Contents
-
Table of Contents
-
Bookmarks
Quick Links
Contents
Introduction to HV
Intr
Intr
oduction to HV
oduction to HVAC
oduction to HV
Intr
Intr
oduction to HV
Software version …………………………………………………………………………………………………… 3
Safety regulations …………………………………………………………………………………………………. 4
Available literature …………………………………………………………………………………………………. 7
fans and pumps? ………………………………………………………………………………………………….. 8
Control principle …………………………………………………………………………………………………. 12
CE-labelling ……………………………………………………………………………………………………….. 16
Application examples …………………………………………………………………………………………… 17
Specification text ………………………………………………………………………………………………… 24
Ordering guide ……………………………………………………………………………………………………. 30
Choice of frequency converter ……………………………………………………………………………….. 30
Ordering form VLT 6000 HVAC ……………………………………………………………………………… 35
Installation
Installation
Installation
Installation
Installation
General technical data …………………………………………………………………………………………. 42
Mains supply 3 x 200 — 240 V ……………………………………………………………………………….. 45
Mechanical dimensions ………………………………………………………………………………………… 48
Mechanical installation …………………………………………………………………………………………. 50
Enclosure protection ……………………………………………………………………………………………. 50
Field-mounting …………………………………………………………………………………………………… 50
High voltage warning …………………………………………………………………………………………… 52
Earthing …………………………………………………………………………………………………………….. 52
Cables ………………………………………………………………………………………………………………. 52
Screened/armoured cables …………………………………………………………………………………… 52
Extra protection ………………………………………………………………………………………………….. 52
RFI switch …………………………………………………………………………………………………………. 53
High voltage test …………………………………………………………………………………………………. 53
Use of EMC-correct cables …………………………………………………………………………………… 55
VLT 6000 HVAC enclosures ………………………………………………………………………………….. 57
Mains connection ……………………………………………………………………………………………….. 62
Pre-fuses …………………………………………………………………………………………………………… 62
Motor connection ……………………………………………………………………………………………….. 62
DC bus connection ……………………………………………………………………………………………… 64
High-voltage relay ……………………………………………………………………………………………….. 64
Switches 1-4 ……………………………………………………………………………………………………… 67
MG.60.B1.02 — VLT is a registered Danfoss trademark
VLT
®
AC
AC
AC
AC
6000 HVAC
1
Summary of Contents for Danfoss VLT 6000 HVAC
Page 1
VLT® 6000 HVAC1MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVACContents ProgrammingAll aboutVLT 6000 HVACInstallationIntrIn
Page 2
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark10 Better regulationIf a frequency converter is used for regulating the flowor p
Page 3
VLT® 6000 HVAC100★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regi
Page 4 — Warning:
VLT® 6000 HVAC101MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
Page 5
VLT® 6000 HVAC102★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regi
Page 6
VLT® 6000 HVAC103MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
Page 7
VLT® 6000 HVAC104★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regi
Page 8
VLT® 6000 HVAC105MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
Page 9
VLT® 6000 HVAC106★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regi
Page 10 — 6000 HVAC
VLT® 6000 HVAC107MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
Page 11 — Introduction to
VLT® 6000 HVAC108★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regi
Page 12
VLT® 6000 HVAC109MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
Page 13
VLT® 6000 HVAC11MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVACWWWWWithout a frithout a frithout a frithout a frithout a frequ
Page 14
VLT® 6000 HVAC110★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regi
Page 15
VLT® 6000 HVAC111MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
Page 16
VLT® 6000 HVAC112★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regi
Page 17
VLT® 6000 HVAC113MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
Page 18
VLT® 6000 HVAC114★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regi
Page 19
VLT® 6000 HVAC115MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
Page 20
VLT® 6000 HVAC116★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regi
Page 21
VLT® 6000 HVAC117MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
Page 22
VLT® 6000 HVAC118★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regi
Page 23
VLT® 6000 HVAC119MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
Page 24 — ■ Specification text
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark121. Mains voltage3 x 200 — 240 V AC, 50 / 60 Hz3 x 380 — 460 V AC, 50 / 60 Hz.2. Rec
Page 25
VLT® 6000 HVAC120★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regi
Page 26
VLT® 6000 HVAC121MG.60.B1.02 — VLT is a registered Danfoss trademarkProgramming Serial communication for FC protocolMasterSlave 31 (126)Slave 2Slave
Page 27
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark122- — — — — — — — — — -MastertelegramSlavetelegramPausetimeResponse-timePausetimeEa
Page 28
VLT® 6000 HVAC123MG.60.B1.02 — VLT is a registered Danfoss trademarkProgramming Data character (byte)The build-up of data blocks depends on the type
Page 29
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark1241. Parameter bytes1514131211109876543210Parameter commands and replies (AK)Bits no
Page 30 — Ordering guide
VLT® 6000 HVAC125MG.60.B1.02 — VLT is a registered Danfoss trademarkProgrammingLowbyteHighbyteExample — Index:The first error code (index [1]) in para
Page 31
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark126PKEINDPWEHIGHPWELOWPKEINDPWEHIGHPWELOWPKEINDPWEHIGHPWELOWPKEINDPWEHIGHPWELOWParame
Page 32
VLT® 6000 HVAC127MG.60.B1.02 — VLT is a registered Danfoss trademarkProgramming PCD1 PCD2Control telegram Control word Reference value(master➝slave)Re
Page 33
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark128Bit 03, Coasting stop:Bit 03 = «0» means that the VLT frequency converte
Page 34
VLT® 6000 HVAC129MG.60.B1.02 — VLT is a registered Danfoss trademarkProgramming Status word as per FC protocolThe status word is used to inform t
Page 35
VLT® 6000 HVAC13MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVACGood torque control properties, smooth transition tocurrent lim
Page 36
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark130Example — control word andserial communication ref.:The VLT frequency converter mu
Page 37
VLT® 6000 HVAC131MG.60.B1.02 — VLT is a registered Danfoss trademarkProgramming Present output frequencySlave➝Master1514131211109876543210Bit no.
Page 38
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark132✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
Page 39
VLT® 6000 HVAC133MG.60.B1.02 — VLT is a registered Danfoss trademark✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
Page 40
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark134✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
Page 41
VLT® 6000 HVAC135MG.60.B1.02 — VLT is a registered Danfoss trademark✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
Page 42
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark136✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
Page 43 — Installation
VLT® 6000 HVAC137MG.60.B1.02 — VLT is a registered Danfoss trademark✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
Page 44
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark138✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
Page 45
VLT® 6000 HVAC139MG.60.B1.02 — VLT is a registered Danfoss trademark✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
Page 46
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark14Advanced motor protectionVLT 6000 HVAC features integrated electronic,thermal motor
Page 47
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark140✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
Page 48
VLT® 6000 HVAC141MG.60.B1.02 — VLT is a registered Danfoss trademark✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
Page 49
VLT® 6000 HVAC142★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regi
Page 50
VLT® 6000 HVAC143MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
Page 51
VLT® 6000 HVAC144★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regi
Page 52
VLT® 6000 HVAC145MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
Page 53
VLT® 6000 HVAC146★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regi
Page 54
VLT® 6000 HVAC147MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
Page 55
VLT® 6000 HVAC148MG.60.B1.02 — VLT is a registered Danfoss trade mark Status messagesStatus messages appear in the 4th line of the display- see e
Page 56
VLT® 6000 HVAC149MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACStatus messages, cont.Freeze output request (FRZ.REQ.)A sta
Page 57
VLT® 6000 HVAC15MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVACPC software and serial communicationDanfoss offers various opti
Page 58
VLT® 6000 HVAC150MG.60.B1.02 — VLT is a registered Danfoss trade mark List of warnings and alarmsThe table gives the different warnings and alarm
Page 59
VLT® 6000 HVAC151MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVAC WarningsA warning will flash in line 2, while an expl
Page 60
VLT® 6000 HVAC152MG.60.B1.02 — VLT is a registered Danfoss trade markWarnings and alarms, cont.WARNING/ALARM 8Undervoltage (DC LINK UNDERVOLT)If the i
Page 61
VLT® 6000 HVAC153MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACASYMMETRICAL IMPEDANCE [2]AMA has detected an asymmetrical
Page 62
VLT® 6000 HVAC154MG.60.B1.02 — VLT is a registered Danfoss trade markALARM: 32Motor phase W missing(MISSING MOT.PHASE U):Motor phase W between VLT fre
Page 63
VLT® 6000 HVAC155MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACWARNING: 41MOTOR TOO BIG (MOTOR TOO BIG)The motor used is p
Page 64
VLT® 6000 HVAC156MG.60.B1.02 — VLT is a registered Danfoss trade mark Aggressive environmentsIn common with all electronic equipment, a VLTfreque
Page 65
VLT® 6000 HVAC157MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACGalvanic isolation Galvanic isolation (PELV)PELV offer
Page 66
VLT® 6000 HVAC158MG.60.B1.02 — VLT is a registered Danfoss trade mark Extreme running conditionsShort circuitVLT 6000 HVAC is protected against s
Page 67
VLT® 6000 HVAC159MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACIf very small motors are used without phase coilinsulation,
Page 68
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark16 CE-labellingWhat is CE-labelling ?What is CE-labelling ?What is CE-labelling
Page 69
VLT® 6000 HVAC160MG.60.B1.02 — VLT is a registered Danfoss trade mark Derating for ambient temperatureThe ambient temperature (TAMB,MAX) is the m
Page 70
VLT® 6000 HVAC161MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVAC Derating for running at low speedWhen a centrifugal p
Page 71 — 50.0Hz
VLT® 6000 HVAC162MG.60.B1.02 — VLT is a registered Danfoss trade mark EfficiencyTo reduce energy consumption it is very important tooptimize the
Page 72
VLT® 6000 HVAC163MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACThe voltage distortion on the mains supply dependson the si
Page 73
VLT® 6000 HVAC164MG.60.B1.02 — VLT is a registered Danfoss trade mark EMC test results (Emission, Immunity)The following test results have been o
Page 74 — HAND LOCAL RUN
VLT® 6000 HVAC165MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACClass A-1:Equipment used in a manufacturing environment.Cla
Page 75 — Programming
VLT® 6000 HVAC166MG.60.B1.02 — VLT is a registered Danfoss trade markDM: Differential modeCM: Common modeCCC: Capacitive clamp couplingDCN: Direct cou
Page 76
VLT® 6000 HVAC167MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACDigital inputs:The digital inputs can be used for controlli
Page 77
VLT® 6000 HVAC168MG.60.B1.02 — VLT is a registered Danfoss trade markLSB:Least significant bit.Used in serial communication.MCM:Stands for Mille Circu
Page 78
VLT® 6000 HVAC169MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACDatatype Factory settingsConversionindexPNU Parameter
Page 79
VLT® 6000 HVAC17MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVAC Application examplesThe next few pages give typical examp
Page 80
VLT® 6000 HVAC170MG.60.B1.02 — VLT is a registered Danfoss trade markPNU Parameter Factory setting Range Changes 4-Setup# description during operation
Page 81
VLT® 6000 HVAC171MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACPNU Parameter Factory setting Range Changes 4-Setup# descri
Page 82
VLT® 6000 HVAC172MG.60.B1.02 — VLT is a registered Danfoss trade mark Factory settingsDatatype56566665555445554455667666Conversionindex00-10-1-10
Page 83
VLT® 6000 HVAC173MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACPNU Parameter Factory setting Range Changes 4-Setup# descri
Page 84
VLT® 6000 HVAC174MG.60.B1.02 — VLT is a registered Danfoss trade markPNU Parameter Factory setting Range Changes 4-Setup# description during operation
Page 85
VLT® 6000 HVAC175MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACAAcoustic noise …
Page 86
VLT® 6000 HVAC176MG.60.B1.02 — VLT is a registered Danfoss trade markHHand start…
Page 87
VLT® 6000 HVAC177MG.60.B1.02 — VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACTTechnical dataGeneral technical data …
Page 88
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark18 Variable Air VolumeVAV or Variable Air Volume systems, are used tocontrol bot
Page 89
VLT® 6000 HVAC19MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVAC Constant Air VolumeCAV, or Constant Air Volume systems ar
Page 90
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark2ProgrammingProgrammingProgrammingProgrammingProgrammingControl unit LCP…
Page 91
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark20Water InletWater OutletCHILLERTemperatureSensorBASINConderserWater pumpSupply
Page 92
VLT® 6000 HVAC21MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVACWater InletWater OutletCHILLERBASINConderserWater pumpSupplyTem
Page 93
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark22 Primary pumpsPrimary pumps in a primary/secondary pumpingsystem can be used t
Page 94
VLT® 6000 HVAC23MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVAC Secondary pumpsSecondary pumps in a primary/secondary chi
Page 95
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark24 Specification textThe following is a proposal for a HVAC frequencyconverter s
Page 96
VLT® 6000 HVAC25MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVAC1.06 Quality AssuranceA. The frequency converters shall be manu
Page 97
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark262.05 Protective FeaturesA. Class 20 I2t electronic motor overload protectionfor sin
Page 98
VLT® 6000 HVAC27MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVAC2.06 ControlA. Hand/Off/Auto selector switches shall be provide
Page 99
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark28V. The frequency converter will sense the loss of loadand signal a no load/broken
Page 100
VLT® 6000 HVAC29MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVAC3.03 ExaminationA. Contractor to verify that job site condition
Page 101 — Programming
VLT® 6000 HVAC3MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVACThis Design Guide can be used with all VLT 6000 HVAC fre-quency
Page 102
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark30 Ordering guideThis section makes it easier for you to specify andorder a VLT
Page 103
VLT® 6000 HVAC31MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVACMains voltage 380 — 415 VTypical shaft outputMax continuous out
Page 104
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark32 EnclosureVLT 6000 HVAC is available with the followingenclosures:- IP 00: 30
Page 105
VLT® 6000 HVAC33MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVAC Fieldbus protocolsDanfoss VLT frequency converters are ab
Page 106
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark34 Unpacking and ordering a VLT frequencyconverterAre you are in doubt as to whi
Page 107
VLT® 6000 HVAC35MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVAC▲▲▲▲▲ Ordering form VLT 6000 HVACPower sizese.g. 6008Appli
Page 108
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark36Control unitLCPOPTIONS1) IP 4x/NEMA 1 top cover is for IP 20 units only and onlyhor
Page 109
VLT® 6000 HVAC37MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVAC LC filters for VLT 6000 HVACWhen a motor is controlled by
Page 110
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark38 Ordering numbers, LC filter modulesMains supply 3 x 200 — 240 VMains supply 3
Page 111
VLT® 6000 HVAC39MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVAC LC filters 6002-6006, 200 — 240 V / 6002-6011 380 — 460 V
Page 112
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark4Warning:Touching the electrical parts may be fatal — even after theequipment has bee
Page 113
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark40The table and the drawing give the measurements ofIP 00 LC filters for Compact unit
Page 114
VLT® 6000 HVAC41MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVACLC-filter IP 20LC type A [mm] B [mm] C [mm] D [mm] E [mm] F [mm
Page 115
VLT® 6000 HVAC42MG.60.B1.02 — VLT is a registered Danfoss trade mark General technical dataMains supply (L1, L2, L3):Supply voltage 200-240 V uni
Page 116
VLT® 6000 HVAC43MG.60.B1.02 — VLT is a registered Danfoss trade markInstallation General technical dataControl card, pulse input:No. of programma
Page 117
VLT® 6000 HVAC44MG.60.B1.02 — VLT is a registered Danfoss trade mark General technical dataCable lengths and cross-sections:Max. motor cable leng
Page 118
VLT® 6000 HVAC45MG.60.B1.02 — VLT is a registered Danfoss trade markInstallation Mains supply 3 x 200 — 240 VAccording to international requirem
Page 119
VLT® 6000 HVAC46MG.60.B1.02 — VLT is a registered Danfoss trade markVLVLVLVLVLT typeT typeT typeT typeT type600260026002600260026003600360036003600360
Page 120
VLT® 6000 HVAC47MG.60.B1.02 — VLT is a registered Danfoss trade markInstallationVLVLVLVLVLT typeT typeT typeT typeT type607560756075607560756100610061
Page 121
VLT® 6000 HVAC48MG.60.B1.02 — VLT is a registered Danfoss trade mark Mechanical dimensionsAll measurements in mm.VLT type A B C a b a/b TypeBooks
Page 122
VLT® 6000 HVAC49MG.60.B1.02 — VLT is a registered Danfoss trade markInstallation Mechanical dimensions
Page 123
VLT® 6000 HVAC5MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVAC Introduction to the Design GuideThis Design Guide is a too
Page 124
VLT® 6000 HVAC50MG.60.B1.02 — VLT is a registered Danfoss trade mark Mechanical installationPlease pay attention to the requirementsthat apply to
Page 125
VLT® 6000 HVAC51MG.60.B1.02 — VLT is a registered Danfoss trade markInstallationSide-by-sideVLT 6075-6275 IP 00 and IP 20All IP 00 and IP 20 units in
Page 126
VLT® 6000 HVAC52MG.60.B1.02 — VLT is a registered Danfoss trade mark High voltage warningThe voltage of the frequency converter is dangerous when
Page 127
VLT® 6000 HVAC53MG.60.B1.02 — VLT is a registered Danfoss trade markInstallation RFI switchMains supply isolated from earth:When the VLT frequenc
Page 128
VLT® 6000 HVAC54MG.60.B1.02 — VLT is a registered Danfoss trade mark EMC-correct electrical installationGeneral points to be observed to ensure E
Page 129
VLT® 6000 HVAC55MG.60.B1.02 — VLT is a registered Danfoss trade markInstallation Use of EMC-correct cablesScreened/armoured cables are recommende
Page 130
VLT® 6000 HVAC56MG.60.B1.02 — VLT is a registered Danfoss trade mark Earthing of screened/armoured control cablesGenerally speaking, control cabl
Page 131
VLT® 6000 HVAC57MG.60.B1.02 — VLT is a registered Danfoss trade markInstallation VLT 6000 HVAC enclosuresBookstyle IP 20VLT 6002-6005, 200-240 VV
Page 132
VLT® 6000 HVAC58MG.60.B1.02 — VLT is a registered Danfoss trade mark VLT 6000 HVAC enclosuresIP 54VLT 6006-6032, 200-240 VVLT 6016-6062, 380-460
Page 133
VLT® 6000 HVAC59MG.60.B1.02 — VLT is a registered Danfoss trade markInstallationIP 20VLT 6150-6275, 380-460 VIP 00VLT 6150-6275, 380-460 VIP 54VLT 615
Page 134
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark6Installation:Installation:Installation:Installation:Installation: This section shows
Page 135
VLT® 6000 HVAC60MG.60.B1.02 — VLT is a registered Danfoss trade markCompact IP 20/IP 54VLT 6002-6005, 200-240 VVLT 6002-6011, 380-460 VIP 20VLT 6006-6
Page 136
VLT® 6000 HVAC61MG.60.B1.02 — VLT is a registered Danfoss trade markInstallationIP 54VLT 6150-6275, 380-460 VIP 00/20VLT 6150-6275, 380-460 VIP 00/20V
Page 137
VLT® 6000 HVAC62MG.60.B1.02 — VLT is a registered Danfoss trade mark Tightening-up torque and screw sizesThe table shows the torque required when
Page 138 — VLT NO.8
VLT® 6000 HVAC63MG.60.B1.02 — VLT is a registered Danfoss trade markInstallation Motor cablesSee Technical data for correct sizing of motor cable
Page 139
VLT® 6000 HVAC64MG.60.B1.02 — VLT is a registered Danfoss trade mark DC bus connectionThe DC bus terminal is used for DC back-up, with theinterme
Page 140
VLT® 6000 HVAC65MG.60.B1.02 — VLT is a registered Danfoss trade markInstallation Electrical installation, control cablesTorque: 0.5 — 0.6 Nm.Scre
Page 141
VLT® 6000 HVAC66MG.60.B1.02 — VLT is a registered Danfoss trade mark Connection example, VLT 6000 HVACThe diagram below gives an example of a typ
Page 142
VLT® 6000 HVAC67MG.60.B1.02 — VLT is a registered Danfoss trade markInstallation Switches 1-4The dipswitch is located on the control card.It is u
Page 143 — EXT. REFERENCE, %
VLT® 6000 HVAC68MG.60.B1.02 — VLT is a registered Danfoss trade mark Connection examplesSingle-pole start/stop- Start/stop using terminal 18.Para
Page 144
VLT® 6000 HVAC69MG.60.B1.02 — VLT is a registered Danfoss trade markProgramming Control unit LCPThe front of the VLT frequency converter features
Page 145
VLT® 6000 HVAC7MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVAC Available literatureThe chart below gives an overview of t
Page 146
VLT® 6000 HVAC70MG.60.B1.02 — VLT is a registered Danfoss trade mark[+/-] is used for selecting parameters andfor changing a chosen parameter. Theseke
Page 147
VLT® 6000 HVAC71MG.60.B1.02 — VLT is a registered Danfoss trade markProgramming Display mode, cont.The table below gives the operating data optio
Page 148 — 40.0Hz
VLT® 6000 HVAC72MG.60.B1.02 — VLT is a registered Danfoss trade markDisplay mode II Display mode III:This display mode can be generated as long a
Page 149 — VLT 6000 HVAC
VLT® 6000 HVAC73MG.60.B1.02 — VLT is a registered Danfoss trade markProgramming Changing dataRegardless of whether a parameter has been selectedu
Page 150
VLT® 6000 HVAC74MG.60.B1.02 — VLT is a registered Danfoss trade markQuick menu: Parameter 1 of 12Used to select the language for the display.Quick men
Page 151 — ALARM:12
VLT® 6000 HVAC75MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
Page 152
VLT® 6000 HVAC76★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regis
Page 153
VLT® 6000 HVAC77MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
Page 154
VLT® 6000 HVAC78★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regis
Page 155
VLT® 6000 HVAC79MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
Page 156
VLT® 6000 HVACMG.60.B1.02 — VLT is a registered Danfoss trademark8Why use a frequency converter for controllingfans and pumps?A frequency converter ta
Page 157
VLT® 6000 HVAC80★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regis
Page 158
VLT® 6000 HVAC81MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
Page 159
VLT® 6000 HVAC82★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regis
Page 160
VLT® 6000 HVAC83MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
Page 161
VLT® 6000 HVAC84★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regis
Page 162
VLT® 6000 HVAC85MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
Page 163
VLT® 6000 HVAC86★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regis
Page 164
VLT® 6000 HVAC87MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
Page 165
VLT® 6000 HVAC88★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regis
Page 166
VLT® 6000 HVAC89MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
Page 167
VLT® 6000 HVAC9MG.60.B1.02 — VLT is a registered Danfoss trademarkIntroduction to HVACExample with varying flow over 1 yearThe example below is calcul
Page 168
VLT® 6000 HVAC90★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regis
Page 169
VLT® 6000 HVAC91MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
Page 170
VLT® 6000 HVAC92★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regis
Page 171
VLT® 6000 HVAC93MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
Page 172
VLT® 6000 HVAC94★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regis
Page 173
VLT® 6000 HVAC95MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
Page 174
VLT® 6000 HVAC96★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regis
Page 175
VLT® 6000 HVAC97MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
Page 176
VLT® 6000 HVAC98★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 — VLT is a regis
Page 177
VLT® 6000 HVAC99MG.60.B1.02 — VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
Danfoss VLT 6000 HVAC DC Drives PDF User Guides and Manuals for Free Download: Found (6) Manuals for Danfoss VLT 6000 HVAC Device Model (Quick Setup Manual, Instruction Manual)
More Controller Device Models:
-
Doli
EDC220
EDC220 EDC220 5) VAI32 einbauen / mount VAI32 / 安装 VAI32 6) Deckel wieder montieren / Remount the lid / 重新装上顶盖 Siehe Schritt 1 in umgekehrter Reihenfolge. / See step 1 in reversed order. /依步骤一反向行之 Montageanleitung EDC220 + I. RS232A (Best.Nr. 1744) …
EDC220 Controller, 2
-
Varian
Turbo-V 6000
Turbo-V 6000 Model 969-9081 Model 969-9082 MANUALE DI ISTRUZIONI BEDIENUNGSHANDBUCH NOTICE DE MODE D’EMPLOI MANUAL DE INSTRUCCIONES MANUAL DE INSTRUÇÕES BEDRIJFSHANDLEIDING INSTRUKSTIONSBOG BRUKSANVISNING INSTRUKSJON MANUAL OHJEKÄSIKIRJA ODHGIES CRHSEWS INSTRUCTION MANUAL 87-900-838-01(B)MARCH 2003 …
Turbo-V 6000 Water Pump, 40
-
Curtis
1222
ManualModel 1222Electric Steering Controller Read Instructions Carefully!Specifications are subject to change without notice.© 2013 Curtis Instruments, Inc. ® Curtis is a registered trademark of Curtis Instruments, Inc.© The design and appearance of the products depicted herein are the copyright of Curtis Instrum …
1222 Controller, 124
-
Graco
Series A
INSTRUCTIONS–PARTS LIST307–860Rev. DSupersedes BThis manual contains IMPORTANTWARNINGS AND INSTRUCTIONSREAD AND RETAIN FOR REFERENCEModel AS4000MMANUAL ELECTROSTATIC METALLICAIR SPRAY GUN100 psi (7 bar) MAXIMUM WORKING PRESSUREPart Number 221–179 Series AWith 180–739 air cap and 0.047 in. (1.2 mm) fluid noz …
Series A Paint Sprayer, 28
Recommended Documentation:
Types of Manuals:
The main types of Danfoss VLT 6000 HVAC instructions:
- User guide — rules of useing and characteristics
- Service manual — repair, diagnostics, maintenance
- Operation manual — description of the main functions of equipment
Controller, DC Drives, Media Converter Instructions by Danfoss:
-
D+H ZA 35-K-BSY+
deenfiesOriginalbetriebsanleitung . . . . . . . . . . . . . . . . . . . Seite . . . . . . . 2Original instructions . . . . . . . . . . . . . . . . . . . . . . . Page . . . . . . . 6Käyttöohje . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . Sivu . . . . . . . 10Manual original . . . . . . . . . . . . . …
ZA 35-K-BSY+ Industrial Equipment, 20
-
Siemens SINUMERIK 840D sl
SINUMERIKSINUMERIK 840D sl / 828DBasic Functions Function Manual 01/20156FC5397-0BP40-5BA2PrefaceFundamental safety instructions1A2: Various NC/PLC interface signals and functions2A3: Axis Monitoring, Protection Zones3B1: Continuous-path mode, Exact stop, Look Ahead4B2: Acceleration5F1: Travel to fixed stop6G2: Velocit …
SINUMERIK 840D sl Controller, 1726
-
Dakota Digital ECD-100
MAN# 650445:C 1 ECD-100 ELECTRONIC CABLE DRIVE The Dakota Digital ECD-100 is designed operate a cable-driven speedometer from a transmission or ECM electric speed signal. Cables are available for GM thread-on (5/8” thread), GM clip-on, or Ford clip-on. The supplied cable threads on to one end of the ECD-100 and the …
ECD-100 DC Drives, 4
-
Toshiba VF-MB1
E6581750 TOSVERT VF-MB1 Traverse control Instruction Manual ~For textile machines~ © Toshiba Schneider Inverter Corporation 2010 All rights reserved. The technical information in this manual is provided to explain the principal functions and applications of the product …
VF-MB1 Control Unit, 6
-
Kinco FV20 Series
PrefaceThank you for using FV20 series Variable Frequency Drive made by Kinco Automation.FV20 series inverter is a general-purpose high-performance vector inverter, which is mainly used to controland adjust the speed and torque of three-phase AC asynchronous motor. It is a technical upgrade product ofFV100 series. FV20 …
FV20 Series Inverter Drive, 119
-
Rockwell Automation PowerFlex 700S
Installation InstructionsPowerFlex® 700S and 700H Frame 14 Replacement Power StructuresIntroductionImportant:The Power Modules on PowerFlex 700S Phase II and 700H frame 14 drives are matched at the factory and cannot be paired with any other Power Modules. Therefore, when a Power Module fails, you must replace both po …
PowerFlex 700S Controller, 24
VLT® 6000 HVAC
■Introduction
Variable speed drives have been used in industrial applications for years because of their ability to provide precise process control. They have also become the standard method of control for heating ventilation and air-conditioning (HVAC) systems due to their precise control and significant energy savings.
The operational concerns for HVAC systems are quite different from those for industrial applications. In most HVAC installations there is a large installed base of sensitive electronic equipment such as computers, outstations and radios. Airports, hospitals and research facilities will for example make much heavier demands on the variable speed drives than the industrial plants.
This feature note will deal with one aspect of electrical noise generation in variable speed drives: Radio Frequency Interference (RFI) on the AC power line. We describe the causes and effects of such noise as well as the considerations that are to be made in connection with the selection and installation of a variable speed drive.
■ Causes of Radio Frequency Interference
(RFI)
ee
Figure 1: Schematic of Basic Drive design
Most variable speed drives operate by using a bridge rectifier to convert the incoming AC voltage into a DC bus voltage. The inverter bridge of the drive then converts the DC bus voltage into the controlled voltage and frequency that the motor requires.
For the most common types of drives in use today, IGBTs are used to convert the DC voltage into an AC voltage with controlled amplitude and frequency. To perform this control most drives incorporate sophisticated control circuitry with micro-processors of high clock frequencies.
Both the inverter and the control circuitry generate electrical noise at frequencies higher than 150 kHz.
If the drive is not designed carefully, this noise will be conducted to the surroundings, causing malfunction of other electronic equipment, especially if it is not designed with a high level of immunity to such high frequency noise.
■ Measuring Radio Frequency Interference
The levels of RFI from a drive is dependent on many different factors. The design of the drive is most important, since this determines how low the distortion can get.
The measuring results for different drives may vary a lot, so to get a real picture it is important to know exactly how the measuring was made. Some of the most important factors are:
Impedance between drive chassis and ground Type of motor cable used or transfer impedance of cable screen
Length of motor cable
Radiated emission is almost impossible to reproduce. The reason is that even a slight change in the measuring set-up will influence the results a lot. Measuring made on site will always be unreliable, since it is impossible to create a clean environment.
■Radio frequency interference limits
The most important international standard defining RFI limits for drives is:
EN 55011/CISPR 11
EN55011 sets three different limits:
Emission,
screened motor cable
dB/uV |
Average levels |
||
90 |
EN 55011 2A |
||
80 |
|||
76 |
|||
66 |
|||
60 |
EN 55011 1A |
||
56 |
EN 55011 1B |
||
50 |
|||
46 |
|||
150 kHz |
500 kHz |
5 MHz |
30 MHz |
Figure 2: Average conducted emission levels
MN.60.G1.02 — VLT is a registered Danfoss trademark |
1 |