rotation. SJ100 Inverter HITACHI 5 0.0 STOP RESET 2–23.

  • Page 72
    NOTE: Some factory automation devices such as PLCs have alternate Run/Program modes; the device is in either one mode or the other. In the Hitachi inverter, however, Run Mode alternates with Stop Mode, and Program Mode alternates with Monitor Mode.
  • Page 73: Configuring Drive Parameters

    Configuring Drive Parameters In This Chapter… — Choosing a Programming Device — Using Keypad Devices — “D” Group: Monitoring — “F” Group: Main Profile Parameters — “A” Group: Standard Functions — “B” Group: Fine Tuning Functions — “C” Group: Intelligent Terminal —…

  • Page 74: Choosing A Programming Device

    Therefore, it is okay to begin running the motor with a loosely tuned system. By making specific, individual changes and observing their effects, you can achieve a finely tuned system. And, the SJ100 Series inverters have a built-in auto-tuning algorithm to set certain motor parameters.

  • Page 75: Using Keypad Devices

    Using Keypad Devices Inverter Front Panel Keypad The SJ100 Series inverter front keypad contains all the elements for both monitoring and programming parameters. The keypad layout is pictured below. All other programming devices for the inverter have a similar key arrangement and function.

  • Page 76
    3–4 Using Keypad Devices Keypad Navigational Map You can use the inverter’s front panel keypad to navigate to any parameter or function. The diagram below shows the basic navigational map to access these items. Monitor Mode PRG LED=OFF Display Data 0 0 0.0 FUNC.
  • Page 77: Operational Modes

    Please refer to “Software Lock Mode” on page 3–28 Control Algorithms The motor control program in the SJ100 inverter has three sinusoidal PWM switch- ing algorithms. The intent is that you select the best algorithm for the motor characteris- tics in your application.

  • Page 78: D» Group: Monitoring Functions

    3–6 “D” Group: Monitoring Functions “D” Group: Monitoring Functions Parameter Monitoring Functions You can access important system parameter values with the “D” Group monitoring functions, whether the inverter is in Run Mode or Stop Mode. After selecting the function code number for the parameter you want to monitor, press the Function key once to show the value on the display.

  • Page 79
    EEPROM 0.0Hz 0.0A EEPROM 0.0Hz 0.0A Displays total time the inverter has been in RUN mode in hours. 000000H Displays cumulative number of trip events. 3–7 SJ100 Inverter Range Mode Edit Units — Range Mode Edit Units — — —…
  • Page 80: F» Group: Main Profile Parameters

    3–8 “F” Group: Main Profile Parameters “F” Group: Main Profile Parameters The basic frequency (speed) profile is defined by parameters contained in the “F” Group as shown to the right. The set running frequency is in Hz, but accelera- tion and deceleration are specified in the time duration of the ramp (from zero to maximum frequency, or from maximum frequency to zero).

  • Page 81: A» Group: Standard Functions

    A 04 100% Constant torque Maximum Frequency “Configuring the Inverter for Multiple Mode Description Edit ✘ ✘ digital operator ✘ 3–9 SJ100 Inverter A 03 A 04 Base frequency = maximum frequency Defaults –FE –FU –FR Units (CE) (UL) (Jpn) —…

  • Page 82
    3–10 “A” Group: Standard Functions “A” Function Func. Name / Code SRW Display A203 Base frequency setting, 2nd motor 2F-BASE 060Hz A_04 Maximum frequency setting F-MAX 060Hz A204 Maximum frequency setting, 2nd motor 2F-MAX 060Hz Analog Input Settings The inverter has the capability to accept an external analog input that can command the output frequency to the motor.
  • Page 83
    IN F-SAMP Multi-speed and Jog Frequency Setting The SJ100 inverter has the capability to store and output up to 16 preset frequencies to the motor (A_20 to A_35). As in traditional motion terminology, we call this multi-speed profile capability. These preset frequencies are selected by means of digital inputs to the inverter.
  • Page 84
    3–12 “A” Group: Standard Functions “A” Function Func. Name / Code SRW Display A_20 Multi-speed frequency setting SPD FS 000.0Hz A220 Multi-speed frequency setting, 2nd motor SPD 2FS 000.0Hz A_21 Multi-speed frequency settings A_35 (for both motors) SPD 1 000.0Hz SPD 2 000.0Hz SPD 3…
  • Page 85
    V/f ratio (shown at right). The boost is applied from zero to 1/2 the base frequency. You set the breakpoint of the boost (point A on the graph) by using SJ100 Inverter Inverter Torque Control Algorithms V/f control, constant torque…
  • Page 86
    3–14 “A” Group: Standard Functions parameters A_42 and A_43. The manual boost is calculated as an addition to the standard straight V/f line (constant torque curve). NOTE: Manual torque boost is not operational when sensorless vector control is in use. Be aware that running the motor at a low speed for a long time can cause motor overheating.
  • Page 87
    00… Constant torque 2CONTROL 01… Reduced torque 02… Sensorless vector control A_45 V/f gain setting Sets voltage gain of the inverter from 50 to 100% V-Gain 100% SJ100 Inverter Mode –FE Description Edit (CE) ✘ ✘ ✔ ✔…
  • Page 88
    3–16 “A” Group: Standard Functions DC Braking Settings The DC braking feature can provide additional stopping torque when compared to a normal deceleration to a stop. DC braking is particularly useful at low speeds when normal decelera- tion torque is minimal. When you enable DC braking, the inverter injects a DC voltage into the motor windings during deceleration below a frequency you can specify (A_52).
  • Page 89
    A_62 Frequency lower limit Sets a limit on output setting frequency greater than zero Range is 0.5 to 360.0 Hz LIMIT L 000.0Hz 0.0.. setting is disabled >0.1 setting is enabled SJ100 Inverter Output frequency Upper A 61 limit Lower A 62 limit…
  • Page 90
    3–18 “A” Group: Standard Functions Jump Frequencies – Some motors or machines exhibit resonances at particular speed(s), which can be destructive for prolonged running at those speeds. The inverter has up to three jump frequencies as shown in the graph. The hysteresis around the jump frequencies causes the inverter output to skip around the sensitive frequency values.
  • Page 91: Pid Control

    01… [O] terminal (voltage in) NOTE: The setting A_73 for the integrator is the integrator’s time constant Ti, not the gain. The integrator gain Ki = 1/Ti. When you set A_73 = 0, the integrator is disabled. SJ100 Inverter for more information. Mode –FE…

  • Page 92
    3–20 “A” Group: Standard Functions Automatic Voltage Regulation (AVR) Function The automatic voltage regulation (AVR) feature keeps the inverter output waveform at a relatively constant amplitude during power input fluctuations. This can be useful if the installation is subject to input voltage fluctuations. However, the inverter cannot boost its motor output to a voltage higher than the power input voltage.
  • Page 93
    Second Acceleration and Deceleration Functions The SJ100 inverter features two-stage acceleration and deceleration ramps. This gives flexibility in the profile shape. You can specify the frequency transition point, the point at which the standard acceleration (F_02) or deceleration (F_03) changes to the second acceleration (A_92) or deceleration (A_93).
  • Page 94
    3–22 “A” Group: Standard Functions “A” Function Func. Name / Code SRW Display A_95 Acc1 to Acc2 frequency transition point ACC CHFr 000.0Hz A295 Acc1 to Acc2 frequency transition point, 2nd motor 2ACCCHFr 000.0Hz A_96 Dec1 to Dec2 frequency transition point DEC CHFr 000.0Hz A296 Dec1 to Dec2 frequency transition point, 2nd…
  • Page 95
    00… linear ACCEL LINE 01… S-curve A_98 Deceleration curve Set the characteristic curve of selection Acc1 and Acc2, two options: 00… linear DEC LINE 01… S-curve SJ100 Inverter Output frequency Accel. curve selection Target freq. Acceleration period Mode –FE Description…
  • Page 96: B» Group: Fine Tuning Functions

    3–24 “B” Group: Fine Tuning Functions “B” Group: Fine Tuning Functions The “B” Group of functions and parameters adjust some of the more subtle but useful aspects of motor control and system configuration. Automatic Restart Mode The restart mode determines how the inverter will resume operation after a fault causes a trip event.

  • Page 97
    (if applicable) as shown in the following table. Mode Description Edit ✘ no automatic restart frequency matching ✘ ✘ Torque Constant torque 100% 3–25 SJ100 Inverter Defaults –FE –FU –FR Units (CE) (UL) (Jpn) — sec. sec. B_13 = 01 Reduced…
  • Page 98
    3–26 “B” Group: Fine Tuning Functions “B” Function Func. Name / Code SRW Display B_12 Level of electronic thermal setting E-THM LVL 03.00A B212 Level of electronic thermal setting, 2nd motor 2E-THMLVL 03.00A B_13 Electronic thermal characteristic E-THM CHAR B213 Electronic thermal characteristic, 2nd motor 2E-THMCHAR…
  • Page 99
    1% of rated current B_23 Deceleration rate at Sets the deceleration rate when overload restriction inverter detects overload, range is 0.1 to 30.0, resolution is 0.1. OLOAD CONST 01.0 SJ100 Inverter Motor Current Restriction area B 22 Output frequency…
  • Page 100
    3–28 “B” Group: Fine Tuning Functions Software Lock Mode The software lock function keeps personnel from accidentally changing parameters in the inverter memory. Use B_31 to select from various protection levels. The table below lists all combinations of B_31 option codes and the ON/OFF state of the [SFT] input.
  • Page 101
    B_31 and output frequency F_01 setting are locked NOTE: To disable parameter editing when using B_31 lock modes 00 and 01, assign the [SFT] function to one of the intelligent input terminals. “Software Lock” on page SJ100 Inverter Mode –FE Description Edit (CE) ✘…
  • Page 102
    3–30 “B” Group: Fine Tuning Functions Miscellaneous Settings The miscellaneous settings include scaling factors, initialization modes, and others. this section covers some of the most important settings you may need to configure. B_83: Carrier frequency adjustment – The internal switching frequency of the inverter circuitry (also called the chopper frequency).
  • Page 103
    0.1 to 99.9 /Hz01.0 0.00 B_87 STOP key enable Select whether the STOP key on the keypad is enabled, two STOP-SW option codes: 00… enabled 01… disabled SJ100 Inverter Mode –FE Description Edit (CE) ✔ ✘ ✘ ✘…
  • Page 104
    3–32 “B” Group: Fine Tuning Functions B_91/B_88: Stop Mode / Restart Mode Configuration – You can configure how the inverter performs a standard stop (each time Run FWD and REV signals turn OFF). Setting B_91 determines whether the inverter will control the deceleration, or whether it will perform a free-run stop (coast to a stop).
  • Page 105
    “Dynamic Braking” on page 5–5 braking accessories. Mode Description Edit ✘ ✔ terminals (D_05) terminals (D_06) (D_07) ✘ ✘ ✘ OFF during stop for more information on dynamic 3–33 SJ100 Inverter Defaults –FE –FU –FR Units (CE) (UL) (Jpn) — — — —…
  • Page 106: C» Group: Intelligent Terminal Functions

    Functions and Options –The function codes in the following table let you assign one of nineteen options to any of the six logic inputs for the SJ100 inverters. The functions C_01through C_06 configure the terminals [1] through [6] respectively. The “value” of these particular parameters is not a scalar value, but it is a discrete number that selects one option from many available options.

  • Page 107
    (such as [FW]) to show the assigned option. The option codes for C_11 to C_16 determines the active state of the logical input (active high or active low). SJ100 Inverter Mode –FE Description…
  • Page 108
    3–36 “C” Group: Intelligent Terminal Functions Input Function Summary Table – This table shows all nineteen intelligent input functions at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in page 4–8. Option Terminal Function Name Code…
  • Page 109
    F_01 or change the value of F_01 while the inverter is in Run Mode (motor running). If it is necessary to check the value of F_01 during Run Mode, please monitor D_01 instead of F_01. SJ100 Inverter Description On powerup, the inverter will not resume a Run…
  • Page 110
    3–38 “C” Group: Intelligent Terminal Functions Output Terminal Configuration The inverter provides configuration for logic (discrete) and analog outputs, shown in the table below. “C” Function Func. Name / Code SRW Display C_21 Terminal [11] function OUT-TM 1 C_22 Terminal [12] function OUT-TM 2 C_23 [FM] signal selection MONITOR…
  • Page 111
    PID error is less than the set threshold for the deviation signal when an alarm signal has occurred and has not been cleared when no alarm has occurred since the last clearing of alarm(s) 3–39 SJ100 Inverter “Using Intelligent…
  • Page 112
    3–40 “C” Group: Intelligent Terminal Functions Analog Function Summary Table – This table shows all three functions for the analog output [FM] (frequency meter) terminal. Detailed descriptions, related parameters and settings, and example wiring diagrams are in page 4–33. Option Function Name Code Analog Frequency…
  • Page 113
    C_42 Frequency arrival Sets the frequency arrival setting for acceleration setting threshold for the output frequency during acceleration ARV ACC 000.0Hz SJ100 Inverter Motor current C 41 Overload signal Output frequency C 42 Arrival signal PID Error (PV–SP) deviation threshold…
  • Page 114
    3–42 “C” Group: Intelligent Terminal Functions “C” Function Func. Name / Code SRW Display C_43 Arrival frequency setting for deceleration ARV DEC 000.0Hz C_44 PID deviation level setting OV PID 003.0% C_81 O input span calibration Scale factor between the ADJ-O C_82 OI input span calibra- tion…
  • Page 115: H» Group: Motor Constants Functions

    (SLV) control “Restoring Factory Default Settings” on page 4–35. Please read these before trying to auto- Mode Description Edit ✘ ✘ ✘ ✘ ✘ ✘ 3–43 SJ100 Inverter A 44 Output 6–8. “Auto-tuning Defaults –FE –FU –FR Units (CE) (UL) (Jpn) —…

  • Page 116
    3–44 “H” Group: Motor Constants Functions “H” Function Func. Name / Code SRW Display H204 Motor poles setting, 2nd motor 2AUXP H_05 Motor speed constant AUX KP H205 Motor speed constant, 2nd motor 2AUXKP H_06 Motor stabilization constant AUX KCD H206 Motor stabilization constant, 2nd motor 2AUXKCD…
  • Page 117
    H_34 Auto-tuned motor Auto-tuning data (do not edit) constant J (not displayed) H234 Auto-tuned motor Auto-tuning data (do not edit) constant J, 2nd motor (not displayed) SJ100 Inverter Mode –FE Description Edit (CE) ✘ Factory set according to inverter model ✘…
  • Page 118
    Operations and Monitoring In This Chapter… — Introduction — Connecting to PLCs and Other Devices — Using Intelligent Input Terminals — Using Intelligent Output Terminals — Analog Input Operation — Analog and Digital Monitor Output — Auto-tuning for Sensorless Vector Control —…
  • Page 119: Introduction

    This chapter shows the parameters and input/output terminals associated with PID loop operation. 6. Multiple motors – A single SJ100 inverter may be used with two or more motors in some types of applications. This chapter shows the electrical connections and inverter parameters involved in multiple-motor applications.

  • Page 120
    Otherwise, it may cause injury to personnel. WARNING: If the power supply is cut OFF for a short period of time, the inverter may restart operation after the power supply recovers if the Run command is active. If a restart may pose danger to personnel, so be sure to use a lock-out circuit so that it will not restart after power recovery.
  • Page 121: Connecting To Plcs And Other Devices

    Connecting to PLCs and Other Devices Connecting to PLCs and Other Devices Hitachi inverters (drives) are useful in many types of applications. During installation, the inverter keypad (or other programming device) will facilitate the initial configura- tion. After installation, the inverter will generally receive its control commands through the control logic connector or serial interface from another controlling device.

  • Page 122: Example Wiring Diagram

    N(L3) (T3) Input – circuits – [5] configurable as discrete input or thermistor input Output circuits 4–5 SJ100 Inverter Motor DC reactor (optional) Braking unit (optional) Braking resistor (optional) Alarm contacts, type 1 Form C Open collector outputs Run signal Load Freq.

  • Page 123
    4–6 Example Wiring Diagram Specifications of Control and Logic Connections The control logic connectors are located just behind the front panel half-door. The relay contacts are accessible behind the main door. Connector labeling is shown below. Logic inputs Specifications for the logic connection terminals are in the following table: Terminal Name [P24] +24V for logic inputs…
  • Page 124
    Terminal Listing Use the following tables to locate pages for intelligent input and output material in this chapter. Symbol Code Symbol Code SJ100 Inverter Intelligent Inputs Name Forward Run/Stop Reverse Run/Stop Multi-speed Select, Bit 0 (LSB) Multi-speed Select, Bit 1…
  • Page 125: Using Intelligent Input Terminals

    The input circuits can use the inverter’s internal (isolated) +24V field supply (P24) to power the inputs. The input circuits are internally connected to the power supply ground. As the diagram shows, you can use a switch (or jumper) to activate an input terminal that has been configured.

  • Page 126
    WARNING: If the power is turned ON and the Run command is already active, the motor starts rotation and is dangerous! Before turning power ON, confirm that the Run command is not active. SJ100 Inverter State Description Inverter is in Run Mode, motor runs forward…
  • Page 127
    4–10 Using Intelligent Input Terminals Multi-Speed Select The inverter can store up to 16 different target frequencies (speeds) that the motor output uses for steady-state run condition. These speeds are acces- sible through programming four of the intelligent terminals as binary-encoded inputs CF1 to CF4 per the table to the right.
  • Page 128
    A_20 to A_35 in the first procedure 1. a) to 1. d). Input State Example (some CF inputs require input configuration; some are default inputs—see page 3–34): See I/O specs on page 4–6. keys to edit the value. 4–11 SJ100 Inverter Description (MSB) (LSB) keys.
  • Page 129
    4–12 Using Intelligent Input Terminals Jogging Command The Jog input [JG] is used to command the motor to rotate slowly in small increments for manual operation. The speed is limited to 10 Hz. The frequency for the jogging opera- tion is set by parameter A_38. Jogging does not use an acceleration ramp, so we recom- mend setting the jogging frequency A_38 to 5 Hz or less to prevent tripping.
  • Page 130
    Do not use the [DB] feature for continuous or high duty cycle as a holding brake. The [DB] input is designed to improve stopping performance. Use a mechanical brake for holding a stop position. SJ100 Inverter [FW, RV] [DB] Output…
  • Page 131: Set Second Motor

    4–14 Using Intelligent Input Terminals Set Second Motor If you assign the [SET] function to an intelligent input terminal, you can select between two sets of motor parameters. The second parameters store an alternate set of motor characteristics. When the terminal [SET] is turned ON, the inverter will use the second set of parameters to generate the frequency output to the motor.

  • Page 132
    Notes: • Function A_94 selects the method for second stage acceleration. It must be set = 00 to select the input terminal method in order for the [2CH] terminal assignment to operate. SJ100 Inverter Output frequency second initial [2CH] [FW],…
  • Page 133
    4–16 Using Intelligent Input Terminals Free-run Stop When the terminal [FRS] is turned ON, the inverter stops the output and the motor enters the free-run state (coasting). If terminal [FRS] is turned OFF, the output resumes sending power to the motor if the Run command is still active. The free-run stop feature works with other parameters to provide flexibility in stopping and starting motor rotation.
  • Page 134: External Trip

    When assigned input transitions OFF to ON, inverter latches trip event and displays E12 No trip event for ON to OFF, any recorded trip events remain in history until Reset Example (requires input configuration— see page 3–34): See I/O specs on page 4–6. 4–17 SJ100 Inverter…

  • Page 135: Unattended Start Protection

    OFF the Run command per this example (or applying a reset). Then the Run command can turn ON again and start the inverter output. RUN command [FW, RV] [USP] terminal Alarm output terminal Inverter output frequency Inverter power supply Option Terminal Function Name Code Symbol…

  • Page 136: Software Lock

    Software lock can include the output frequency by setting B_31. • Software lock by the operator is also possible without the [SFT] terminal being used (B_31). SJ100 Inverter Input Description State The keypad and remote programming devices are prevented from changing parameters The parameters may be edited and stored Example (requires input configuration—see…

  • Page 137: Analog Input Operation

    Input Description State Terminal OI is enabled for current input (uses terminal L for power supply return) Terminal O is enabled for voltage input (uses terminal L for power supply return) Example (default input configuration shown for –FU models; –FE and –FR models require input configuration—see page 3–34):…

  • Page 138: Reset Inverter

    The Stop/Reset key on the inverter is only operational for a few seconds after inverter powerup when a hand-held remote operator is connected to the inverter. • If the [RS] terminal is turned ON while the motor is running, the motor will be free running (coasting). SJ100 Inverter [RS] approx. 30 ms Alarm…

  • Page 139: Thermistor Thermal Protection

    4–22 Using Intelligent Input Terminals Thermistor Thermal Protection Motors that are equipped with a thermistor can be protected from overheating. Input terminal [5] has the unique ability to sense a thermistor resistance. When the resistance value of the thermistor connected to terminal [TH] (5) and [L] is more than 3 k Ohms ±10%, the inverter enters the Trip Mode, turns OFF the output to the motor, and indicates the trip status E35.

  • Page 140
    A_04 (maximum frequency setting). • The minimum ON time of [UP] and [DWN] is 50 ms. • This setting modifies the inverter speed from using F_01 output frequency setting as a starting point. SJ100 Inverter Input Description State Accelerates (increases output frequency) motor…
  • Page 141: Using Intelligent Output Terminals

    Be sure to use a diode across the coil of the relay as shown (reverse-biased) in order to suppress the turn-off spike, or use a solid-state relay. SJ100 Inverter Open collector outputs Logic output common – Load Load…

  • Page 142: Run Signal

    NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode to prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s output transistor. SJ100 Inverter [FW], [RV] B 82 Output start freq.

  • Page 143
    4–26 Using Intelligent Output Terminals Frequency Arrival Signals The Frequency Arrival group of outputs help coordinate external systems with the current velocity profile of the inverter. As the name implies, output [FA1] turns ON when the output frequency arrives at the standard set frequency (parameter F_01). Output [FA2] relies on programmable accel/ decel thresholds for increased flexibility.
  • Page 144
    60 ms delay after the frequency thresholds are crossed. Having different accel and decel thresholds provides an asymmetrical output function. However, you can use equal ON and OFF thresholds, if desired. SJ100 Inverter Output 1.5 Hz freq. 0.5 Hz F 01 0.5 Hz…
  • Page 145: Overload Advance Notice Signal

    4–28 Using Intelligent Output Terminals Overload Advance Notice Signal When the output current exceeds a preset value, the [OL] terminal signal turns ON. The parameter C_41 sets the overload threshold. The overload detection circuit operates during powered motor opera- tion and during regenerative braking. The output circuits use open-collector transistors, and are active low.

  • Page 146: Output Deviation For Pid Control

    PID error is less than the set threshold for the deviation signal Example (requires output configuration— see page 3–38): Inverter output terminal circuit H O OI See I/O specs on page 4–6. 4–29 SJ100 Inverter Process variable Setpoint Description FM CM2 12 11 –…

  • Page 147: Alarm Signal

    [AL] are different from the contact output terminals [AL0], [AL1], [AL2]. • When the inverter power supply is turned OFF, the alarm signal output is valid as long as the external control circuit has power. •…

  • Page 148
    N.O. contact (inverted by C_33 setting) During normal running or power is turned OFF AL0- Contact Power N.O. Open (set Closed C_33=00) Closed 4–31 SJ100 Inverter When an alarm occurs AL0- AL0- State Normal Open Closed Trip Closed Open — Open…
  • Page 149: Analog Input Operation

    4–32 Analog Input Operation Analog Input Operation The SJ100 inverters provide for analog input to command the inverter frequency output value. The analog input terminal group includes the [L], [OI], [O], and [H] terminals on the control connector, which provide for Voltage [O] or Current [OI] input.

  • Page 150: Analog And Digital Monitor Output

    Waveform H O OI C_23 = 00 C_23 = 01 B 81 T = 4 ms 4–33 SJ100 Inverter FM CM2 12 11 Full Scale value 0 – Max. frequency (Hz) 0 – 200% 0 – Max. frequency (Hz) FM CM2 12 11 –…

  • Page 151
    4–34 Analog and Digital Monitor Output TIP: When using the analog meter for monitoring, adjust the meter so it has a zero reading when the [FM] output is zero. Then use scale factor B_81 to adjust the [FM] output so the maximum frequency in the inverter corresponds to a full-scale reading on the meter.
  • Page 152: Auto-Tuning For Sensorless Vector Control

    Auto-tuning for Sensorless Vector Control The SJ100 inverter has a built-in auto-tuning algorithm. Its purpose is to detect and record the motor parameters to use in sensorless vector control. As you may recall from Chapter 3, sensorless vector control (SLV) is the more sophisticated control algorithm the SJ100 inverter can use to deliver higher torque levels at different speeds.

  • Page 153
    4–36 Auto-tuning for Sensorless Vector Control Parameter Step Code Name A_82 AVR voltage select Select output voltage for motor A_51 DC braking enable Set = 00 to disable DC braking H_01 Auto-tuning Setting — — — — — — NOTE: During step 11, the motor will make a slight humming sound during the AC and DC excitation (A and B) steps of the auto-tuning process.
  • Page 154
    Be sure the motor is stopped before you carry out an auto-tuning procedure. Auto-tuning data that is derived while the motor is still running may not be correct. SJ100 Inverter Adjustment Increase the motor speed constant R1 step by step, up to 1.2 times initial value.
  • Page 155
    4–38 Auto-tuning for Sensorless Vector Control Note 6: Do not interrupt the auto-tuning procedure by removing power or by using the Stop command, unless it is an emergency. If this does occur, initialize the inverter’s parameters to the factory default settings (see Default Settings”…
  • Page 156: Pid Loop Operation

    ∑ Process Variable (Feedback) Analog input scaling A 12 A 11 A 15 A 13 A 14 PID V/I input select 4–39 SJ100 Inverter External Motor Process Sensor Scale factor A 75 F 01 P gain A 72 Frequency setting I gain ∑…

  • Page 157: Configuring The Inverter For Multiple Motors

    (fault) events. • Sometimes the slower version of the machine does not have special braking options, but a higher performance version does have braking features. SJ100 U/T1 V/T2…

  • Page 158
    Motor capacity Motor poles setting Motor constant R1 Motor constant R2 Motor constant L Motor constant I Motor constant J Motor speed constant Motor stabilization constant 4–41 SJ100 Inverter Parameter Codes 1st motor 2nd motor A_20 A220 F_02 F202 F_03 F203…
  • Page 159: Chapter 5: Inverter System Accessories

    Inverter System Accessories In This Chapter… — Introduction — Component — Dynamic Braking Descriptions… page…

  • Page 160
    Combination: ALI–x2–xxx LPF–xxx R–2–xxx Note: The Hitachi part number series for accesso- ries includes different sizes of each part type, specified by the –x suffix. Hitachi product litera- ture can help match size and rating of your inverter to the proper accessory size.
  • Page 161: Component Descriptions

    • If the unbalanced factor of the power supply is 3% or higher • If the power supply capacity is at least 10 times greater than the inverter capacity (the power supply capacity is 500 kVA or more) •…

  • Page 162
    EMI Filter The EMI filter reduces the conducted noise on the power supply wiring generated by the inverter. Connect the EMI filter to the inverter primary (input side). The FFL100 series filter is required for compliance to the EMC Class A directive (Europe) and C-TICK (Australia).
  • Page 163: Dynamic Braking

    In many applications, the over-voltage condi- tion serves as a warning signal that we have exceeded the deceleration capabilities of the system. SJ100 inverters have a built-in braking unit, which sends the regenerative energy from the motor during deceleration to the optional braking resistor(s).

  • Page 164
    5–6 Dynamic Braking Dynamic Braking Usage Ratio The inverter controls braking via a duty cycle method (percent of the time braking is ON versus total time). Parameter B_90 sets the dynamic braking usage ratio. In the graph to the right, the example shows three uses of dynamic braking in a 100-second period.
  • Page 165
    SJ100 Dynamic Braking Selection Tables The SJ100 series inverter models have internal braking units. Additional stopping torque is available by adding external resistors. The required braking torque depends on your particular application. Other tables in this section will help you choose the proper resistor.
  • Page 166
    The example diagram shows a parallel configuration. Please refer to the braking resistor documentation for detailed wiring diagrams. 200V Class JRB Series SJ100 Type & Total Model (Qty) Ohms Number 002NFE/NFU 120–1…
  • Page 167
    Selecting Braking Resistors for External Braking Units 200V Class Inverters – The following tables specify the braking options for 200V class SJ100 inverters and the braking torque for each option. You can connect a single braking unit to the inverter, or two braking units for additional stopping torque.
  • Page 168
    Note the column meanings in the tables: • Column “A” = Average braking torque from 60 Hz to 3 Hz. • Column “B” = Average braking torque from 120 Hz to 3 Hz. SJ100 Inverter 200V Models Braking torque Model Number…
  • Page 169
    400V Class Inverters –The following tables specify the braking options for 400V class SJ100 inverters and the braking torque for each option. You can connect a single braking unit to the inverter, or two braking units for additional braking torque.
  • Page 170: Troubleshooting

    Troubleshooting and Maintenance In This Chapter… — Troubleshooting… — Monitoring Trip Events, History, & Conditions — Restoring Factory Default Settings — Maintenance and Inspection — Warranty… page…

  • Page 171: Troubleshooting

    Please read the following safety messages before troubleshooting or performing mainte- nance on the inverter and motor system. WARNING: Wait at least five (5) minutes after turning OFF the input power supply before performing maintenance or an inspection. Otherwise, there is the danger of electric shock.

  • Page 172: Troubleshooting Tips

    [U/T1], [V/T2], and [W/T3]? Are the control terminals [FW] and [RV] wired correctly? Is parameter F_04 properly set? 6–3 SJ100 Inverter Solution • Make sure the parameter setting A_01 is correct. • Make sure the parameter setting A_02 is correct.

  • Page 173
    • Check frequency upper limit setting (A_61) • Increase the motor capacity (both inverter and motor). • Fix power supply problem. • Change the output frequency slightly, or use the jump frequency setting to skip the problem frequency. • Verify the V/f settings match motor specifications.
  • Page 174: Error Codes

    Braking resistor overload E 0 7 Over voltage protection E 0 8 EEPROM error E 0 9 Under-voltage error SJ100 Inverter STOP RESET Fault Trip (setting B_84=00 will clear the trip history but Cause(s) The inverter output was short-circuited, or the motor shaft is locked or has a heavy load.

  • Page 175
    6–6 Monitoring Trip Events, History, & Conditions Error Code E 1 0 CT (current transformer) error E 1 1 CPU error E 2 2 E 1 2 External trip E 1 3 E 1 4 Ground fault E 1 5 Input over-voltage E 2 1 Inverter thermal trip…
  • Page 176
    (n-1) Error exists? E 0 3 FUNC. (n-2) Error exists? E 0 5 No error FUNC. 6–7 SJ100 Inverter and E ) using the FUNC. Trip History history Previous _ _ _ error #1 FUNC. history Previous _ _ _ error #2 FUNC.
  • Page 177: Restoring Factory Default Settings

    6–8 Restoring Factory Default Settings Restoring Factory Default Settings You can restore all inverter parameters to the original factory (default) settings for the intended country of use. After initializing the inverter, use the powerup test in Chapter 2 to get the motor running again. To initialize the inverter, follow the steps below. Use the FUNC.

  • Page 178: Maintenance And Inspection

    ✔ Visual ✔ Visual ✔ Visual ✔ Visual 6–11. 6–9 SJ100 Inverter Criteria Ambient temperature between -10 to 40°C, non-condensing Stable environment for electronic controls 200V class: 200 to 240V 50/60 Hz 400V class: 380 to 460V 50/60 Hz 5 Meg.

  • Page 179: Megger Test

    I/O, analog terminals, etc. Doing so could cause damage to the inverter. CAUTION: Never test the withstand voltage (HIPOT) on the inverter. The inverter has a surge protector between the main circuit terminals above and the chassis ground. Add test jumper wire Disconnect motor wires SJ100 Earth – Motor Megger, 500VDC…

  • Page 180: Spare Parts

    Quantity Symbol Used Spare Variable-frequency Drive Internal Inverter DC Bus – Capacitor Life Curve Operation for 12 hours/day 6–11 SJ100 Inverter Notes 022NF, 030HF, 037LF, 015HF to 075HF • Front case • Key cover • Case • Bottom cover Motor…

  • Page 181
    6–12 Maintenance and Inspection General Inverter Electrical Measurements The following table specifies how to measure key system electrical parameters. The diagrams on the next page show inverter-motor systems and the location of measurement points for these parameters. Circuit location Parameter of measurement Supply voltage –…
  • Page 182
    The voltage to be measured is the funda- mental wave effective voltage. The power to be measured is the total effective power. Single-phase Measurement Diagram Three-phase Measurement Diagram SJ100 Inverter Inverter Inverter 6–13…
  • Page 183
    6–14 Maintenance and Inspection Inverter Output Voltage Measurement Techniques Taking voltage measurements around drives equipment requires the right equipment and a safe approach. You are working with high voltages and high-frequency switching waveforms that are not pure sinusoids. Digital voltmeters will not usually produce reliable readings for these waveforms.
  • Page 184
    ≅ 0 Ω ≅ ∞ Ω ≅ ∞ Ω ≅ 0 Ω ≅ ∞ Ω ≅ 0 Ω ≅ ∞ Ω ≅ 0 Ω 6–15 SJ100 Inverter Measured Part Value – ≅ 0 Ω [–] ≅ ∞ Ω [–] ≅ 0 Ω…
  • Page 185: Warranty

    (2) years from the date of manufacture (“DATE” on product nameplate), or one (1) year from the date of installation, whichever occurs first. The warranty shall cover the repair or replacement, at Hitachi’s sole discretion, of ONLY the inverter that was installed.

  • Page 186: Appendix A: Glossary And Bibliography

    Glossary and Bibliography In This Appendix… — Glossary — Bibliography page…

  • Page 187
    Auto-tuning is a common feature of process controllers with PID loops. Hitachi inverters feature auto tuning to determine motor parameters for optimal commutation. Auto-tuning is avail- able as a special command from a digital operator panel. See also Digital Operator Panel.
  • Page 188
    Digital Operator Panel For Hitachi inverters, “digital operator panel” (DOP) refers first to the operator keypad on the front panel of the inverter. It also includes hand-held remote keypads, which connect to the inverter via a cable.
  • Page 189
    A device that electronically changes DC to AC current through an alternating process of switching the input to the output, inverted and non-inverted. A variable speed drive such as the Hitachi SJ100 is also called an inverter, since it contains three inverter circuits to generate 3-phase output to the motor.
  • Page 190
    The ability of a motor drive to store preset discrete speed levels for the motor, and control motor speed according to the currently selected speed preset. The Hitachi inverters have 16 preset speeds. Motor Load In motor terminology, motor load consists of the inertia of the physical mass that is moved by the motor and the related friction from guiding mechanisms.
  • Page 191
    A–6 Glossary Reactance Rectifier Regenerative Braking Regulation Reverse Torque Rotor Saturation Voltage Sensorless Vector Control Setpoint (SP) Pulse-width modulation: A type of AC adjustable frequency drive that accomplishes frequency and voltage control at the output section (inverter) of the drive. The drive output voltage waveform is at a constant amplitude, and by “chopping”…
  • Page 192
    Hot varies sinusoidally above and below Neutral. This power source is named Single Phase to differentiate it from three-phase power sources. Some Hitachi inverters can accept single phase input power, but they all output three-phase power to the motor. See also Three-phase.
  • Page 193
    The saturation voltage has been decreasing, resulting in less heat dissipation. Hitachi inverters use state-of-the- art semiconductors to provide high performance and reliability in a compact package. See also IGBT and Saturation Voltage.
  • Page 194: Appendix B: Drive Parameter Settings Tables

    Drive Parameter Settings Tables In This Appendix… — Introduction — Parameter Settings for Keypad Entry… page…

  • Page 195
    Parameter Settings for Keypad Entry SJ100 series inverters provide many functions and parameters that can be configured by the user. We recommend that you record all parameters that have been edited, in order to help in troubleshooting or recovery from a loss of parameter data.
  • Page 196: Standard Functions

    Multi-speed 5 setting A_26 Multi-speed 6 setting A_27 Multi-speed 7 setting A_28 Multi-speed 8 setting A_29 Multi-speed 9 setting A_30 Multi-speed 10 setting A_31 Multi-speed 11 setting SJ100 Inverter Default Setting –FR (Europe) (USA) (Japan) 50.0 60.0 60.0 50.0 60.0 60.0 50.0 60.0…

  • Page 197
    B–4 Parameter Settings for Keypad Entry “A” Group Parameters Func. Name Code A_32 Multi-speed 12 setting A_33 Multi-speed 13 setting A_34 Multi-speed 14 setting A_35 Multi-speed 15 setting A_38 Jog frequency setting A_39 Jog stop mode A_41 Torque boost method selection A241 Torque boost method selection, 2nd motor…
  • Page 198
    2nd motor A_96 Dec1 to Dec2 frequency transi- tion point A296 Dec1 to Dec2 frequency transi- tion point, 2nd motor A_97 Acceleration curve selection A_98 Deceleration curve selection SJ100 Inverter Default Setting –FR (Europe) (USA) (Japan) 1.00 1.00 1.00 230/400 230/460 200/400 15.0…
  • Page 199
    B–6 Parameter Settings for Keypad Entry Fine Tuning Functions “B” Group Parameters Func. Name Code B_01 Selection of automatic restart mode B_02 Allowable under-voltage power failure time B_03 Retry wait time before motor restart B_12 Level of electronic thermal setting B212 Level of electronic thermal setting, 2nd motor…
  • Page 200
    “B” Group Parameters Func. Name Code B_89 Data select for digital op. OPE-J B_90 Dynamic braking usage ratio B_91 Stop mode selection B_92 Cooling fan control SJ100 Inverter Default Setting –FR (Europe) (USA) (Japan) B–7 User Setting…
  • Page 201
    B–8 Parameter Settings for Keypad Entry Intelligent Terminal Functions “C” Group Parameters Func. Name Code C_01 Terminal [1] function C_02 Terminal [2] function C_03 Terminal [3] function C_04 Terminal [4] function C_05 Terminal [5] function C_06 Terminal [6] function C_11 Terminal [1] active state C_12 Terminal [2] active state…
  • Page 202
    H206 Motor stabilization constant, 2nd motor H_20 Motor constant R1 H220 Motor constant R1, 2nd motor H_21 Motor constant R2 H221 Motor constant R2, 2nd motor SJ100 Inverter Default Setting –FR (Europe) (USA) (Japan) 0000 0000 0000 — — —…
  • Page 203: Parameter Settings For Keypad Entry

    B–10 Parameter Settings for Keypad Entry “H” Group Parameters Func. Name Code H_22 Motor constant L H222 Motor constant L, 2nd motor H_23 Motor constant Io H223 Motor constant Io, 2nd motor H_24 Motor Constant J H224 Motor constant J, 2nd motor H_30 Auto-tuned motor constant R1 H230…

  • Page 204: Appendix C: Ce-Emc Installation Guidelines

    CE–EMC Installation Guidelines In This Appendix… — CE–EMC Installation Guidelines — Hitachi EMC Recommendations page…

  • Page 205: Ce-Emc Installation Guidelines

    CE–EMC Installation Guidelines CE–EMC Installation Guidelines You are required to satisfy the EMC directive (89/336/EEC) when using an SJ100 inverter in an EU country. To satisfy the EMC directive and to comply with standard, follow the guidelines in this section.

  • Page 206
    • Ground the filter with a conductor of at least 10 mm • Connect a second grounding conductor, using a separate grounding terminal parallel to the protective conductor. (The cross section of each single protective conductor terminal must be sized for the required nominal load.) C–3 SJ100 Inverter cross-sectional area.
  • Page 207
    C–4 CE–EMC Installation Guidelines SJ100 inverter with footprint-type filter…
  • Page 208
    C–5 SJ100 Inverter SJ100 inverter with book-type filter…
  • Page 209: Hitachi Emc Recommendations

    Failure to observe this precaution could result in bodily injury. Use the following checklist to ensure the inverter is within proper operating ranges and conditions. 1. The power supply to SJ100 inverters must meet these specifications: • Voltage fluctuation ±10% or less • Voltage imbalance ±3% or less •…

  • Page 210: Index

    Index A Group functions 3–9 AC reactors 5–3 Acceleration 1–22, 3–8 characteristic curves 3–23 second function 3–21 two-stage 4–15 Access levels 3–5, 3–28, 4–19 Access to terminals 2–2 Accessories 5–2 Alarm signal 4–30 Algorithms 3–43 Algorithms, torque control 3–5 Ambient temperature 2–8, A–2 Analog input settings 3–10…

  • Page 211
    Index–2 D Group parameters 3–6 DC braking 3–16, 4–12, 4–13, DC link choke 5–4 Deadband A–3 Deceleration 1–22, 3–8, characteristic curves second function 3–21 two-stage 4–15 Default parameter values Default settings restoring 6–8 Derating curves 1–12 Derivative gain 3–19 Digital operator 2–21, 3–3 Digital operator panel A–3…
  • Page 212
    Multi-speed operation 4–10, Multi-speed profiles Multi-speed settings Nameplate 1–4 Navigational map 2–23, trip events A–5 NEMA A–5 NEMA rating Noise filters 5–2 AC reactor Index–3 SJ100 Inverter 3–23 4–6 3–8 6–9 1–4 1–4 3–4 3–6 2–28 3–43 4–35 2–26 2–18 2–9 2–7…
  • Page 213
    Index–4 Open-collector outputs 4–24, Operational modes 3–5 Operator interfaces 1–3 Optional components 2–5 Options 1–2 Output adjustment parameters Output circuits 4–24 Output deviation for PID control Output frequency 3–8 Output overload 3–27 Output terminals 2–18 Overload advance notice signal Overload restriction 3–27 Parameter editing 2–21, Parameter settings tables…
  • Page 214
    6–5 external 4–17 monitoring 6–5 Trip history 6–7 Trip mode 4–21 Troubleshooting tips 6–3 Two-stage accel/decel 4–15 SJ100 Inverter UL instructions Unattended start protection Unpacking 2–2 Up/Down functions V/f control 3–13 Variable torque 3–13 Variable-frequency drives introduction 1–18 Velocity profile 1–22…

  • Страница 1

    HIT A CHI SJ100 Series In ver ter Instruction Man ual • Single-phase Input 200V Class • Three-phase Input 200V Class • Three-phase Input 400V Class After r eading this manual, keep it handy f or futur e r eference. Hitachi Industrial Equipment Systems Co., Ltd. Manual Number : NB585XF December 2003 Co v er[…]

  • Страница 2

    SJ100 Inverter i Saf ety Messa ges For the best results with the SJ100 Series in v erter , carefully read this manual and all of the warning labels attached to the in v erter before installing and operating it, and follo w the instructions exactly . K eep th is manual handy for quick reference. Definitions and Symbols A safety instruction (message)[…]

  • Страница 3

    ii General Precautions — Read These Fir st! W ARNING: This equipment should be installed, adjusted, and serviced by qualified electrical maintenance personnel familiar w ith the construction and operation of the equipment and the hazards in volv ed. Failure to observe this precaution could result in bodily injury . W ARNING: The user is responsible[…]

  • Страница 4

    SJ100 Inverter iii W ARNING: Rotating shafts and above -ground electr ical potentials can be hazardous. Therefore, it is strongly recommended that all electrical work conform to the National Electrical Codes and local regulations. Inst allation , alignment and maintenance should be performed only by qualified p ersonnel. Factory-recommended test pr[…]

  • Страница 5

    iv Inde x to W arnings and Cautions in This Manual Installation — Cautions fo r Mounting Pr ocedures Wiring — W arnings for Electrical Practices and Wire Specifications CA UTION: The in verter is shipped w ith a plastic cover o ver the top v ent grill. REMO VE this cover after the installation is complete. Operation with this cov e r in place will […]

  • Страница 6

    SJ100 Inverter v Wiring — Cautions f or Electrical Practices W ARNING: “Suitable for use on a circui t capable of deli vering not more than 5,000 rms symmetrical amperes, 480 V maximum. ” For models with suf fix H. …. 2–13 HIGH V OL T A GE: Be sure to ground the unit. Otherwise, there is a danger of electric shock and/or f ire. …. 2–13 […]

  • Страница 7

    vi P owerup T est Caution Messages CA UTION: Remarks for using ground fault interrupter break ers in the main po wer supply: Adjustable freque nc y in verters with CE-f ilters (RFI- filter) and shielded (screened) motor cables ha ve a higher leakage current to ward Earth GND. Especially at the moment of switching ON this can cause an inadvertent tr[…]

  • Страница 8

    SJ100 Inverter vii W arnings for Configuring Drive P arameters Cautions f or Configuring Drive P arameters W arnings for Operations and Monitoring W ARNING: When parameter B_12, lev e l of electronic thermal setting, is set to de vice FLA rating (Full Load Ampere nameplate rating), the device provides solid state motor o verload pr otection at 115%[…]

  • Страница 9

    viii Cautions f or Operations and Monitoring W ARNING: Be sure not to touch the insi de of the energized in verter or to put any conducti ve object into it. Othe rwise, there is a danger of electric shock and/or fire. ……. 4–3 W ARNING: If power is turned ON when the Run command is already acti ve, the motor will automatically start and injury[…]

  • Страница 10

    SJ100 Inverter ix W arnings and Cautions for T r oubleshooting and Maintenance General W arnings and Cautions W ARNING: Nev er modify the unit. Otherwise, there is a danger of electric shock and/ or injury . CA UTION: W ithstand voltage tests and insula tion resistance tests (HIPO T ) are ex ecuted before the units are shipped, so there is no need […]

  • Страница 11

    x CA UTION: Do not stop operation by switching OFF electromagnetic contactors on the primary or secondary sides of the in verter . When there has been a sudden po wer failure while an operation instru ction is acti ve, then the unit may restart operation automatical ly after the power failure has end ed. If there is a possibility that such an oc cu[…]

  • Страница 12

    SJ100 Inverter xi CA UTION: SUPPRESSION FOR NOISE INTERFERENCE FR OM INVER TER The in verter uses many semiconductor switc hing elements such as transistors and IGBTs. Thus, a radio recei ver or measuring instrument located near the in verter is susceptible to noi se interference. T o protect the instruments from erroneous op eration due to noise i[…]

  • Страница 13

    xii CA UTION: When the EEPR OM error E08 occurs, be sure to conf irm the setting v alues again. CA UTION: When using normally closed acti ve state settings (C_11 to C_16) for e xter- nally commanded Forw ard or Re verse terminal s [FW] or [R V], the inv erter may start automatically when the e xternal system is power ed OFF or disconnected fr om th[…]

  • Страница 14

    SJ100 Inverter xiii T erminal Tightening T or que and Wire Size The wire size range and tightening torque fo r f ield wiring terminals are presented in the table below . Wire Connectors W ARNING: Field wiring connections must be made by a UL Listed and CSA Certified ring lug terminal connector sized for the wire gauge being used. The connector must[…]

  • Страница 15

    xiv Cir cuit Breaker and Fuse Sizes The in verter’ s connections to input power mu st include UL Listed in verse time circuit breakers with 600V rating, or UL Listed fuses as sho wn in the table below . Motor Overload Pr otection Hitachi SJ100 in verters pro vide solid state motor ov e rload protection, which depends on the proper setting of the […]

  • Страница 16

    xv SJ100 Inverter Safety Messages Hazardous High Voltage i General Precautions — Read These Fi rst! ii Index to Warnings and Cautions in This Manual iv General Warnings and Cautions ix UL ® Cautions, Warnings, and Instructions xii Table of Contents Revisions xvii Contact Information xviii Chapter 1: Getting Started Introduction 1–2 SJ100 Inverte[…]

  • Страница 17

    xvi Chapter 4: Operations and Monitoring Introduction 4–2 Connecting to PLCs and Other Devices 4–4 Example Wiring Diagram 4–5 Using Intelligent Input Terminals 4–8 Using Intelligent Output Terminals 4–24 Analog Input Operation 4–32 Analog and Digital Monitor Output 4–33 Auto-tuning for Sensorless Vector Control 4–35 PID Loop Operati[…]

  • Страница 18

    SJ100 Inverter xvii Revisions Revision History T able No. Revision Comments Date of Issue Operation Manual No. Initial release of manual NB585X April 1999 NB585X 1 Re vision A Added 7.5 and 10 HP models to tables and drawings in Chapt. 1 and 2, Minor corrections throughout manual May 1999 NB585XA 2 Re vision B Pages 1-4, 5 – Specs tables: correct[…]

  • Страница 19

    xviii Contact Inf ormation NO TE: T o receive technical support for the Hita chi in verter you purchased, contact the Hitachi in verter deal er from whom you purchased the unit, or the sales of f ice or factory contact listed abov e. Please be prepared to provide the follo wing in verter nameplate information: 1. Model 2. Date of purchase 3. Manufa[…]

  • Страница 20

    Getting Star ted In This Chapter … p age — Introduction …………….. ……………….. ……………. 2 — SJ100 Inverter S pecifications ……………. ………. 5 — Introduction to V ariable-Frequency Drives …. 18 — Frequently Asked Questions ……………………. 23 1[…]

  • Страница 21

    Introduction Getting Star ted 1–2 Intr oduction Main Features Congratulations on your purchase of an SJ100 Series Hitachi in verter! This in verter dri ve features state-of-the-art circuitry and components to provide high performance. The housing footprint is exceptionally small, gi ven the size of the corresponding motor . The Hitachi SJ100 prod[…]

  • Страница 22

    SJ100 Inverter Getting Star ted 1–3 A full line of accessories from Hitachi is av ailabl e to complete your motor application. These include: • Digital remote operator ke ypad • Braking resistors (sho wn at right) • Radio noise f i lters • CE compliance f ilters • DIN rail mounting adapter (35mm rail size) Operator Interface Options The[…]

  • Страница 23

    Introduction Getting Star ted 1–4 In ver ter Specifications Label The Hitachi SJ100 in verters hav e product labels located on the right side of the housing, as pictured belo w . Be sure to verify that the specifications on the labels match your power source, motor , and application safety requirements. Model Number Con vention The model number f[…]

  • Страница 24

    SJ100 Inverter Getting Star ted 1–5 SJ100 In ver ter Specifications Model-specific tables f or 200V and 400V class in ver ters The follo wing tables are specif ic to SJ100 in verters for the 200V and 400V class model groups. Note that “ General Specif ications ” on page 1–9 apply to both voltage class groups. Footnotes for all specif icati […]

  • Страница 25

    SJ100 Inverter Specificatio ns Getting Star ted 1–6 Footnotes for the preceding table and the tables that follo w: Note 1: The protection method conforms to JEM 1030. Note 2: The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When using other motors, care must be taken to pre vent the rated motor current (50/ 60 Hz) from exce[…]

  • Страница 26

    SJ100 Inverter Getting Star ted 1–7 SJ100 In verter Specif ications, continued… Item 200V Class Specif ications, continued SJ100 in verters, 200V models CE version 015NFE 022NFE — — — UL version 015NFU 022NFU 037LFU 055LFU 075LFU Applicable motor size *2 kW 1.5 2.2 3.7 5.5 7.5 HP 2 3 5 7.5 10 Rated capacity (kV A) *12 230V 3.1 4.3 6.9 9.5[…]

  • Страница 27

    SJ100 Inverter Specificatio ns Getting Star ted 1–8 Item 400V Class Specif ications SJ100 in verters, 400V models CE version 004HFE 007HFE 015HFE 022HFE UL version 004HFU 007HFU 015HFU 022HFU Applicable motor size *2 kW 0.4 0.75 1.5 2.2 HP 1/2 1 2 3 Rated capacity (460V) kV A 1.1 1.9 2.9 4.2 Rated input voltage 3-phase: 380 to 460V ±10%, 50/60 H[…]

  • Страница 28

    SJ100 Inverter Getting Star ted 1–9 General Specifications The follo wing table applies to all SJ100 in verters. Item 400V Class Specif ications, continued SJ100 in verters, 400V models CE version 030HFE 040HFE 055HFE 075HFE UL version — 040HFU 055HFU 075HFU Applicable motor size *2 kW 3.0 4.0 5.5 7.5 HP 4 5 7.5 10 Rated capacity (460V) kV A 6.[…]

  • Страница 29

    SJ100 Inverter Specificatio ns Getting Star ted 1–10 Input signal Freq. setting Operator panel Up and Down k eys / V alue setting s Potentiometer Analog setting External signal *8 0 to 10 VDC (input impedance 10k Ohms), 4 to 20 mA (input impedance 250 Ohms), Potentiometer (1k to 2k Ohms, 2W) FWD/ REV Run Operator panel Run/Stop (Forward /Re verse[…]

  • Страница 30

    SJ100 Inverter Getting Star ted 1–11 Signal Ratings Detailed ratings are in “ Specifications of Control and Logic Connections ” on page 4–6 . Signal / Contact Ratings Built-in power for inputs 24VDC, 30 mA maximum Discrete logic inputs 27VDC maximum Discrete logic outputs 50mA maximum ON state current, 27 VDC maximum OFF state voltage PWM ([…]

  • Страница 31

    SJ100 Inverter Specificatio ns Getting Star ted 1–12 Derating Curves The maximum av ailable in verter current output is limited by the carrier frequency and ambient temperature. The carrier frequency is the in verter’ s internal power switching frequency , settable from 0.5 kHz to 16 kHz. Choosing a higher carrier frequency tends to decrease au[…]

  • Страница 32

    SJ100 Inverter Getting Star ted 1–13 Derating curves, continued… SJ100–007NFE/NFU 0 . 5 2468 1 0 1 2 1 4 1 6 70% 80% 90% 100% 95% 85% 75% % of rated output current Carrier frequency kHz SJ100–0015NFE /NFU 0 . 5 2468 1 0 1 2 1 4 1 6 70% 80% 90% 100% 95% 85% 75% % of rated output current Carrier frequency kHz SJ100–022NFE/NFU 0 . 5 2468 1 0[…]

  • Страница 33

    SJ100 Inverter Specificatio ns Getting Star ted 1–14 Derating curves, continued… SJ100–037LF/LFU 0 . 5 2468 1 0 1 2 1 4 1 6 40% 60% 80% 100% 90% 70% 50% % of rated output current Carrier frequency kHz SJ100–055LFU 0 . 5 2468 1 0 1 2 1 4 1 6 70% 80% 90% 100% 95% 85% 75% % of rated output current Carrier frequency kHz SJ100–075LFU 0 . 5 246[…]

  • Страница 34

    SJ100 Inverter Getting Star ted 1–15 Derating curves, continued… SJ100–004HFE/HFU 0 . 5 2468 1 0 1 2 1 4 1 6 40% 60% 80% 100% 90% 70% 50% % of rated output current Carrier frequency kHz SJ100–007HFE/HFU 0 . 5 2468 1 0 1 2 1 4 1 6 40% 60% 80% 100% 90% 70% 50% % of rated output current Carrier frequency kHz SJ100–015HFE/HFU 0 . 5 2468 1 0 1[…]

  • Страница 35

    SJ100 Inverter Specificatio ns Getting Star ted 1–16 Derating curves, continued… SJ100–022HFE/HFU 0 . 5 2468 1 0 1 2 1 4 1 6 40% 60% 80% 100% 90% 70% 50% % of rated output current Carrier frequency kHz SJ100–040HFE/HFU 0 . 5 2468 1 0 1 2 1 4 1 6 40% 60% 80% 100% 90% 70% 50% % of rated output current Carrier frequency kHz SJ100–055HFE/HFU […]

  • Страница 36

    SJ100 Inverter Getting Star ted 1–17 Derating curves, continued… SJ100–075HFE/HFU 0 . 5 2468 1 0 1 2 1 4 1 6 70% 80% 90% 100% 95% 85% 75% % of rated output current Carrier frequency kHz[…]

  • Страница 37

    Introduction to Varia ble-Frequency Drives Getting Star ted 1–18 Intr oduction to V ariable-Frequency Drives The Purpose of Motor Speed Contr ol for Industry Hitachi in verters provide speed control fo r 3-phase A C induction motors. Y ou connect A C power to the in verter , and connect the in verter to the motor . Many applications benefit from […]

  • Страница 38

    SJ100 Inverter Getting Star ted 1–19 T orque and Constant V olts/Her tz Operation In the past, A C variab le speed dri ves used an open loop (scalar) technique to control speed. The constant-volts-per -hertz operation maintains a constant ra tio between the applied voltage and the applied frequenc y . W ith these conditions, A C induction motors […]

  • Страница 39

    Introduction to Varia ble-Frequency Drives Getting Star ted 1–20 In ver ter Output to the Motor The A C motor must be connected only to the in verter’ s output terminals. The output terminals are uniquely labeled (to dif ferentiate them from the input terminals) with the designations U/T1, V/T2, and W/T3. This corresponds to typical motor lead […]

  • Страница 40

    SJ100 Inverter Getting Star ted 1–21 Intelligent Functions and P arameters Much of this manual is de voted to describ ing how to use in ve rter functions and how to conf ig- ure in verter parameters. The in verter is micro- processor- controlled, and has many indepen dent functions. The microprocessor has an on-board EEPR OM for parameter storage[…]

  • Страница 41

    Introduction to Varia ble-Frequency Drives Getting Star ted 1–22 V elocity Pr ofiles The SJ100 in verter is capable of sophisticated speed control. A graphi cal representation of that capability will help you understand and conf igure the associated parameters. This manual makes use of the v elocity profile graph used in industry (shown at right)[…]

  • Страница 42

    SJ100 Inverter Getting Star ted 1–23 Frequentl y Asked Questions Q. What is the main advantage in using an in verter to dri ve a motor , c ompared to alternativ e solutions? A. An in verter can vary the motor speed wi th very little loss of eff iciency , unlike mechanical or hydraulic speed control solutions. The resulting ener gy sa vings usuall[…]

  • Страница 43

    Frequently Asked Qu estions Getting Star ted 1–24 Q. Why does the manual or other document ation use termin ology such as “200V class” instead of naming the actual v oltage, such as “230 V A C?” A. A specific in verter model is set at the factory to work across a v oltage range particular to the destination country fo r that model. The mo[…]

  • Страница 44

    SJ100 Inverter Getting Star ted 1–25 Q. Ho w will I kno w if my application will require resistiv e braking? A. For ne w applications, it may be dif f icult to tell before you actually test a motor/driv e solution. In general, some applications can rely on system losses such as friction to serve as the decelerating force, or otherwise can tolerat[…]

  • Страница 45

    In ver ter Mounting and Installation In This Chapter …. p age — Orientation to Inverter Features …………………. 2 — Basic System Description ……………… …………. 5 — S tep-by-S tep Basic Installation …………………… 6 — Powerup T est ………………………………………… 19 — Using the Front Panel[…]

  • Страница 46

    Orientation to I nverter Features In v er ter Mounting and Installation 2–2 Orientation to In ver ter Features Unpack ing and Inspection Please take a fe w moments to unpack your new SJ100 in verter and perform these steps: 1. Look for any damage that may ha ve occurred during shipping. 2. V e rify the contents of the box include: a. One SJ100 in[…]

  • Страница 47

    SJ100 Inverter In v er ter Mounting and Installation 2–3 2. Second-le vel access — Locate the lift tab at the right lower corner of the front panel near the safety warning messa ge. Lift the corner to swi ng the half-door around to the left. This exposes fou r more control buttons and some connectors. The FUNC., , , and STR ke ys allo w an operat[…]

  • Страница 48

    Orientation to I nverter Features In v er ter Mounting and Installation 2–4 3. Third-level access — First, ensure no po wer source of any kind is connected to the in verter . If power has been connected, wait fi ve minutes after po werdown and v erify the Power LED is OFF to proceed. Then locate the rece ssed retention screw on the left side main[…]

  • Страница 49

    SJ100 Inverter In v er ter Mounting and Installation 2–5 Basic System Description A motor control system will obviously include a motor and in verter , as well as a breaker or fuses for safety . If you are connecting a motor to the in verter on a test bench just to get started, that’ s all you may need for now . But a system can also ha ve a v […]

  • Страница 50

    Step-by-St ep Ba sic Installation In v er ter Mounting and Installation 2–6 W ARNING: In the cases below in volving a gene ral-purpose in verter , a large peak current can flo w on the power supply side , sometimes destro ying the con verter module: 1.The unbalance factor of the po wer supply is 3% or higher . 2.The po wer supply capacity is at l[…]

  • Страница 51

    SJ100 Inverter In v er ter Mounting and Installation 2–7 Choosing a Mounting Location Step 1: Study the follo wing caution messages associated with mounting the in verter . This is the time when mistakes are most likely to occur that will result in expensi ve re work, equipment damage, or personal injury . CA UTION: Be sure to install the unit on[…]

  • Страница 52

    Step-by-St ep Ba sic Installation In v er ter Mounting and Installation 2–8 Ensure Adequate V e ntilation Step 2: T o summarize the caution messages—you wi ll need to find a solid, non-flamma- ble, vertical surface that is in a relati vely clean and dry en vironment. In order to ensure enough room for air circulation around the in verter to aid[…]

  • Страница 53

    SJ100 Inverter In v er ter Mounting and Installation 2–9 3. When installing the in verter in an encl osure, maintain the clearance around the in verter and verify that its ambient temperature is within specif ication when the enclosure door is closed. 4. Do not open the main front panel door at any time during operation. Check In ver ter Dimensio[…]

  • Страница 54

    Step-by-St ep Ba sic Installation In v er ter Mounting and Installation 2–10 Dimensional drawings, continued… FAN MODEL External Dimensions SJ 100 -004HFE -004HFU -007NFE -007NFU 98(3.86) 118(4.65) 5(0.20) 130(5.12) 5(0.20) Air Air 98(3.86) 118(4.65) SJ 100 -007HFE(No fan) -007HFU(No fan) -015HFE -015HFU 110(4.33) 4(0.16) 10(0.39) 7(0.28) 2.5(0[…]

  • Страница 55

    SJ100 Inverter In v er ter Mounting and Installation 2–11 Dimensional drawings, continued … FAN SJ100 -015NFE -015NFU SJ100 -022NFE -022NFU -030HFE -037LFU -040HFE -040HFU 140(5.51) 168(6.61) 180(7.08) 128(5.04) 5(0.20) 5(0.20) 7(0.28) Ground Terminal 164(6.46) 6(0.24) Air Air Ground Terminal 7(0.28) 153(6.02) 3.5(0.14) 180(7.09) 5(0.20) 140(5.[…]

  • Страница 56

    Step-by-St ep Ba sic Installation In v er ter Mounting and Installation 2–12 Dimensional drawings, continued… NO TE: Model SJ100-075LFU has (2) fans. All other models in this housing ha ve (1) fan. 182 (7.17) 160 (6.30) 236 (9.29) 170 (6.69) Air Air 257 (10.12) 1 7 (0.28) 7 (0.28) 7 (0.28) 6 (0.24) Ground Terminal SJ100 -055LFU -055HFE -055HFU […]

  • Страница 57

    SJ100 Inverter In v er ter Mounting and Installation 2–13 Prepare for Wiring Step 5: It is ve ry important to perform the wi ring steps carefully and correctly . Before proceeding, please study the caution and warning messages belo w . W ARNING: “Use 60/75°C Cu wire only” or equiv alent. W ARNING: “Open T ype Equipment. ” W ARNING: “Su[…]

  • Страница 58

    Step-by-St ep Ba sic Installation In v er ter Mounting and Installation 2–14 Determining Wire and Fuse Sizes The maximum motor currents in your applic ation determines the recommend ed wire size. The follo wing table give s the wire size in A WG. The “Po wer Lines” column applies to the in verter input po wer , output wires to the motor , the[…]

  • Страница 59

    SJ100 Inverter In v er ter Mounting and Installation 2–15 T erminal Dimensions and T or que Specs The terminal scre w dimensions for all SJ100 in verters are listed in table below . This information is useful in sizing spade lug or ring lug connectors for wire terminations. CA UTION: F asten the scre ws with the specif ied fastening torque in the[…]

  • Страница 60

    Step-by-St ep Ba sic Installation In v er ter Mounting and Installation 2–16 Please use the terminal arrangement be lo w corresponding to your in verter model. NO TE: An in verter po wered by a portable po we r generator may recei ve a disto rted power w a veform, o verheating the generator . In general, the generator capacity should be fi ve tim[…]

  • Страница 61

    SJ100 Inverter In v er ter Mounting and Installation 2–17 CA UTION: Be sure not to connect an A C po wer supply to the output terminals. Other- wise, there is the possibility of damage to th e in verter and the danger of injury and/or fir e . CA UTION: Remarks for using ground f ault interr upter breakers in the main po wer supply: Adjustable fre[…]

  • Страница 62

    Step-by-St ep Ba sic Installation In v er ter Mounting and Installation 2–18 Wire the In ver ter Output to Motor Step 7: The process of motor selection is beyond the scop e of this manual. Ho we ver , it must be an A C induction motor with three phases. It should also come with a chassis ground lug. If the motor does not ha ve three po wer input […]

  • Страница 63

    SJ100 Inverter In v er ter Mounting and Installation 2–19 Uncover the In ver ter V ents Step 8: After mounting and wiring the in verter , remov e any cov e rs from the in verter housing. This includes material ov er the side ventilation ports. Remov e the square cov er panel at the top of the housing. W ARNING: Make sure the input po wer to the i[…]

  • Страница 64

    Powerup Test In v er ter Mounting and Installation 2–20 Pre-test and Operational Precautions The follow ing instructions apply to the powerup test, or to an y time the inv erter is powered and operating. Please study the follo wing instructions and messages before proceeding with the po werup test. 1. The po wer supply must ha ve fusing suitable […]

  • Страница 65

    SJ100 Inverter In v er ter Mounting and Installation 2–21 Using the Fr ont P anel Ke ypad Fr ont P anel Introduction Please take a moment to familiarize yourself with the keypad layout sho wn in the figure belo w . These are the visible controls and i ndicators when the front panel door is closed. The display is used in programming the in ve rter[…]

  • Страница 66

    Using the Front Panel Keypad In v er ter Mounting and Installation 2–22 • Parameter Display — A 4-digit, 7-se gment display for parameters and function codes. • Display Units, Hertz/Amperes — One of these LEDs will be ON to indicate the units associated with the paramete r display . • Po wer LED — This LED is ON when the po wer input to the[…]

  • Страница 67

    SJ100 Inverter In v er ter Mounting and Installation 2–23 Ke ypad Navigational Map The SJ100 Series in verter dri ves hav e ma ny programmable functi ons and parameters. Chapter 3 will cov er these in detail, but you need to access just a few items to perform the po werup test. The menu structure makes use of function codes and parameter codes to[…]

  • Страница 68

    Using the Front Panel Keypad In v er ter Mounting and Installation 2–24 Selecting Functions and Editing P arameters In order to run the motor for the po werup test, this section will show ho w to: • select the in verter’ s maximum output frequency to the motor • select the ke ypad potentiometer as th e source of motor speed comm and • sel[…]

  • Страница 69

    SJ100 Inverter In v er ter Mounting and Installation 2–25 Select the Potentiometer f or Speed Command — The motor speed may be controlled from the follo wing sources: • Potentiometer on front panel ke ypad • Control terminals • Remote panel Then follo w the steps in the table belo w to select the potentiometer for the speed command (the tab[…]

  • Страница 70

    Using the Front Panel Keypad In v er ter Mounting and Installation 2–26 Conf igure the In vert er f or the Number of Motor P oles — The number of magnetic poles of a motor is determined by the moto r’ s internal winding arrangement. The specifi- cations label on the motor usually indicate s its number of poles. For proper operation, verify the […]

  • Страница 71

    SJ100 Inverter In v er ter Mounting and Installation 2–27 Monitoring P arameters with the Displa y After using the ke ypad for parameter editing, it’ s a good idea to switch the in verter from Program Mode to Monitor Mode and close the panel door (puts the ke ys for parameter editing out of sight). This will also turn out the PRG LED, and the H[…]

  • Страница 72

    Using the Front Panel Keypad In v er ter Mounting and Installation 2–28 P owerup T est Obser vations and Summary Step 10: Reading this section will help you make some useful observ ations when f irst running the motor . Err or Codes — If the in verter displays an error code (format is “ E x x ”), see “ Monitorin g T rip Events, History , &a[…]

  • Страница 73

    Configuring Drive P arameter s In This Chapter …. p age — Choosing a Programming Device ………………. 2 — Using Keypad Devices ……………….. ……………. 3 — “D” Group: Monitoring Functions ………………… 6 — “F” Group: Main Profile Parameters ……………. 8 — “A” Group: S tandard Functions ……[…]

  • Страница 74

    Choosing a Programmin g Device Configuring Drive P arameters 3–2 Choosing a Pr ogramming Device Intr oduction Hitachi v ariable frequenc y dri ves (in verte rs) use the latest electronics technology for getting the right A C wav eform to the motor at the right time. The benefits are many , including energy sa vings and higher machin e output or p[…]

  • Страница 75

    SJ100 Inverter Configuring Drive P arameters 3–3 Using K e ypad De vices In ver ter Front P anel Ke ypad The SJ100 Series in verter fr ont ke ypad contains all the elements for both monitoring and programming parameters. The ke ypad layout is pictured belo w . All other programming de vices for the in verter hav e a s imilar ke y arrangement and […]

  • Страница 76

    Using Keypad Devices Configuring Drive P arameters 3–4 Ke ypad Navigational Map Y ou can use the inv erter’ s front panel keypad to na vigate to any parameter or fun ction. The diagram below sho ws the basic navigational map to access these items. NO TE: The in verter 7-segment display sho ws lo wer case “b” and “d, ” meaning the same a[…]

  • Страница 77

    SJ100 Inverter Configuring Drive P arameters 3–5 Operational Modes The R UN and PGM LEDs tell just part of the story; Run Mode and Program Modes are independent modes, not opposite modes. In the state diagram to the right, Run alternates with Stop, and Program Mode alternates with Monitor Mode. This is a very important ability , for it sho ws tha[…]

  • Страница 78

    “D” Group: Monitoring Fun ctions Configuring Drive P arameters 3–6 “D” Gr oup: Monitoring Functions P arameter Monitoring Functions Y ou can access important system paramete r values with the “D” Group monitoring functions, whether the in verter is in R un Mode or Stop Mode. After selecting the function code number for the parameter y[…]

  • Страница 79

    SJ100 Inverter Configuring Drive P arameters 3–7 T rip Event and Histor y Monitoring The trip e vent and history monitoring featur e lets you cycle through related information using the ke ypad. See “ Monitoring T rip Events, History , & Conditions ” on page 6–5 for more details. D_07 Scaled output frequency monitor Displays the output […]

  • Страница 80

    “F” Group: Main Profile Parameters Configuring Drive P arameters 3–8 “F” Gr oup: Main Profile P arameters The basic frequency (speed) pro file is defined by parameters contained in the “F” Group as sho wn to the right. The set running frequency is in Hz, b ut accelera- tion and deceleration are specified in the time duration of the ra[…]

  • Страница 81

    SJ100 Inverter Configuring Drive P arameters 3–9 “A” Gr oup: Standard Functions Basic P arameter Settings These settings af fect the most fundamental be ha vior of the in verter—the outputs to the motor . The frequency of the in verter’ s A C output determines the motor speed. Y ou may select from three different sources for th e referenc[…]

  • Страница 82

    “A” Group: Standard Function s Configuring Drive P arameters 3–10 Analog Input Settings The in verter has the capability to accept an external analog input that can command the output frequency to the motor . V oltage i nput (0 –10V) and current input (4–20mA) are av ailable on separate terminal s ([O] and [OI], respecti vely). T erminal […]

  • Страница 83

    SJ100 Inverter Configuring Drive P arameters 3–11 Multi-speed and Jog Frequency Setting The SJ100 in verter has the capability to store and output up to 16 preset frequencies to the motor (A_20 to A_35). As in traditional motion terminology , we call this multi-speed pr ofile capability . These preset frequencies are se lected by means of digital[…]

  • Страница 84

    “A” Group: Standard Function s Configuring Drive P arameters 3–12 “A” Function Run Mode Edit Defaults Func. Code Name / SR W Display Description –FE (CE) –FU (UL) –FR (Jpn) Units A_20 Multi-speed frequency setting Defines the f irst speed of a multi-speed profile, range is 0 to 360 Hz A_20 = Speed 0 (1st motor) ✔ 000 H z SPD FS 00[…]

  • Страница 85

    SJ100 Inverter Configuring Drive P arameters 3–13 T orque Contr ol Algorithms The in verter generates the motor output according to the V/f algorithm or the sensor- less vector control algorithm. P arameter A_44 selects the in verter algorithm for gener- ating the frequency output, as sho wn in the diagram to the right (A244 for 2nd motor). The f[…]

  • Страница 86

    “A” Group: Standard Function s Configuring Drive P arameters 3–14 parameters A_42 and A_43. The manual boost is calculated as an addition to the standard straight V/f line (constant torque curv e). NO TE: Manual torque boost is not operational when sensorless vector control is in use. Be aw are that running the motor at a lo w speed for a lon[…]

  • Страница 87

    SJ100 Inverter Configuring Drive P arameters 3–15 The follo wing table sho w s the methods of torque control selection. “A” Function Run Mode Edit Defaults Func. Code Name / SR W Display Description –FE (CE) –FU (UL) –FR (Jpn) Units A_41 T orque boost method selection T wo options: 00… Manual torque boost 01… Automatic torque b oost[…]

  • Страница 88

    “A” Group: Standard Function s Configuring Drive P arameters 3–16 DC Braking Settings The DC braking feature can provide additional stopping torque when compared to a normal deceleration to a stop. DC braking is particularly useful at lo w speeds when normal decelera- tion torque is minimal. When you enable DC braking, the in verter injects a[…]

  • Страница 89

    SJ100 Inverter Configuring Drive P arameters 3–17 Frequency-related Functions Frequency Limits – Upper and lo wer limits can be imposed on the inv erter output frequency . These limits will appl y regardless of the sou rce of the speed refer- ence. Y ou can configure the lo wer frequency limit to be greater than zero as show n in the graph. The[…]

  • Страница 90

    “A” Group: Standard Function s Configuring Drive P arameters 3–18 Jump Fr equencies – Some motors or machines exhi bit resonances at particular speed(s), which can be destructi ve for prolo nged running at those speeds. The in verter has up to three jump fr equencies as sho wn in the graph. The hysteresis around the jump frequencies causes […]

  • Страница 91

    SJ100 Inverter Configuring Drive P arameters 3–19 PID Contr ol When enabled, the built- in PID loop calculates an ideal in verter output v alue to cause a loop feedback process v a riable (PV) to mov e closer in v a lue to the setpoint (SP). The current frequency command serv es as the SP . The PID loop algorithm will read the analog input for th[…]

  • Страница 92

    “A” Group: Standard Function s Configuring Drive P arameters 3–20 A utomatic V oltage Regulation (A VR) Function The automatic v oltage regulation (A VR) featur e keeps the in verter output w aveform at a relati vely constant amplitude during po wer input fluctuations. This can be useful if the installation is subject to input voltage fluctu […]

  • Страница 93

    SJ100 Inverter Configuring Drive P arameters 3–21 Second Acceleration and Deceleration Functions The SJ100 in verter features two-stage accele ration and deceleration ramps. This gi ves flexibility in the prof ile shape. Y o u can sp ecify the frequency transition point, the point at which the standard acceleration (F_02) or deceleration (F_03) c[…]

  • Страница 94

    “A” Group: Standard Function s Configuring Drive P arameters 3–22 NO TE: F or A_95 and A_96 (and for 2nd motor settings), if you set a very rapid Acc1 or Dec1 time (less than 1.0 second), the in verter ma y not be able to change rates to Acc2 or Dec2 before reaching the ta rget fr equenc y . In that case, the in verter de creases the rate of […]

  • Страница 95

    SJ100 Inverter Configuring Drive P arameters 3–23 Accel/Decel Standard acceleration and deceleration is linear . The in verter CPU can also calculate an S-curve acceleration or deceleration curve as sho wn. This profile is useful for fa voring the load characteristics in particu- lar applications. Curve settings for acceleration and decel- eratio[…]

  • Страница 96

    “B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–24 “B” Gr oup: Fine T uning Functions The “B” Group of functions and parameters adju st some of the more subtle b ut useful aspects of motor control and system conf iguration. A utomatic Restar t Mode The restart mode determines how the in verter will resume operation a[…]

  • Страница 97

    SJ100 Inverter Configuring Drive P arameters 3–25 Electr onic Thermal Overload Alarm Setting The thermal ov erload detection protects the in verter and motor from ov erheating due to an excessi ve load. It uses a current/in verse time curve to determine the trip point. First, use B_13 to select the torque charac- teristic that matches your load. […]

  • Страница 98

    “B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–26 W ARNING: When parameter B_12, level of electroni c thermal setting, is set to de vice FLA rating (Full Load Ampere nameplate rating), the device pro vides solid state motor ov erload protection at 115% of de vice FL A or equi v alent. Parameter B_12, le vel of electronic th[…]

  • Страница 99

    SJ100 Inverter Configuring Drive P arameters 3–27 Overload Restriction If the in verter’ s output current e xceeds a preset current le vel you specify during acceleration or constant speed, the ov e rload restriction feature automatically reduces the output frequenc y to restrict the ov erload. This feature does not generate an alarm or trip ev[…]

  • Страница 100

    “B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–28 Software Loc k Mode The software lock function keeps personnel fr om accidentally cha nging parameters in the in verter memory . Use B_31 to select from various protection le vels. The table belo w lists all combinations of B_31 option codes and the ON/OFF state of the [SFT][…]

  • Страница 101

    SJ100 Inverter Configuring Drive P arameters 3–29 NO TE: T o disable parameter editing when using B_31 lock mo des 00 and 01, assign the [SFT] function to one of the intelligent input terminals. See “ Software Lock ” on page 4–19 . “B” Function Run Mode Edit Defaults Func. Code Name / SR W Display Description –FE (CE) –FU (UL) –FR[…]

  • Страница 102

    “B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–30 Miscellaneous Settings The miscellaneous settings include scaling factors, initialization modes, and others. this section cov e rs some of the most importa nt setting s you may need to conf igure. B_83: Carrier frequency adjustment – The internal switching frequency of the[…]

  • Страница 103

    SJ100 Inverter Configuring Drive P arameters 3–31 “B” Function Run Mode Edit Defaults Func. Code Name / SR W Display Description –FE (CE) –FU (UL) –FR (Jpn) Units B_81 [FM] terminal analog meter ad justment Adjust 8-bit gain to analog meter connected to terminal [FM], range is 0 to 255 ✔ 80 80 80 — ADJ 080 B_82 Start frequency adjus[…]

  • Страница 104

    “B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–32 B_91/B_88: Stop Mode / Restart Mode Conf iguration – Y ou can configure ho w the in verter performs a standard stop (each time Run FWD and REV signals turn OFF). Setting B_91 determines whether the in verter will control the deceleration, or whether it will perform a free-[…]

  • Страница 105

    SJ100 Inverter Configuring Drive P arameters 3–33 B_90: Dynamic braking usage ratio – This parameter limits th e amount of time the in verter can use the dynamic braking accessory de vice without entering the T rip Mode. Please refer to “ Dynamic Braking ” on page 5–5 for more information on dynamic braking accessories. “B” Function R[…]

  • Страница 106

    “C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–34 “C” Gr oup: Intellig ent T erminal Functions The six input terminals [ 1] , [ 2] , [ 3] , [ 4] , [ 5] , and [ 6] can be configured for an y of 19 dif ferent functions. The next tw o tables sho w ho w to configure the six terminals. The inputs are logical, in that[…]

  • Страница 107

    SJ100 Inverter Configuring Drive P arameters 3–35 The input logic con vention is programmable for each of the six inputs. Most inputs default to normally open (acti ve high), b ut you ca n select normally closed (acti ve lo w) in order to in vert the sense of the logic. NO TE: An input terminal conf igured for opt ion code 18 ([RS] Reset command)[…]

  • Страница 108

    “C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–36 Input Function Summary T able – This table show s all nineteen intelligent input functions at a glance. Detailed descriptions of these functions, related parameters and settings, and e xample wiring diagrams are in “ Using Intelligent Input T erminals ” on page[…]

  • Страница 109

    SJ100 Inverter Configuring Drive P arameters 3–37 Note 1: When using the Multi-speed Select settings CF1 to CF4, do not display parameter F_01 or change the v alue of F _01 while the in verter is in Run Mode (motor running). If it is necessary to check the v alue of F_01 during Run Mode, please monitor D_01 instead of F_01. 13 USP Unattended Star[…]

  • Страница 110

    “C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–38 Output T erminal Configuration The in verter provides conf iguration for logi c (discrete) and analog outputs, shown in the table belo w . The output logic con vention is programmabl e for terminals [11], [12], and the alarm relay terminals. The open-collector output[…]

  • Страница 111

    SJ100 Inverter Configuring Drive P arameters 3–39 Output Function Summary T able – This table sho ws all six functions for the logical outputs (terminals [11], [12]) at a glance. Detailed descriptions of these functions, related parameters and settings, a nd example wiring diagrams are in “ Using Intelligent Output T erminals ” on page 4–[…]

  • Страница 112

    “C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–40 Analog Function Summary T able – This table shows all three functions for the analog output [FM] (frequency meter) terminal. Deta iled description s, related parameters and settings, and e xample wiring diagrams are in “ Analog and Digital Monitor Output ” on p[…]

  • Страница 113

    SJ100 Inverter Configuring Drive P arameters 3–41 Output Function Adjustment P arameters The follow ing parameters work in conjunction with the intelligent output function, when configured. The o verload le vel parameter (C_41) sets the motor current le vel at which the o verload signal [OD] turns ON. The range of settings is from 0% to 200% of t[…]

  • Страница 114

    “C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–42 NO TE: Settings C_81 and C_82 are fact ory-calibrated for each in verter . Do not change these settings unless absolutely necessary . Note that if you restore factory def a ults for all parameters, these settings will not change. C_43 Arriv al frequency setting for d[…]

  • Страница 115

    SJ100 Inverter Configuring Drive P arameters 3–43 “H” Gr oup: Motor Constants Functions Intr oduction The “H” Group parameters configure the in verter for the motor characteristics. You must manually set H_03 and H_04 values to match the motor. The remaining parameters are related to sensorless vector control (SLV), and are in use only wh[…]

  • Страница 116

    “H” Group: Motor Co nstants Functions Configuring Drive P arameters 3–44 H204 Motor poles setting, 2n d motor Four selections: 2 / 4 / 6 / 8 ✘ 4 4 4 poles 2AUXP 4p H_05 Motor speed constant Motor proportional gain constant (factory set), range is 0 to 99 ✘ 20 20 20 — AUX KP 20 H205 Motor speed constant, 2nd motor Motor proportional gain[…]

  • Страница 117

    SJ100 Inverter Configuring Drive P arameters 3–45 H_24 Motor Constant J Ratio (unit-less), range is 1.0 to 1000 ✘ Factory set according to in verter model — AUX J 0020.0 H224 Motor constant J, 2nd motor Ratio (unit-less), range is 1.0 to 1000 ✘ Factory set according to in verter model — 2AUXJ 0020.0 H_30 Auto-tuned motor constant R1 Auto-[…]

  • Страница 118

    Operations and Monitoring In This Chapter …. p age — Introduction …………….. ……………….. ……………. 2 — Connecting to PLCs and Other Devices ……… 4 — Using Intelligent Input T erminals ………………… 8 — Using Intelligent Output T erminals ……………. 24 — Analog Input Operation ……………….[…]

  • Страница 119

    Introduction Operations and Monitoring 4–2 Intr oduction The pre vious material in Chapter 3 ga ve a reference listing of all the programmable functions of the in verter . W e suggest that you first scan through the listing of in ve rter functions to gain a general familiarity . This chapter will build on that knowledge in the following w ays: 1.[…]

  • Страница 120

    SJ100 Inverter Operations and Monitoring 4–3 W arning Messages for Operating Pr ocedures Before continuing, please read the follo wing W arning messages. W ARNING: Be sure to turn ON the input po wer supply only after closing the front case. While the in verter is energized, be sure not to open the front case. Otherwise, ther e is the danger of e[…]

  • Страница 121

    Connecting to PLCs and Other Devices Operations and Monitoring 4–4 Connecting to PLCs and Other De vices Hitachi in verters (dri ves) are useful in many types of applications . During installation, the in verter ke ypad (or other programming de vice) will facilitate the initial configura- tion. After installation, the in verter will ge nerally re[…]

  • Страница 122

    SJ100 Inverter Operations and Monitoring 4–5 Example Wiring Diagram The schematic diagram below pro vides a gene ral example of logic connector wirin g, in addition to basic po wer and motor wiring co ve red in Chapter 2. The goal of this chapter is to help you determine the proper connecti ons for the v arious terminals shown belo w for your spe[…]

  • Страница 123

    Example Wiring Di agram Operations and Monitoring 4–6 Specifications of Contr ol and Logic Connections The control logic connectors are located just behind the front panel half-door . The relay contacts are accessible behind the main door . Connector labeling is shown belo w . Specifications for th e logic connection terminals are in the follo w […]

  • Страница 124

    SJ100 Inverter Operations and Monitoring 4–7 T erminal Listing Use the follo wing tables to locate pages for intelligent input and output material in this chapter . Intelligent Inputs Symbol Code Name Page FW 00 Forward Run/Stop 4–9 R V 01 Reverse Run/Stop 4–9 CF1 02 Multi-speed Select, Bit 0 (LSB) 4–10 CF2 03 Multi-speed Select, Bit 1 4–[…]

  • Страница 125

    Using Intelligent Input Terminals Operations and Monitoring 4–8 Using Intelligent Input T erminals T erminals [1], [2], [3], [4], [5], and [6 ] are identical, programmable inputs for general use. The input circuits can use the in verter’ s internal (isolated) +24V f ield supply (P24) to po wer the inputs. The input circuits ar e internally conn[…]

  • Страница 126

    SJ100 Inverter Operations and Monitoring 4–9 Forwar d Run/Stop and Re verse Run/Stop Commands: When you input the Run command via the terminal [FW], the in verter ex ecutes the Forw ard Run command (high) or Stop command (lo w). When you input the Run command via the terminal [R V], the in verter executes the Re verse Run command (high) or Stop c[…]

  • Страница 127

    Using Intelligent Input Terminals Operations and Monitoring 4–10 Multi-Speed Select The in verter can store up to 16 dif ferent target frequencies (speeds) that the motor output uses for steady-state run condition. These speeds are acces- sible through programming four of the intelligent terminals as binary-encoded inputs CF1 to CF4 per the table[…]

  • Страница 128

    SJ100 Inverter Operations and Monitoring 4–11 While using the multi-speed capability, you ca n monitor the current frequency with monitor function D_01 during each se gment of a multi-speed operation. NO TE: When using the Multi-speed Sel ect setti ngs CF1 to CF4, do not display parame- ter F_01 or change the value of F_01 while th e in verter is[…]

  • Страница 129

    Using Intelligent Input Terminals Operations and Monitoring 4–12 Jogging Command The Jog input [JG] is used to command the motor to rotate slowly in small i ncrements for manual operation. The speed is limited to 10 Hz. The frequency for the jogging opera- tion is set by parameter A_38. Jogging does not use an acceleration ramp, so we recom- mend[…]

  • Страница 130

    SJ100 Inverter Operations and Monitoring 4–13 External Signal f or DC Braking When the terminal [DB] is turned ON, the DC braking feature is enabled. Set the follow- ing parameters when the external DC braking terminal [DB] is to be used: • A_53 – DC braking delay time setting. The range is 0.1 to 5.0 seconds. • A_54 – DC braking force se[…]

  • Страница 131

    Using Intelligent Input Terminals Operations and Monitoring 4–14 Set Second Motor If you assign the [SET] function to an intel ligent input terminal, you can select between two sets of motor parameters. The second pa rameters store an alternate set of motor characteristics. When the terminal [SET] is turned ON, the in verter will use the second s[…]

  • Страница 132

    SJ100 Inverter Operations and Monitoring 4–15 T wo-stage Acceleration and Deceleration When terminal [2CH] is turned ON, the in verter changes the rate of acceleration and deceleration from the initial settings (F_02 and F_03) to use the second set of accelera- tion/deceleration v alues. When the terminal is turned OFF , the in verter is returned[…]

  • Страница 133

    Using Intelligent Input Terminals Operations and Monitoring 4–16 Free-run Stop When the terminal [FRS] is turned ON, the in verter stops the output and the motor enters the free-run state (coasting). If terminal [F RS] is turned OFF , the output resumes sending power to the motor if the Run command is still acti ve. The free-run stop feature work[…]

  • Страница 134

    SJ100 Inverter Operations and Monitoring 4–17 External T rip When the terminal [EXT] is turned ON, the in verter enters the trip state, indicates error code E12, and stops the output. This is a gene ral purpose interrupt type feature, and the meaning of the error depends on what you c onnect to the [EXT] terminal. Ev en if the [EXT] input is turn[…]

  • Страница 135

    Using Intelligent Input Terminals Operations and Monitoring 4–18 Unattended Start Protection If the Run command is already set when power is turned ON, the in verter starts running immediately after po werup. The Unattended Start Protection (USP) function prev ents that automatic startup, so that the in verter will not run without outside interve[…]

  • Страница 136

    SJ100 Inverter Operations and Monitoring 4–19 Software Loc k When the terminal [SFT] is turned ON, the data of all the parameters and functions (except the output frequenc y , depending on the setting of B_31) is locked (prohibited from editing). When the data is locked, the ke ypad ke ys cannot edit in verter parameters. T o edit parameters agai[…]

  • Страница 137

    Using Intelligent Input Terminals Operations and Monitoring 4–20 Analog Input Current/V oltage Select The [AT] terminal selects whether the inverter uses the voltage [O] o r current [OI] input terminals for external frequency control. Wh en intelligent input [A T] is ON, you can set the output frequency by applying a current input signal at [OI]-[…]

  • Страница 138

    SJ100 Inverter Operations and Monitoring 4–21 Reset In ver ter The [RS] terminal causes the inverter to execute the reset operation. If the inverter is in Trip Mode, the reset cancels the Trip state. When the signal [RS] is turned ON and OFF, the inverter executes the reset operation. The minimum pulse width for [RS] must be 12 ms or greater. The[…]

  • Страница 139

    Using Intelligent Input Terminals Operations and Monitoring 4–22 Thermistor Thermal Pr otection Motors that are equipped with a thermisto r can be protected from o verheating. Input terminal [5] has the unique ability to sense a thermistor resistance. When the resistance va lue of the thermistor connected to terminal [TH] (5) and [L] is more than[…]

  • Страница 140

    SJ100 Inverter Operations and Monitoring 4–23 Remote Contr ol Up and Down Functions The [UP] [D WN] terminal functions can adju st the output frequenc y for remote control while the motor is running. The acceleration ti me and deceleration time of this function is same as normal operation A CC1 and DE C1 (2A CC1,2DEC1). The input terminals operat[…]

  • Страница 141

    Using Intelligent Output Terminals Operations and Monitoring 4–24 Using Intelligent Output T erminals The intelligent output terminals are programmable in a similar way to the intelligent input terminals. The in verter has se veral output functions that you can assign individu- ally to three physical logic outputs. T wo of the outputs are open-co[…]

  • Страница 142

    SJ100 Inverter Operations and Monitoring 4–25 Run Signal When the [R UN] signal is selected as an intelligent output terminal, the in verter outputs a signal on that terminal when it is in Run Mode. The output logic is acti ve low , and is the open collector type (switch to ground). NO TE: The example circuit in the table abo ve dri ves a relay c[…]

  • Страница 143

    Using Intelligent Output Terminals Operations and Monitoring 4–26 Frequency Arriv al Signals The F requ ency Arrival group of outputs help coordinate external systems with the current velocity prof ile of the in verter . As the name implies, output [F A1] turns ON when the output fr equency arrives at the standard set frequency (parameter F_01 ).[…]

  • Страница 144

    SJ100 Inverter Operations and Monitoring 4–27 Frequency arri val output [F A1] uses the standard output frequency (parameter F_01) as the threshold for switching. In the figure to the right, Frequenc y Arriv al [F A1] turns ON when the outpu t frequency gets within 0.5 Hz belo w or 1.5 Hz abov e the target constant frequency . This provides hyste[…]

  • Страница 145

    Using Intelligent Output Terminals Operations and Monitoring 4–28 Overload Adv ance Notice Signal When the output current e xceeds a preset value, the [OL] terminal signal turns ON. The parameter C_41 sets the ov erload threshold. The ov e rload detection circuit operates during po wered motor opera- tion and during regenerati ve braking. The out[…]

  • Страница 146

    SJ100 Inverter Operations and Monitoring 4–29 Output Deviation f or PID Control The PID loop error is defined as the magnitude (absolute v alue) of the dif fer- ence between the Set point (target v alue) and the Process V a riable (actual v alue). When the error magnitude exceeds the preset v alue for C_44, the [OD] terminal signal turns ON. Refe[…]

  • Страница 147

    Using Intelligent Output Terminals Operations and Monitoring 4–30 Alarm Signal The in verter alarm signal is acti ve when a f a ult has occurred and it is in the T rip Mode (refer to the diagram at right). When the fault is cleared the alarm signal becomes ina cti ve. W e must make a distinction between the alarm signal AL and the alarm relay con[…]

  • Страница 148

    SJ100 Inverter Operations and Monitoring 4–31 The alarm output terminals are connected as sho wn below (left) by defa ult. The contact logic can be in verted as sho wn (belo w ri ght) by using the parameter setting C_33. The relay contacts normally open (N.O.) and nor mally closed (N.O.) con vention uses “normal” to mean the in verter has po […]

  • Страница 149

    Analog Input Oper ation Operations and Monitoring 4–32 Analog Input Operation The SJ100 in verters provide for analog input to command the in verter frequency output va lue. The analog input terminal group includes the [L], [OI], [O], and [H] terminals on the control connector , which provide for V oltage [O] or Current [OI] input. All analog inp[…]

  • Страница 150

    SJ100 Inverter Operations and Monitoring 4–33 Analog and Digital Monitor Output In the system design for in verter applications it is useful to monitor the in verter operation from a remote location. In some cases, this requires only a panel-mounted analog meter (moving-coil type). In other cases, a contro ller de vice such as a PLC may command t[…]

  • Страница 151

    Analog and Digita l Monitor Output Operations and Monitoring 4–34 TIP: When using the analog meter for monitoring, adjust the meter so it has a zero reading when the [FM] output is zero. Then use scale factor B_81 to adjust the [FM] output so the maximum frequency in the in ve rter corresponds to a full-scale reading on the meter . The follo wing[…]

  • Страница 152

    SJ100 Inverter Operations and Monitoring 4–35 A uto-tuning f or Sensorless V e ctor Contr ol The SJ100 in verter has a b uilt-in auto-tuning algorithm. Its purpose is to detect and record the motor parameters to use in sensorless v ector control. As you may recall from Chapter 3, sensorless vector control (SL V) is the more sophisticated control […]

  • Страница 153

    Auto-tuning for Sen sorless Vector Con trol Operations and Monitoring 4–36 NO TE: During step 11, the motor will make a slight humming sound during the A C and DC excitation (A and B) steps of the auto-tuning process. Th is sound is normal. NO TE: When the SL V control method is selected with A_44, set the carrier frequency to 2.1 kHz or higher w[…]

  • Страница 154

    SJ100 Inverter Operations and Monitoring 4–37 If the in verter dri ves a motor/load with a small inertia, the motor may e xhibit “hunting” during running. If this occurs, ta ke the follo wing correctiv e steps: 1. Adjust the stabilization constant H_06/H206. 2. Decrease the carrier frequenc y B_83, but not belo w 2.1 kHz. 3. Set the Automatic[…]

  • Страница 155

    Auto-tuning for Sen sorless Vector Con trol Operations and Monitoring 4–38 Note 6: Do not interrupt the auto-tuning proce dure by remov ing power or by using the Stop command, unless it is an emer gency . If this does occur , init ialize the in verter’ s parameters to the factory def a ult settings (see “ Restoring F actory Default Settings ?[…]

  • Страница 156

    SJ100 Inverter Operations and Monitoring 4–39 PID Loop Operation In standard operation, the in verter uses a reference source sele cted by parameter A_01 for the output frequency , which may be a fix ed value (F_01), a v ariable set by the front panel potentiometer , or value from an analog i nput (v oltage or current). T o enable PID operation, […]

  • Страница 157

    Configuring the Inver ter for Multiple Motors Operations and Monitoring 4–40 Configuring the In ver ter f or Multiple Motors Simultaneous Connections For some app lications, you may need to connect two or more motors (wired in parallel) to a single in verter’ s output. For e xample, this is common in con veyor applications where two sepa rate c[…]

  • Страница 158

    SJ100 Inverter Operations and Monitoring 4–41 Having tw o motor profiles lets you store two “per sonalities” for motors in one in verter’ s memory . The in verter allo ws the final selec tion between the two motor ty pes to be made in the f ield through the use of an intelligent input terminal function [SET]. This provides an extra le vel o[…]

  • Страница 159

    In ver ter System Accessories In This Chapter …. p age — Introduction …………….. ……………….. ……………. 2 — Component Descriptions ……………….. …………. 3 — Dynamic Braking ……………………………………… 5 5[…]

  • Страница 160

    Introduction Motor Control Accessories 5–2 Intr oduction A motor control system will obviously include a motor and in verter , as well as fuses for safety . If you are connecting a motor to the in verter on a test bench just to get started, that’ s all you may need for no w . But a fully de veloped system can also ha ve a v ariety of additional[…]

  • Страница 161

    SJ100 Inverter Motor Control Accessories 5–3 Component Descriptions A C Reactors, Input Side This is useful in suppressing harmonics i nduced on the po wer supply lines, or when the main po wer voltage imbalance exceed s 3% (and po wer source capacity is more than 500 kV A), or to smooth out line fluctuations. It also improv es the power factor .[…]

  • Страница 162

    Component D escriptions Motor Control Accessories 5–4 Zer o-phase Reactor (RF Noise Filter) The zero-phase reactor helps reduce radiated noise from the in verter wiring. It can be used on the input or output side of the in verter . The example zero-phase reactor sho wn to the right comes with a mounting bracket. The wiring must go through the ope[…]

  • Страница 163

    SJ100 Inverter Motor Control Accessories 5–5 Dynamic Braking Intr oduction The purpose of dynamic braking is to improv e the ability of the in verter to stop (decelerate) the motor and load. This becomes neces- sary when an application has some or all of the following characteris- tics: • High load inertia compared to the av ai lable motor torq[…]

  • Страница 164

    Dynamic Braking Motor Control Accessories 5–6 Dynamic Braking Usage Ratio The in verter controls braking via a duty cycle method (percent of the time braking is ON versus total time). Parameter B_90 sets the dynamic braking usage ratio. In the graph to the right, the example sho ws three uses of dynamic braking in a 100-second period. The in vert[…]

  • Страница 165

    SJ100 Inverter Motor Control Accessories 5–7 SJ100 Dynamic Braking Selection T ables The SJ100 series in verter models hav e inte rnal braking units. Additional stopping torque is a vailable by adding extern al resistors. The required braking torq ue depends on your particular application. Other tables in this section will help you choose the pro[…]

  • Страница 166

    Dynamic Braking Motor Control Accessories 5–8 Selecting Braking Resistors f or Internal Braking Units Y ou can add one or more resi stors to your in verter conf i guration to increase braking torque performance. The tables belo w lists th e resistor types for in verter models with internal braking units. T ables for in verters with e xternal brak[…]

  • Страница 167

    SJ100 Inverter Motor Control Accessories 5–9 The table below lists 400V -class in verter models with built-in braking units. Depending on the desired braking torque or on the in verter model, the resistor selection sp ecifies multiple resistors in a parallel or series combination. The example diagram sho ws a parallel conf iguration. Please refer[…]

  • Страница 168

    Dynamic Braking Motor Control Accessories 5–10 Use one BRD–E2 braking unit for the braki ng torque listed in th e follo wing table. Note the column meanings in the tables: • Column “ A ” = A verage braking torque from 60 Hz to 3 Hz. • Column “B” = A verage braking torque from 120 Hz to 3 Hz. Connect a second braking unit in parallel[…]

  • Страница 169

    SJ100 Inverter Motor Control Accessories 5–11 400V Class In verters – The follo wing tables specify the braking options for 400V class SJ100 in verters and the braking torque for each option. Y ou can c onnect a single braking unit to the in verter , or two braking units for additional braking torque. Use one BRD–E2 braking unit for the braki[…]

  • Страница 170

    T r oub leshooting and Maintenance In This Chapter …. p age — T roubleshooting …………………….. ………………… 2 — Monitoring T rip Events , History , & Conditions . 5 — Restoring Factory Default Settings …………….. 8 — Maintenance and Inspection ……………………… 9 — W arranty ……………….. […]

  • Страница 171

    Troubleshooting T roub leshooting and Maintenance 6–2 T r oubleshooting Safety Messages Please read the followin g safety messages before troubleshooting or performing mainte- nance on the in verter and motor system. W ARNING: W ait at least f i ve (5) minutes after turning OFF the input po wer supply before performing maintenance or an insp ecti[…]

  • Страница 172

    SJ100 Inverter T roub leshooting and Maintenance 6–3 T roub leshooting Tips The table below lists typical symptoms and the corresponding solution(s). Symptom/condition Probable Cause Solution The motor will not run. The in verter outputs [U], [V], [W] are not supplying voltage. • Is the frequency command source A_01 parameter setting correct? ?[…]

  • Страница 173

    Troubleshooting T roub leshooting and Maintenance 6–4 The motor speed will not reach the target frequenc y (desired speed). • If using the analog input, is the current or voltage at [O] or [OI]? • Check the wiring. • Check the potentiometer or signal generating de vice. • Is the load too heavy? • Reduce the load. • Heavy loads acti va[…]

  • Страница 174

    SJ100 Inverter T roub leshooting and Maintenance 6–5 Monitoring T rip Events, History , & Conditions Fa ult Detection and Clearing The microprocessor in the in verter detects a v ariety of fault conditions and captures the e vent, record- ing it in a history table. The in verter output turns OFF , or “trips” similar to the way a circuit b[…]

  • Страница 175

    Monitoring Trip Events , History, & C onditions T roub leshooting and Maintenance 6–6 NO TE: If an EEPR OM error (E08) occurs, be sure to conf irm the parameter data v a lues are still correct. If the po wer is turned OFF while the [RS] (Reset) intelligent input terminal is ON, an EEPR OM error will occur when po wer is restored. E1 0 CT (cur[…]

  • Страница 176

    SJ100 Inverter T roub leshooting and Maintenance 6–7 T rip Histor y and In ver ter Status W e recommend that you first f ind the cause of the fault before clearing it. When a fault occurs, the in verter stores important performa nce data at the moment of the fault. T o access the data, use the monitor functions (D _xx) and select D_08 for details[…]

  • Страница 177

    Restoring Factory Default Settings T roub leshooting and Maintenance 6–8 Restoring F actor y Default Settings Y ou can restore all inv erter parameters to th e original factory (default) settings for the intended country of use. After initializing the in verter , use the po werup test in Chapter 2 to get the motor running again. T o initialize th[…]

  • Страница 178

    SJ100 Inverter T roub leshooting and Maintenance 6–9 Maintenance and Inspection Monthly and Y early Inspection Char t Note 1: The life of a capacitor is affected by the ambient te mperature. See “ Ca pacitor Life Curve ” on p age 6–11 . Note 2: The in verter must be cleaned periodica lly . If dust accumulates on the fan and heat sink, it ca[…]

  • Страница 179

    Maintenan ce and Inspecti on T roub leshooting and Maintenance 6–10 Megger T est The me gger is a piece of test equipment that us es a high v oltage to determine if an insulation degradation has occurred. F or in vert ers, it is important that the po wer termi- nals be isolated from the Earth GND terminal via the proper amount of insulation. The […]

  • Страница 180

    SJ100 Inverter T roub leshooting and Maintenance 6–11 Spare par ts W e recommend that you stock spare parts to reduce do wn time, including these parts: Capacitor Life Curve The DC b us inside the in verter uses a large capacitor as sho wn in the diagram below . The capacitor handles high v oltage and current as it smooths the po wer for use by t[…]

  • Страница 181

    Maintenan ce and Inspecti on T roub leshooting and Maintenance 6–12 General In ver ter Electrical Measurements The follow ing table specifies ho w t o measur e ke y system electrical parameters. The diagrams on the ne xt page sho w in verter-mot or systems and the location of measurement points for these parameters. Note 1: Use a meter indicating[…]

  • Страница 182

    SJ100 Inverter T roub leshooting and Maintenance 6–13 The figu res belo w show measurement locations for v oltage, c urrent, and po wer measure- ments listed in the table on the pre vious page. The v oltage to be measured is the funda- mental wa ve ef fecti ve v oltage. The power to be measured is the total ef fectiv e po wer . E 1 W 1 I 1 I 1 I […]

  • Страница 183

    Maintenan ce and Inspecti on T roub leshooting and Maintenance 6–14 In ver ter Output V oltage Measurement T echniques T aking voltage measurements around dri ves equipment requires the right equipment and a safe approach. Y ou are working with high voltages and high-frequenc y switching wa veforms that are not pure sinusoids. Di gital v oltmeter[…]

  • Страница 184

    SJ100 Inverter T roub leshooting and Maintenance 6–15 IGBT T est Method The follo wing procedure will check the in verter transistors (IGBTs) and diodes: 1. Disconnect input po wer to terminals [R, S, and T] and motor terminals [U, V , and W]. 2. Disconnect any wires from terminals [+ ] and [RB] for re generati ve brakin g. 3. Use a Digital V olt[…]

  • Страница 185

    Warranty T roub leshooting and Maintenance 6–16 W arranty W arranty T erms The warranty period under normal inst allation and handling conditions shall be two (2) years from the da te of manuf acture (“DA TE” on product nameplate), or one (1) year from the date of installation, whichev er occurs first. The w arranty shall cov er the repair or[…]

  • Страница 186

    Glossar y and Bib liograph y In This Appendix…. p age — Glossary …………………. ……………….. ……………. 2 — Bibliography ………………. ……………….. …………. 8 A[…]

  • Страница 187

    Glossary Appendix A A–2 Glossary Ambient T emperatur e The air temperature in the cham ber containing a po wered electronic unit. A unit’ s heat sinks rely on a lo wer ambient temperature in order to dissipate heat aw ay from sensiti ve electronics. Arriv al Frequency The arriv al frequency refers to the set output frequenc y of the in verter f[…]

  • Страница 188

    SJ100 Inverter Appendix A A–3 DC Braking The in verter DC braking feature stops the A C commutation to the motor , and sends a DC current through the motor windings in order to stop the motor . Also called “DC injection braking, ” it has li ttle ef fect at high speed, and is used as the motor is nearing a stop. Deadband In a control system, t[…]

  • Страница 189

    Glossary Appendix A A–4 Fr equency Setting While frequenc y has a broad meani ng in electronics, it typically refers to moto r speed for variable-frequency driv es (in verters). This is because the output frequency of the in verter is v ariable, and is proportional to the attained motor speed. For e xample, a motor with a base frequency of 60 Hz […]

  • Страница 190

    SJ100 Inverter Appendix A A–5 Jump Fr equency A jump frequency is a point on the in verter output frequency range that you want the in verter to skip around. This feature may be used to av oid a resonant frequency , and you can program up to three jump frequencies in the in verter . Line Reactor A three-phase inductor generally inst alled in the […]

  • Страница 191

    Glossary Appendix A A–6 PWM Pulse-width modulation: A type of A C adjustable frequency dri ve that accomplishes frequenc y and voltage control at the output section (in verter) of the dri ve. Th e driv e output voltage w a veform is at a constant amplitude, and by “chopping” the w av e form (pulse- width-modulating), the a verage v oltage is […]

  • Страница 192

    SJ100 Inverter Appendix A A–7 Single-phase power An A C power source consisting of Hot and Neutral wires. An Earth Ground connection usually accompanies them. In theory , the voltage potential on Neutral stays at or near Earth Ground, while Hot v aries sinusoidally abov e and below Neutral. This po wer source is named Single Phase to dif feren ti[…]

  • Страница 193

    Bibliography Appendix A A–8 T or que The rotational force e xerted by a mo tor sh aft. The units of measure- ment consist of the distance (r adius from shaft center axis) and force (weight) applied at that di stance. Units are usually gi ven as pound-feet, ounce-inches, or Ne wton-meters. T ransistor A solid state, three-terminal devi ce that pro[…]

  • Страница 194

    Drive P arameter Settings T ab les In This Appendix…. p age — Introduction …………….. ……………….. ……………. 2 — Parameter Settings for Keyp ad Entry ………….. 2 B[…]

  • Страница 195

    Introduction Appendix B B–2 Intr oduction This appendix lists the user-programmable parameters for the SJ100 series in verters and the default v alues for European and U.S. product types. The right-most column of the tables is blank, so you can record v alues you have changed from the default. This in volves just a fe w parameters for most appl i[…]

  • Страница 196

    SJ100 Inverter Appendix B B–3 Standar d Functions “A” Gr oup Parameters Default Setting User Setting Func. Code Name -FE (Europe) -FU (USA) –FR (Japan) A_01 Frequency source setting 01 01 00 A_02 Run command source setting 01 01 02 A_03 Base frequenc y setting 50.0 60.0 60.0 A203 Base frequenc y setting, 2nd motor 50.0 60.0 60.0 A_04 Maximu[…]

  • Страница 197

    Parameter Settings for Keypad Entry Appendix B B–4 A_32 Multi-speed 12 setting 0 0 0 A_33 Multi-speed 13 setting 0 0 0 A_34 Multi-speed 14 setting 0 0 0 A_35 Multi-speed 15 setting 0 0 0 A_38 Jog frequency setting 1.0 1.0 1.0 A_39 Jog stop mode 00 00 00 A_41 T orque boost method selection 00 00 00 A241 T orque boost method selection, 2nd motor 00[…]

  • Страница 198

    SJ100 Inverter Appendix B B–5 A_72 PID proportional gain 1.0 1.0 1.0 A_73 PID integral time constant 1.0 1.0 1.0 A_74 PID deri vati ve gain 0.0 0.0 0.0 A_75 PV scale con version 1.00 1.00 1.00 A_76 PV source setting 00 00 00 A_81 A VR function select 02 00 02 A_82 A VR voltage select 230/400 230/460 200/400 A_92 Acceleration (2) time setting 15.0[…]

  • Страница 199

    Parameter Settings for Keypad Entry Appendix B B–6 Fine T uning Functions “B” Gr oup Parameters Default Setting User Setting Func. Code Name -FE (Europe) -FU (USA) –FR (Japan) B_01 Selection of automatic restart mode 00 00 00 B_02 Allowable under -voltage po wer failure time 1.0 1.0 1.0 B_03 Retry wait time before motor restart 1.0 1.0 1.0 […]

  • Страница 200

    SJ100 Inverter Appendix B B–7 B_89 Data select for digital op. OPE-J 01 01 01 B_90 Dynamic braking usage ratio 0.0 0.0 0.0 B_91 Stop mode selection 00 00 00 B_92 Cooling fan control 00 00 00 “B” Group P arameters Default Setting User Setting Func. Code Name -FE (Europe) -FU (USA) –FR (Japan)[…]

  • Страница 201

    Parameter Settings for Keypad Entry Appendix B B–8 Intelligent T erminal Functions “C” Group P arameters Default Setting User Setting Func. Code Name -FE (Europe) -FU (USA) –FR (Japan) C_01 T erminal [1] function 00 00 00 C_02 T erminal [2] function 01 01 01 C_03 T erminal [3] function 02 16 02 C_04 T erminal [4] function 03 13 03 C_05 T er[…]

  • Страница 202

    SJ100 Inverter Appendix B B–9 Motor Constants Functions C_91 Debug mode enable 00 00 00 Do not edit C_92 Core monitor address 0000 0000 0000 Do not edit C_93 Core monitor date — — — Do not edit C_94 Core set address d001 d001 d001 Do not edit C_95 Core set date 00 00 00 Do not edit “C” Group P arameters Default Setti ng User Setting Fun[…]

  • Страница 203

    Parameter Settings for Keypad Entry Appendix B B–10 H_22 Motor constant L Factory set Factory set Factory set H222 Motor constant L, 2nd motor F actory set Factory set Factory set H_23 Motor constant Io Factory set Factory set Factory set H223 Motor constant Io, 2nd motor Factory set Factory set Factory set H_24 Motor Constant J Factory set Facto[…]

  • Страница 204

    CE–EMC Installation Guidelines In This Appendix…. p age — CE–EMC Installation Guidelines ………………… 2 — Hitachi EMC Recommendations ………………… 6 C[…]

  • Страница 205

    CE–EMC Installation Guidelines Appendix C C–2 CE–EMC Installation Guidelines Y ou are required to satisfy the EMC dire ctiv e (89/336/EEC) when using an SJ100 in verter in an EU country . T o satisfy the EMC directive an d to comply with standard, follow the guidelines in this section. 1. As user you must ensure that the HF (hi gh frequency) […]

  • Страница 206

    SJ100 Inverter Appendix C C–3 4. T ake measures to minimize interference that is frequently coupled in through installa- tion cables. • Separate interfering cables with 0.25m minimum from cables susceptible to inter- ference. A particularly critical point is laying parallel cables ov er longer distances. If two cables intersect (one cr osses ov[…]

  • Страница 207

    CE–EMC Installation Guidelines Appendix C C–4 L1 L2 L3 PE M 3~ SJ100 in ver ter with footprint-type filter[…]

  • Страница 208

    SJ100 Inverter Appendix C C–5 L1 L2 L3 PE SJ100 in ver ter with book-type filter M 3~[…]

  • Страница 209

    Hitachi EMC Recommendations Appendix C C–6 Hitachi EMC Recommendations W ARNING: This equipment should be installed, adjusted, and serviced by qualified personal familiar with construction and ope ration of the equipment and the hazards in volv ed. Failure to observ e this precaution could result in bodily injury . Use the follo wing checklist to[…]

  • Страница 210

    Inde x A A Group functions 3–9 AC reactors 5–3 Acceleration 1–22 , 3–8 characteristic curves 3–23 second function 3–21 two-stage 4–15 Access levels 3–5 , 3–28 , 4–19 Access to terminals 2–2 Accessories 5–2 Alarm signal 4–30 Algorithms 3–43 Algorithms, torque control 3–5 Ambient temperature 2–8 , A–2 Analog input se[…]

  • Страница 211

    Index –2 D D Group parameters 3–6 DC braking 3–16 , 4–12 , 4–13 , A–3 DC link choke 5–4 Deadband A–3 Deceleration 1–22 , 3–8 , 4–12 characteristic curves 3–23 second function 3–21 two-stage 4–15 Default parameter values B–2 Default settings restoring 6–8 Derating curves 1–12 Derivative gain 3–19 Digital operator […]

  • Страница 212

    SJ100 Inverter Index –3 I IGBT 1–18 , A–4 test method 6–15 Index of terminal functions 4–7 Inertia A–4 Initialization 6–8 Initialization codes 3–30 Input circuits 4–8 Input terminals 2–15 Inspection electrical mea surements 6–12 IGBT test method 6–15 measurement techniques 6–14 procedures 6–9 unpacking 2–2 Installation[…]

  • Страница 213

    Index –4 O Open-collector outputs 4–24 , A–5 Operational modes 3–5 Operator interfaces 1–3 Optional components 2–5 Options 1–2 Output adjustment parameters 3–41 Output circuits 4–24 Output deviation for PID control 4–29 Output frequency 3–8 Output overload 3–27 Output terminals 2–18 Overload advance notice signal 4–28 Ov[…]

  • Страница 214

    SJ100 Inverter Index –5 Specifica tions derating curves 1–12 general 1–9 inverter 1–5 label 1–4 , 2–3 logic signals 4–6 Speed control 1–18 , 1–22 , 4–10 Speed pot 2–25 Squirrel cage A–7 Standard functions 3–9 Stator A–7 Stop command 4–9 Stop Mode 3–32 Supply wiring 2–15 Switching frequency 3–30 Symbol definitions[…]

Cover

HITACHI

SJ100 Series Inverter
Instruction Manual

• Single-phase Input 200V Class

• Three-phase Input 200V Class

• Three-phase Input 400V Class

Manual Number: NB585XF

December 2003

After reading this manual,

keep it handy for future reference.

Hitachi Industrial Equipment Systems Co., Ltd.

Safety Messages

For the best results with the SJ100 Series inverter, carefully read this manual and all of
the warning labels attached to the inverter before installing and operating it, and follow
the instructions exactly. Keep this manual handy for quick reference.

Definitions and Symbols

A safety instruction (message) includes a “Safety Alert Symbol” and a signal word or
phrase such as WARNING or CAUTION. Each signal word has the following meaning:

HIGH VOLTAGE: This symbol indicates high voltage. It calls your attention to items
or operations that could be dangerous to you and other persons operation this equipment.
Read the message and follow the instructions carefully.

WARNING: Indicates a potentially hazardous situation that, if not avoided, can result in
serious injury or death.

SJ100 Inverter

i

CAUTION: Indicates a potentially hazardous situation that, if not avoided, can result in
minor to moderate injury, or serious damage to the product. The situation described in
the CAUTION may, if not avoided, lead to serious results. Important safety measures
are described in CAUTION (as well as WARNING), so be sure to observe them.

1 Step 1: Indicates a step in a series of action steps required to accomplish a goal. The

number of the step will be contained in the step symbol.

NOTE: Notes indicate an area or subject of special merit, emphasizing either the
product’s capabilities or common errors in operation or maintenance.

TIP: Tips give a special instruction that can save time or provide other benefits while
installing or using the product. The tip calls attention to an idea that may not be obvious
to first-time users of the product.

Hazardous High Voltage

HIGH VOLTAGE: Motor control equipment and electronic controllers are connected
to hazardous line voltages. When servicing drives and electronic controllers, there may
be exposed components with housings or protrusions at or above line potential. Extreme
care should be taken to protect against shock.
Stand on an insulating pad and make it a habit to use only one hand when checking com­ponents. Always work with another person in case an emergency occurs. Disconnect
power before checking controllers or performing maintenance. Be sure equipment is
properly grounded. Wear safety glasses whenever working on electronic controllers or
rotating machinery.

ii

General Precautions — Read These First!

WARNING: This equipment should be installed, adjusted, and serviced by qualified
electrical maintenance personnel familiar with the construction and operation of the
equipment and the hazards involved. Failure to observe this precaution could result in
bodily injury.

WARNING: The user is responsible for ensuring that all driven machinery, drive train
mechanism not supplied by Hitachi Industrial Equipment Systems Co., Ltd., and process
line material are capable of safe operation at an applied frequency of 150% of the
maximum selected frequency range to the AC motor. Failure to do so can result in
destruction of equipment and injury to personnel should a single-point failure occur.

WARNING: For equipment protection, install a ground leakage type breaker with a fast
response circuit capable of handling large currents. The ground fault protection circuit is
not designed to protect against personal injury.

WARNING: HAZARD OF ELECTRICAL SHOCK. DISCONNECT INCOMING
POWER BEFORE WORKING ON THIS CONTROL.

WARNING: Wait at least five (5) minutes after turning OFF the input power supply
before performing maintenance or an inspection. Otherwise, there is the danger of
electric shock.

CAUTION: These instructions should be read and clearly understood before working
on SJ100 series equipment.

CAUTION: Proper grounds, disconnecting devices and other safety devices and their
location are the responsibility of the user and are not provided by Hitachi Industrial
Equipment Systems Co., Ltd.

CAUTION: Be sure to connect a motor thermal disconnect switch or overload device to
the SJ100 series controller to assure that the inverter will shut down in the event of an
overload or an overheated motor.

HIGH VOLTAGE: Dangerous voltage exists until power light is OFF. Wait at least five
(5) minutes after input power is disconnected before performing maintenance.

WARNING: This equipment has high leakage current and must be permanently (fixed)
hard-wired to earth ground via two independent cables.

SJ100 Inverter

WARNING: Rotating shafts and above-ground electrical potentials can be hazardous.
Therefore, it is strongly recommended that all electrical work conform to the National
Electrical Codes and local regulations. Installation, alignment and maintenance should
be performed only by qualified personnel.
Factory-recommended test procedures included in the instruction manual should be
followed. Always disconnect electrical power before working on the unit.

CAUTION:

a) Class I motor must be connected to earth ground via low resistive path (< 0.1Ω)
b) Any motor used must be of a suitable rating.
c) Motors may have hazardous moving parts. In this event suitable protection must

be provided.

CAUTION: Alarm connection may contain hazardous live voltage even when inverter
is disconnected. When removing the front cover for maintenance or inspection, confirm
that incoming power for alarm connection is completely disconnected.

CAUTION: Hazardous (main) terminals for any interconnection (motor, contact
breaker, filter, etc.) must be inaccessible in the final installation.

iii

CAUTION: This equipment should be installed in IP54 or equivalent (see EN60529)
enclosure. The end application must be in accordance with BS EN60204-1. Refer to the
section
be suitably amended for your application.

CAUTION: Connection to field wiring terminals must be reliably fixed having two
independent means of mechanical support. Use a termination with cable support (figure
below), or strain relief, cable clamp, etc.

CAUTION: A double-pole disconnection device must be fitted to the incoming main
power supply close to the inverter. Additionally, a protection device meeting IEC947-1/
IEC947-3 must be fitted at this point (protection device data shown in

Wire and Fuse Sizes” on page 2–14).

Choosing a Mounting Location” on page 2–7. The diagram dimensions are to

Terminal (ring lug) Cable support

Cable

Determining

NOTE: The above instructions, together with any other requirements highlighted in this
manual, must be followed for continued LVD (European Low Voltage Directive)
compliance.

iv

Index to Warnings and Cautions in This Manual

Installation — Cautions for Mounting Procedures

CAUTION: The inverter is shipped with a plastic cover over the top vent
grill. REMOVE this cover after the installation is complete. Operation
with this cover in place will not allow proper cooling, and damage to the
inverter may result.

CAUTION: Be sure to install the unit on flame-resistant material such as
a steel plate. Otherwise, there is the danger of fire.

CAUTION: Be sure not to place any flammable materials near the
inverter. Otherwise, there is the danger of fire.

CAUTION: Be sure not to let the foreign matter enter vent openings in
the inverter housing, such as wire clippings, spatter from welding, metal
shavings, dust, etc. Otherwise, there is the danger of fire.

CAUTION: Be sure to install the inverter in a place that can bear the
weight according to the specifications in the text (Chapter 1, Specifica­tions Tables). Otherwise, it may fall and cause injury to personnel.

CAUTION: Be sure to install the unit on a perpendicular wall that is not
subject to vibration. Otherwise, it may fall and cause injury to personnel.

CAUTION: Be sure not to install or operate an inverter that is damaged
or has missing parts. Otherwise, it may cause injury to personnel.

……. 2–6

……. 2–7

……. 2–7

……. 2–7

……. 2–7

……. 2–7

……. 2–7

CAUTION: Be sure to install the inverter in a well-ventilated room that
does not have direct exposure to sunlight, a tendency for high tempera­ture, high humidity or dew condensation, high levels of dust, corrosive
gas, explosive gas, inflammable gas, grinding-fluid mist, salt damage,
etc. Otherwise, there is the danger of fire.

CAUTION: Be sure to maintain the specified clearance area around the
inverter and to provide adequate ventilation. Otherwise, the inverter may
overheat and cause equipment damage or fire.

……. 2–7

……. 2–8

Wiring — Warnings for Electrical Practices and Wire Specifications

WARNING: “Use 60/75°C Cu wire only” or equivalent. ….. 2–13

WARNING: “Open Type Equipment.” ….. 2–13

WARNING: “Suitable for use on a circuit capable of delivering not more
than 5,000 rms symmetrical amperes, 240 V maximum.” For models with
suffix N or L.

….. 2–13

SJ100 Inverter

v

WARNING: “Suitable for use on a circuit capable of delivering not more
than 5,000 rms symmetrical amperes, 480 V maximum.” For models with
suffix H.

HIGH VOLTAGE: Be sure to ground the unit. Otherwise, there is a
danger of electric shock and/or fire.

HIGH VOLTAGE: Wiring work shall be carried out only by qualified
personnel. Otherwise, there is a danger of electric shock and/or fire.

HIGH VOLTAGE: Implement wiring after checking that the power
supply is OFF. Otherwise, you may incur electric shock and/or fire.

HIGH VOLTAGE: Do not connect wiring to an inverter or operate an
inverter that is not mounted according the instructions given in this
manual. Otherwise, there is a danger of electric shock and/or injury to
personnel.

WARNING: Make sure the input power to the inverter is OFF. If the drive
has been powered, leave it OFF for five minutes before continuing.

Wiring — Cautions for Electrical Practices

…. 2–13

…. 2–13

…. 2–13

…. 2–13

…. 2–13

…. 2–19

CAUTION: Fasten the screws with the specified fastening torque in the
table below. Check for any loosening of screws. Otherwise, there is the
danger of fire.

CAUTION: Be sure that the input voltage matches the inverter specifica­tions: • Single/Three phase 200 to 240 V 50/60 Hz (up to 2.2kW) • Three
phase 200 to 230V 50/60Hz (above 2.2kW) • Three phase 380 to 460 V
50/60Hz

CAUTION: Be sure not to power a three-phase-only inverter with single
phase power. Otherwise, there is the possibility of damage to the inverter
and the danger of fire.

CAUTION: Be sure not to connect an AC power supply to the output
terminals. Otherwise, there is the possibility of damage to the inverter
and the danger of injury and/or fire.

Power Input Power Output

(L) (N)

L1 L2 L3

T1 T2 T3

UVW

NOTE:
L, N:

L1, L2, L3:

Single-phase 200 to 240V 50/60 Hz
Three-phase 200 to 240V 50/60 Hz
Three-phase 380 to 460V 50/60 Hz

…. 2–15

…. 2–16

…. 2–16

…. 2–17

vi

CAUTION: Remarks for using ground fault interrupter breakers in the
main power supply: Adjustable frequency inverters with CE-filters (RFI­filter) and shielded (screened) motor cables have a higher leakage current
toward Earth GND. Especially at the moment of switching ON this can
cause an inadvertent trip of ground fault interrupters. Because of the
rectifier on the input side of the inverter there is the possibility to stall the
switch-off function through small amounts of DC current. Please observe
the following: • Use only short time-invariant and pulse current-sensitive
ground fault interrupters with higher trigger current. • Other components
should be secured with separate ground fault interrupters. • Ground fault
interrupters in the power input wiring of an inverter are not an absolute
protection against electric shock.

CAUTION: Be sure to install a fuse in each phase of the main power
supply to the inverter. Otherwise, there is the danger of fire.

CAUTION: For motor leads, ground fault interrupter breakers and
electromagnetic contactors, be sure to size these components properly
(each must have the capacity for rated current and voltage). Otherwise,
there is the danger of fire.

Powerup Test Caution Messages

….. 2–17

….. 2–17

….. 2–17

CAUTION: The heat sink fins will have a high temperature. Be careful
not to touch them. Otherwise, there is the danger of getting burned.

CAUTION: The operation of the inverter can be easily changed from low
speed to high speed. Be sure to check the capability and limitations of the
motor and machine before operating the inverter. Otherwise, there is the
danger of injury.

CAUTION: If you operate a motor at a frequency higher than the inverter
standard default setting (50Hz/60Hz), be sure to check the motor and
machine specifications with the respective manufacturer. Only operate
the motor at elevated frequencies after getting their approval. Otherwise,
there is the danger of equipment damage and/or injury.

CAUTION: Check the following before and during the powerup test.
Otherwise, there is the danger of equipment damage. • Is the shorting bar
between the [+1] and [+] terminals installed? DO NOT power or operate
the inverter if the jumper is removed. • Is the direction of the motor
rotation correct? • Did the inverter trip during acceleration or decelera­tion? • Were the rpm and frequency meter readings as expected? • Were
there any abnormal motor vibrations or noise?

….. 2–20

….. 2–20

…. 2–20,

….. 2–24

….. 2–20

Warnings for Configuring Drive Parameters

SJ100 Inverter

vii

WARNING: When parameter B_12, level of electronic thermal setting, is
set to device FLA rating (Full Load Ampere nameplate rating), the device
provides solid state motor overload protection at 115% of device FLA or
equivalent. Parameter B_12, level of electronic thermal setting, is a
variable parameter.

Cautions for Configuring Drive Parameters

CAUTION: Be careful to avoid specifying a braking time that is long
enough to cause motor overheating. If you use DC braking, we recom­mend using a motor with a built-in thermistor, and wiring it to the
inverter’s thermistor input (see “Thermistor Thermal Protection” on
page 4–22). Also refer to the motor manufacturer’s specifications for
duty-cycle recommendations during DC braking.

Warnings for Operations and Monitoring

WARNING: Be sure to turn ON the input power supply only after closing
the front case. While the inverter is energized, be sure not to open the
front case. Otherwise, there is the danger of electric shock.

…. 3–26

…. 3–16

…… 4–3

WARNING: Be sure not to operate electrical equipment with wet hands.
Otherwise, there is the danger of electric shock.

WARNING: While the inverter is energized, be sure not to touch the
inverter terminals even when the motor is stopped. Otherwise, there is the
danger of electric shock.

WARNING: If the Retry Mode is selected, the motor may suddenly
restart after a trip stop. Be sure to stop the inverter before approaching the
machine (be sure to design the machine so that safety for personnel is
secure even if it restarts.) Otherwise, it may cause injury to personnel.

WARNING: If the power supply is cut OFF for a short period of time, the
inverter may restart operation after the power supply recovers if the Run
command is active. If a restart may pose danger to personnel, so be sure
to use a lock-out circuit so that it will not restart after power recovery.
Otherwise, it may cause injury to personnel.

WARNING: The Stop Key is effective only when the Stop function is
enabled. Be sure to enable the Stop Key separately from the emergency
stop. Otherwise, it may cause injury to personnel.

WARNING: During a trip event, if the alarm reset is applied and the Run
command is present, the inverter will automatically restart. Be sure to
apply the alarm reset only after verifying the Run command is OFF.
Otherwise, it may cause injury to personnel.

…… 4–3

…… 4–3

…… 4–3

…… 4–3

…… 4–3

…… 4–3

viii

WARNING: Be sure not to touch the inside of the energized inverter or to
put any conductive object into it. Otherwise, there is a danger of electric
shock and/or fire.

WARNING: If power is turned ON when the Run command is already
active, the motor will automatically start and injury may result. Before
turning ON the power, confirm that the RUN command is not present.

WARNING: When the Stop key function is disabled, pressing the Stop
key does not stop the inverter, nor will it reset a trip alarm.

WARNING: Be sure to provide a separate, hard-wired emergency stop
switch when the application warrants it.

WARNING: If the power is turned ON and the Run command is already
active, the motor starts rotation and is dangerous! Before turning power
ON, confirm that the Run command is not active.

WARNING: After the Reset command is given and the alarm reset
occurs, the motor will restart suddenly if the Run command is already
active. Be sure to set the alarm reset after verifying that the Run
command is OFF to prevent injury to personnel.

WARNING: You may need to disconnect the load from the motor before
performing auto-tuning. The inverter runs the motor forward and
backward for several seconds without regard to load movement limits.

……. 4–3

……. 4–3

……. 4–3

……. 4–3

……. 4–9

….. 4–21

….. 4–35

Cautions for Operations and Monitoring

CAUTION: The heat sink fins will have a high temperature. Be careful
not to touch them. Otherwise, there is the danger of getting burned.

CAUTION: The operation of the inverter can be easily changed from low
speed to high speed. Be sure check the capability and limitations of the
motor and machine before operating the inverter. Otherwise, it may cause
injury to personnel.

CAUTION: If you operate a motor at a frequency higher than the inverter
standard default setting (50Hz/60Hz), be sure to check the motor and
machine specifications with the respective manufacturer. Only operate
the motor at elevated frequencies after getting their approval. Otherwise,
there is the danger of equipment damage.

CAUTION: It is possible to damage the inverter or other devices if your
application exceeds the maximum current or voltage characteristics of a
connection point.

……. 4–2

……. 4–2

……. 4–2

……. 4–4

SJ100 Inverter

Warnings and Cautions for Troubleshooting and Maintenance

ix

WARNING: Wait at least five (5) minutes after turning OFF the input
power supply before performing maintenance or an inspection. Other­wise, there is the danger of electric shock.

WARNING: Make sure that only qualified personnel will perform
maintenance, inspection, and part replacement. Before starting to work,
remove any metallic objects from your person (wristwatch, bracelet,
etc.). Be sure to use tools with insulated handles. Otherwise, there is a
danger of electric shock and/or injury to personnel.

WARNING: Never remove connectors by pulling on its wire leads (wires
for cooling fan and logic P.C.board). Otherwise, there is a danger of fire
due to wire breakage and/or injury to personnel.

CAUTION: Do not connect the megger to any control circuit terminals
such as intelligent I/O, analog terminals, etc. Doing so could cause
damage to the inverter.

CAUTION: Never test the withstand voltage (HIPOT) on the inverter.
The inverter has a surge protector between the main circuit terminals
above and the chassis ground.

HIGH VOLTAGE: Be careful not to touch wiring or connector terminals
when working with the inverters and taking measurements. Be sure to
place the measurement circuitry components above in an insulated
housing before using them.

…… 6–2

…… 6–2

…… 6–2

…. 6–10

…. 6–10

…. 6–14

General Warnings and Cautions

WARNING: Never modify the unit. Otherwise, there is a danger of electric shock and/
or injury.

CAUTION: Withstand voltage tests and insulation resistance tests (HIPOT) are
executed before the units are shipped, so there is no need to conduct these tests before
operation.

CAUTION: Do not attach or remove wiring or connectors when power is applied. Also,
do not check signals during operation.

CAUTION: Be sure to connect the grounding terminal to earth ground.

CAUTION: When inspecting the unit, be sure to wait five minutes after tuning OFF the

power supply before opening the cover.

x

CAUTION: Do not stop operation by switching OFF electromagnetic contactors on the
primary or secondary sides of the inverter.

Ground fault

interrupter

Power

Input

L1, L2, L3

Inverter

U, V, W

P24

FW

Motor

When there has been a sudden power failure while an operation instruction is active,
then the unit may restart operation automatically after the power failure has ended. If
there is a possibility that such an occurrence may harm humans, then install an electro­magnetic contactor (Mgo) on the power supply side, so that the circuit does not allow
automatic restarting after the power supply recovers. If the optional remote operator is
used and the retry function has been selected, this will also cause automatic restarting
when a Run command is active. So, please be careful.

CAUTION: Do not insert leading power factor capacitors or surge absorbers between
the output terminals of the inverter and motor.

Power

Input

Ground fault

interrupter

L1, L2, L3

U, V, W

Inverter

GND lug

Surge absorber

Motor

Leading power

factor capacitor

CAUTION: MOTOR TERMINAL SURGE VOLTAGE SUPPRESSION FILTER
(For the 400 V CLASS)

In a system using an inverter with the voltage control PWM system, a voltage surge
caused by the cable constants such as the cable length (especially when the distance
between the motor and inverter is 10 m or more) and cabling method may occur at the
motor terminals. A dedicated filter of the 400 V class for suppressing this voltage surge
is available. Be sure to install a filter in this situation.

SJ100 Inverter

CAUTION: SUPPRESSION FOR NOISE INTERFERENCE FROM INVERTER

The inverter uses many semiconductor switching elements such as transistors and
IGBTs. Thus, a radio receiver or measuring instrument located near the inverter is
susceptible to noise interference.
To protect the instruments from erroneous operation due to noise interference, they
should be used well away from the inverter. It is also effective to shield the whole
inverter structure.
The addition of an EMI filter on the input side of the inverter also reduces the effect of
noise from the commercial power line on external devices.
Note that the external dispersion of noise from the power line can be minimized by
connecting an EMI filter on the primary side of inverter.

EMI Filter Inverter

R1

S1

T1

R2

S2

T2

L1

L2

L3

U

V

W

Motor

xi

noise

EMI Filter

Completely ground the
enclosed panel, metal
screen, etc. with as
short a wire as possible.

Inverter

Remote

Operator

Motor

Grounded frame

Conduit or shielded
cable—to be grounded

CAUTION: EFFECTS OF POWER DISTRIBUTION SYSTEM ON INVERTER

In the cases below involving a general-purpose inverter, a large peak current can flow on
the power supply side, sometimes destroying the converter module:

1. The unbalance factor of the power supply is 3% or higher.

2. The power supply capacity is at least 10 times greater than the inverter capacity (or
the power supply capacity is 500 kVA or more).

3. Abrupt power supply changes are expected, due to conditions such as:
a. Several inverters are interconnected with a short bus.
b. A thyristor converter and an inverter are interconnected with a short bus.
c. An installed phase advance capacitor opens and closes.

Where these conditions exist or when the connected equipment must be highly reliable,
you MUST install an input-side AC reactor of 3% (at a voltage drop at rated current)
with respect to the supply voltage on the power supply side. Also, where the effects of an
indirect lightning strike are possible, install a lightning conductor.

xii

CAUTION: When the EEPROM error E08 occurs, be sure to confirm the setting values
again.

CAUTION: When using normally closed active state settings (C_11 to C_16) for exter-
nally commanded Forward or Reverse terminals [FW] or [RV], the inverter may start
automatically when the external system is powered OFF or disconnected from the
inverter! So, do not use normally closed active state settings for Forward or Reverse
terminals [FW] or [RV] unless your system design protects against unintended motor
operation.

CAUTION: In all the illustrations in this manual, covers and safety devices are
occasionally removed to describe the details. While operating the product, make sure
that the covers and safety devices are placed as they were specified originally and
operate it according to the instruction manual.

UL® Cautions, Warnings, and Instructions

Wiring Warnings for Electrical Practices and Wire Sizes

The Cautions, Warnings, and instructions in this section summarize the procedures
necessary to ensure an inverter installation complies with Underwriters Laboratories
guidelines.

WARNING: “Use 60/75°C Cu wire only” or equivalent.

WARNING: “Open Type Equipment.”

WARNING: “Suitable for use on a circuit capable of delivering not more than 5,000

rms symmetrical amperes, 240 V maximum.” For models with suffix N or L.

WARNING: “Suitable for use on a circuit capable of delivering not more than 5,000
rms symmetrical amperes, 480 V maximum.” For models with suffix H.

®

Terminal Tightening Torque and Wire Size

The wire size range and tightening torque for field wiring terminals are presented in the
table below.

SJ100 Inverter

xiii

Input

Voltage

200V

400V

Motor Output

Inverter Model

kW HP ft-lbs (N-m)

0.2 1/4 SJ100-002NFE/NFU

0.55 3/4 SJ100-005NFE

0.75 1 SJ100-007NFE/NFU

1.1 1 1/2 SJ100-011NFE

1.5 2 SJ100-015NFE/NFU 12

2.2 3 SJ100-022NFE/NFU 10

3.7 5 SJ100-037LFU 12

5.5 7 1/2 SJ100-055LFU 10

7.5 10 SJ100-075LFU 8

0.4 1/2 SJ100-004HFE/HFU

0.75 1 SJ100-007HFE/HFU

1.5 2 SJ100-015HFE/HFU

2.2 3 SJ100-022HFE/HFU

3.0 4 SJ100-030HFE

4.0 5 SJ100-040HFE/HFU

Wiring Size

Range (AWG)

16 0.6 0.80.4 1/2 SJ100-004NFE/NFU

14

16

14

Torq ue

0.9 1.2

1.5 2.0

0.9 1.2

5.5 7 1/2 SJ100-055HFE/HFU

7.5 10 SJ100-075HFE/HFU

Wire Connectors

WARNING: Field wiring connections must be
made by a UL Listed and CSA Certified ring lug
terminal connector sized for the wire gauge being
used. The connector must be fixed using the
crimping tool specified by the connector
manufacturer.

12 1.5 2.0

Terminal (ring lug)

Cable support

Cable

xiv

Circuit Breaker and Fuse Sizes

The inverter’s connections to input power must include UL Listed inverse time circuit
breakers with 600V rating, or UL Listed fuses as shown in the table below.

Input

Voltage

200V

Motor Output

Inverter Model

kW HP

0.2 1/4 SJ100-002NFE/NFU 10

0.4 1/2 SJ100-004NFE/NFU 10

0.55 3/4 SJ100-005NFE 10

0.75 1 SJ100-007NFE/NFU 15

1.1 1 1/2 SJ100-011NFE 15

1.5 2 SJ100-015NFE/NFU 20 (single ph.)

2.2 3 SJ100-022NFE/NFU 30 (single ph.)

3.7 5 SJ100-037LFU 30

5.5 7 1/2 SJ100-055LFU 40

7.5 10 SJ100-075LFU 50

0.4 1/2 SJ100-004HFE/HFU 3

0.75 1 SJ100-007HFE/HFU 6

1.5 2 SJ100-015HFE/HFU 10

Fuse (A)

(UL-rated,

class J, 600V)

15 (three ph.)

20 (three ph.)

400V

2.2 3 SJ100-022HFE/HFU 10

3.0 4 SJ100-030HFE 15

4.0 5 SJ100-040HFE/HFU 15

5.5 7 1/2 SJ100-055HFE/HFU 20

7.5 10 SJ100-075HFE/HFU 25

Motor Overload Protection

Hitachi SJ100 inverters provide solid state motor overload protection, which depends on
the proper setting of the following parameters:

• B_12 “electronic overload protection”

• B212 “electronic overload protection, 2nd motor”

Set the rated current [Amperes] of the motor(s) with the above parameters. The setting
range is 0.5 * rated current to 1.2 * rated current.

WARNING: When two or more motors are connected to the inverter, they cannot be
protected by the electronic overload protection. Install an external thermal relay on each
motor.

SJ100 Inverter

Table of Contents

Safety Messages

Hazardous High Voltage i
General Precautions — Read These First! ii
Index to Warnings and Cautions in This Manual iv
General Warnings and Cautions ix
UL® Cautions, Warnings, and Instructions xii

Table of Contents

Revisions xvii
Contact Information xviii

xv

Chapter 1: Getting Started

Introduction 1–2
SJ100 Inverter Specifications 1–5
Introduction to Variable-Frequency Drives 1–18
Frequently Asked Questions 1–23

Chapter 2: Inverter Mounting and Installation

Orientation to Inverter Features 2–2
Basic System Description 2–5
Step-by-Step Basic Installation 2–6
Powerup Test 2–19
Using the Front Panel Keypad 2–21

Chapter 3: Configuring Drive Parameters

Choosing a Programming Device 3–2
Using Keypad Devices 3–3
“D” Group: Monitoring Functions 3–6
“F” Group: Main Profile Parameters 3–8
“A” Group: Standard Functions 3–9
“B” Group: Fine Tuning Functions 3–24
“C” Group: Intelligent Terminal Functions 3–34
“H” Group: Motor Constants Functions 3–43

xvi

Chapter 4: Operations and Monitoring

Introduction 4–2
Connecting to PLCs and Other Devices 4–4
Example Wiring Diagram 4–5
Using Intelligent Input Terminals 4–8
Using Intelligent Output Terminals 4–24
Analog Input Operation 4–32
Analog and Digital Monitor Output 4–33
Auto-tuning for Sensorless Vector Control 4–35
PID Loop Operation 4–39
Configuring the Inverter for Multiple Motors 4–40

Chapter 5: Inverter System Accessories

Introduction 5–2
Component Descriptions 5–3
Dynamic Braking 5–5

Chapter 6: Troubleshooting and Maintenance

Troubleshooting 6–2
Monitoring Trip Events, History, & Conditions 6–5
Restoring Factory Default Settings 6–8
Maintenance and Inspection 6–9
Warranty 6–16

Appendix A: Glossary and Bibliography

Glossary A–2
Bibliography A–8

Appendix B: Drive Parameter Settings Tables

Introduction B–2
Parameter Settings for Keypad Entry B–2

Appendix C: CE–EMC Installation Guidelines

CE–EMC Installation Guidelines C–2
Hitachi EMC Recommendations C–6

Index

Revisions

Revision History Table

SJ100 Inverter

xvii

No. Revision Comments Date of Issue

Initial release of manual NB585X April 1999 NB585X

1 Revision A

Added 7.5 and 10 HP models to tables and drawings in
Chapt. 1 and 2,
Minor corrections throughout manual

2 Revision B

Pages 1-4, 5 – Specs tables: corrected weights (lbs), added
row for input current, corrected dynamic braking % torque
Page 2-11 – Added note about fans at bottom of page
Page 2-15 – Added torque specs for 7.5 and 10 HP models
Page 3-36 – Added larger motor sizes to H_03/H203 motor
capacity settings in table
Page 3-41 – Added note about SLV operation at top of page
Pages 4-30, 31 – Changed text in notes for Steps 1, 2, and
10 in table to clarify auto-tuning procedure
Pages 4-31, 32 – Added auto-tuning notes at bottom of 4-31
and new page 4-32 about motor parameters, frame size, etc.
Page 5-5 – Added braking res. specs for 7.5/10 HP models

3 Revision C

Updated company name on cover, contact page, and
nameplate photo
Updated text, figures, and tables throughout manual per
technical corrections or usability improvements
Pages xii to xiv – Added UL Instructions
Page xviii – Contact page update
Pages 1-5 to 1-8 – Added watt loss, efficiency data to tables
Pages 1-10 to 1-15 – Added derating graphs
Page 2-16 – Added power terminal diagrams
Page 4-5 – Added system wiring diagram
Page 4-7 – Added terminal index listing
Page 4-8 – Added input terminal wiring diagrams
Page 4-24 – Added output terminal wiring diagrams
Pages 5-5 to 5-10 – Added braking tables and figures
Page 6-10 – Added megger test procedure and figure
Page 6-15 – Added IGBT test method, figure, and table
Pages C-1 to C-6 – Added appendix on CE-EMC
Removed DOP+ info from Ch3 and Appendix B

May 1999 NB585XA

August 1999 NB585XB

May 2002 NB585XC

Operation

Manual No.

4 Revision D

Minor corrections throughout

5 Revision E

Minor corrections throughout

5 Revision F

Minor corrections throughout

Nov. 2002 NB585XD

July 2003 NB585XE

Dec. 2003 NB585XF

xviii

Contact Information

Hitachi America, Ltd.
Power and Industrial Division
50 Prospect Avenue
Tarrytown, NY 10591
U.S.A.
Phone: +1-914-631-0600
Fax: +1-914-631-3672

Hitachi Europe GmbH
Am Seestern 18
D-40547 Düsseldorf
Germany
Phone: +49-211-5283-0
Fax: +49-211-5283-649

Hitachi Asia Ltd.
16 Collyer Quay
#20-00 Hitachi Tower, Singapore 049318
Singapore
Phone: +65-538-6511
Fax: +65-538-9011

Hitachi Australia Ltd.
Level 3, 82 Waterloo Road
North Ryde, N.S.W. 2113
Australia
Phone: +61-2-9888-4100
Fax: +61-2-9888-4188

Hitachi Industrial Equipment Systems Co, Ltd.
International Sales Department
WBG MARIVE WEST 16F
6, Nakase 2-chome
Mihama-ku, Chiba-shi,
Chiba 261-7116 Japan
Phone: +81-43-390-3516
Fax: +81-43-390-3810

Hitachi Industrial Equipment Systems Co, Ltd.
Narashino Division
1-1, Higashi-Narashino 7-chome
Narashino-shi, Chiba 275-8611
Japan
Phone: +81-47-474-9921
Fax: +81-47-476-9517

Hitachi Asia (Hong Kong) Ltd.
7th Floor, North Tower
World Finance Centre, Harbour City
Canton Road, Tsimshatsui, Kowloon
Hong Kong
Phone: +852-2735-9218
Fax: +852-2735-6793

NOTE: To receive technical support for the Hitachi inverter you purchased, contact the
Hitachi inverter dealer from whom you purchased the unit, or the sales office or factory
contact listed above. Please be prepared to provide the following inverter nameplate
information:

1. Model

2. Date of purchase

3. Manufacturing number (MFG No.)

4. Symptoms of any inverter problem
If any inverter nameplate information is illegible, please provide your Hitachi contact
with any other legible nameplate items. To reduce unpredictable downtime, we recom­mend that you stock a spare inverter.

Getting Started

1

In This Chapter… page

Introduction …………………………………………….. 2

SJ100 Inverter Specifications…………………….. 5
Introduction to Variable-Frequency Drives …. 18

Frequently Asked Questions ……………………. 23

1–2

Getting Started

Introduction

Introduction

Main Features

Congratulations on your purchase of an SJ100
Series Hitachi inverter! This inverter drive
features state-of-the-art circuitry and components
to provide high performance. The housing
footprint is exceptionally small, given the size of
the corresponding motor. The Hitachi SJ100
product line includes more than a dozen inverter
models to cover motor sizes from 1/4 horsepower
to 10 horsepower, in either 230 VAC or 460 VAC
power input versions. The main features are:

• 200V and 400V Class inverters

• UL or CE version available

• Sensorless vector control

• Regenerative braking circuit

• Convenient keypad for parameter settings

• Built-in RS-422 communications interface to

allow configuration from a PC and for field
bus external modules.

• Sixteen programmable speed levels

• Motor constants are programmable, or may be set via auto-tuning

• PID control adjusts motor speed automatically to maintain a process variable value

The design in Hitachi inverters overcomes many of the traditional trade-offs between
speed, torque and efficiency. The performance characteristics are:

• High starting torque of 200% rating or greater

• Continuous operation at 100% torque within a 1:10 speed range (6/60 Hz / 5/50 Hz)

without motor derating

• Fan has ON/OFF selection to provide longer life for cooling fan (on models with fan)

Model SJ100-004NFU

A full line of accessories from Hitachi is available to
complete your motor application. These include:

• Digital remote operator keypad

• Braking resistors (shown at right)

• Radio noise filters

• CE compliance filters

• DIN rail mounting adapter (35mm rail size)

Operator Interface Options

The optional SRW-0EX digital operator / copy
unit is shown to the right. It has the additional
capability of reading (uploading) the parameter
settings in the inverter into its memory. Then you
can connect the copy unit on another inverter and
write (download) the parameter settings into that
inverter. OEMs will find this unit particularly
useful, as one can use a single copy unit to
transfer parameter settings from one inverter to
many.

SJ100 Inverter

1–3

Getting Started

Braking Resistor

Other digital operator interfaces may be available
from your Hitachi distributor for particular indus­tries or international markets. Contact your
Hitachi distributor for further details.

Digital Operator / Copy Unit

1–4

Getting Started

Introduction

Inverter Specifications Label

The Hitachi SJ100 inverters have product labels located on the right side of the housing,
as pictured below. Be sure to verify that the specifications on the labels match your
power source, motor, and application safety requirements.

Regulatory agency approvals

Specifications label

Inverter model number

Motor capacity for this model

Power Input Rating:
frequency, voltage, phase, current

Output Rating:
Frequency, voltage, current

Manufacturing codes:
Lot number, date, etc.

Model Number Convention

The model number for a specific inverter contains useful information about its operating
characteristics. Refer to the model number legend below:

SJ100 004 H F U

Series name

Restricted distribution:
E=Europe, U=USA

Configuration type
F = with digital operator (keypad)

Input voltage:
N = single or three-phase 200V class
H = three-phase 400V class
L = three phase only, 200V class

Applicable motor capacity in kW

002 = 0.2 kW
004 = 0.4 kW
005 = 0.55 kW
007 = 0.75 kW
011 = 1.1 kW
015 = 1.5 kW

022 = 2.2 kW
030 = 3.0 kW
037 = 3.7 kW
040 = 4.0 kW
055 = 5.5 kW
075 = 7.5 kW

SJ100 Inverter

1–5

SJ100 Inverter Specifications

Model-specific tables for 200V and 400V class inverters

The following tables are specific to SJ100 inverters for the 200V and 400V class model
groups. Note that
groups. Footnotes for all specifications tables follow the table below.

Item 200V Class Specifications

SJ100 inverters,
200V models

Applicable motor size *2 kW 0.2 0.4 0.55 0.75 1.1

Rated capacity
(kVA) *12

Rated input voltage 1-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,

Rated input
current (A)

CE version 002NFE 004NFE 005NFE 007NFE 011NFE

UL version 002NFU 004NFU 007NFU

230V 0.6 1.0 1.1 1.5 1.9

240V 0.6 1.0 1.2 1.6 2.0

1-phase 3.5 5.8 6.7 9.0 11.2

3-phase 2.0 3.4 3.9 5.2 6.5

General Specifications” on page 1–9 apply to both voltage class

HP 1/4 1/2 3/4 1 1.5

3-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,

(037LFU, 055LFU, and 075LFU 3phase only)

Getting Started

Rated output voltage *3 3-phase: 200 to 240V (corresponding to input voltage)

Rated output current (A) 1.6 2.6 3.0 4.0 5.0

Efficiency at 100% rated output (%) 90.5 92.8 93.6 94.1 95.4

Watt loss,
approximate (W)

Starting torque *6 200% or more

Dynamic braking
approx. %
torque, short
time stop *7

DC braking Variable operating frequency, time, and braking force

Weight kg 0.7 0.85 0.85 1.3 1.3

at 70% output 15 21 25 31 38

at 100% output 19 29 32 41 51

without resistor,
from 50 / 60 Hz

with resistor 150%

lb 1.54 1.87 1.87 2.87 2.87

100%: 50Hz

50%: 60Hz

70%: 50Hz
50%: 60Hz

1–6

Getting Started

SJ100 Inverter Specifications

Footnotes for the preceding table and the tables that follow:

Note 1: The protection method conforms to JEM 1030.
Note 2: The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When

using other motors, care must be taken to prevent the rated motor current (50/
60 Hz) from exceeding the rated output current of the inverter.

Note 3: The output voltage decreases as the main supply voltage decreases (except

when using the AVR function). In any case, the output voltage cannot exceed
the input power supply voltage.

Note 4: To operate the motor beyond 50/60 Hz, consult the motor manufacturer for

the maximum allowable rotation speed.

Note 5: When SLV is selected, please set the carrier frequency higher than 2.1 kHz.
Note 6: At the rated voltage when using a Hitachi standard 3-phase, 4-pole motor

(when selecting sensorless vector control—SLV).

Note 7: The braking torque via capacitive feedback is the average deceleration torque

at the shortest deceleration (stopping from 50/60 Hz as indicated). It is not
continuous regenerative braking torque. The average deceleration torque
varies with motor loss. This value decreases when operating beyond 50 Hz. If
a large regenerative torque is required, the optional regenerative braking
resistor should be used.

Note 8: The frequency command is the maximum frequency at 9.8V for input voltage

0 to 10 VDC, or at 19.6 mA for input current 4 to 20 mA. If this characteristic
is not satisfactory for your application, contact your Hitachi sales representa­tive.

Note 9: If operating the inverter at 40 to 50° C, reduce the carrier frequency to 2.1

kHz, derate the output current by 80%, and remove the top housing cover.
Note that removing the top cover will nullify the NEMA rating for the inverter
housing.

Note 10: The storage temperature refers to the short-term temperature during transport.
Note 11: Conforms to the test method specified in JIS C0911 (1984). For the model

types excluded in the standard specifications, contact your Hitachi sales repre­sentative.

Note 12: The input voltage of xxLFU is 230V.

SJ100 Inverter Specifications, continued…

Item 200V Class Specifications, continued

SJ100 Inverter

1–7

Getting Started

SJ100 inverters,
200V models

Applicable motor size *2 kW 1.5 2.2 3.7 5.5 7.5

Rated capacity
(kVA) *12

Rated input voltage 1-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,

Rated input
current (A)

Rated output voltage *3 3-phase: 200 to 240V (corresponding to input voltage)

Rated output current (A) 8.0 11.0 17.5 24 32

Efficiency at 100% rated output (%) 94.7 95.1 95.1 96.1 96.2

Watt loss,
approximate (W)

Starting torque *6 200% or more 180% or more

Dynamic braking
approx. %
torque, short
time stop *7

CE version 015NFE 022NFE

UL version 015NFU 022NFU 037LFU 055LFU 075LFU

HP 2 3 5 7.5 10

230V 3.1 4.3 6.9 9.5 12.7

240V 3.0 4.5 7.2 9.9 13.3

3-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,

(037LFU, 055LFU, 075LFU 3-phase only)

1-phase 17.5 24.0

3-phase 10.0 14.0 22.0 30.0 40.0

at 70% output 57 78 130 152 204

at 100% output 79 107 181 216 288

without resistor,
from 50 / 60 Hz

with resistor 150% 100% 80%

70%: 50Hz
50%: 60Hz

20%: 50Hz
20%: 60Hz

DC braking Variable operating frequency, time, and braking force

Weight kg 2.2 2.8 2.8 5.5 5.7

lb 4.85 6.17 6.17 12.13 12.57

1–8

SJ100 Inverter Specifications

Item 400V Class Specifications

Getting Started

SJ100 inverters,
400V models

Applicable motor size *2 kW 0.4 0.75 1.5 2.2

Rated capacity (460V) kVA 1.1 1.9 2.9 4.2

Rated input voltage 3-phase: 380 to 460V ±10%, 50/60 Hz ±5%

Rated input current (A) 2.0 3.3 5.0 7.0

Rated output voltage *3 3-phase: 380 to 460V (corresponding to input voltage)

Rated output current (A) 1.5 2.5 3.8 5.5

Efficiency at 100% rated output (%) 92.0 93.7 95.7 95.8

Watt loss,
approximate (W)

Starting torque *6 200% or more

Dynamic braking
approx. %
torque, short
time stop *7

DC braking Variable operating frequency, time, and braking force

CE version 004HFE 007HFE 015HFE 022HFE

UL version 004HFU 007HFU 015HFU 022HFU

HP 1/2 1 2 3

at 70% output 25 33 48 68

at 100% output 32 44 65 92

without resistor,
from 50/60 Hz

with resistor 150% 100%

100%: 50Hz

50%: 60Hz

70%: 50Hz
20%: 60Hz

Weight kg 1.3 1.7 1.7 1.8

lb 2.87 3.75 3.75 3.97

SJ100 Inverter

1–9

Item 400V Class Specifications, continued

SJ100 inverters,
400V models

Applicable motor size *2 kW 3.0 4.0 5.5 7.5

Rated capacity (460V) kVA 6.2 6.6 10.3 12.7

Rated input voltage 3-phase: 380 to 460V ±10%, 50/60 Hz ±5%

Rated input current (A) 10.0 11.0 16.5 20.0

Rated output voltage *3 3-phase: 380 to 460V (corresponding to input voltage)

Rated output current (A) 7.8 8.6 13 16

Efficiency at 100% rated output (%) 95.4 96.2 96.0 96.5

Watt loss,
approximate (W)

Starting torque *6 180% or more

Dynamic braking
approx. %
torque, short time
stop *7

CE version 030HFE 040HFE 055HFE 075HFE

UL version 040HFU 055HFU 075HFU

HP 4 5 7.5 10

at 70% output 100 108 156 186

at 100% output 138 151 219 261

without resistor,
from 50/60 Hz

with resistor 100% 80%

20%: 50Hz
20%: 60Hz

Getting Started

DC braking Variable operating frequency, time, and braking force

Weight kg 2.8 2.8 5.5 5.7

lb 6.17 6.17 12.13 12.57

General Specifications

The following table applies to all SJ100 inverters.

Item General Specifications

Protective housing *1 IP20

Control method Sine wave pulse-width modulation (PWM) control

Output frequency range *4 0.5 to 360 Hz

Frequency accuracy Digital command: 0.01% of the maximum frequency

Analog command: 0.1% of the maximum frequency (25°C ± 10°C)

Frequency setting resolution Digital: 0.1 Hz; Analog: max. frequency/1000

Volt./Freq. characteristic *5 V/f optionally variable, V/f control (constant torque, reduced

torque), sensorless vector control

Overload current rating 150%, 60 seconds

Acceleration/deceleration time 0.1 to 3000 sec., (linear accel/decel), second accel/decel setting

available

1–10

SJ100 Inverter Specifications

Item General Specifications

Getting Started

Input
signal

Output
signal

Alarm output contact ON for inverter alarm (1C contacts, both normally open or closed

Other functions AVR function, curved accel/decel profile, upper and lower limiters,

Freq.
setting

FWD/
REV
Run

Intelligent input
terminal

Intelligent output
terminal

Frequency monitor PWM output; Select analog output frequency monitor, analog output

Operator panel Up and Down keys / Value settings

Potentiometer Analog setting

External signal *80 to 10 VDC (input impedance 10k Ohms), 4 to 20 mA (input

impedance 250 Ohms), Potentiometer (1k to 2k Ohms, 2W)

Operator panel Run/Stop (Forward/Reverse run change by command)

External signal Forward run/stop, Reverse run/stop

FW (forward run command), RV (reverse run command), CF1~CF4
(multi-stage speed setting), JG (jog command), 2CH (2-stage accel./
decel. command), FRS (free run stop command), EXT (external
trip), USP (startup function), SFT (soft lock), AT (analog current
input select signal), RS (reset), PTC (thermal protection), DB (exter­nal DC braking command), SET (2nd setting selection), UP (remote
control, accel.), DWN (remote control, decel.)

RUN (run status signal), FA1,2 (frequency arrival signal), OL
(overload advance notice signal), OD (PID error deviation signal),
AL (alarm signal)

current monitor or digital output frequency monitor

avail.)

16-stage speed profile, fine adjustment of start frequency, carrier
frequency change (0.5 to 16 kHz) frequency jump, gain and bias
setting, process jogging, electronic thermal level adjustment, retry
function, trip history monitor, 2nd setting selection, auto tuning, fan
ON/OFF selection

Protective function Over-current, over-voltage, under-voltage, overload, extreme high/

low temperature, CPU error, memory error, ground fault detection at
startup, internal communication error, electronic thermal, CT error

Operat­ing
Environ
ment

Coating color Munsell 8.5YR6.2/0/2, cooling fins in base color of aluminum

Options Remote operator unit, copy unit, cables for the units, braking unit,

Temperature Operating (ambient): -10 to 50°C (*9) / Storage: -25 to 70°C (*10)

Humidity 20 to 90% humidity (non-condensing)

Vibration *11

Location Altitude 1,000 m or less, indoors (no corrosive gasses or dust)

2

5.9 m/s

braking resistor, AC reactor, DC reactor, noise filter, DIN rail
mounting

(0.6G), 10 to 55 Hz

SJ100 Inverter

1–11

Signal Ratings

Detailed ratings are in “Specifications of Control and Logic Connections” on page 4–6.

Signal / Contact Ratings

Built-in power for inputs 24VDC, 30 mA maximum

Discrete logic inputs 27VDC maximum

Discrete logic outputs 50mA maximum ON state current, 27 VDC maximum OFF state voltage

PWM (analog/digital) output 0 to 10VDC, 1 mA, PWM and 50% duty digital

Analog input, current 4 to 19.6 mA range, 20 mA nominal

Analog input, voltage 0 to 9.6 VDC range, 10VDC nominal, input impedance 10 k

+10V analog reference 10VDC nominal, 10 mA maximum

Alarm relay contacts 250 VAC, 2.5A (R load) max., 0.2A (I load, P.F.=0.4) max.

100 VAC, 10mA min.
30 VDC, 3.0A (R load) max., 0.7A (I load, P.F.=0.4) max.
5 VDC, 100mA min.

Getting Started

1–12

Derating Curves

Getting Started

SJ100 Inverter Specifications

The maximum available inverter current output is limited by the carrier frequency and
ambient temperature. The carrier frequency is the inverter’s internal power switching
frequency, settable from 0.5 kHz to 16 kHz. Choosing a higher carrier frequency tends to
decrease audible noise, but it also increases the internal heating of the inverter, thus
decreasing (derating) the maximum current output capability. Ambient temperature is
the temperature just outside the inverter housing—such as inside the control cabinet
where the inverter is mounted. A higher ambient temperature decreases (derates) the
inverter’s maximum current output capacity.

Use the following derating curves to help determine the optimal carrier frequency setting
for your inverter, and to find the output current derating. Be sure to use the proper curve
for your particular SJ100 inverter model number.

Legend:

SJ100–002NFE/NFU

100%

Standard ratings at 40°C

Ratings at 50°C max. with top cover removed

Ratings at 55°C max. with top cover removed

% of rated

output current

SJ100–004NFE/NFU

100%

% of rated

output current

95%

90%

85%

80%

75%

70%

0.5246810121416

Carrier frequency

95%

90%

85%

kHz

80%

75%

70%

0.5246810121416

Carrier frequency

kHz

Derating curves, continued…

SJ100–007NFE/NFU

100%

95%

90%

SJ100 Inverter

1–13

Getting Started

% of rated

output current

SJ100–0015NFE/NFU

% of rated

output current

85%

80%

75%

70%

100%

95%

90%

85%

80%

75%

kHz

0.5246810121416

Carrier frequency

SJ100–022NFE/NFU

100%

% of rated

output current

70%

0.5246810121416

Carrier frequency

95%

90%

85%

80%

75%

70%

0.5246810121416

Carrier frequency

kHz

kHz

1–14

SJ100 Inverter Specifications

Derating curves, continued…

SJ100–037LF/LFU

100%

90%

80%

Getting Started

% of rated

output current

SJ100–055LFU

% of rated

output current

70%

60%

50%

40%

0.5246810121416

Carrier frequency

100%

95%

90%

85%

80%

75%

kHz

SJ100–075LFU

% of rated

output current

70%

0.5246810121416

Carrier frequency

100%

95%

90%

85%

80%

75%

70%

0.5246810121416

Carrier frequency

kHz

kHz

Derating curves, continued…

SJ100–004HFE/HFU

100%

90%

80%

SJ100 Inverter

1–15

Getting Started

% of rated

output current

SJ100–007HFE/HFU

100%

% of rated

output current

70%

60%

50%

40%

0.5246810121416

Carrier frequency

90%

80%

70%

60%

50%

kHz

SJ100–015HFE/HFU

100%

% of rated

output current

40%

0.5246810121416

Carrier frequency

90%

80%

70%

60%

50%

40%

0.5246810121416

Carrier frequency

kHz

kHz

1–16

SJ100 Inverter Specifications

Derating curves, continued…

SJ100–022HFE/HFU

100%

90%

80%

Getting Started

% of rated

output current

SJ100–040HFE/HFU

100%

% of rated

output current

70%

60%

50%

40%

0.5246810121416

Carrier frequency

90%

80%

70%

60%

50%

kHz

SJ100–055HFE/HFU

100%

% of rated

output current

40%

0.5246810121416

Carrier frequency

95%

90%

85%

80%

75%

70%

0.5246810121416

Carrier frequency

kHz

kHz

Derating curves, continued…

SJ100–075HFE/HFU

100%

95%

90%

SJ100 Inverter

1–17

Getting Started

% of rated

output current

85%

80%

75%

70%

0.5246810121416

Carrier frequency

kHz

1–18

Introduction to Variable-Frequency Drives

The Purpose of Motor Speed Control for Industry

Getting Started

What is an Inverter?

Introduction to Variable-Frequency Drives

Hitachi inverters provide speed control for 3-phase AC induction motors. You connect
AC power to the inverter, and connect the inverter to the motor. Many applications
benefit from a motor with variable speed, in several ways:

• Energy savings — HVAC

• Need to coordinate speed with an adjacent process—textiles and printing presses

• Need to control acceleration and deceleration (torque)

• Sensitive loads — elevators, food processing, pharmaceuticals

The term inverter and variable-frequency drive are related and somewhat interchange-
able. An electronic motor drive for an AC motor can control the motor’s speed by
varying the frequency of the power sent to the motor.

An inverter, in general, is a device that converts DC power to AC power. The figure
below shows how the variable-frequency drive employs an internal inverter. The drive
first converts incoming AC power to DC through a rectifier bridge, creating an internal
DC bus voltage. Then the inverter circuit converts the DC back to AC again to power the
motor. The special inverter can vary its output frequency and voltage according to the
desired motor speed.

Power

Input

L1

L2

L3

The simplified drawing of the inverter shows three double-throw switches. In Hitachi
inverters, the switches are actually IGBTs (isolated gate bipolar transistors). Using a
commutation algorithm, the microprocessor in the drive switches the IGBTs on and off
at a very high speed to create the desired output waveforms. The inductance of the motor
windings helps smooth out the pulses.

Converter

Rectifier

Variable-frequency Drive

Internal
DC Bus

+

Inverter

+

Motor

U/T1

V/T2

W/T3

Torque and Constant Volts/Hertz Operation

In the past, AC variable speed drives used an
open loop (scalar) technique to control speed.
The constant-volts-per-hertz operation
maintains a constant ratio between the applied
voltage and the applied frequency. With these
conditions, AC induction motors inherently
delivered constant torque across the operating
speed range. For some applications, this scalar
technique was adequate.

Today, with the advent of sophisticated micro­processors and digital signal processors (DSPs),
it is possible to control the speed and torque of AC induction motors with unprecedented
accuracy. The SJ100 utilizes these devices to perform complex mathematical calcula­tions required to achieve superior performance. The technique is referred to as sensorless
vector control. It allows the drive to continuously monitor its output voltage and current,
and their relationship to each other. From this it mathematically calculates two vector
currents. One vector is related to motor flux current, and the other to motor torque
current. The ability to separately control these two vectors is what allows the SJ100 to
deliver extraordinary low-speed performance and speed control accuracy.

Output

voltage

SJ100 Inverter

V

Constant torque

0

Output frequency

1–19

Getting Started

f

100%

Inverter Input and Three-Phase Power

The Hitachi SJ100 Series of inverters includes two sub-groups: the 200V class and the
400V class inverters. The drives described in this manual may be used in either the
United States or Europe, although the exact voltage level for commercial power may be
slightly different from country to country. Accordingly, a 200V class inverter requires
(nominal) 200 to 240VAC, and a 400V class inverter requires from 380 to 460VAC.
Some 200V class inverters will accept single-phase or three-phase power, but all 400V
class inverters require a three-phase power supply.

TIP: If your application only has single phase power available, refer to SJ100 inverters
of 3HP or less; they can accept single phase input power.

The common terminology for single phase power is Line (L) and Neutral (N). Three­phase power connections are usually labeled Line 1 (L1), Line 2 (L2) and Line 3 (L3). In
any case, the power source should include an earth ground connection. That ground
connection will need to connect to the inverter chassis and to the motor frame (see

the Inverter Output to Motor” on page 2–18).

Wire

1–20

Introduction to Variable-Frequency Drives

Inverter Output to the Motor

Getting Started

The AC motor must be connected only to the inverter’s
output terminals. The output terminals are uniquely
labeled (to differentiate them from the input terminals)
with the designations U/T1, V/T2, and W/T3. This
corresponds to typical motor lead connection designa­tions T1, T2, and T3. It is often not necessary to connect
a particular inverter output to a particular motor lead for
a new application. The consequence of swapping any
two of the three connections is the reversal of the motor
direction. In applications where reversed rotation could
cause equipment damage or personnel injury, be sure to verify direction of rotation
before attempting full-speed operation. For safety to personnel, you must connect the
motor chassis ground to the ground connection at the bottom of the inverter housing.

Notice the three connections to the motor do not include one marked “Neutral” or
“Return.” The motor represents a balanced “Y” impedance to the inverter, so there is no
need for a separate return. In other words, each of the three “Hot” connections serves
also as a return for the other connections, because of their phase relationship.

The Hitachi inverter is a rugged and reliable device. The intention is for the inverter to
assume the role of controlling power to the motor during all normal operations. There­fore, this manual instructs you not to switch off power to the inverter while the motor is
running (unless it is an emergency stop). Also, do not install or use disconnect switches
in the wiring from the inverter to the motor (except thermal disconnect). Of course,
safety-related devices such as fuses must be in the design to break power during a
malfunction, as required by NEC and local codes.

3-Phase AC Motor

U/T1

W/T3

V/T2

Earth

GND

Intelligent Functions and Parameters

Much of this manual is devoted to describing
how to use inverter functions and how to config­ure inverter parameters. The inverter is micro­processor-controlled, and has many independent
functions. The microprocessor has an on-board
EEPROM for parameter storage. The inverter’s
front panel keypad provides access to all
functions and parameters, which you can access
through other devices as well. The general name
for all these devices is the digital operator, or
digital operator panel. Chapter 2 will show you
how to get a motor running, using a minimal set
of function commands or configuring parame­ters.

The optional read/write programmer will let you
read and write inverter EEPROM contents from
the programmer. This feature is particularly
useful for OEMs who need to duplicate a particu­lar inverter’s settings in many other inverters in
assembly-line fashion.

SJ100 Inverter

1–21

Getting Started

Braking

In general, braking is a force that attempts to slow or stop motor rotation. So it is associ­ated with motor deceleration, but may also occur even when the load attempts to drive
the motor faster than the desired speed (overhauling). If you need the motor and load to
decelerate quicker than their natural deceleration during coasting, we recommend
installing a braking resistor. The dynamic braking unit (built into the SJ100) sends
excess motor energy into a resistor to slow the motor and load (see

page 5–2 and “Dynamic Braking” on page 5–5 for more information). For loads that

continuously overhaul the motor for extended periods of time, the SJ100 may not be
suitable (contact your Hitachi distributor).

The inverter parameters include acceleration and deceleration, which you can set to
match the needs of the application. For a particular inverter, motor, and load, there will
be a range of practically achievable accelerations and decelerations.

Introduction” on

1–22

Velocity Profiles

Getting Started

Introduction to Variable-Frequency Drives

The SJ100 inverter is capable of sophisticated
speed control. A graphical representation of

Speed

Set speed

that capability will help you understand and
configure the associated parameters. This
manual makes use of the velocity profile
graph used in industry (shown at right). In the
example, acceleration is a ramp to a set speed,

0

Accel Decel

t

Velocity Profile

and deceleration is a decline to a stop.

Acceleration and deceleration settings specify
the time required to go from a stop to

Speed

Maximum speed

maximum frequency (or visa versa). The
resulting slope (speed change divided by time)
is the acceleration or deceleration. An increase
in output frequency uses the acceleration
slope, while a decrease uses the deceleration
slope. The accel or decel time a particular
speed change depends on the starting and

0

Acceleration

(time setting)

t

ending frequencies. However, the slope is constant, corresponding to the full-scale accel
or decel time setting. For example, the full-scale acceleration setting (time) may be 10
seconds—the time required to go from 0 to 60 Hz.

The SJ100 inverter can store up to 16 preset
speeds. And, it can apply separate acceleration
and deceleration transitions from any preset to
any other preset speed. A multi-speed profile
(shown at right) uses two or more preset
speeds, which you can select via intelligent
input terminals. This external control can

Speed

Speed 2

Speed 1

0

t

Multi-speed Profile

apply any preset speed at any time. Alterna­tively, the selected speed is infinitely variable across the speed range. You can use the
potentiometer control on the keypad for manual control. The drive accepts analog 0-10V
signals and 4-20 mA control signals as well.

The inverter can drive the motor in either
direction. Separate FW and RV commands

Speed

Forward move

select the direction of rotation. The motion
profile example shows a forward motion
followed by a reverse motion of shorter
duration. The speed presets and analog signals

0

t

Reverse move

control the magnitude of the speed, while the
FWD and REV commands determine the

Bi-directional Profile

direction before the motion starts.

NOTE: The SJ100 can move loads in both directions. However, it is not designed for use
in servo-type applications that use a bipolar velocity signal that determines direction.

SJ100 Inverter

1–23

Frequently Asked Questions

Q. What is the main advantage in using an inverter to drive a motor, compared to

alternative solutions?

A. An inverter can vary the motor speed with very little loss of efficiency, unlike

mechanical or hydraulic speed control solutions. The resulting energy
savings usually pays for the inverter in a relatively short time.

Q. The term “inverter” is a little confusing, since we also use “drive” and “amplifier”

to describe the electronic unit that controls a motor. What does “inverter” mean?

A. The terms inverter, drive, and amplifier are used somewhat interchangeably

in industry. Nowadays, the terms drive, variable-frequency drive, variable-
speed drive, and inverter are generally used to describe electronic, micropro­cessor-based motor speed controllers. In the past, variable-speed drive also
referred to various mechanical means to vary speed. Amplifier is a term
almost exclusively used to describe drives for servo or stepper motors.

Q. Although the SJ100 inverter is a variable speed drive, can I use it in a fixed-speed

application?

A. Yes, sometimes an inverter can be used simply as a “soft-start” device,

providing controlled acceleration and deceleration to a fixed speed. Other
functions of the SJ100 may be useful in such applications, as well. However,
using a variable speed drive can benefit many types of industrial and
commercial motor applications, by providing controlled acceleration and
deceleration, high torque at low speeds, and energy savings over alternative
solutions.

Getting Started

Q. Can I use an inverter and AC induction motor in a positioning application?

A. That depends on the required precision, and the slowest speed the motor will

must turn and still deliver torque. The SJ100 inverter will deliver full torque
while turning the motor at only 0.5 Hz (15 RPM). DO NOT use an inverter if
you need the motor to stop and hold the load position without the aid of a
mechanical brake (use a servo or stepper motion control system).

Q. Does the optional digital operator interface or the PC software (DOP Professional)

provide features beyond what is available from the keypad on the unit?

A. Yes. However, note first that the same set of parameters and functions are

equally accessible from either the unit’s keypad or from remote devices. The
DOP Professional PC software lets you save or load inverter configurations
to or from a disk file. And, the hand-held digital operator provides hard­wired terminals, a safety requirement for some installations.

1–24

Getting Started

Frequently Asked Questions

Q. Why does the manual or other documentation use terminology such as “200V

class” instead of naming the actual voltage, such as “230 VAC?”

A. A specific inverter model is set at the factory to work across a voltage range

particular to the destination country for that model. The model specifications
are on the label on the side of the inverter. A European 200V class inverter
(“EU” marking) has different parameter settings than a USA 200V class
inverter (“US” marking). The initialization procedure (see

Factory Default Settings” on page 6–8) can set up the inverter for European

or US commercial voltage ranges.

Q. Why doesn’t the motor have a neutral connection as a return to the inverter?

A. The motor theoretically represents a “balanced Y” load if all three stator

windings have the same impedance. The Y connection allows each of the
three wires to alternately serve as input or return on alternate half-cycles.

Q. Does the motor need a chassis ground connection?

A. Yes, for several reasons. Most importantly, this provides protection in the

event of a short in the motor that puts a hazardous voltage on its housing.
Secondly, motors exhibit leakage currents that increase with aging. Lastly, a
grounded chassis generally emits less electrical noise than an ungrounded
one.

Restoring

Q. What type of motor is compatible with the Hitachi inverters?

A. Motor type – It must be a three-phase AC induction motor. Use an inverter-

grade motor that has 800V insulation for 200V class inverters, or 1600V
insulation for 400V class.
Motor size – In practice, it’s better to find the right size motor for your
application; then look for the inverter to match the motor.

NOTE: There may be other factors that will affect motor selection, including heat dissi­pation, motor operating speed profile, enclosure type, and cooling method.

Q. How many poles should the motor have?

A. Hitachi inverters can be configured to operate motors with 2, 4, 6, or 8 poles.

The greater the number of poles, the slower the top motor speed will be, but
it will have higher torque at the base speed.

Q. Will I be able to add dynamic (resistive) braking to my Hitachi SJ100 drive after

the initial installation?

A. Yes. The SJ100 inverter already has a dynamic braking circuit built in. Just

add the resistor sized to meet the braking requirements. More information on
dynamic braking is located in Chapter 5.

SJ100 Inverter

1–25

Q. How will I know if my application will require resistive braking?

A. For new applications, it may be difficult to tell before you actually test a

motor/drive solution. In general, some applications can rely on system losses
such as friction to serve as the decelerating force, or otherwise can tolerate a
long decel time. These applications will not need dynamic braking.
However, applications with a combination of a high-inertia load and a
required short decel time will need dynamic braking. This is a physics
question that may be answered either empirically or through extensive calcu­lations.

Q. Several options related to electrical noise suppression are available for the Hitachi

inverters. How can I know if my application will require any of these options?

A. The purpose of these noise filters is to reduce the inverter electrical noise so

the operation of nearby electrical devices is not affected. Some applications
are governed by particular regulatory agencies, and noise suppression is
mandatory. In those cases, the inverter must have the corresponding noise
filter installed. Other applications may not need noise suppression, unless
you notice electrical interference with the operation of other devices.

Getting Started

Q. The SJ100 features a PID loop feature. PID loops are usually associated with

chemical processes, heating, or process industries in general. How could the PID
loop feature be useful in my application?

A. You will need to determine the particular main variable in your application

the motor affects. That is the process variable (PV) for the motor. Over time,
a faster motor speed will cause a faster change in the PV than a slow motor
speed will. By using the PID loop feature, the inverter commands the motor
to run at the optimal speed required to maintain the PV at the desired value
for current conditions. Using the PID loop feature will require an additional
sensor and other wiring, and is considered an advanced application.

Inverter Mounting

2

and Installation

In This Chapter…. page

Orientation to Inverter Features …………………. 2

Basic System Description …………………………. 5

Step-by-Step Basic Installation…………………… 6

Powerup Test ………………………………………… 19

Using the Front Panel Keypad …………………. 21

2–2

Orientation to Inverter Features

Orientation to Inverter Features

Unpacking and Inspection

Please take a few moments to unpack your new SJ100 inverter and perform these steps:

1. Look for any damage that may have occurred during shipping.

2. Verify the contents of the box include:

a. One SJ100 inverter

b. One Instruction Manual with self-adhesive label for the inverter

c. One SJ100 Quick Reference Guide

d. One packet of desiccant—discard (not for human consumption)

3. Inspect the specifications label on the side of the inverter. Make sure it matches the

product part number you ordered.

Main Physical Features

and Installation

Inverter Mounting

The SJ100 Series inverters vary in size according to the current output rating and motor
size for each model number. All feature the same basic keypad and connector interface
for consistent ease of use. The inverter construction has a heat sink at the back of the
housing. The larger models include a fan(s) to enhance heat sink performance. The
mounting holes are pre-drilled in the heat sink for your convenience. Never touch the
heat sink during or just after operation; it can be very hot.

The electronics housing and front panel are built onto the front of the heat sink. The
front panel has three levels of physical access designed for convenience and safety:

First-level access – for basic use of inverter and editing parameters (power ON)

Second-level access – for editing parameters and wiring control signals (power ON)

Third-level access – for wiring the inverter power supply or motor (power OFF)

1. First-level Access — View the unit just as it

came from the box as shown. The four-digit
display can show a variety of performance
parameters. LEDs indicate whether the
display units are Hertz or Amperes. Other
LEDs indicate Power (external), and Run/
Stop Mode and Program/Monitor Mode
status. Membrane keys Run and Stop/Reset,
and a Min/Max frequency control knob
control motor operation. These controls and
indicators are usually the only ones needed
after the inverter installation is complete.
You can also access the modular jack for
connecting a programming or monitoring
device such as a PC (see Chapter 3). And,
you can access the two chassis GND screws
on the metal tab at the bottom of the inverter.

SJ100 Inverter

2. Second-level access — Locate the lift tab at the right lower corner of the front panel

near the safety warning message. Lift the corner to swing the half-door around to the
left. This exposes four more control buttons and some connectors.
The FUNC., , , and STR keys allow an operator to access and change the
inverter’s functions and parameter values. The two 8-position connectors provide the
interface for logic-level control signals. These signals are generally low-voltage in
nature and are appropriate for second-level access.

2

1

Controls for mode

and parameter

changes

2–3

Inverter Mounting

and Installation

Lift tab for

opening door

Locate the label sheet that came with the manual. This is a good moment to apply the
self-sticking labels as shown below. Adhere the larger label for monitor codes and
basic functions to the rear of the half-door panel. Then adhere the remaining trip code
label to the area beside the connectors. Be careful not to cover the screw access on
models like the one shown.

Control signal

connectors

2–4

and Installation

Inverter Mounting

Orientation to Inverter Features

3. Third-level access — First, ensure no power

source of any kind is connected to the
inverter. If power has been connected, wait
five minutes after powerdown and verify
the Power LED is OFF to proceed. Then
locate the recessed retention screw on the
left side main front panel (it is along the
left hinge area on some models, or behind
the first access door on others). Use a small
screwdriver (Regular or Phillips) to loosen
the screw. Swing the door around to the
right to reveal the internal components of
the drive. The two-level tiered 12-position
terminal block accepts wires for the power
input and wires to the motor.

Notice the housing partition that lifts out to
allow full access to the terminals for wiring as
shown. Never operate the inverter drive with
the partition removed or the full access door
opened.
The alarm circuit connections are accessible
on the 3-position connector near the modular
connector on the rear of the main panel door.
The nearby relay provides both normally­open and normally-closed logic for interface
to an external alarm. The alarm circuit may
carry hazardous live voltages even when the
main power to the inverter is OFF. So, never
directly touch any terminal or circuit compo­nent. A notch in the removable partition
serves as the exit path for alarm circuit wiring.

Retention screw

Alarm

connector

Housing partition

The following sections will describe the
system design and guide you through a
step-by-step installation process. After the
section on wiring, this chapter will show
how to use the front panel keys to access
functions and edit parameters.

Power and motor

connector terminals

Basic System Description

A motor control system will obviously include a motor and inverter, as well as a breaker
or fuses for safety. If you are connecting a motor to the inverter on a test bench just to get
started, that’s all you may need for now. But a system can also have a variety of
additional components. Some can be for noise suppression, while others may enhance
the inverter’s braking performance. The figure and table below show a system with all
the optional components you may need in your finished application.

From power supply

SJ100 Inverter

2–5

L1 L2 L3

+1

+

Inverter

RB

GND

T1 T2 T3

Motor

Thermal

switch

Breaker,

MCCB or

GFI

Name Function

Breaker / discon­nect

Input-side
AC Reactor

Radio noise filter Electrical noise interference may occur on nearby

EMI filter (for
CE applications,
see Appendix D)

Radio noise filter
(use in non-CE
applications)

DC link choke Suppresses harmonics generated by the inverter.

Braking resistor This is useful for increasing the inverter’s control

Radio noise filter Electrical noise interference may occur on nearby

Output-side
AC reactor

LCR filter Sine wave shaping filter for output side.

A molded-case circuit breaker (MCCB), ground fault
interrupter (GFI), or a fused disconnect device. NOTE:
The installer must refer to the NEC and local codes to
ensure safety and compliance.

This is useful in suppressing harmonics induced on the
power supply lines and for improving the power factor.
WARNING: Some applications must use an input-
side AC reactor to prevent inverter damage. See
Warning on next page.

equipment such as a radio receiver. This magnetic
choke filter helps reduce radiated noise (can also be
used on output).

Reduces the conducted noise on the power supply
wiring between the inverter and the power distribution
system. Connect to the inverter primary (input side).

This capacitive filter reduces radiated noise from the
main power wires in the inverter input side.

However, it will not protect the input diode bridge
rectifier.

torque for high duty-cycle (ON-OFF) applications, and
improving the decelerating capability.

equipment such as a radio receiver. This magnetic
choke filter helps reduce radiated noise (can also be
used on input).

This reactor reduces the vibrations in the motor caused
by the inverter’s switching waveforms, by smoothing
the waveform to approximate commercial power
quality. It is also useful to reduce harmonics when
wiring from the inverter to the motor is more than 10m
in length.

Inverter Mounting

and Installation

NOTE: Note that some components are required for regulatory agency compliance (see
Chapter 5 and Appendix C).

2–6

Step-by-Step Basic Installation

and Installation

Inverter Mounting

Step-by-Step Basic Installation

WARNING: In the cases below involving a general-purpose inverter, a large peak
current can flow on the power supply side, sometimes destroying the converter module:

1.The unbalance factor of the power supply is 3% or higher.

2.The power supply capacity is at least 10 times greater than the inverter capacity
(or the power supply capacity is 500 kVA or more).

3.Abrupt power supply changes are expected, due to conditions such as:
a. Several inverters are interconnected with a short bus.
b. A thyristor converter and an inverter are interconnected with a short bus.
c. An installed phase advance capacitor opens and closes.

Where these conditions exist or when the connected equipment must be highly reliable,
you MUST install an input-side AC reactor of 3% (at a voltage drop at rated current)
with respect to the supply voltage on the power supply side. Also, where the effects of an
indirect lightning strike are possible, install a lightning conductor.

This section will guide you through the following basic steps of installation:

1. Study the warnings and instructions associated with mounting the inverter.

2. Select a suitable mounting location.

NOTE: If the installation is in an EU country, study the EMC installation guidelines in

Appendix C.

3. Place covers over the inverter’s ventilation openings to prevent debris from entering.

4. Check the inverter mounting dimensions for footprint and mounting hole locations.

5. Study the caution and warning messages associated with wiring the inverter.

6. Connect wiring for the inverter power input.

7. Connect wiring to the motor.

8. Remove any covers applied in Step 3 from the inverter’s ventilation openings.

CAUTION: The inverter is shipped with a plastic cover over the top vent grill.

REMOVE this cover after the installation is complete. Operation with this cover in place
will not allow proper cooling, and damage to the inverter may result.

9. Perform a powerup test.

10. Make observations and check your installation.

Loading…

File Specifications:

429/429569-sj100.pdf file (01 Mar 2023)

Accompanying Data:

Hitachi SJ100 Series Inverter PDF Instruction Manual (Updated: Wednesday 1st of March 2023 06:46:09 PM)

Rating: 4.1 (rated by 99 users)

Compatible devices: L300P Series, SJ Series, HFC-VAH2 series, P1-00044-L, NT2021XA, L300P-110L, E10U, SJ100DN DeviceNet Series Addendum.

Recommended Documentation:

Instruction Manual (Text Version):

(Ocr-Read Summary of Contents of some pages of the Hitachi SJ100 Series Document (Main Content), UPD: 01 March 2023)

  • Hitachi SJ100 Series User Manual

  • Hitachi SJ100 Series User Guide

  • Hitachi SJ100 Series PDF Manual

  • Hitachi SJ100 Series Owner’s Manuals

Recommended: HTS17BCSLWW — 16.6 cu. Ft. Top Freezer Refrigerator, FD8156, SD-P2600, T 8428 C, PDG-DHT100H

Links & Tools

  • www.championpowerequipment.com© Champion Power Equipment 2021.All Rights Reserved. / Todos los derechos reservados. WARNING:Read the ENTIRE operator’s manual to become familiar with thefeatures of the product before operating.Failure to operate the product correctly can result in damage tothe product, per …

    200977 4

  • 1 / 16 PI500A Series basic frequency inverter user manual 1. Foreword Thank you for choosing POWTRAN PI500A serices basic frequency inverter . The diagram of operating manual ,Maybe slightly different from the product for convenience of explanation, Due to product upgrades, they may be slightly dif …

    PI500A Series 16

  • DE M174 | Solar-Laderegler Dual 16 AWird zwischen Solarpanel 12 V und 1 oder 2 Akkus geschaltet, um ein Überladen der Akkus zu ver-hindern. Sind 2 Akkus angeschlossen, werden diese getrennt voneinander geladen. Es bekommt immer der Akku mehr Ladestrom, der die niedrigste Ladespannung hat. Mit LED-Anzeig …

    M174 4

  • AXI.International AXInternational AXIFuel AXIFuel1.239.690.95891.877.425.4239 Toll Free www.AXI-International.comREV03121080011217SFM 1080 INSTRUCTION, OPERATING,AND MAINTENANCE MANUALSolar Powered Fuel Maintenance System …

    SFM 1080 21

Operating Impressions, Questions and Answers:

Table of Contents

Part 1 / 2                                                                                  3
Description of  SJ100 Display …………………………………………  3
Operation procedure (example for the digital operator)…………  3
Setting extended functions (example for group A extended
functions) ……………………………………………………………………  4
Protective Functions………………………………………………………  5
SJ100 data setting values  ……………………………………………….  5
Drive keypad display sequence  ……………………………………….  5

Part  2 / 2                                                                                 9
CE-EMC Installation, Guidelines……………………………………..  9
WIRING EXAMPLES: ………………………………………………….. 11

Set value 4..20mA and thermistor …………………………………. 11
Fixed set values; FA1 output and RUN output  ………………… 11
Flow control  …………………………………………………………….. 11

External dimensions and terminal positions  ………………………. 12
TECHNICAL SPECIFICATIONS: ………………………………….. 13

SJ100, 200V series  ……………………………………………………. 13
SJ100, 400V series  ……………………………………………………. 14

© 1999 Hitachi Europe Ltd.

Am Seestern 18

D-40547 Düsseldorf

Phone: +49 (0) 2 11 – 52 83 –0

Fax: +49 (0) 2 11 – 52 83 –649

e-Mail: info-dus.inv@hitachi-eu.com

Internet: www.hitachi-ds.com

Понравилась статья? Поделить с друзьями:
  • Артроцин таблетки инструкция по применению для суставов цена
  • Инструкция по уходу за велосипедом по пунктам
  • Руководство дистрибьюторами дистрибьюторов
  • Ингавирин инструкция по применению таблетки детям инструкция по применению
  • Докапласт с серебром инструкция по пользованию